Electrical Machines Lab Manual
Electrical Machines Lab Manual
The Electrical Machines – I lab evaluation can be broadly classified as per the contents
2. The end examination shall be conducted with external examiner and laboratory
teacher.
3. The external examiner shall be appointed from the cluster of colleges as decided
by the University examination branch.
Learning objectives:
The Significance of Electrical Machines-I is renowned in the various fields of
Engineering. For an Electrical Engineer, it is obligatory to have the practical idea about
the Electrical Machines-I.
Learning Outcomes
The student will:
Apparatus Required:
Motor
Generator
a) Rated Armature Voltage →
b) Rated full load Current →
c) Rated Speed →
d) Rated Power →
e) Type of excitation →
Fuse rating: For Open Circuit test 10% of rated full load current
Theory:
(i) When the field current is zero, there is some generated e.m.f
which is due to residual magnetism in the field poles
(ii) Over a fairly wide range of field current (in the initial portion)
the curve is linear. It is because in this range reluctance of iron
is negligible as compared with that of air gap. The air gap
reluctance is constant and hence linear relation ship.
Circuit Diagram:
3 - Point Starter
L A F
0 - 1A MC
20 A + -
+ A +
0 - 290 ohms
1.6A
R S
0 - 300V MC
220V, DC Supply
Z
+
A A
V
M G
-
AA AA
20 A ZZ ZZ
DC Shunt Motor
- -
DC Shunt Generator
5A
Dh
+
1500 ohms/1.2A
Supply
220V, DC
5A
-
DPST
Tabular Column:
Rated Speed of the Generator = ………….
Eg
X
Field Generated
Sl
Current EMF
No:
If (A) Eg (V)
1.
Conclusion:
Apparatus Required:
Theory:
Circuit diagram:
3 - Point Starter
L A F
0 - 5A MC
5A
+ -
+
+ A 0 - 1A
A MC
-
+ Z
0 - 300V
MC
V A
-
M
5A
AA
ZZ
-
DPST Switch
Part I:
Procedure:
1. Connect the circuit as shown in figure.
2. Insert the correct rating of fuse wires in the circuit.
3. Close the SPST switch and keep field rheostat in minimum
resistance position.
4. Start the motor with the help of starter and by adjusting the field
regulator of
the Motor Such That it runs at its rated speed given on the
nameplate.
5. Now open SPST switch and note down the values of supply
voltage V,
Line Current I Lo, Field current I f .
6. Calculate the efficiency of the machine as a Motor and as a
Generator
for Different Assured Values of load current I L.
Observations:
0
.
.
15A
0
.
.
15 Amp
Part II:
Circuit diagram:
0 - 5A MC
10 A
+ -
+ A
0 - 45 ohms / 5A
+
0 - 30V MC
15V DC Supply
A V
-
A
10 A
AA
-
DPST Switch
Tabular Column:
Sl Va ( V ) IL ( A ) Ra = (Va / IL)
No
1.
2.
3.
4.
Avg Ra =……..……..
Sample Calculation’s:
No load input = V I LO
Armature Resistance Ra =
Armature current Ia = IL - If
Input Power = V IL
Output = V IL
Expected graphs:
as a Generator
% Efficiency
as a Motor
o X
Load Current L
I in Amps
Conclusion:
Viva Questions:
1. Give another name for Swinburne’s test and give reason why it is
called so?
2. What are different methods of calculating efficiency of dc shunt
machine?
3. When a dc machine is run as motor and generator which I s having
higher efficiency?
4. Which method is accurate for calculating efficiency?
5. Give the direct and indirect methods for calculation efficiency?
6. Swinburne’s test can be done only on shunt machines why?
Department Electrical and Electronics Engineering
Geethanjali College of Engineering and Technology
Aim: To perform the Brake test on the given DC Shunt motor and
to obtain the performance characteristics of the motor.
Apparatus Required:
1. Rated Voltage
2. Rated Current
3. Speed
4. Type of Excitation
5. Power
Theory:
There are several tests that are conducted upon a DC
machine (Motor or Generator) to judge its performance. One
important test is performed to measure the efficiency of the DC
machine. Efficiency depends on its losses. The smaller the losses
the greater its efficiency and vice versa. The consideration of losses
in a DC machine is important because they determine the
efficiency of the machine and appreciably influences its operating
cost. And also they determine heating of the machine and
hence the power output that may be obtained without undue
deterioration of the insulation.
Circuit Diagram:
3 - Point Starter
L A F
25A 0 - 20 A MC
+ -
+ A
S1 S2
+ Z
0 - 300V MC
A
V
-
M
25A
AA ZZ
- r = .......................... m
DPST Switch
Procedure:
1. Make the connections as per circuit diagram.
2. Keep the field regulator of the Motor at minimum Resistance
position.
3. At the time of starting check that the belt on the pulley is
free, so that there is no load on the pulley.
4. Start the motor slowly by using stator
5. Adjust the field regulator so that motor runs at its rated
speed.
6. Apply load on the pulley gradually in steps by adjusting of
tension of spring Balance.
7. Take the readings of the Ammeter and Voltmeter and two
spring balance readings and the speed for each step.
8. Cool the pulley through out the loading period by pouring
water.
9. Continue the experiment till full load of the motor is reached.
Tabular Column:
Calculations:
Expected Graphs:
% Efficiency
Load Current
% Efficiency
Load Current
Torque
Speed
Speed
Torque
O X
Conclusion:
Viva Questions:
Apparatus:
S.NO Apparatus required Type Range Quantity
1 Ammeter MC 0-20A 1
2 Ammeter MC 0-2A 1
3 Voltmeter MC 0-300V 1
4 Tachometer digital 0-9999rpm 1
Theory
External characteristics
A plot of the terminal voltage VT and load current IL with
preset values of field current and speed gives External characteristics
curve. The drop in terminal voltage VT is due to armature reaction and
further reduction is due reduction in field current If, since the terminal
voltage fallen because of the above two reasons.
Internal characteristics
A plot of generated armature voltage Eg and armature
current Ia with preset value of field current and speed gives internal
characteristics. The drop in Eg is due to armature reaction and
further reduction in field current is due to drop in terminal voltage
and so on.
Procedure
1. Switch on the prime mover ( i.e. DC motor)
2. Adjust the field of motor to run the generator with rated speed
3. by adjusting the field of generator keep the terminal voltage VL
around 220V
4. Load the generator by keeping the speed of generator constant and
note the values of VL, IL and If.
5. Repeat step 4 till the rated load current is attained.
6. Reduce the load and w\switch off the supply
7. Plot the load characteristics as external and internal
characteristics
3-Point
starter (0 – 2) A ,(MC) (0 – 20) A (MC)
20 A 20 A
L A F + +
+● |●
●
A ●| ● A
| |
| |
| 360Ω,1.2A 360Ω,1.2A |
| |
| (0-300)V
|
(MC) D
+
220 V | D P | L
V
D.C. | P S | O
S
A Z A - T A
Supply Z D
| T |
| M G |
| AA AA |
| AA zzM
ZZG
AA |
● ●
__ ● ●|● A 20 A
20 A |
| |
| : |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
|Department Electrical and Electronics Engineering |
| |
| |
Geethanjali College of Engineering and Technology
Modelgraph:
Vt
Internal
External
Il
Tabular Form:
Result:
The load characteristics of the shunt generator are obtained.
Apparatus:
Theory
Procedure
1.Make the connections as shown in the figure
2.Ensure maximum resistance in armature circuit and minimum
resistance in field circuit, switch on the main supply.
3. Apply rated voltage across armature of the motor and adjust
the rated speed of motor
4. Apply rated excitation and note the readings of all meters
5. Keeping the excitation constant note down the speed and
reading of ll meter by decreasing the voltage across armature
step by step.
6. Repeat the steps from 3 to 5 with reduces excitations
7. Plot the curves W/N Vs N
0-5A
MC
5A +
+ || A
||
||
R2 10 Ω / 5A
||
||
|| 400 Ω /
|| 1.2A
||
||
|| A
||
||
|| F +
220V ||
D M V
P
D.C ||
S
Supply || 0-300V
T
|| MC
|| AA
||
||
|| FF
|| +
|| 0-2 A
A
|| MC
||
||
-
5 A
Q
Full excitation
W/N
θ1 S
P
Reduced excitation
θ2
R
N (rpm)
Model calculations
W/N = (A + C) + (B + D)N
From graph
OP = A+C -----------------(1)
Slope PQ =tan θ1=B+D------(2)
At reduced excitation constants C and D varies to C’ and D’
OR = A+C’ -----------------(3)
Slope RS=Tan θ2=B+D’ ----(4)
Result:
Iron and mechanical losses are separated for the given D.C.Shunt
machine.
Viva questions
1. What is meant by hysteresis losses
2. What is meant by eddy current losses
3. What are the different types of constant losses.
4. What is meant by stray load losses
5. Which losses are proportional to frequency of voltage
Theory:
There are several tests that are conducted upon a DC machine
(Motor or Generator) to judge its performance. One important test is
performed to measure the efficiency of the DC machine. Efficiency
depends on its losses. The smaller the losses the greater its efficiency
and vice versa. The consideration of losses in a DC machine is
important because they determine the efficiency of the machine and
appreciably influences its operating cost. And also they determine
heating of the machine and hence the power output that may be
obtained without undue deterioration of the insulation.
||
|| M
||
|| AA ZZ
BRAKE
_ ||
DRUM
||
|| 20 A
Procedure:
1. Make the connections as per circuit diagram.
2. Keep the field regulator of the Motor at minimum Resistance
position.
3. At the time of starting check that the belt on the pulley is
free, so that there is no load on the pulley.
4. Start the motor slowly by using stator
5. Adjust the field regulator so that motor runs at its rated
speed.
6. Apply load on the pulley gradually in steps by adjusting of
tension of spring Balance.
7. Take the readings of the Ammeter and Voltmeter and two
spring balance readings and the speed for each step.
8. Cool the pulley through out the loading period by pouring
water.
9. Continue the experiment till full load of the motor is reached.
Tabular Column:
Expected Graphs:
% Efficiency
Load Current
% Efficiency
Load Current
Torque
Speed
Speed
Torque
O X
Conclusion:
Viva Questions:
Apparatus
Disadvantages
The main disadvantage lies in the requirement of two identical machines
(0-2) A (MC)
CIRCUIT DIAGRAM: HOPKINSON’S
TTEST _
+ A
(0-10) A (MC)
3 – point
10 A
V
● ● || ● A Lstarter
A F + -
+ || + (0-600) V
|| (MC)
||
+
A (0-2) A
|| + (0-5) A (MC)
A +
|| _ (MC) (0-10) A
|| 18 Ω , 12 A A (MC)
360 Ω , 1.2 A
|| 360 Ω , 1.2 A
||
220 V ||
D.C. ||
||
Supply ||
||
|| A Z A Z
||
||
|| MA G ZZ
|| ZZ A
A A
_ ● ● |||| ●
10
|| A
||
||
||
Tabular form
Iam Iag IL Ifm Ifg V1m V2g
Model calculations:
AIM: To conduct the load test on DC series Generator and obtain the
characteristics.
APPARATUS REQUIRED:
THEORY:
L+ L-
_
20 A || ● +
+ ● ● || ●
||
A ●
||
A
Y ||
|| Y ||
|| LOAD
||
||
||
||
|| D
| P + (0-300)
YY D
220V S YY V
V P
DC T (MC)
A S
Supply - T
A
M AA
G
_ AA
● ● ● ● ●
20
A
PROCEDURE:
1. Connections are made as shown in fig-1.
2. Ensuring the field resistance of motor in minimum position and
generator field resistance in maximum position. Motor is switched
ON by dragging the starters handle slowly still it attains ON
position.
3. The speed of the Generator is adjusted, seen that it induces rated
voltage, by adjusting the motor to rated speed by varying the motor
field resistance.
4. At rated speed of the Generator, the voltage across the terminals is
noted.
5. At different loads on the Generator, the induced emf is noted and
also armature current is noted.
6. After noting all the values the motor is switched OFF by bringing
the field resistance of both motor and Generator to its initial
position.
7. Armature resistance and series field resistance is calculated by
armature-voltmeter method as shown in fig-2 and fig-3
respectively.
8. Ia (Ra + Rse) values are calculated and tabulated.
9. Graph for Vt versus If is plotted.
Il
Viva Questions:
APPARATUS REQUIRED:
Theory:
K x V-Ia Ra /Ф = K x Eb /Ф
Where V is the applied voltage and Eb is the back emf
Field Control :
In a D.C. shunt motor applied voltage is constant and hence the
exciting current is constant . The flux will have maximum value at no
load and because of armature reactance it will decrease slightly as load
increases. Neglecting this Ф can be regarded more or less as constant.
Eb1 α Ф1 N1
Eb2 α Ф2 N2
Ф2 = Ф1 Eb2/Eb1 * N1/N2
Thye speed is inversely proportional to the flux or field current. This
method of speed control is generally adopted to obtain speeds greater
than normal speed.
Armature control :
0-5 A 3 pt starter
MC
5A A
|| L F
+ ||
+ A -
||
|| 360 Ω, 1.2 A
||
||
|| 290 Ω, 2.8 A +
0-2 A
|| MC
|| A
|| D -
220 V || P
D.C. || S _
Supply || T -
|| A Z +
-
|| +
|| 0-300 V V
|| MC
|| -M M
V
|| C
|| AA
ZZ
5A
Procedure:
Field Control:
1. Keep the armature voltage constant and vary the field current in steps.
2. Note the field current and speed at each step.
3. Plot Va vs N and If vs N.
Result:
Viva Questions:
Apparatus Required :
1 Ammeter MC 0–5A 1
0 – 20 A 1
2 Rheostats WW 270 ohm / 1.2 A 1
1500 ohm / 1.2 A 1
3 Voltmeter MC 0 – 300 V 1
Theory :
Procedure :
1. The connections are made as per the circuit diagram
2. Ensuring the motor starter handle in off position, and
minimum resistance in motor field circuit the d.c main
supply is switched on and the motor is started using starter.
3. The speed is adjusted to its rated voltage by varying the
motor shunt field resistance.
4. Generator terminal voltage is adjusted to rated value using
generator field rheostat.
5. Vary the load in steps and note down the terminal voltage
and load current maintaining speed at rated value.
6. Draw the graph terminal; voltage Vs Load current.
7. Repeat the steps from (2) to (6) for circuits as shown in fig
(2),fig(3) and fig(4)
Tabular Form:
Si.No Load Terminal Voltage(V)
current(A)
Model Graphs:
Vt Cumulative
Differential
Il
|| ||
|| 20 A ||
|| ||
|| ||
|| || LOAD
|| Y ||
360Ω/1.2A ||
||
|| ||
360Ω/1.2A
D
220 V ||
|| P
D.C. ||
|| YY S
|| ||
Supply T
|| (0-300)V + ||
|| (MC) ||
V
|| ||
|| A Z A - ||
|| Z ||
||
|| M G ||
||
|| ||
AA AA ||
|| ZZ
|| ZZ ||
● || ●
●
CIRCUIT ●
● ||DIAGRAM: LOAD TEST ON DC DIFFERENTIAL SHORT SHUNT COMPOUND GENERATOR20 A
|| ||
||
Result:
Load characteristics of the given D.C.Compound generator are obtained for cumulative and differential modes.
Viva Questions:
Apparatus:
Theory:
In this method, two identical DC series machine, mechanically and
electrically coupled are required. This test gives efficiencies of both the
machines. Field’s test is not a regeneration one because of the generator
out put is wasted in resistances and not fed to motor.
Procedure:
1. Make the connections as shown in the fig.
2. Ensure maximum resistance in load circuit, switch –on the main
supply.
Department
3. The Electrical
speedandof Electronics
motor – Engineering
generator set speed is beyond its normal
value.
4. Note the meter readings under this condition.
Geethanjali College of Engineering and Technology
Motor efficiency
Motor input = V3 I1
Total motor losses (Wtm )= ( Ram + Rse) I12 +Wo
%Motor = ( V3 I1- Wtm / V3 I1) X100
Generator efficiency
Total generator losses (Wtg) = I22( Rag)+ ( Rse) I12+Wo
% Generator = ( V2I2 / V2I2 + Wtg ) X100
Tabular Form:
Result:
VIVA Questions:
1. Is it possible to conduct Swinburne’s test on DC series motor?
2. Can we conduct regenerative test on DC series motors?
3. What are the applications of series motors?
4.What is the purpose of connecting the two fields of machines in series?