ChE170 Lecture 9 (Control Tuning) PDF
ChE170 Lecture 9 (Control Tuning) PDF
Lecture 9
Controller tuning
Criteria for good control
• Most operators of processes know what they want in the form of a
response to a change in set point or load.
• For example, a response that gives minimum overshoot and ¼ decay ratio is
often considered as a satisfactory response.
• In many cases, tuning is done by trial and error until such a response is
obtained.
Performance Criteria for Closed-Loop Systems
1. The closed-loop system must be stable
2. The effects of disturbances are minimized, providing good disturbance
rejection
3. Rapid, smooth responses to set-point changes are obtained, that is, good
set-point tracking
4. Steady-state error (offset) is eliminated
5. Excessive control action is avoided.
6. The control system is robust, that is, insensitive to changes in process
conditions and to inaccuracies in the process model
Tradeoffs between Performance and Robustness
Balance Satisfactory
Rapid performance to wide
Smooth range of condition.
Performance Robustness
Little Conservative
oscillation controller settings.
Tradeoffs between set point tracking and disturbance
rejection
Balance
Excellent set point Excellent disturbance
tracking will provide Set point Disturbance rejection will produce
sluggish response to Tracking Rejection large overshoot in
disturbance set-point changes.
Performance Criteria
Quarter-Amplitude Decay
ØIf a loop is oscillating, each peak deviation should be only one-
fourth of the previous peak deviation on the same side of set
point.
ØAlso called “Quarter-wave decay”, “Quarter-wave damping”
Quarter-Amplitude Decay Response
Quarter-Amplitude Decay Response
Quarter-wave decay ratio response
•A control loop tuned to have a Quarter-wave
Amplitude decay response in a set point change
will show a sluggish response in a load
disturbance.
•A control loop tuned to have a Quarter-wave
Amplitude decay response in a load upset will
show a too oscillatory response in a set point
change.
Quarter-wave decay ratio response
• For many applications, the quarter-amplitude-decay criterion
provides acceptable damping of the oscillations that follow a set
point change. For other applications, quarter-amplitude decay
may be too oscillatory. A plant’s operations and engineering staff
may be willing to accept a more sluggish response to a load upset
in order to minimize the overshoot that follows a set point
change.
• Some operators prefer to see loops that are critically damped;
that is, they want the measurement to rise rapidly to the new set
point value and yet avoid overshoot.
Quarter-wave decay ratio response
• For many control loops, the set point is rarely changed. The
purpose of these loops is to minimize the effect of disturbances.
Even so, because set point changes are usually made more easily
than load changes, in actual practice many loops are tuned for a
suitable response to a set point change. Then, the resulting
response for a load upset is accepted even though it may not be
the best.
• A preferable tuning strategy would be to tune the controller for
best response to a load change, then use one of the set point
“softening” techniques to ameliorate the effect of occasional set
point changes.
Performance Criteria for Closed-Loop Systems
ØDecay ratio alone does not provide a complete performance
specification.
ØOther criteria that are sometimes used to specify, or measure,
control loop performance include:
§ Rise time—the time between a set point change and the first
crossing of the set point;
§ Overshoot ratio—the ratio of the magnitude of the first overshoot
above set point to the magnitude of the set point change itself;
§ Settling time—the time, following a set point change or
disturbance, that it takes for the oscillation to become so small
that the deviation does not exceed some specified amount.
ØIntegral Error Criteria
Integral Error Criteria
Ø based on minimizing the integral of some
function of the error.
Graphical interpretation of
IAE. The shaded area is the
IAE value.
Note: ! = ! # = $%& − $(
Integral Error Criteria
The ultimate period Pu is defined as the period of the sustained cycling that would occur
if a proportional controller with gain Kcu were used.
• Several IMC guidelines for !" have been published for the model in Eq.
12-10:
#$
> 0.8 and !+ > 0.1! Rivera et al., 1986
&
! > !+ > - Chien and Fruehauf, 1990
!+ = - (Skogestad, 2003)
Other tuning relation