Applying Orthogonal Combination Procedure As Per ASCE-7-05 For SDC C in Etabs Program. - Computers and Structures - ETABS - Eng-Tips
Applying Orthogonal Combination Procedure As Per ASCE-7-05 For SDC C in Etabs Program. - Computers and Structures - ETABS - Eng-Tips
Dear all,
Structures that have horizontal structural irregularity Type 5 in Table 12.3-1 (non-parallel system), ASCE-7-05 requires to take
take 100%of seismic force in one direction + 30% of seismic force in the other direction.
Example Ex+0.3Ey.
for the case of doing dynamic analysis ( response spectrum) in etabs and after defining respose spectrum function.
3-input response spectrum do we combine the two directions of seismic forces (U1 & U2)in one response
spectrum case or we do it separatly for every seismic force direction?
Reviewing ACE OCP: A Simple, Easy-to-Use Career Advancement Starts with Awareness!
Program for the AEC World
Sunny Egypt Interested in Wind Power Gestures and Pens: The Perfect Combination
for 3D Sketching
Would reference you the analysis reference that comes with the program for a lot of this, but for short answers:
1. I use CQC. CQC can account for coupling of modes. SRSS cannot. Both are acceptable per ASCE 7.
2. You can do either. I usually use both just to make sure I'm covered. See below.
C. 100% U2 (ABS combination, though could be SRSS since it's only one direction)
D. 100% U2 + 30% U1 (ABS combination)
E. 100% U1 + 100% U2 (SRSS)
I typically find that either B and D governs.
4. I generally don't do input a response spectrum for Z (vertical) direction. Vertical response spectrum accelerations tend to be
very site specific, depending on many more factors than a standard response spectrum can hope to address. As far as I know,
there are no response spectrum functions for vertical acceleration provide in ASCE 7. Vertical acceleration is accounted for in
ASCE 7 through amplifying the dead load by 0.2*Sds. See 12.4.2.2 and 12.4.2.3
Dear MarkHirschi,
really i am very Grateful for you help,but i still have some questions if you don't mind.
note: after running the analysis the scale factors should be modified to make (static force = dynamic force) before starting
design of the structure.
best regards
To start, the scaling factor should be Ig/R. The dynamic base shear must be at least 85% of the static.
See: https://wiki.csiamerica.com/display/etabs/Scale+fa... . I knew an engineer that had a building where scaling
with Ig/R yielded a higher base shear than static. I think he was stuck with the higher base shear (I always wondered if
something was wrong with the model). The code does not say you can decrease the dynamic base shear because it is higher
than the static.
https://www.eng-tips.com/viewthread.cfm?qid=349597 2/2