Datasheet - 1606-XLDNET4
Datasheet - 1606-XLDNET4
1606-XLDNET4
• World-wide approvals ( )
for industry
• Input: AC 230V/115V, DC 210...375V • No switch-off at overload
• Output: 24V/4 A • Wide-Range Input
• 100 VA Limited Power Source • Robust mechanics and EMC
Input Output
Input voltage AC100...120/200...240V (switchable), 47...63 Hz Output voltage 24V DC +5% –1%
(85...132VAC / 176...264VAC, 210...375VDC,
see also“Output: Continuous Loading”) Output noise Radiated EMI values below EN50081-1, even when
Wide-Range Input: With the switch in the 230V position the power-supply unit op- suppression using long, unscreened output cables.
erates at low and moderate loads (up to 2 A) at any input voltage between 95 and Ambient temperature range Operation: -10°C...+70°C (>60°C Derating)
264VAC. Tamb Storage: -25°C...+85°C
Note: At DC input, always leave the switch in the 230V position
Input current < 2.0 A (switch in 115V position) Continuous loading Switch AC/DCin Iout
< 1.1 A (switch in 230V position)
(Tamb = -10°C...+60°C, 230V 176...264V ACin 4A
convection cooling), see also 95...176V ACin 3A
DCin at open output typ. 5 mA (preserves battery sources) diagram
For start at Tamb<0°C and low 210...375V DCin 4A
Inrush current typ. < 15 A at 264V AC and cold start input voltage, please contact 150...210V DCin 3A
If you intend to protect the primary side of the power supply with a fuse or a circuit Rockwell Automation. 100...150V DCin 2A
breaker, a 10 A slow acting fuse (HBC) or a supplementary protector 1492- 115V 85...132V ACin 4A
SPU1C100 is recommended. In order to meet local requirements, please consult lo- Output is protected against short circuit, open circuit and overload.
cal codes and regulations for proper installation..
Transient Transient resistant acc. to VDE 0160 / W2 Derating typ. 3 W/K (at Tamb=+60°C...+70°C)
handling (750V / 1.3 ms), for all load conditions.
Voltage regulation better 2% Vout over all
Hold-up time > 20 ms at 196VAC, 24V/4 A
(see diagram) Ripple / Noise < 25 mVPP (20 MHz bandwidth, 50 Ω measurement)
Overvolt. protection typ. 29V
Efficiency, Reliability etc. Parallel operation yes
6
DCin 25
Output current Iout [A]
UL Limited Power
4 Source Class 2
20 P max 100 W
2 Imax < 8A
6 10
ACin
Output current Iout [A]
switch at 115V
4 switch at
230V 5
95 0
85 132 176 264 0 2 4 6 8 10
100 200 300 400
Input voltage ACin [V] Output current Iout [A]
Efficiency (min.)
90 90
89 89
88 88
87 87
Efficiency [%]
Efficiency [%]
86 86
85 85 176 VAC
84 85 VAC 84 230 VAC
83 115 VAC 83 264 VAC
82 132 VAC 82
81 81
80 80
1 2 3 4 5 1 2 3 4 5
Output current Iout [A] Output current Iout [A]
100 100
70
Hold-up time [ms]
Iout=3A
60 60
Iout=3A 50
50
40 switch pos. Iout=4A
40 230V
Iout=4A 30
30
20 20
10 ACin
10 DCin
0 0
90 110 130 150 170 190 210 230
130 170 210 250 290 330 Input voltage VACin [V]
Input voltage VDCin [V]
Specifications valid for 230V AC input voltage, +25°C ambient temperature, and 5 min
www.rockwellautomation.com run-in time, unless otherwise stated. They are subject to change without prior notice.
Corporate Headquarters
Rockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201
Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing Solutions
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36-BP 3A/B, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication 1606-AP031A-EN-E March 2003 2003 Rockwell International. All Rights Reserved. Printed in US