The routine test certificate summarizes testing done on 3CX2.5 sq mm, 1100V, 2xWY type power cable from Polycab India Limited. Testing included a high voltage test at 3kV for 5 minutes which the cable passed, and conductor resistance measurements for each core within the maximum specification of 7.41 ohms/km. The cable was produced in a job lot of 1982 meters with red, yellow, and blue colored cores, and was certified as meeting specification requirements.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
1K views1 page
3cx2.5sqmm Cable TC
The routine test certificate summarizes testing done on 3CX2.5 sq mm, 1100V, 2xWY type power cable from Polycab India Limited. Testing included a high voltage test at 3kV for 5 minutes which the cable passed, and conductor resistance measurements for each core within the maximum specification of 7.41 ohms/km. The cable was produced in a job lot of 1982 meters with red, yellow, and blue colored cores, and was certified as meeting specification requirements.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
POLYCAB INDIA LIMITED
(formerly known as Polycab Wires Limited & Polycab Wires Private Limited)
ROUTINE TEST CERTIFICATE
Report Number 256133 Voltage Grade 1100V Report Date 30/11/2019 Cable Size 3CX2.5 SQ MM SO Number 18190028983 Type 2XWY Customer PO Number Plan for the Month of July Month 2018 Halol Customer Name POLYCAB INDIA LIMITED Item Code LVBS09CXSWYL003C2.5SA001S Item Description POLYCAB MAKE 1100 VOLTS STRANDED (CLASS 2) BARE COPPER CONDUCTOR, XLPE INSULATED, INSULATED CORES LAYING FOR LAID UP, EXTRUDED ST2 PVC I/SH, SINGLE LAYER GALVANISED STEEL ROUND WIRE ARMOURED AND EXTRUDED FR-LSH PVC ST2 OUTER SHEATHED LV POW ER CABLE GEN. AS PER BS
Drum Nos. Job Lot Core Colour High Voltage Cond
Quantity Test Resistance (MTR) at 3 Kv For 5 Value Minutes ohm/km(Max) 7.41 1982 RED Ok 7.286 27CFG19111098 1982 YELLOW Ok 7.284 1982 BLUE Ok 7.288
The above has been tested as per specification (GENERALLY SPECIFICATION) and found meeting the requirements.
Remarks:
Tested By: Lokesh Patel Approved By: Vishnu I Patel