Elnet GR User Manual PDF
Elnet GR User Manual PDF
2
4.3 TOU Setting............................................................37
4.4 Change language....................................................38
4.5 Time Settings..........................................................38
4.6 Date Settings...........................................................40
4.7 Zero Accumulating Values ....................................41
CHAPTER 5 — FRONT PANEL DISPLAYS....................42
5.1 Current for 3 Phases..............................................42
5.2 Frequency for 3 Phases..........................................43
5.3 Current in Neutral Line ........................................44
5.4 Voltage for 3 Phases ...............................................46
5.5 Active Power for all 3 Phases (P)..........................47
5.6 Reactive Power for all 3 Phases (Q) .....................49
5.7 Apparent Power for all 3 Phases (S).....................50
5.8 Power Factor for each Phase.................................51
5.9 Overall Power Factor ............................................52
5.10 Active Energy......................................................53
5.11 Reactive Energy ..................................................54
5.12 Apparent Energy ................................................55
5.13 Power Quality .....................................................56
5.13 .1 Wave Form Graphs ......................................56
5.13 .2 Harmonics Bar Graphs ................................61
5.13 .3 Voltage Total Harmonic Distortion (THD) .64
5.13 .4 Current Total Harmonic Distortion (THD) 65
3
5.13 .5 Current THD,TDD,KF.................................67
CHAPTER 6 — ALARM REPORT ....................................68
6.1.1. Alarm setting.................................................69
6.1.2. Display Alarms Report.................................71
CHAPTER 7 — DEMAND REPORTS ..............................72
CHAPTER 8 — DATA LOGGING .....................................73
CHAPTER 9 — COMMUNICATION................................76
9.1 Communication Connections................................76
9.2 Communication Settings .......................................76
9.3 Address ................................................................77
9.4 Baud Rate ............................................................77
9.5 Parity ...................................................................78
9.6 Communication Set Up .........................................78
9.7 Communication with UniArt Software ................82
CHAPTER 10 — Specifications .........................................84
Appendix A — Installation & Configuration Check List...85
4
CHAPTER 1 ─ INTRODUCTION
5
MEMORY with a capacity of recording up to 2 years of power
malfunctions and interruptions.
6
CHAPTER 3, Using the ElNet Energy & Power
Multimeter, describes in detail front Panel, the functions of the
control buttons, and the Lock Utility.
WARNING
8
• Users should stay alert and not approach the
rear of the ElNet Energy & Power
Multimeter while tired or under the
influence of alcohol, medicines or any other
chemical substance that would tend to make a
person drowsy.
• Do not wear loose clothing or dangling
jewelry.
• Above all use common sense at all times.
1.4 Warranty
CONTROL APPLICATIONS Ltd provides a 12- Month warranty
against faulty workmanship or components from date of dispatch
provided that the product was properly installed and used.
CONTROL APPLICATIONS Ltd does not accept liability for any
damage that may be caused by natural disasters (such as floods,
fire, earthquake, lightening etc.).
CONTROL APPLICATIONS Ltd does not accept liability for any
damage that may be caused by malfunction of the ElNet
Energy & Power Multimeter.
9
The ElNet Energy & Power Multimeter has no user
serviceable parts and should be opened and serviced by a duly
qualified authorized representative only. The sensitive electronics
could become damaged if exposed to a static environment. This
action would void the warranty.
This warranty is limited to the repair and/or replacement at
CONTROL APPLICATION Ltd sole discretion of the defective
product during the warranty period. Repaired or replaced products
are warranted for ninety (90) days from the date of repair or
replacement, or for the remainder of the original product’s
warranty period, whichever is longer.
CONTROL APPLICATIONS Ltd is always at your service to
advise the customer on any problem that may be encountered
regarding any installation, operation, parameter & configuration
settings or maintenance.
10
1.5 Your comments are welcome
11
1.6 Disclaimer
12
CHAPTER 2 — INSTALLATION
In this Chapter you will find the information and instructions that
the Installation Technician needs to mount and connect the
ElNet Energy & Power Multimeter
WARNING!
13
2.1 Contents of packaging
The ElNet Energy & Power Multimeter is packed and
shipped in a carton approximately 24.5 cm long X 19 cm wide X
12 and cm high.
Before opening the package, ensure the area, clean and dry.
14
2.2 Mechanical mounting
To Mount the ElNet Energy & Power Multimeter
NOTE!
Do not mount the ElNet Energy & Power
Multimeter too close to any main electrical
conductors.
Allow sufficient space to carry out
maintenance to the back of the ElNet
Energy & Power Multimeter
Width
Height 138 mm
138 mm
15
• Slide the ElNet Energy & Power
Multimeter into the pre-prepared rectangular
hole (ensure it is the right way up), then push
the two mounting clips provided in the
packaging into position. Use mild force to
ensure the clips are securely positioned on the
outer case of the ElNet Energy & Power
Multimeter.
• Tighten the two mounting screws and ensure
the ElNet Energy & Power Multimeter
is firmly in place.
16
2.3 Wiring Schematics
Rear
Panel
17
2.4 Rear Panel Connections
Please re-read section 1.3 for safety instructions.
To connect the Rear Panel
All Connections, except those to the CT core of the ElNet
Energy & Power Multimeter are made via terminal connector
plugs (Voltage input, Power Supply, Communication etc.).
Max. recommended tightening torque for the connector screws is
0.5 Nm.
The CT cores of the ElNet Energy & Power Multimeter are
located externally on the rear of the instrument and the lead from
the leg of the external Current Transformer must pass through in
the correct direction.
NOTE!
Insert the lead from side “L” of the Current Transformers of Line
1 through the bottom of the CT core I1A, (top left looking from
back), of the ElNet Energy & Power Multimeter.
18
• Ensure the leads from leg “L” of the Current
Transformer on Line 1 pass through the bottom of
CT core I1A.
WARNING!
WARNING
Repeat the procedure for Line 2 and Line 3.
19
Connect the rest of the connections to the ElNet Energy &
Power Multimeter by means of terminal connector plugs.
The Rear Panel (See Figure 2.4.) has all connections printed and
is simple to follow. (See table 2-1 for connections)
20
Pin Description Remarks
Designation
VN Neutral
21
Pin
Designation Description Remarks
22
2.5 Manufacturing Data.
Press F1 on the keyboard for 6 seconds. The following screen will
appear.
23
CHAPTER 3 — USING THE ElNet Multimeter
In this chapter you will find descriptions and functions of the
front panel and the control buttons and how to use them.
24
3.2 Control Buttons
To operate the Control Buttons on Front Panel
The ElNet Energy & Power Multimeter has six Control
Buttons. With these buttons the User and Senior Electrical
Engineer can achieve all the functions necessary.
The Control Buttons are arranged on a keypad below the display
screen and require slight finger pressure to click.
25
Buttons operate exactly the same as
button F1
NOTE!
26
To Lock press for six (6) seconds.
27
Figure 3.4. Keyboard Unlocked
NOTE!
28
CHAPTER 4 — NECESSARY ElNet SETTINGS
In this chapter you will find instructions to set the minimum
settings that are necessary to allow the ElNet Energy &
Power Multimeter to function properly.
WARNING!
29
4.1 Settings for Current Transformer
NOTE!
2 Click
30
Figure 4.1. Check Password
NOTE!
The password is 1
3 Move the cursor with the F1, F2, F3, & F4 buttons to
number 1. (See Section 3.2 for description of button
functions).
4 Click
6 Click
32
The Technical Menu screen appears
8 Click
9 Click
34
4.2 Electrical Connection Check
NOTE!
OPP Incorrect Phase Order i.e. Line 2 does not follow Line 1
and/or Line 1 does not follow Line3
36
4.3 TOU Setting
To set TOU
See Section 4.1 for instructions to arrive at the Technical Menu
From Technical Menu scroll to TOU Setting
Click
The TOU Setting screen appears
37
4.4 Change language
NOTE!
To set Time
See Section 4.1 for instructions to arrive at the Technical Menu
Click
38
The Set Clock screen appears
39
4.6 Date Settings
To set Date
See Sectio 4.1 for instructions to arrive at the Technical Menu
Click
40
Use or to select Day, Month, Year.
41
CHAPTER 5 — FRONT PANEL DISPLAYS
In this chapter you will find instructions on how to obtain the
readings that the ElNet Energy & Power Multimeter
provides, e.g., Current, Voltage Power, Power Factor, Energy, and
Power quality.
2 Click
42
5.2 Frequency for 3 Phases
To display Frequency for all 3 Phases
2 Click “ TABLE”
3 Click “ FREQ”
43
You can reset the Peak values by using the “CLEAR” button
Read the Frequency in Line 1, Line 2, Line3
2 Click
4 Click - “ TABLE”
5 The Current & Voltage table screen appears
44
Current in Neutral line
45
5.4 Voltage for 3 Phases
2 Click
3 Click “VOLT”
46
5.5 Active Power for all 3 Phases (P)
To display Active Power for all 3 phases
1 From Main Menu scroll to Power Display
2 Click
NOTE!
48
5.6 Reactive Power for all 3 Phases (Q)
To display Reactive Power for all 3 phases
1 From Main Menu scroll to Power Display
2 Click
3 Click
2 Click
3 Click
50
5.8 Power Factor for each Phase
To display Power Factor for each phase
1 From Main Menu scroll to Power Display
2 Click
51
4 Click
52
The Power Table screen appears
2 Click
The Energy Meter screen appears
Active Energy
53
3 Read the Active Energy for Line1, Line2, Line3
To return to Main Menu
To return to Main Menu click
Reactive Energy
54
5.12 Apparent Energy
To display Overall Apparent Energy
1 From Main Menu scroll to Energy Display
2 Click
Apparent Energy
55
5.13 Power Quality
NOTE!
2. Click
The Power Quality screen appears
4. Click
The Wave Form Graphs screens appear.
NOTE!
Available Wave Form Graphs
1. Volts Line 1, Line 2 and Line 3
2. Current Line 1, Line 2 and Line 3
3. Active Power Line 1, Line 2 and Line 3
4. Reactive Power Line 1, Line 2 and Line 3
5. Apparent Power Line 1, Line 2 and Line 3
To display Voltage Wave Form Graphs
1. Click
The Voltage Graph screens appears
1. Click
58
To display Active Power Wave Form Graphs
1. Click
59
To display Reactive Power Wave Form Graphs
1. Click
60
To display Apparent Power Wave Form Graphs
1. Click
The Apparent Power Graph screens appears
2. Click
61
The Power Quality screens appears
4. Click
62
5. Press to change Harmonics Volts Bar
Graph to Line 1, Line 2
and Line 3
NOTE!
Click
The Harmonic Current Bar Graph screens appears
NOTE!
2. Click
3. Scroll to Harmonic (Table)
4. Click
64
The Harmonics Volt Table screens appears
65
1. Click
66
5.13 .5 Current THD,TDD,KF
From Main Menu scroll to Power Quality Display and then scroll to
THD, TDD, KF Current.
The Current, THD, TDD, KF Table screens appears
In order to enable the system to calculate properly the TDD value, user
should set the max line current value by using “F4”.
67
CHAPTER 6 — ALARM REPORT
Every second automatically the ElNet monitor all the electrical values and
compare them to the pre-setting alarm values.
The ElNet can handle and store up to1,000 alarms that are stored in the
ElNet memory with their time & date data.
The ElNet has three alarm relays each one of them can be linked to one or
more pre-defined alarms.
68
For each one of the above alarms the user can define two alarms - low value
alarm and high value alarm.
The user can select one of sixteen different timers in order to delay each one
of the alarms.
In order to set the time duration for the sixteen timers select “Set Delay
Timer” form the screen described in Figure 6.1. Alarm Setting
Screens the following screen appears.
70
6.1.2. Display Alarms Report
In order to generate an alarm report, from the Main Menu scroll to “Alarm
report “ and press enter, scroll to “ Historical Repot or Current report “ and
select one of them by using ( F3/F4) and press enter. A list of alrms appear –
Press “INFO” (F1) in order to get detailed information. The following screen
will appear:
71
CHAPTER 7 — DEMAND REPORTS
ElNet Multimeter can generate reports that will inform the user the date of
the maximum demand. The reports include:
Maximum Demand – for active power and power factor.
Maximum Demand –for reactive power and power factor.
Maximum Demand – for apparent power and power factor.
Maximum Demand – for current and voltage.
The ElNet informs the value of the demand and the relevant power factor,
the time. The date, for all three phases, the demand is the maximum value
within the predefine time interval specified by the user.
Press F1 in order to select I / PF - Current / power factor maximum Demand
Press F2 in order to select P / Q / S active / reactive / apparent power Demand
Press F4 n order to see the power factor together with the power demand
Press F3 “DATE” in order to change the time interval within which the
ElNet will check the maximum demand.
72
CHAPTER 8 — DATA LOGGING
ElNet multimeter collects automatically important electrical data day by
day, for approximately two years.
From the Main Menu scroll to “Data Logging “ and press Enter. The
following screen appears
F1 / F2 – change the interval - time base between week / month / 128 days
F3 /F4 – change the date, each press will increase / decrease the date by week
/ month / 128 days.
74
Power Demand :
The operation metod is very similar to the above paragraph “Daily peaks” and
the informatin includes the maximum average for 15 minutes of the active
power, reactive power and apparent power demand.
Total Energy :
The operation metod is very similar to the above paragraph “Daily peaks” and
the informatin includes the toatl energy values for active energy, reactive
energy and apparent energy for each phase and total energy.
Daily Energy :
The operation metod is very similar to the above pragraph “Daily peaks” and
the informatin daily energy consumption for active energy, reactive energy
and apparent energy for each phase and total energy.
Set Fast Trend :
Selecting Data logging form the screen described in Figure 8.1. will enable
you to set a trend report. The size of the trend report is 4200 samples of all
the measurements (currents, voltages, power, power factor and more for all
phases).
The user can set only the cycle time (sampling rate) and the range is from one
second up to 3600 seconds (one hour)
76
9.3 Address
77
9.5 Parity
The choices of parity are either NONE or EVEN (see section
6.1.1 for description of Parity).
1 Click
78
From Communication Setup Menu scroll to Serial Comm.
2 Click
79
NOTE!
1 Click
80
The Set IP Address screen appears
81
9.7 Communication with UniArt Software
CONTROL APPLICATIONS Ltd propriety software, “UniArt” is
used to Read and Write Registers of the ElNet Energy &
Power Multimeter. Each Item number in the Registers Table is
a unique field containing information. The UniArt software
manages each Item number as a parameter.
Refer to the UniArt manual how to set up parameters.
82
E.G. 1 If the user the wishes to read Voltage Line 2 (Item No 2)
By applying the formula: 2 - [0 X 128] = 2
File = 0 and Point within that file = 2
E.G. 2 If the user the wishes to read 30th Harmonics for Volts Line1
(Item No 330)
By applying the formula: 330 - [2 X 128] = 74
File = 2 and Point within that file = 74
E.G. 3 If the user the wishes to read 7th Harmonic for Current Line 3
(Item No 467)
By applying the formula: 467 - [3 X 128] = 83
File = 3 and Point number within that file = 83
More Examples
83
CHAPTER 10 — Specifications
Item Description
84
Appendix A — Installation & Configuration
Check List
INSTALLATION CHECK LIST
85