UPS Comparison
UPS Comparison
Static
UPS: A Quantitative Comparison for
Cooling and IT Applications
Executive summary
A number of published comparisons indicate
that DRUPS is a superior solution for data
center cooling and IT applications. The inaccu-
rate assumptions and mistakes found in these
comparisons are explained with support from
third party sources. In this paper, we present a
detailed quantitative comparison from a design
architecture-level perspective between low
voltage DRUPS and low voltage Static UPS.
We consider capital expenses, energy losses,
maintenance costs, footprint, and TCO using a
common 2N architecture. The analysis shows
the Static UPS is less expensive to purchase,
install, operate, and maintain while having a
slightly larger footprint.
Schneider Electric – Data Center Science Center White Paper 222 Rev 0 2
Introduction Some published comparisons indicate that low voltage DRUPS is a superior solution
for data centre cooling and IT applications. When you consider the details of these
comparisons, however, it becomes apparent that they are often misleading and do
not provide a factual comparison. These comparisons often make the mistake of
using very old static UPSs with very poor efficiency curves and long battery auton-
omy, and the comparisons do not address how redundant-type design architectures
typically used in mission critical facilities today affect the analysis.
The following section lists common myths and explains them away.
1
White Paper 231, FAQs for Using Lithium-ion Batteries with a UPS
The analysis that follows in this paper addresses each of these common myths. It
assumes the DRUPs and Static UPS system is being used to back up the entire
data center with a 2N electrical infrastructure supporting both the IT and cooling
loads, although the static UPS architecture also uses a thermal buffer system to
ensure continuous cooling.
This paper offers a fact-based, “apples-to-apples”, and more realistic analysis that
quantifies the capital expense, total cost of ownership (TCO), maintenance costs,
and footprint to ensure better informed decision-making.
Methodology and A common 2N redundant architecture was used for this analysis (see sidebar). The
IT load density is assumed to be 6 kW/rack (average) for 500 IT racks. This yields a
assumptions total IT load of 3 MW.
In today’s data centres, a challenge that some face is an increase in rack power
density and higher density applications. In addition to this rise in density, ASHRAE
has expanded its recommendations for thermal limits in recent years encouraging
some to raise inlet air temperatures to increase economization hours. With increas-
ing densities and/or higher temperatures in the white space, an effective thermal
ride through strategy that keeps air temperatures from going too high in the event of
an outage becomes more critical. This strategy ensures the data centre and critical
plants are able to “ride through” the plant restart times and chiller loading time after
a power failure as the generators come on line, and vice versa, when the generator
is off line and grid power then returns.
The two most common strategies for maintaining cooling air during an outage
adopted by data centre designers and used in this analysis are:
• Thermal storage system (buffer tank of chilled water and static UPSs for fans/
pumps/ controls)
• Entire cooling system on DRUPSs
For the thermal storage system, the buffer tank is sized to offer 8 minutes of ride-
Design assumptions
through time before the chilled water supply temperature will begin to rise above its
summary set point. The Static UPSs provide backup to the chilled water pumps, chiller control
• 3MW IT load, 500 racks at system, CRACs and fan coil units. This ensures this equipment continues to deliver
6kW/rack average chilled water and cold air to the data centre as well as the M&E plant during the time
• Calculated cooling load - before backup power systems (e.g., generators) have started and begin to provide
945RT power.
• Water cooled chilled water
system at N+1
The battery runtime for the Static UPSs is 5 minutes which is typical for most data
• 8 - 15°C CHW temperature
• Canopy/ containerized type centers. Note that depending on the UPS model selected, it is possible to spec a
of generator shorter runtime to reduce capital expense and save space. This 5 minute runtime
• Static UPS: specification is more than sufficient to bridge the total duration required for the
o 2 paralleled 1600 kVA generator to start, ramp up to speed, and also to account for the timing delay for the
Symmetra MW UPSs at ATS switching.
2N for IT loads
o 400 kW Symmetra PX
In the DRUPS architecture, the entire cooling system and all IT equipment are
UPSs at 2N for cooling
loads supported by DRUPS. Remember that the Static UPS only needs to support some
• DRUPs: of the M&E plant to support the thermal ride-through process: chilled water pumps,
o Canopy/ containerized chiller controls, CRACs, and fan coil units (FCUs). It typically takes between 8 and
type of low voltage 12 seconds to go from a loss of utility power to completing the startup of the diesel
DRUPS generator within a DRUPS system.
o 2 paralleled 2000 kVA
DRUPs at 2N for IT
loads
See sidebar for all the design parameters and assumptions used in this analysis.
o 1670 kVA DRUPs at 2n Each subsection below details the comparison results on capital expense, UPS
for cooling load system efficiency, maintenance costs, footprint, and the 10 year TCO.
• Comparison and TCO
calculation focus only on The schematic diagrams for the 2N architectures are shown below. Figure 1
the electrical plant equip- illustrates the architecture where the entire facility’s IT and cooling loads are
ment supporting the whole
supported by DRUPS.
data centre
• Original calculations were
done in Singapore dollars
and were converted to USD
using a conversion rate of 1
Singapore $ to 0.7135
USD.
Figure 1
2N architecture using
DRUPS for IT and cooling
application (i.e., the full
data centre)
Figure 2 shows the architecture where a Static UPS system is supporting the IT and
cooling equipment (i.e., chilled water pumps, chiller controls, CRAC and FCU).
Buffer tanks are also present for storing chilled water to ensure there is sufficient
cooling before the alternative power source takes over in the event of an outage.
Figure 2
2N architecture using static
UPS for IT and cooling
application (i.e., full data
centre) with buffer tanks for
thermal ride through
Figure 3 illustrates the UPS efficiency curves based on one of the top DRUPS in the
market against Schneider Electric’s Symmetra MW Static UPS for the IT load and
Symmetra PX Static UPS for the cooling load.
100%
90%
System Efficiency
DRUPS 2000kVA
(One of the top DRUPS in market)
Symmetra MW 1600kVA
80%
70%
Figure 3 60%
UPS efficiency as a 0% 10% 25% 50% 75% 100%
function of % load Load
100%
90%
System Efficiency
DRUPS 1675kVA
(One of the top DRUPS in market)
Symmetra PX 400kVA
80%
70%
60%
0% 10% 25% 50% 75% 100%
Load
As you can see from the above figure, the efficiency of Static UPSs has improved
significantly over the years especially at low load conditions. The gap between
Static UPSs and DRUPSs widens substantially when the load drops below 50%,
which is very common in data centres today and is, indeed, required for a 2N
system.
The Static UPS has 68% less energy losses than the DRUPS. This has a major
impact on TCO which will be shown later in this paper. Table 1 shows the details.
Footprint analysis
There is a common market perception that Static UPSs always take up much more
space than a DRUPS system due to the battery storage space requirement.
However, our more detailed analysis which was based on commonly used design
architecture and more realistic assumptions regarding the application showed that
the difference in footprint between the two systems is not nearly as significant
as commonly thought.
Let’s take a look at the below comparison. Apart from the actual equipment dimen-
sions, the electrical plant layout below also takes into consideration the space or
access necessary for maintenance.
Figure 4
DRUPS – 2N topology
overall plant layout (IT
and Cooling loads)
Figure 5
Static UPS with 5 min of
runtime and thermal
storage tanks– 2N
topology overall plant
layout (IT and partial
Cooling loads)
In this real world example, the Static UPS system requires only 4.3% more
space than the DRUPS system. Note that this calculation even includes the area
required for the thermal storage tanks.
TCO Savings (Static UPS) excluding potential rental gains over 10 years –
$5,892,095 (approx 7% savings).
Based on this example, the Static UPS system costs less to purchase and
install, maintain, and operate.
Table 3 shows that a full 2N Static UPS system’s electrical infrastructure supporting
both the IT and cooling loads of a data centre has a 10 year TCO savings of
$5,892,095 (7.2%) over a full 2N DRUPS electrical infrastructure, but at a small
2
penalty of needing 48 m additional floor space.
So if the data center in our example analysis was a collocation data center, how
might the potential rental gains in the DRUPs scenario affect the overall TCO? We
assumed a rough rental rate estimate of $1285/rack per month. Note that this is
gross revenue and not profit.
For a full 2N Static UPS electrical infrastructure supporting both the IT and cooling
loads of a data centre, the overall 10 year TCO savings using a Static UPS
system vs. a DRUPs system (including money earned through increased rental
space in the case of the DRUPs-based architecture) is $2,932,695 (3.7%
savings).
A way to overcome this power limitation of the low voltage system is to move to a
medium voltage (MV) distribution solution. This topic is the subject of another
research project at Schneider Electric and its analysis will be released in another
white paper in the future.
Additional In the Appendix, several other analyses are shown in detail to compare DRUPSs
and Static UPSs under different architectures and for specific applications. These
comparisons additional comparisons include:
NOTE: IF you take the potential additional rental gains into account that the
extra space provides, the DRUPS system 10 year TCO is 10.6% better than the
Static UPS system TCO.
NOTE: With rental gains taken into consideration, the overall TCO savings is
reduced slightly from 3.2% to 2.6%.
2
NOTE: If rental gains are taken into consideration, the 88 m space savings
will increase overall 10 year TCO savings from 12.1% to 56.3% in favor of
Static UPSs.
2
NOTE: If rental gains are taken into consideration, the 69 m space savings will
increase overall 10 year TCO savings from 9.5% to 24.7% in favor of Static
UPSs.
Conclusion Using the common 2N architecture described above as an example, this paper
demonstrated how it is important to consider the entire system and facility when
comparing capital expenses, energy costs, maintenance costs, footprint, and overall
TCO between one data centre backup system type and another. The analysis
described in this paper clearly showed that a data centre physical infrastructure
architecture employing a low voltage Static UPS system outperformed the same
architecture using a low voltage DRUPS on all of these comparison points except
footprint.
Hng Yong Way is the Principal Engineer for DC Centre of Excellence at Schneider Electric. He has
over 13 years of experience in the area of consulting engineering, project and construction
management including extensive experience in the concept and detailed design in particular
mission critical facilities, institutions, residential and commercial developments.
Sanjeet Sandhu is Vice President for the DC Centre of Excellence at Schneider Electric. Sanjeet
heads a team that supports the strategy and delivery of the full lifecycle of Data Centre Services
that include consulting, design, project execution, assessments, software, and managed services
(including critical facility operations). Sanjeet is a registered Professional Engineer in Singapore.
Browse all
TradeOff Tools™
tools.apc.com
Contact us
© 2016 Schneider Electric. All rights reserved.
For feedback and comments about the content of this white paper:
Data Center Science Center
[email protected]
If you are a customer and have questions specific to your data center project:
Contact your Schneider Electric representative at
www.apc.com/support/contact/index.cfm
Appendix
IT load only The IT application comparison looks at the commonly adopted redundancy architec-
tures, i.e. 2N topology. The IT load density is assumed to be 6kW/rack for 500 IT
comparison – racks with a final IT load of 3MW.
2N architecture
Each subsection below details the results of the capital expense, UPS system
energy loss, maintenance costs, footprint, and total cost of ownership (TCO) for the
Design Parameters
2N topology. Schematic diagrams of the two 2N architectures for IT application are
and Assumptions shown above in Figure 1 for DRUPS and Figure 2 for Static UPS in the earlier
• 3MW IT load, 500 racks at section of this paper.
6kW/rack
• Canopy type of generator The ride-through time for DRUPS flywheel is 8 – 12 seconds and the battery runtime
• Canopy type of DRUPS for the Static UPS is a typical 5 minutes, though it can be further reduced depending
• Comparison and TCO on the selected UPS model.
calculation focus only on
the electrical plant equip-
ment supporting the IT See sidebar for all the design parameters and assumptions used in this analysis.
infrastructure only - "varia-
ble" UPS system energy loss analysis
• M&E plant supporting
lighting, general purpose The UPS utilization factor is 47% for both DRUPS and Static UPS under normal
power, cooling load, and operating conditions based on the total IT load of 3000kW with 2N topology. An
other main equipment, e.g. energy loss comparison based on 2N topology shows the difference of energy loss
chiller, CRAC, etc. are between a DRUPS and a Static UPS.
excluded from the case
DRUPS System – approx. 680m2 (7,319 ft2) Static UPS System – approx. 816m2 (8,783 ft2)
Figure A1
IT application – 2N
architecture overall plant
layout
However, if take rental gains from the additional 20% plant space into consideration,
the 2N DRUPSs have a TCO savings of 10.6% in 10 years over the 2N Static UPSs.
In this case, for a sole IT load application the 2N DRUPSs perform better than the
2N Static UPSs.
IT load only In this section, a tri-redundant design with the same assumptions for the IT load is
analyzed. The same set of design parameters and assumptions were used here as
comparison – in the 2N architecture. Figure A2 and A3 show the basic schematic diagram of the
Tri-redundant architecture
architecture
Figure A2
DRUPS, tri-redundant
architecture diagram for
IT application
Figure A3
Static UPS, tri-redundant
architecture diagram for
IT application
Footprint analysis
For the tri-redundant architecture, the footprint difference is marginal. The Static
UPSs take up 1% more space than DRUPSs.
DRUPS System – approx. 568m2 (6,114 ft2) Static UPS System – approx. 574m2 (6,178 ft2)
Figure A4
IT application – Tri-
redundant architecture
overall plant layout
TCO analysis
TCO analysis based on a 10 year life cycle was done using the same assumptions
and parameters.
From the analysis, it demonstrates that Static UPSs provide better values and better
overall TCO compared to DRUPSs, with a marginally higher space requirement of
an additional 1.05%. The overall TCO savings for 10 years is 3.2%, approximately
$1.79 million.
With rental gains into consideration, the overall TCO savings reduced slightly from
3.2% to 2.6%.
Cooling load only Each subsection below details the results of the capital expense, UPS system
energy loss, maintenance costs, footprint, and total cost of ownership (TCO) for the
comparison – 2N topology. Schematic diagrams of the two 2N topologies for IT application are
2N architecture shown in Figure 1 for DRUPS and Figure 2 for Static UPS in the earlier section of
this paper.
Footprint analysis
Based on a 2N architecture, the Static UPSs are more space efficient. It takes
19.6% less space compared with DRUPSs.
DRUPS System – approx. 448m2 (4,822 ft2) Static UPS System – approx. 360m2 (3,875 ft2)
Figure A5
Cooling load only – 2N
architecture overall plant
layout
Design Parameters
and Assumptions
TCO analysis
• Calculated cooling load -
945RT For Static UPS, the capital cost of the For DRUPS, the capital cost of the below
• Water cooled chilled water below main equipment are included main equipment are included
system in N+1,
• 8 - 15°C CHW temperature
• 1600kVA prime rated canopy gen- • 1675kVA canopy diesel rotary UPS
• Canopy type of generator
erator • Main switchboards
• Canopy type of DRUPS
• Comparison and TCO • Main switchboards c/w automatic • Main distribution boards
calculation focus only on transfer switch
the electrical plant equip-
ment supporting the cooling • Main distribution boards
infrastructure only - "varia- • 400kW Symmetra PX static UPS
ble" c/w 6 min battery
• M&E plant supporting IT
load, lighting, general • N+1 FCU for UPS and battery
purpose power and other room
main equipment, e.g. IT
• Buffer tanks 2 x 28.6 m3
UPS, etc. are excluded
from the case study for
simplicity - "constant"
TCO Savings (Static UPS) over 10 years – $2,752,474 (approx 12% savings)
IT load only Same set of design parameters and assumptions were used here in the tri-
redundant architecture where the battery autonomy for the Static UPSs is sized to
comparison – offer 6 minutes to match the short ride-through time of a DRUPSs’ flywheel (8 – 12
Tri-redundant seconds) for a more accurate, “apples to apples” comparison.
architecture The two tri-redundant architectures for the cooling application are shown in the
diagram below; one used a DRUPSs (Figure A6) and the other used a Static UPSs
Design parameters (Figure A7).
and assumptions
Same set of parameters and
assumptions as per the 2N
topology with the exception of
the below:
Figure A6
DRUPS – Tri-redundant
architecture diagram for
cooling application
Figure A7
Static UPS – Tri-
redundant architecture
diagram for cooling
application
Footprint analysis
In a tri-redundant architecture, the Static UPS system is more space efficient. The
area consumed by the equipment is11.4% less than a comparable DRUPS system.
DRUPS System – approx. 605m2 (6,512 ft2) Static UPS System – approx. 536m2 (5,769 ft2)
Figure A8
Cooling application – tri-
redundant architecture
overall plant layout
TCO analysis
TCO analysis based on a 10 years cycle was done using the same assumption and
parameters.
TCO Savings (Static UPS) over 10 years – $4,074,401 (approx 10% savings)
This demonstrates that the Static UPS system provides better value and better
overall TCO compared to a DRUPS system. The TCO savings for 10 years is very
substantial at 9.5%.
2
If rental gains are taken in consideration, the 69m space savings will increase
overall 10 years TCO savings from 9.5% to 24.7% in favor of Static UPSs.