This document provides busbar sizing recommendations for Masterpact circuit breakers based on temperature and current load. It includes a table with the number and size of copper busbars recommended for different Masterpact models based on the maximum service current and temperature around the circuit breaker. An example is also given of determining the proper busbar sizing for a 1800A load at 50 degrees C temperature, recommending three 80x5mm bars or two 63x10mm bars. The document notes that the values are only a guide and cannot replace testing or experience.

Uploaded by

andri prista
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
142 views

ACB Busbar Sizing

This document provides busbar sizing recommendations for Masterpact circuit breakers based on temperature and current load. It includes a table with the number and size of copper busbars recommended for different Masterpact models based on the maximum service current and temperature around the circuit breaker. An example is also given of determining the proper busbar sizing for a 1800A load at 50 degrees C temperature, recommending three 80x5mm bars or two 63x10mm bars. The document notes that the values are only a guide and cannot replace testing or experience.

Uploaded by

andri prista
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Installation

Busbar sizing  0

recommendations

Basis of tables:
b maximum permissible busbars temperature: 100 °C
b Ti: temperature around the circuit breaker and its
connection
b busbar material is unpainted copper.

Front or rear horizontal connection


DB101484

Masterpact Maximum Ti : 40 °C Ti : 50 °C Ti : 60 °C
service No. of 5 mm No. of 10 mm No. of 5 mm No. of 10 mm No. of 5 mm No. of 10 mm
current thick bars thick bars thick bars
thick bars thick bars thick bars
NT06 400 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10
NT06 630 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10
NT08 ou NW08 800 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.63 x 10
NT10 ou NW10 1000 3b.50 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10
NT12 ou NW12 1250 3b.50 x 5 2b.40 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10
2b.80 x 5 2b.40 x 10 2b.80 x 5
NT16 ou NW16 1400 2b.80 x 5 2b.40 x 10 2b.80 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10
NT16 ou NW16 1600 3b.80 x 5 2b.63 x 10 3b.80 x 5 2b.63 x 10 3b.80 x 5 3b.50 x 10
NW20 1800 3b.80 x 5 2b.63 x 10 3b.80 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10
NW20 2000 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 3b.100 x 5 3b.63 x 10
NW25 2200 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 4b.80 x 5 2b.100 x 10
NW25 2500 4b.100 x 5 2b.100 x 10 4b.100 x 5 2b.100 x 10 4b.100 x 5 3b.80 x 10
NW32 2800 4b.100 x 5 3b.80 x 10 4b.100 x 5 3b.80 x 10 5b.100 x 5 3b.100 x 10
NW32 3000 5b.100 x 5 3b.80 x 10 6b.100 x 5 3b.100 x 10 8b.100 x 5 4b.80 x 10
NW32 3200 6b.100 x 5 3b.100 x 10 8b.100 x 5 3b.100 x 10 4b.100 x 10
NW40 3800 4b.100 x 10 5b.100 x 10 5b.100 x 10
NW40 4000 5b.100 x 10 5b.100 x 10 6b.100 x 10
NW50 4500 6b.100 x 10 6b.100 x 10 7b.100 x 10
NW50 5000 7b.100 x 10 7b.100 x 10
With Masterpact NT, it is recommanded to use 50 mm wideness bars (see “Recommended busbars drilling”).

Example
Conditions:
b drawout version
b horizontal busbars
b Ti: 50 °C
b service current: 1800 A.
Solution:
For Ti = 50 °C, use an NW20 which can be connected
with three 80 x 5 mm bars or two 63 x 10 mm bars.

Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.