Trip
Trip
Get More Electrical Concept And Interview Questions By Using This Link
https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 1/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u
1. Plant layout
2. Means how generator is connected to high voltage transmission line.
3. There are two different ways:
Also Know About: Local Breaker Backup Protection LBB 50Z or 50BF
Class A
Class B
Class C
Class A trips:
Class A trip involves a serious electrical fault like differen al, stator earth fault etc. and is
considered to be the most dangerous in terms of the shock on the unit. Since it involves serious
electrical faults, connec ons from both generator and the EHV bus is immediately switched off
https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 2/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u
to limit the damage at the fault point and also to isolate the healthy system. Hence the unit x
(turbine, generator and boiler) has to be tripped.
Class B trip:
Class B primarily relates to mechanical problems. This results in tripping of turbine followed by
generator.
Class C trip:
Class C involves basically external system related problems like frequency, overvoltage etc. This x
does not involve instant tripping of the unit. CPP unit operates on house load.
Also Know About: Neutral Voltage Protection -59GN- 95% stator Earth fault
protection
https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 3/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u
Class A1:
Class A-I trip is mainly for faults in generator transformer and unit transformer. In this class, trip
goes to following equipments without me delay.
Class A2:
Class AII trip is for faults in generator. In this class, trip goes to following equipments without
me delay.
Turbine,
Generator breaker (GCB),
Field breaker.
The auxiliaries are fed through unit transformer by back charging of GT. Thus in Class A2 trip we
are able to maintain uninterrupted power to the Unit bus and auxiliaries which was not
possible in the scheme without GCB.
https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 4/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u
Class B
Class B trip also leads to generator breaker (GCB) tripping. In this class, trip goes to only
turbine. There are 7 generator protec ons come into Class B
Ref: h p://ijaems.com/upload_images/SITE_SPECIAL_ISSUE_FILE_PATHJIT-093.pdf
electrical
https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 5/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u
https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 6/6