Two-Phase Flow Venting From Reactor
Two-Phase Flow Venting From Reactor
vessels
This pdper provides an overview of the emergency relief requirements for reactor vessels under
runaway conditions. The importance of utilizing appropriate thermokinetic data in providing the
necessary energy release rate and pressure generation rate is emphasized with experimental styrene
data. The effect of two-phase flow venting on reducing the volumetric flow capacity of a pressure
relief device is clearly elucidated. In addition, the paper presents a concise and unified treatment of
two-phase flashing flow in the form of formulae and design charts covering single component fluids,
multicomponent mixtures, nozzles, long pipes, elevation changes, and back pressure effects.
Finally, the effect of allowing for overpressure in lowering the required relief area during two-phase
venting relative to the no overpressure case can be quickly assessed via the proposed normalized
relief sizing formula.
Emergency relief systems (ERS) are installed to protect identified above in terms of the energy release rate and
process vessels from the catastrophic effects of an the pressure generation rate.
excessive overpressure and subsequent rupture. The Characterization of the flow regime behaviour in both
purpose of this paper is to focus on this important ERS the vessel and the relief system.
technology particularly in view of the recent advances Safe disposal of the relief discharge when the material
upon completion of the Design Institute for E1yrgency is considered too hazardous to be vented directly to the
Relief Systems (DIERS) research program ’ Relief atmosphere.
devices, properly sized only for the vapour load, may
‘Ihe discussion in this paper will be centred around the
often be ineffective because of the inadequate disen-
second and third considerations. However, it is equally
gagement of the vapour from the liquid and the resul-
important to recognize that the first item is by far the
ting two-phase flow. Numerous articles3-5, have
most difficult to define, and in fact the whole design
appeared in recent years dealing with emergency relief
rests on the adequacy of this ‘worst case’ to cover all
sizing for two-phase flow situations. Our approach is
credible upset conditions.
not to illustrate the use of these various design methods,
but rather to build on the existing technology. Speci-
fically, we will present a unified treatment of two-phase Thermokinetic data
flashing flow in pressure relief systems and downstream
Thermal data in terms of temperature and pressure are
piping with particular reference to multicomponent
crucial in the relief sizing calculation for the case of
mixtures, frictional losses, elevation changes, and back
runaway chemical reactions. As will be discussed later,
pressure effects.
these data provide the equivalent vapour/gas volumetric
To begin, the proper and safe design of an ERS for
generation rates. The approach based on detailed
coping with an uncontrolled runaway reaction requires
modelling of reaction kinetics and vapour-liquid-
the following considerations:
equilibrium (VLE) is often both time-consuming and
l Identification of the worst credible upset scenario to cost ineffective. However, it does offer the versatility of
establish the design basis. being able to extend the data to related conditions that
l Thermal characterization of the runaway reaction may be necessary to evaluate process variable changes.
In general a runaway reaction can best be experimen-
tally simulated in an apparatus that has a low thermal
inertia and thus approaches the behaviour in a process
This paper was presented at the ASME Winter Annual Meeting,
vessel. Such a bench-scale apparatus has been developed
27 November-2 December 1988, Chicago, Illinois, USA
as part of DIERS research program6,‘, and is available
Received I7 JQN&U~ 1989 commercially under the name Vent Sizing Package
0950-4230/89/020078-09S3.00
Zl 1989 Butterwonh & Co. (Publishers) Ltd
78 J. Loss Prev. Process lnd., 7989, Vol2, April
Two-phase flow venting from reactor vessels: J. C. Leung and H. G. Fisher
: 0.25
0.50 0.25
0.50 0.25
0.00 0.25
0.00 323.8
160.3 0.15
0.29 2660
3700 40.3
19.2 3050
1516 3100
1511 0.984
1.003
3 0.25 0.49 0.25 0.01 195.3 0.22 2970 30.1 1940 1960 0.990
4 0.25 0.25 0.45 0.05 273.1 0.15 2720 20.8 2690 2710 0.993
5 0.05 0.25 0.45 0.25 398.6 0.10 2200 13.6 3960 4020 0.985
o in the range of 2@40 (typical values for most organics calculated ” using the formula
in the low quality region) as shown in Figures 4 and 5. Go (-2[wln 773+(w- l)(l- TJ~)])“’
Similar plots have also been presented by First and (9)
) PPO LOU/q3- 1) + 1
Huff l2 with xo instead of w as the correlating param-
eter. where Ga is the mass flux for the nozzle and 73 = P3/P,
i.e., the ratio of the back pressure Pa to the stagnation
E~ofekvationdmnge pressure P. It is convenient at this point to introduce a
To extend the above pipe flow correlation to include correction factor due to unchoked flow CF. Graphically,
elevation changes, an additional parameter in the form the results can be presented as CF versus
of (1 --~a)/l-noc) as shown in Figure 7. Once again the
additional correlating parameter is w. The critical values
Fr=gD-e p0gDc-e G,, and not are obtained from the corresponding nozzle
(8)
4fPvo 4fP correlations in Figure 3.
is required where 0 is the angle of inclination of the vent For the case of a vent line, the following approximate
line from the vertical. This is a modified Froude number formula has been found to yield reasonable results for
with the Fanning friction factor term 4 f incorporated in subcritical flow,
the denominator so as to allow use of the same value in
2(r1-9a- N Fr/ea)l I”
both N and Fr. F&m-e 6 presents such an extended (10)
NEa + 2(e3 - El)
correlation for situations commonly encountered in
reactor relief sizing (i.e., w ranging from 20 to 40). As and
shown, the higher the Froude number, the greater the
flow reduction or the smaller the critical discharge
p, = 773+ NC1 + W but limiting 71 not
l+N
coefficient at a given L/D. Note that this Froude to exceed 1.0. (11)
number does not explicitly contain the elevation change
ta = (VI + ?3)/2
term. But-for a given L/D and cos 0, a larger diameter
pipe would give rise to higher Froude number and larger 773 = P3lP
Figure 6 Generalized correlation for flashing choked flow in a Figure 7 Generalized correlation for flashing flow in nozzles and
pipe with elevation change horizontal pipes with back pressure effect (Fr = 01
113> Q (unchoked).
Co
>V3%QXIO) approximate G/G, as
nozzle case is first obtained from Figure 3. Then the The Arrhenius nature of a chemical reaction can be
mass flux G is simply given by C&G,,. Again, Equation approximated by the following formula*,
(10) offers an equally acceptable alternative. The
example in the appendix illustrates the use of these :=;[I +exp(+J] (22)
methods in various situations.
where A Ta is the temperature increase needed to double
the reaction rate and AT is the over temperature
Venting with ova-pressure
corresponding to the selected overpressure AP, these
Leung’ presented a closed form relief sizing formula for latter two quantities are =lated via the Clausius-
the case of homogeneous-vessel venting applicable to a Clapeyron equation. Up0 stitution, a generalized
wide range of overpressure. The equation as repeated relief sizing equation is ot
below reduces exactly to Equation (3) ‘when no over-
1 + exp[w”‘PAP/PJ
pressure is permitted, +,,= (2 + AP/P,)[l + (wAp/M”21’ (23)
~=o.5cp[(~)s+
($J (18) (24)
Here subscripts s and p denote the conditions corres- Equation (23) suggests that as long as the physical
ponding to the set pressure and the peak turnaround parameters w and 6 are similar in any two systems,
pressure, respectively. the normalized vent area AlAa variation with the
The effect of overpressure on the required relief area normalized overpressure AP/ P, will be identical.
can best be illustrated by transforming Equation (17) The above-mentioned similarity can be demonstrated
into dimensionless form. By making use of Equation (3) using the styrene and phenolic reaction systems dis-
and the definition for w, the following equation is cussed in Leung’. Here both ue (or V/me) and AT2 for
obtained the phenolic case are judiciously chosen so as to yield
the same 8 value as the styrene case. Although the
GA (&Is )
(19) individual physical properties tabulated in Table 3 are
G,Ao = [lt (wAP/P~,“*12
quite different from each other, both systems yield an w
where G, would denote the mass flux at the set pressure. value of 2.5 and a /3 value of 0.4. Figure 8 shows the
In this equation the first term 010 in the definition of w prediction according to Equation (23) compared with
has been Adropped thus the results based on numerical integration of the time-
2 dependent mass and energy equations. These so-called
O.! j7-
0.'
0.:
s
0.:
ReComnended
0. L- 0.I-
( )-
0 0. I 0.2 0.3 0.4 0.5 0 0.1 0.2 0.3 04 0.5
AP/P, AP/P,
Figure 8 Generalized relief sizing equation in comparison with Figure9 Generalized relief sizing equation in comparison with
exact numerical solutions for w = 25: 0, styrene reaction; 0, DIERS styrene relief data: 0, ICRE-32 (top); 0, ICRE-32 (bottom);
phenolic reaction; p, Equation (23) o, ICRE-2000 (top)
‘exact’ calculations gave similar behaviour for A/& homogeneous-vessel venting is shown in Figure 9 to
uersus APIPS as expected. Note that at higher APIPs, provide an adequate, but conservative correlation of the
the analytical equation tends to yield a somewhat larger DIERS experimental data. The discrepancy is mostly
A/&, hence a more conservative result. Also shown in due to the observed vapour-liquid disengagement
this figure is the overpressure response at other values behaviour, which results in lower overpressures than the
of p. The curve for 0 = 0 corresponds to a constant idealized (homogeneous vessel venting) case. It is of
self-heat rate case and here the vent area decreases interest to note that the bottom-venting tests with no
monotonically as overpressure is increased. However, vapour-liquid disengagement gave results nearly in per-
with a @ value of 1.0, which would correspond to a fect agreement with Equation (23).
doubling in rate for every 11 “C temperature increase
for the styrene system (instead of 28 “C used in the
Conclusion
numerical example), Equation (23) yields a minimum in
relief area versus overpressure. This is due entirely to Simple models have been provided for assessing ERS
the approximation of taking the averaged q to arrive at requirements for runaway reactions assuming two-
the closed form solution. Note that the assumption of a phase homogeneous venting from a vessel. The advan-
temperature dependent q at the start would result in a tage of allowing for overpressure above the relief set
non-linear differential energy equation, which cannot be pressure can be quickly quantified using the proposed
solved exactly. To avoid the unrealistic solution beyond relief sizing formula. This paper also summarizes and
the minimum area overpressure, it is recommended that extends the generalized two-phase flow methodology to
the minimum area solution be extended to the higher include multicomponent systems, elevation changes and
overpressures as shown in Figure 8 (Ref. 18). back pressure effects.
The above illustration has shown that Equation (23)
provides a rapid means of evaluating the effect of References
overpressure once the key parameters w and /3 are
found. This equation also points out that a more Fisher, H. G., Chewi. Eng. Prog. 1985, 81 (8). 33
Fisher, H. G., in ‘The DIERS Users Group (A Forum for
meaningful definition of overpressure would be relative Development/Dissemination of Emergency Relief System Design
to the relief set pressure P, in the absolute scale. Technology)‘, Paper presented to the 1988 Spring AIChE Meeting,
Currently the practice is to define the per cent over- New Orleans, LA, USA, 1988
Huff, 1. E., Plant~Operations Progress 1982, l(4), 211
pressure with respect to the gauge set pressure. Fauske, H. K.. Chem. Eng. Prog.. 1985, 81 (8), 53
Finally, a comparison can be made between Equation Leung, J. C., AIChE Journal, 1986, 32 (lo), 1622
(23) and the available DIERS reacting system data’s*16. Fauske, H. K. and Leung J. C., Ci~em. Eng. Prog. 1985.81 (4). 39
Leung, J. C., Fauske, H. K. and Fisher, H. G., Thermochimica
Both large-scale (2000 1) and small-scale (32 1) styrene Acta 1986, 104. 13
runaway experiments were conducted with relief Whiting, L. F. and Tou, J. C., J.Thermot
Analysis, 1982, 24, 111
pressures around 550 kPa. The effective vent area incor- Fauske & Associates, Inc. in ‘Emergency Relief Systems for
Runaway Chemical Reactions and Storage Vessels: A Summary of
porates the flow reduction factor due to a long vent line Multiphase Flow Methods’, Technology Summary, DlERS/
according to Figure 5. Equation (23), which is based on AIChE. 1986
Flow is choked since 13 <Q and Figure 6 is applicable. 0.43, which is very close to the above result. This may be
fortuitous since Figure 7 is only intended for horizontal
(0.47I.yQ) = 0.074
lieff/Ao = CDA/AO = flow (Fr = 0). Equation (10) is recommended for Fr > 0
situations.
API Ps = 0.45 (Figure 8 with p = 0.4)