Potterton - Profile - 40 50 60 80el Install - Guide
Potterton - Profile - 40 50 60 80el Install - Guide
40eL - 80eL
About the Boiler See inside cover for models covered by these instructions.
This is a Wall Mounted Fan Assisted Balanced Flue Gas Boiler.
This boiler is for use with Natural Gas (G20) only at 20 mbar and for use in GB & IE.
About Safety The Gas Safety (Installation and Use) Regulations 1998.
‘‘ In your own interest, and that of safety, it is law that all gas appliances are installed by competent
persons, in accordance with the above regulations. Failure to install appliances correctly could
lead to prosecution.’’
Installation must be in accordance with the Installation & Service Instructions and the rules in
force.
Leave these instructions and the Benchmark Log Book with the user for use on future calls.
PRF0002A
TM
Boiler model
40 50 60 80
Output kW (Btu/h) 11.72 (40,000) 14.65 (50,000) 17.58 (60,000) 23.45 (80,000)
Input kW (Btu/h) max 14.42 (49,200) 18.02 (61,500) 21.66 (73,900) 28.88 (98,500)
Gas rate m³/h (ft³/h) max 1.34 (47.5) 1.68 (59.4) 2.02 (71.3) 2.69 (95.1)
Burner Pressure max 12.3 (4.9) 11.5 (4.6) 13.0 (5.2) 12.2 (4.9)
mbar (in wg)
This appliance must be installed and serviced by a competent Samples of the Profile gas boilers have been examined by
person, in accordance with the above regulations. Advantica Technologies Limited, a United Kingdom Notified
Body. The range is certified to comply with the essential
In the UK 'Corgi' Registered Installers (including the regions requirements of the Gas Appliance Directive 90/396/EEC,
of British Gas Plc) undertake to work to a safe and the Low Voltage Directive 72/23/EEC and shows compliance
satisfactory standard. with the Electro Magnetic Compatibility Directive 89/336/
EEC, the Boiler Efficiency Directive 92/42/EEC and are
Failure to install appliances correctly could lead to therefore permitted to carry the CE Mark.
prosecution.
Delivery & Kits Available
It is in your own interest, and that of safety, to ensure that
the regulations are complied with. The unit is delivered in two packages (1) the boiler with
fittings and (2) the flue/terminal assembly. All boilers can be
Profile boilers are fully automatically controlled, wall supplied with either of the following types of flue system:
mounted, fan powered, balanced flue appliances using a
cast iron heat exchanger and are available in outputs • Standard horizontal flue system suitable for wall thickness
ranging from 11.72 - 23.45 kW (40,000 - 80,000 Btu/h) of 100 mm to 510 mm.
• 2 metre horizontal flue system which provides a maximum
The boilers which are designed to provide domestic hot flue length of 1955 mm.
water and/or central heating must be used on INDIRECT hot • Vertical flue system which allows the flue to pass
water systems only. The cast iron heat exchangers are through a flat roof and terminate at a maximum height of
suitable for use on open vented gravity domestic hot water/ 1980 mm measured from the top of the boiler case.
pumped central heating systems or fully pumped systems
which may be sealed or open vented. Various kits are available for the Profile range of boilers, see
page 33.
Before installing the boiler on a gravity domestic hot water
system, consult the current building regulations as to any
restrictions.
1. Installation Requirements
1.1 Health and Safety Information for the Precautions - Dust goggles will protect eyes. People
Installer and Service Engineer with a history of skin complaints may be particularly
susceptible to irritation. High dust levels are only likely
Under the Consumer Protection Act 1987 and Section 6 of to arise following harsh abrasion. In general, normal
the Health and Safety at Work Act 1974, we are required to handling and use will not present high risk, follow good
provide information on substances hazardous to health. hygiene practices, wash hands before, touching eyes,
consuming food, drinking or using the toilet.
Small quantities of adhesives and sealants used in the First Aid - Medical attention must be sought following
product are cured and present no known hazards. eye contact or prolonged reddening of the skin.
Fan Mounting
WARNING
Plate
F F
Fan Supply
Leads
Gravity DHW/
Pump Over-run
Thermostat Overheat
Capillary Thermostat
Capillary
Combustion
Chamber
Pilot
Main Burner
Thermostat
Capillary Air Deflector
Retaining Clip Channel
PRF0001A
Gravity DHW/
Pump Over-run
Thermostat
Control Box
Gas Cock
Code Badge
Fig. 1
170
'D' 64
Electrical
*25
PRF0003A
Connections (35)
Inside Control
Box 100
'C' 143 143 143 143 Dimensions in brackets ( ) apply when the mounting plate is
'D' 87 87 107 107 inverted.
Fig. 2
Ventilated Cupboard/Compartment: If the boiler is installed in a cupboard or compartment, permanent air vents are
required in the cupboard or compartment, one at high level and one at low level, either direct to the outside air or to a room.
Both high level and low level air vents must communicate with the same room or must be on the same wall to outside
air. Both the high level and low level vent must each have a free area as stated below. The free area of each vent may
be halved if the ventilation is provided directly from outside.
The flue system can be run from either the left, right, rear or top of the
boiler.
M
D,E
L C
G G
B
F
K,N
FLU0001A
F
P A
A
H J J
G
• IMPORTANT: It is absolutely
ESSENTIAL, to ensure that products of Reduced Clearances
combustion discharging from the terminal
The Profile range of boilers has been tested and approved for use
cannot re-enter the building, or any other
with certain clearances less than those shown above.
adjacent building, through ventilators,
windows, doors, natural air infiltration, or Only one of these reductions may be used on a single
forced ventilation/air conditioning. If installation.
products of combustion are found to be re-
D Below a gutter, or sanitary pipework 25
entering any building, the appliance MUST E Below the eaves 25
be turned OFF IMMEDIATELY. F Below a balcony or carport roof 25
H From vertical drain/soil pipe work 75
J From an internal or external corner 25
Vent
Optional Optional
3 Port Zone
Valve Valves
Max. 30.5m (100ft)
Min. 305mm (1ft)
By-pass
balancing
valve
Top
of Heat Alternative By-pass arrangement using the
Exchanger Boiler Bathroom Radiator fitted with two locksheild valves
PRF0008A
Fig. 5
By-pass
balancing
Expansion valve
Vessel
Filling Point
Fig. 6
Fig. 7
PRF0011A
Fig. 8
The resistance through the heat exchanger with Disc Without Disc
when operating with a water flow rate Litres/sec gal/min KN/m² in wg KN/m² in wg
producing an 11°C temperature rise at
maximum boiler output are shown in the 40 .25 3.34 2.7 11.0 .75 3.0
table. If other controls such as three position
50 .32 4.17 4.0 16.0 1.25 5.0
valves are used in the system, the resistance
60 .38 5.0 5.7 23.0 1.75 7.0
through them, quoted in their manufacturers
80 .51 6.67 10.5 42.0 3.0 12.0
literature must be taken into account. The
pump may be fitted on either the flow or
return and MUST be wired directly to the
boiler terminal block. It must be fitted with kN/m² in wg
With
two isolating valves which are positioned as Injector
close to the pump as possible. Closing of 10.5 42 Disc
any valve must always leave the open vent
unobstructed.
9.0 36
7.5 30
6.0 24
4.5 18
3.0 12 Without
Injector
Disc
1.5 6
PRF0007A
Imp. Gall/min. 1 2 3 4 5 6 7
Litres/sec .076 .152 .227 .303 .379 .455 .53
PRF0012A
Note: Take into account the note within the boiler Fold
dimensions on Page 7. Line D
for RH
Flue
2.3. Boiler Mounting Plate Outlet Bottom of boiler Template
Fig. 9
Remove template and carefully cut flue outlet hole
through wall. If necessary, make good around the hole
to enable holes 'B' to be drilled.
Fixing
Wall Sealing Screw
Note: If using internal flue fitment kit refer to the Plug Collar (2 off)
Hole for
instructions supplied with the kit. Flue Outlet (2 off)
Cupwasher
screws provided, (accessory pack B). Make good the (4 off)
internal wall surface around flue sealing collar.
Fig. 10
Rear Flue
Fig. 13
Boiler Main
Assembly
Connector
PRF0017A
Controls Cover Fig. 14
5. Insert the assembly into the wall sliding the rope Note: If side fluing, loosen the two brass securing
sealing ring along the air duct into the flue sealing nuts beneath the flue elbow outlet and remove the
collar. Bend the six tabs on the flue sealing collar other two. Tilt the flange and withdraw the elbow.
inwards to retain the rope sealing ring. Ensure air
duct flange studs do not obstruct lifting of boiler The boiler is supplied with the flue outlet sealing plate
onto mounting bracket. removed on one side. If another flue outlet direction is
required, remove the appropriate flue outlet sealing plate
2.6. Prepare the Boiler and transfer it to the left hand position.
Wing
Nuts
PRF0019A
(4 off)
Fig. 16
Position boiler on its mounting bracket so
that the sides of the boiler line up with the
reference lines ‘C’ on the rear wall.
Adjustment
Screw
PRF0020A
Remove
Transportation
Foot
Fig. 17
Rotate the left hand adjustment screw to
align one of the holes in the base plate with
PRF0021A
Fig. 18
PRF0022A
Fig. 19
Olive
28mm
Nut
28mm Gravity
Return
Injector
Disc
28mm
28mm
Pumped
Fig. 20 Olive Return
Gravity
Flow
Injector Disc
Pumped Gravity
Flow Return
PRF0023A
Connect system pipework to the boiler, compression fittings should be used. Ensure that the flow and return pipes do not
rotate during tightening. The return pipe is marked with an identation, this should face towards the front of the boiler.
If however capillary fittings are used it is essential to temporarily remove the thermostat bulb from the flow pipe before
soldering.
A drain off tap should be installed close to the boiler if it is in a low point of the system.
On combined gravity hot water/pumped central heating installations the flow and return pipes for both the gravity hot water
circuit and pumped central heating circuit must be connected to tees fitted directly to the flow and return pipes on the boiler.
The injector disc (accessory pack H) must be positioned in the pumped return branch of the tee and the pipes connected
to the tees as illustrated in Fig. 20.
Connect the gas supply pipe to the inlet of the gas cock. Ensure that the gas cock is in a position where it can be easily
operated when the controls cover is removed.
PRF0025A
DHW system the bulb of the overheat Fully Pumped Gravity DHW
thermostat must be repositioned as shown System Position Position
in Fig. 21. To do this loosen the plastic
retaining screw and withdraw the thermostat
bulb from its pocket.
Fig. 21
Position the bulb as illustrated and secure it
by finger tightening the plastic screw. Do not
over-tighten.
The boiler and all external control circuit EXTERNAL ROOM AND/OR
wiring must be supplied from the same ELECTRICITY PROGRAMMER CYLINDER
SUPPLY THERMOSTAT
single isolating switch or plug and socket,
and should be fused at 3A.
4 OR 6 Core 4 OR 5 Core
Care must be taken to ensure that all wiring
to the boiler is kept clear of sharp edges and EXTERNAL 3 Core
ISOLATOR JUNCTION BOX
hot surfaces. SWITCH
PRF0024A
wiring from all the on site controls and CONTROL
therefore the installer will usually need to VALVES BOILER PUMP
ETC. 3 Core
incorporate a suitable junction box. This
may not be required if a Potterton Electronic
Programmer is used as this incorporates a
junction box. The principle of wiring is shown Fig. 22
in Fig. 22.
Securing Screw
Fig. 23
PRF0030A
Route a four core cable through the plastic bush
in the rear of the control box and the cable clamp
as illustrated in Fig. 24 and connect it to the
boiler input terminals as follows:-
If required, the gap between the casing sides and rear wall can be closed
off using the infill panels supplied.
Ensure the casing surface is fully clean and dry. Remove the protective
backing paper from the adhesive strip on the infill panel, carefully align
and press into place, applying firm even pressure down the full length of
contact area between panel and case. It conditions are near freezing, the
boiler case should be warmed prior to application of the infill panel.
Fig. 25
Sealed Systems Turn off the external electricity supply and gas service
cock.
Note: The system can be filled using a sealed system
filler pump with a break tank or by any other method Remove gas control valve plug from the test socket and
approved by the Local Water Authority. Refer to ‘The refit the plug into the socket on the left hand side of the
System’, Section 1.9, Page 9 in these instructions, also control box see Fig. 24.
BS6798: 1987.
Refit the combustion chamber front panel.
Remove pump and flush out the system thoroughly with
cold water. Refit the pump. Fill and vent the system until Fit the case door into position by lifting it onto the top
the pressure gauge registers 1.5 bar (21.5 Ib/in²). hinge brackets and secure it with the lower two fixing
Examine for leaks. screws. ENSURE THAT A GOOD SEAL IS OBTAINED
IMPORTANT: The pressure relief valve is factory tested Remove the temporary label from the front of the casing,
and does not need testing during the commissioning of having checked compliance with the information it
the boiler. It must not be used to reduce system contains.
pressure as it may cause debris in the system to foul the
valve. First Lighting
All Systems Warning: Before lighting the boiler, ensure that the
CASE DOOR HAS BEEN CORRECTLY FITTED and
Refit the fan assembly and reconnect the fan supply that the sealing strip fitted to the case door is forming a
leads, (polarity of the fan leads is not important). tight seal with the main boiler casing. Before proceeding
to light the boiler, check that the external electricity
The whole of the gas installation including the meter supply to the boiler is switched off and that the boiler
should be inspected and tested for soundness and thermostat is in the ‘0’ position.
purged in accordance with the recommendations of
BS6891. Turn on the gas service cock, ensure that the pump and
radiator isolating valves are open, ensure that the time
Test pilot unions for gas soundness as follows: Turn control, if fitted is in an on condition, and that the room
boiler thermostat to the ‘0’ position. and/or cylinder thermostats, where fitted are set to high
temperatures.
Unplug the gas control valve supply lead from the
control box and plug it into the test socket adjacent to Switch on the external electricity supply to the boiler.
the boiler thermostat knob, see Fig. 24.
In the event of an electrical fault after installation of the
Turn on gas at the gas service cock. appliance, preliminary electrical system checks must
be carried out i.e.:-
Ensure that the time control if fitted is in an ON
condition, and that the room and/or cylinder thermostats A. Earth Continuity
where fitted are set to high temperatures. B. Short Circuit
C. Polarity
Switch on the external electricity supply to the boiler. D. Resistance to Earth
Turn the boiler thermostat on and to a high setting and The pilot is pre-set and no adjustment is required. The
after a period of time the main burner will light, this can pilot flame envelope should cover the electrode tip and
be observed through the sight glass in the front cover of spark earthing strip, see Fig. 30. If the pilot flame is not
the boiler. The time period can vary upwards of 45 as illustrated, remove and clean the pilot as described
seconds, depending on the amount of air in the pipework. in the Servicing Instructions Section 4.3, Pilot Burner,
Page 26.
Test for gas soundness around the boiler components
using leak detection fluid. Boiler Thermostat
Turn the boiler thermostat to ‘0’. Note: There could be a At its minimum and maximum settings, the thermostat
delay in lighting if the control knob is switched on and off should control the water flow temperature at approximately
and then on again rapidly. 55 °C - 82 °C (130 °F - 180 °F).
Setting and Checking of Controls The thermostat has been calibrated by the makers and
no attempt should be made to re-calibrate it on site. Turn
With the controls cover removed. the thermostat to the ‘0’ position and check that the main
burner shuts down.
Fit a pressure gauge to the pressure test nipple in burner
supply pipe. See Fig. 1. Gravity Hot Water/Pump Over-Run Thermostat
Turn on the boiler thermostat and ensure that the main The function of this thermostat is determined by the
burner is alight. Check that the burner pressure is in position in which the GRAVITY/FULLY PUMPED
accordance with values stated on the Data Badge. SYSTEM selection switch is set. The thermostat is pre-
set and no adjustment is possible.
The gas valve is factory set, but if adjustment is required
follow section 4.8. On the FULLY PUMPED switch position it will operate
as a pump over-run thermostat and will keep the pump
With the burner set to its correct pressure, the firing rate running after the boiler has shut down, as long as the
given in Technical Data should also be obtained and water temperature within the boiler is above approximately
this should be checked by meter reading at least 10 80 °C.
minutes after the main burner has been lit.
On the GRAVITY switch position it will operate in series
Shut down the boiler, remove the pressure gauge and with the boiler thermostat when only the gravity domestic
refit the screw in the test nipple ensuring that a tight seal hot water circuit is in operation.
is made.
It will over-ride the boiler thermostat when the water
Refit the controls cover. temperature within the boiler is above 80 °C.
Relight the boiler and heat the system to maximum. Overheat Thermostat
Check for water leaks, turn the boiler off, drain the
system whilst hot. The overheat thermostat is pre-set and no adjustment is
possible. It will require manually resetting if an overheat
Refill the system and on sealed systems adjust to the condition occurs. Access to the reset button is through
correct cold fill pressure. Set the pressure gauge pointer a hole in the underside of the controls cover, see Fig. 1.
to the system design pressure.
Other Boiler Controls
If a by-pass circuit is fitted the by-pass valve should be
adjusted with the boiler operating under minimum load All boiler mounted controls are designed so that if any
conditions to maintain sufficient water flow through the fault should occur they will fail safe. No further setting
boiler to ensure that the overheat thermostat does not or checking is necessary.
operate under normal operating conditions.
PRF0028A
Burner Pressure
Seals
Adjusting Screw
Fig. 26
External Controls
User’s Instructions
Red
Black
Switched Live on 4 NO Pump
White
Fully Pumped Systems Brown 3
2 C Blue Boiler Thermostat
Domestic Hot Water Switched SwL NC
Live on Combined Gravity
D.H.W. Pumped C.H. Systems
Brown
Brown White
N
Blue
Brown
Brown White
T1
Blue GV2
Gas
Overheat T2
Control
Thermostat Black Valve
S1 S2
Blue GV1
Blue T3
Red
T7
Red Fan
T8
N
Blue PRF0029A
Fig. 27
R
R
BR
B BR
R
W
BR
BR R
BR B
BR
BR
G/Y
BK BR
Honeywell Gas Valve B
B
W W OR
BK W
W BR R
B R
G/Y
BR
B W G/Y
BK
G/Y G/Y
BK BK
B G/Y
W B
Colour Key
R
BR = Brown
BK = Black B BR Pump Mains
B = Blue
W = White L N SwL N L
PRF0033A
OR = Orange
G/Y = Green/ Yellow
L N SwL N L
This Appliance must be Earthed
All parts likely to require servicing are readily accessible. Note: After completing any servicing or replacement of
By removing the cover from the boiler controls and removing components check for gas soundness and carry out
functional checks.
PRF0032A
Gas
Control
Valve Plug
Burner
Securing
Screws
Gas Control
Valve/Support
Bracket Screw
Fig. 29
Note: Boilers with side or rear flues have a flue elbow A. Working from above and below the heat exchanger
fitted to the fluehood. use a suitable brush and remove all deposits from
between the fins.
The elbow is replaced by an adapter on vertically flued Slide vertical flue adapter into flue duct.
boilers.
B. Refit the fluehood, ensuring that the rope seal is
A. Remove controls cover by opening the door covering undamaged and that a GOOD SEAL is made with the
the securing screw on the underside of the controls heat exchanger. Fully tighten the four nuts.
cover, see Fig. 14. Undo securing screw, pull controls
cover forward 10 mm, lower it to release it from its C. Slide the flue elbow into the flue duct or lower flue
four side fixings and pull forward clear of the adapter and secure to the fluehood using four nuts.
thermostat knob. Ensure that the gasket between the fluehood and
elbow or adapter is undamaged and a good seal is
B. Remove door by undoing the lower fixing screws and obtained.
lift door off the two upper hinge brackets.
D. Reconnect flexible tubes to elbow or adapter.
C. Remove screws securing the combustion chamber
front panel and remove panel. Note: Red tube connects the front aluminium tube in
the upper chamber to the lower connection on elbow
D. Disconnect the fan supply leads from the connector or adapter, each being identified with a red ring.
adjacent to the fan.
4.3 Pilot Burner
E. Remove the screws securing the fan mounting plate
leaving in place the three screws identified with a red The following operations are only necessary if the pilot
circle or adjacent ‘F’ mark in fan plate. Remove flame is distorted or the wrong size, i.e. too small.
mounting plate complete with fan.
A. Check that the pilot screw Fig. 26, is fully open (turn
F. Disconnect the two flexible tubes from the flue elbow anti-clockwise).
or adapter.
B. Unscrew the aluminium pilot tube from the pilot
G. Loosen the two brass securing nuts beneath the flue assembly. Take care not to damage the electrode.
elbow outlet and remove the other two. Tilt the flange
and withdraw the elbow. Take care not to damage the C. Unscrew the two hexagonal head screws securing
gasket. On vertically flued boilers remove the four the pilot (and shield on 80) to the main burner and
brass nuts and slide the vertical flue adapter up into remove the pilot assembly, be careful that the pilot
the flue duct. injector does not fall out during this operation.
H. Unscrew the four nuts and lift off the fluehood taking D. Lightly brush the pilot and its shield to remove any
care not to damage the rope seal. deposits. Remove the pilot injector and clean its
Lower and lift out vertical flue adapter. orifice or replace.
I. Undo the union on the gas service cock outlet. Note: Do not use a wire brush or pin to clean injector.
J. Unplug the electrical supply leads for the gas control E. Gently clean any deposits from the electrode.
valve from the control box. See Fig. 29.
F. Refit the pilot injector to the pilot burner and assemble
K. Remove the screw securing the gas control valve to the pilot to the aluminium tube.
its support bracket. See Fig. 29.
G. Secure the pilot assembly to the main burner using
L. Disconnect electrode lead from electrode. two hexagonal screws.
M. Remove two screws securing the burner assembly H. Fully tighten the union nut connecting the aluminium
to the bottom of the boiler case and lift out the burner tube to the pilot. Check for gas soundness at this
and gas control assembly. joint by following the procedure described in the
commissioning section of these instructions, Page
21.
PRF0031A
motor and its supports.
A. Check the combustion chamber insulation for damage. Follow the full commissioning procedure as detailed in
If damaged replace as described under replacement. the Commissioning section of these instructions page
21.
A. Lightly brush any deposits from the top of each blade No further servicing is required on any other boiler
and ensure there is no fluff in the entry of the burner mounted units. Repair is by replacement.
venturi. If on re-assembly the burner flame picture is
incorrect or the correct gas rate or burner pressure Fault Finding
cannot be obtained, remove the burner and gas
control assembly and thoroughly clean the burner. Refer to Fault Finding Chart (page 32) and Wiring
Clean or replace the injector. In the event of the Diagrams (page 24).
above procedures not rectifying the flame appearance,
disconnect the burner from the gas control valve at
the flanged connection and replace the burner and
injector.
This operation is most easily carried out by first removing 4.10 Main Burner
the burner and gas control valve assembly as follows:-
1. Switch off the external electricity supply by
1. Switch off the external electricity supply by disconnecting the plug at the socket or switching off
disconnecting the plug at the socket or switching off the external isolating switch.
the external isolating switch.
2. Remove controls cover, case door and combustion
2. Remove controls cover, case door and combustion chamber front panel as described in 4.1.’Preparing
chamber front panel as described in 4.1.’Preparing the Boiler for Servicing’, operations A, B and C.
the Boiler for Servicing’, operations A, B and C.
3. Remove the burner and gas control assembly as
3. Remove the burner and gas control assembly as described in 4.1.’Preparing the Boiler for Servicing’,
described in 4.1. ‘Preparing the Boiler for Servicing’, operations I, J, K, L and M.
operations I, J, K, L and M.
4. Unscrew the union nuts connecting the pilot supply
4. Disconnect the electrical supply wires from the gas pipe to the pilot and gas control valve. Take care not
control valve noting their position. See Figs. 27 & 28. to damage the electrode and be careful that the pilot
injector does not fall out during this operation.
5. Unscrew the union connecting the pilot supply pipe
to the gas control valve. Remove sealing grommet and withdraw the pilot tube
through the hole in the burner mounting flange.
6. Separate the gas control valve from the flanges at
the inlet and outlet ports by removing the securing 5. Separate the burner from the gas control valve at the
screws. flanged connection by removing the four securing
screws.
Note: A spacer is used between the valve outlet and
the burner flange, requiring the use of two seals at Note: A spacer is used between the valve outlet and
this point. See Fig. 26. the burner flange, requiring the use of two seals at
this point. See Fig. 26.
7. Use new seals on re-assembly.
6. Unscrew the pilot, main burner injector and pressure
8. Replacement is the reverse of removal. test nipple from the burner.
9. Check that the burner pressure is in accordance with 7. Use new sealing gaskets on re-assembly.
the information on the data badge. If adjustment is
required, turn the pressure adjusting screw anti- 8. Replacement is the reverse of removal.
clockwise to increase pressure or clockwise to
decrease. 9. Follow the full commissioning procedure as detailed
in the Commissioning section of these instructions
4.9 Fan on page 21.
1. Switch off the external electricity supply by • white wire from terminal C (3) of the control
disconnecting the plug at the socket or switching off thermostat
the external isolating switch. • white wire from terminal NC (2) of the control
thermostat
2. Remove main burner as described in 4.1 ‘Preparing • brown wire from overheat thermostat
the Boiler for Servicing’, operations A, B, C, I, J, K, • blue wire from boiler terminal block connection N
L, M. • green/yellow wire from earth post
3. Bend back retaining tabs and replace insulation. It is 5. Release the control by lifting it from the four retaining
necessary to first remove the side insulation when lugs.
replacing the rear.
6. Remove electronic control.
4. Replacement is the reverse of removal.
7. Replacement is the reverse of removal.
5. Follow the full commissioning procedure as detailed
in the Commissioning section of these instructions 8. Follow the full commissioning procedure as detailed
on page 21. in the Commissioning section of these instructions
on page 21.
4.13 Fuse, 4.14 Electronic Control, 4.15 Pressure Switch,
4.16 Overheat Thermostat, 4.17 Boiler Thermostat, 4.18 4.15 Pressure Switch
Gravity HW/Pump Overrun Thermostat, 4.19 Heat
Exchanger Pipe Seal 4. Remove the screw securing the pressure switch to
the bracket in the control box. Lift pressure switch
Note: 4.13, 4.14 & 4.15 are on this page. 4.16, 4.17, from bracket.
4.18 & 4.19 are on page 30.
5. Disconnect the two plastic tubes.
The following initial operations 1-3 are necessary to
remove and replace any of the above items. Note: the red tube is connected to the pressure
switch connection identified with a red ring, or adjacent
1. Switch off the external electricity supply by red spot.
disconnecting the plug at the socket or switching off
the external isolating switch. 6. Disconnect the three electrical leads, white wire from
terminal No. 1 or NC, orange from terminal No. 2 or
2. Remove controls cover by opening the door covering NO and brown from terminal No. 3 or C. Refer to Figs
the securing screw on the underside of the controls 27 & 28.
cover see Fig. 14. Undo securing screw, pull controls
cover forward 10 mm, lower it to release it from its 7. Replacement is the reverse of removal. Ensure that
four side fixings and pull forward clear of the the plastic tubes are not kinked on re-assembly.
thermostat knob.
8. Follow the full commissioning procedure as detailed
3. Remove control box securing screw and lower control in the Commissioning section of these instructions
box. on page 21.
8. Replacement is the reverse of removal. Ensure the 4.18 Gravity Hot Water/Pump Overrun Thermostat
rubber grommet in the base of the boiler makes a
good seal around the capillary. Ensure that the 4. Remove door by undoing the lower fixing screws and
capillary is secure in the clips provided. Refer to Fig. lifting door off the two upper hinge brackets.
21.
5. Disconnect the electrical connections as follows:
9. Follow the full commissioning procedure as detailed
in the Commissioning section of these instructions 2 red wires from terminal NO (4)
on page 21. 2 brown wires from terminal NC (2)
1 white and 1 blue wire from terminal C (3)
4.17 Boiler Thermostat (These are the larger numbers marked on the
thermostat, ignore the smaller numbers).
4. Remove door by undoing the two lower fixing screws
and lifting door off the two upper hinge brackets. 6. Remove the screws securing the thermostat to the
control box.
5. Disconnect the fan supply leads from the connector
adjacent to the fan. 7. Remove the split pin retaining the thermostat bulb in
the pocket and withdraw the bulb.
6. Remove the screws securing the fan mounting plate,
leaving in place the three screws circled red (or with 8. Remove the split grommet in the base of the boiler.
adjacent 'F' mark), and remove the plate complete Feed the capillary and bulb through the hole.
with fan.
9. Replacement is the reverse of removal. The bulb of
7. Disconnect the electrical connections as follows:- the new thermostat should be coated with heat
conducting paste. Ensure the rubber grommet makes
White from terminal C(3). White from NC(2) - Refer to a good seal around the capillary.
Figs. 27 & 28.
10.Ensure that the capillary is secure in the clips
8. Pull off the outer thermostat knob. provided. Follow the full commissioning procedure
as detailed in the Commissioning section of these
9. Remove inner thermostat post by undoing the two instructions on page 21.
securing screws.
4.19 Heat Exchanger Pipe Seal
10.Remove the nut securing the thermostat to the
control box. 4. Remove door and fan mounting plate as described in
4.17, sections 4, 5 & 6.
11.If the boiler is fitted with a left hand flue, remove the
flue elbow as described in Section 4.1, Preparing the 5. Loosen pipe nut, lift pipe and remove seal.
Boiler for Servicing, operations F & G.
6. The return pipe is marked with an indentation, this
12.Remove the clip securing the thermostat bulb to the should face towards the front of the boiler.
flow pipe.
32 Fault Finding
With the boiler running, turn off at the boiler thermostat. Disconnect the white wire from GV2 on gas control valve and
Temporarily restrict the pilot gas supply by fully screwing in the connect it via a suitable test switch to neutral as shown. Set
All service on gas valve pilot screw clockwise. Turn on at the boiler thermostat: test switch to OFF. Insert an approved ammeter in series
a spark will be present, indicating GV2 is electrically disconnected, with the spark electrode.
Ensure system and the boiler will not light. Now reinstate the pilot supply (three Turn ON the electricity supply and restart the boiler.
change-over
switch in control
complete anti-clockwise turns); pilot and main boiler will light in the NOTE: The pilot will light but not the main burner as GV2 is
box is set normal manner. disconnected.
correctly Test When the pilot is established set the test switch to ON. This
Switch will stop the spark and allow a steady flame current to be
White wire N
Call for heat disconnected measured.
from GV2
Fully pumped
system only
Check full operational Does fan Yes Does fan run Yes Is electrode Yes Does Pilot Yes Does Pilot Yes Does main Yes Does boiler Yes Following a Yes Boiler Yes
operate? without sparking? burner light? cycle off and run period at operate Boiler
sequence to ensure light? remain lit?
cycling on/off on under maximum without operating
that the boiler and No No No No No satisfactory
pump overrun control of temperature, tripping the
No
5. Fault Finding Guide
thermostat Ensure there is Is case door Yes the boiler does pump overheat
leaking? Is there thermostat continue to thermostat?
are operating correctly 240 +
_ 10%
240v +_ 10% Yes when system operate after
between L & N No Yes Does spark
between is up to boiler No
and 240v +
_ 10% stop?
T2 & T3 on temperature. thermostat
between Swl Are sparks Yes electronic No See note operates?
and N. occurring
control? If gas is not
Fully pumped elsewhere?
flowing out No No
system. No Are all
Yes Has overheat No Check case door of pilot, check Check
Check pump is valves
thermostat seal and replace jet is not solenoid Yes
operating and open and
operated? if damaged. Fully blocked & pilot GV2 replace
water is water
tighten two lower screw on gas Switch off if necessary
circulating No Is there circulating
securing screws. valve open external
correctly. 240v +_ 10% correctly
Check fuse on, electricity
Gravity DHW between T2
electronic supply and
system ensure and T4
control follow the
overheat on electrode test Yes
thermostat Replace control procedure
bulb is located electronic Replace
Check all No described
correctly control electronic
appliances above.
see Fig. 21. control
wiring and Ensure air Is there
Press overheat
electrical pressure more than
reset button.
components. tubes are 1.5µA
not kinked recorded?
or blocked Check and/
and are or replace No
_
Is there 240v + correctly electrode
10% between fitted. lead
Yes T6 & T2 on
electronic control?
No Check Check that Replace Replace Replace
Check and/ Replace
Replace Check and/or or replace solenoid pilot is not electronic appropriate pump overheat
fan replace air air pressure GV1 replace partially control thermostat. overrun thermostat
pressure switch switch if necessary blocked. See note thermostat
PRF0034A
NOTE: When pumped central heating is
in operation the boiler is controlled by the
main boiler thermostat.
When only a gravity hot water circuit is in
operation the boiler is controlled by the
Fault Finding Chart main boiler thermostat when set at No.4
or below. At setting above No.4 the
temperature is limited by the operation
of the gravity control thermostat.
11
1 8
6
2
4
3 15 7
12
16 21
21
9
18
10
15 19
13
PRF0035A
17
Fig. 32
General Enquiries
Tel. &%$$%&
Technical *
Tel. &%$"'"'
Service *
Tel. &%$'$'$
Fax. ' $"$
Literature Request
Tel. &%$$$ !
* To aid continuous improvement and staff training, calls to this
line may be monitored or recorded.
All descriptions and illustrations provided in this leaflet have been care-
fully prepared but we reserve the right to make changes and improve-
ments in our products which may affect the accuracy of the information
contained in this leaflet. All goods are sold subject to our standard
Conditions of Sale which are available on request.
Baxi Potterton
Brownedge Road, Bamber Bridge
Preston, Lancashire
PR5 6SN
www.potterton.co.uk