0% found this document useful (0 votes)
200 views

Trip

The document discusses generator tripping schemes classified as Class A, B, and C. Class A trips involve serious electrical faults that require isolating the generator and tripping the unit. Class B relates to mechanical problems, tripping just the turbine first before the generator. Class C involves external system problems without immediate tripping. The classification depends on plant layout and whether a generator circuit breaker is present. With a GCB scheme, Class A is divided into A1 and A2 trips.

Uploaded by

boby
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
200 views

Trip

The document discusses generator tripping schemes classified as Class A, B, and C. Class A trips involve serious electrical faults that require isolating the generator and tripping the unit. Class B relates to mechanical problems, tripping just the turbine first before the generator. Class C involves external system problems without immediate tripping. The classification depends on plant layout and whether a generator circuit breaker is present. With a GCB scheme, Class A is divided into A1 and A2 trips.

Uploaded by

boby
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u

Classification Generator tripping Scheme Class A,


Class B & Class C

Classi cation Generator tripping Scheme Class A, Class B & Class A:


The generator Tripping classified according to the fault.

Protec on of the generator:

Get More Electrical Concept And Interview Questions By Using This Link

Voltage Controlled Over Current Protec on


(51V)
Dead Machine Protec on (50/27)
Generator Circuit Breaker Failure (50BF)
Over Excita on Protec on (24G)
Over Voltage Protec on (59)
Reverse Power Protec on (32R)
Low Forward Power Protec on (32F)
Differen al Protec on (87G)
Under Frequency Protec on (81G)
Over Frequency Protec on (81G)
Loss of Excita on (40G)
95 % Stator Earth Fault (64G1)
100 % Stator Earth Fault (64G2)
Generator Rotor Earth Fault (64F)
Exciter Rotor Earth Fault
I&C Trip from ETS.
ETS
Excita on System Fault
Generator Pole Slipping (78)
Nega ve Phase Sequence Protec on (46)
Backup Impedance Protec on (21)
Generator Cooling Water Loss
Conduc vity High Loss

https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 1/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u

Classification depends upon following: x

1. Plant layout
2. Means how generator is connected to high voltage transmission line.
3. There are two different ways:

Without GCB scheme => GCB -Generator Circuit Breaker


With GCB scheme

Also Know About: Local Breaker Backup Protection LBB 50Z or 50BF

Without GCB Scheme:


Get More Electrical Concept And Interview Ques ons By Using This Link

Generator synchronizing done at switchyard.


Generator, GT& UAT are directly connected to switchyard.
If any faults in generator, then we have to open switchyard breaker.

Without GCB we can classified into 3 class

Class A
Class B
Class C

Class A trips:
Class A trip involves a serious electrical fault like differen al, stator earth fault etc. and is
considered to be the most dangerous in terms of the shock on the unit. Since it involves serious
electrical faults, connec ons from both generator and the EHV bus is immediately switched off
https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 2/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u

to limit the damage at the fault point and also to isolate the healthy system. Hence the unit x
(turbine, generator and boiler) has to be tripped.

Class B trip:
Class B primarily relates to mechanical problems. This results in tripping of turbine followed by
generator.

Class C trip:
Class C involves basically external system related problems like frequency, overvoltage etc. This x
does not involve instant tripping of the unit. CPP unit operates on house load.

Also Know About: Neutral Voltage Protection -59GN- 95% stator Earth fault
protection

With gcb scheme:


Get More Electrical Concept And Interview Ques ons By Using This Link

https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 3/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u

Generator synchronizing done at TG building. x


Generator is not directly connected to GT,UAT & switchyard
If any faults in generator then we have to open GCB.
Classifica on of generator protec on tripping in this scheme are
1. Class A1
2. Class A2
3. Class B

Class A1:
Class A-I trip is mainly for faults in generator transformer and unit transformer. In this class, trip
goes to following equipments without me delay.

Generator Breaker (GCB).


EHV Breaker.
UAT LV breaker and Field Breaker.

Three generator protec ons come into Class-AI.

Voltage Controlled Over Current Protec on (51V).


Dead Machine Protec on (50/27).
Generator Circuit Breaker Failure (50BF).

Class A2:
Class AII trip is for faults in generator. In this class, trip goes to following equipments without
me delay.

Turbine,
Generator breaker (GCB),
Field breaker.

Advantage of GCB scheme:

The auxiliaries are fed through unit transformer by back charging of GT. Thus in Class A2 trip we
are able to maintain uninterrupted power to the Unit bus and auxiliaries which was not
possible in the scheme without GCB.

Also Know About: Advantage of Neutral Grounding Transformer NGT

There are 13 generator protec ons into Class AII:

https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 4/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u

1. Over Excita on Protec on (24G) x


2. Over Voltage Protec on (59)
3. Reverse Power Protec on (32R)
4. Under Frequency stage – 2 (81)
5. Low Forward Power Protec on (32F)
6. Differen al Protec on (87G)
7. Loss of Excita on (40G)
8. 95 % Stator Earth Fault (64G1)
9. 100 % Stator Earth Fault (64G2)
10. Generator Rotor Earth Fault (64F)
11. Exciter Rotor Earth Fault
12. I&C Trip from ETS
13. Excita on System Fault

Class B
Class B trip also leads to generator breaker (GCB) tripping. In this class, trip goes to only
turbine. There are 7 generator protec ons come into Class B

Under frequency stage-1 (81)


Over Frequency Stage-2 (81)
Generator Pole Slipping (78)
Nega ve Phase Sequence Protec on (46)
Backup Impedance Protec on (21)
Generator Cooling Water Loss
Conduc vity High loss.

Ref: h p://ijaems.com/upload_images/SITE_SPECIAL_ISSUE_FILE_PATHJIT-093.pdf

electrical

FOLL O W US ON INS TAGRAM


@HTT P S : //WWW.IN STAGRAM/TECHDOCT

https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 5/6
11/4/2019 Classification Generator tripping Scheme Class A, Class B & Class C | Electrical4u

https://www.electrical4u.net/relay/classification-generator-tripping-scheme-class-a-class-b-class-c/ 6/6

You might also like