Pipe Sizing
Pipe Sizing
2 in. 2 in. 2 in. 1¹⁄₂ in. 1¹⁄₂ in. 1¹⁄₂ in. 1¹⁄₄ in. 1¹⁄₄ in. 1 in. 1 in.
50 mm 50 mm 50 mm 40 mm 40 mm 40 mm 32 mm 32 mm 25 mm 25 mm
Upright sprinkler in
concealed space
Reducer
Ceiling
Nipple,
diameter
Tee
≥3
23.7.2.4 Unless the requirements of 23.7.2.5 are met, pipe sizing up to and including 2½ in.
(65 mm) shall be as shown in Table 23.7.2.4 utilizing the greatest number of sprinklers to be
found on any two adjacent levels.
23.7.2.5 Branch lines and cross mains supplying sprinklers installed entirely above or entirely
below ceilings shall be sized in accordance with Table 23.7.2.2.1.
A fire either above or below a ceiling in a light hazard occupancy will normally be contained in that
area by operating sprinklers (see 23.7.2.5). In light hazard pipe schedule systems, NFPA 13 permits more
The probability of a fire involving the areas both above and below a ceiling in a light hazard occupancy
and opening in excess of 50 sprinklers is extremely remote. When sizing piping for systems with more than
50 sprinklers, the pipe diameter is increased to 3 in. (76 mm) to reduce friction loss (see 23.7.2.6).
23.7.3.5 Where the distance between sprinklers on the branch line exceeds 12 ft (3.7 m) or the
distance between the branch lines exceeds 12 ft (3.7 m), the number of sprinklers for a given
pipe size shall be in accordance with Table 23.7.3.5.
Note: For other pipe and tube sizes, see Table 22.5.3.4.
The requirement of 23.7.3.5 recognizes the increased friction loss when either the distance between sprin-
klers on branch lines or the distance between branch lines exceeds 12 ft (3.7 m). The requirement also
recognizes that the sprinkler’s area of coverage must reach or overlap any adjacent sprinkler’s area of cov-
erage, so that a uniform water discharge and density are achieved. Increasing the pipe sizing as required
reduces pressure losses due to friction and results in a greater amount of pressure at the sprinkler. The
higher pressure increases sprinkler discharge and improves water distribution.
1 (25) 1 1 (25) 1
11⁄4 (32) 2 11⁄4 (32) 2
11⁄2 (40) 5 11⁄2 (40) 5
2 (50) 8 2 (50) 8
21⁄2 (65) 15 21⁄2 (65) 20
3 (80) 27 3 (80) 30
31⁄2 (90) 40 31⁄2 (90) 45
4 (100) 55 4 (100) 65
5 (125) 90 5 (125) 100
6 (150) 150 6 (150) 170
HISTORICAL NOTE
A set of pipe schedule design tables and flow values for extra tect facilities with fire hazards that are likely to operate a large
hazard occupancies were provided in NFPA 13 until 1991. Since number of sprinklers led to a restriction on the pipe schedule
then, concern about pipe schedule systems intended to pro- method for extra hazard occupancies.
Because many existing pipe schedule systems are currently in place, the selection table for extra hazard
occupancies has been retained in Annex A and appears as Table A.23.7.4.
American Fire Sprinkler Association, 9696 Skillman Street, Suite 300, Dallas, TX 75243-8264.
“Water Velocity: Its Impact on the Accuracy of Hydraulic Calculations,” 1996 (available at www.
sprinklernet.org).