SYSTEM ENABLE:
The system will automatically start when the system enable (SYSTEM-EN) is "ON". When the
system enable is "OFF", the system will be disabled.
COMPRESSORS CONTROL:
This system consists of eight Compressors. The compressors shall be controlled via their own
internal controls to maintain ammonia supply temperature. Each compressor will be staged on
and off in order to maintain the differential setpoint of suction pressure. When a compressor is
required, the compressor with the lowest runtime total shall be enabled to run. SCADA system
will responsible for collect and monitor all data from compressors and generate alarms and
reports.
AMMONIA LEAK:
During low level alarm received from ammonia leak detector, the exhaust fans will start for
specific area (Roof or machine room location)
During high level alarm received from ammonia leak detector, the exhaust fans will continue
work and all equipment will stop.
GLYCOL COOLERS:
The coolers shall be controlled via their own internal controls as per attached file (
TEMPERATURE CONTROL:
The unit will control to maintain the zone temperature setpoint as sensed by the zone
temperature sensor.
COOLING valve:
The cooling valve will be modulated to maintain the temperature setpoint.
AMONNIA COOLER:
The coolers shall be controlled via their own internal controls as per attached file (Ammonia
cooler sequence). SCADA system will responsible for collect and monitor all data from Aminnia
controller and generate alarms and reports.