2.ABCD constants and Regulation of 3-φ Transmission line model
2.ABCD constants and Regulation of 3-φ Transmission line model
– EEE DEPARTMENT
POWER SYSTEMS LAB
III B.Tech EEE-II Semester Experiment No:2
ABCD constants, Regulation and efficiency of 3-φ Transmission line model
THEORY:
Consider the power system shown in Fig. The sending and receiving end voltages are
denoted by VS and VR respectively and the currents IS and IR are entering and leaving the
network respectively. The sending end voltage and current are then defined in terms of
the ABCD parameters as
VS AVR BI R
I S CVR DI R
VS VS
A B
VR I R 0
IR VR 0
IS IS
C D
VR I R 0
IR V 0
R
Page 1 of 6
G.N.I.T.S. – EEE DEPARTMENT
POWER SYSTEMS LAB
III B.Tech EEE-II Semester Experiment No:2
ABCD constants, Regulation and efficiency of 3-φ Transmission line model
ZSO= VS / IS = Line impedance measured at sending end with receiving end open-circuited.
ZSS= VS / IS = Line impedance measured at sending end with receiving end short-circuited.
ZRO= VR / IR = Line impedance measured at receiving end with sending end open-circuited.
ZRS= VR / IR = Line impedance measured at receiving end with sending end short-circuited.
Page 2 of 6
G.N.I.T.S. – EEE DEPARTMENT
POWER SYSTEMS LAB
III B.Tech EEE-II Semester Experiment No:2
ABCD constants, Regulation and efficiency of 3-φ Transmission line model
Page 3 of 6
G.N.I.T.S. – EEE DEPARTMENT
POWER SYSTEMS LAB
III B.Tech EEE-II Semester Experiment No:2
ABCD constants, Regulation and efficiency of 3-φ Transmission line model
PROCEDURE:
O.C& S.C. tests at Receiving end side:
1. Connect the circuit as per Fig.(1) for O.C. test at receiving end side.
2. 3-Φ Variac should be in minimum position and receiving end should be kept open.
3. Switch on mains.
4. Apply 230V at sending end side using 3-Φ Variac.
5. Note down Vs, Is, VR and IR meter readings.
6. Bring back the 1-Φ Variac to its minimum position and switch off the mains.
7. Connect the circuit as per Fig.(2) for S.C. test at receiving end side.
8. 3-Φ Variac should be in minimum position and receiving end should be short with
ammeter.
Page 4 of 6
G.N.I.T.S. – EEE DEPARTMENT
POWER SYSTEMS LAB
III B.Tech EEE-II Semester Experiment No:2
ABCD constants, Regulation and efficiency of 3-φ Transmission line model
9. Switch on mains.
10. Apply rated current of 5A at sending end side using 3-Φ Variac.
11. Note down Vs, Is, VR and IR meter readings.
12. Bring back the 1-Φ Variac to its minimum position and switch off the mains.
O.C& S.C. tests at sending end side:
1. Connect the circuit as per Fig.(3) for O.C. test at sending end side.
2. 3-Φ Variac should be in minimum position and sending end should be kept open.
3. Switch on mains.
4. Apply 230V at receiving end side using 3-Φ Variac.
5. Note down Vs, Is, VR and IR meter readings.
6. Bring back the 1-Φ Variac to its minimum position and switch off the mains.
7. Connect the circuit as per Fig.(4) for S.C. test at sending end side.
8. 3-Φ Variac should be in minimum position and sending end should be short with
ammeter.
9. Switch on mains.
10. Apply rated current of 5A at receiving end side using 3-Φ Variac.
11. Note down Vs, Is, VR and IR meter readings.
12. Bring back the 1-Φ Variac to its minimum position and switch off the mains.
13. Calculate ABCD constants using appropriate equations.
Regulation and efficiency of 3-Φ transmission line model:
1. Connect the circuit as per the circuit diagram shown in Fig.(5).
2. 3-Φ Variac should be in minimum position and the 3-Φ resistive load should be kept in
OFF position.
3. Switch on mains.
4. Apply 400V at sending end side using 3-Φ Variac.
5. Apply half load i.e 2.5A by switching ON load switch1.
6. Note down Vs, Is, W1S, W2S, VR, IR, W1R and W2R meter readings under half-load
condition.
7. Apply full load i.e 5A by switching ON load switch1 and 2.
8. Note down Vs, Is, W1S, W2S, VR, IR, W1R and W2R meter readings under full-load
condition
9. Switch OFF all Load.
10. Note down Vs, Is, W1S, W2S, VR, IR, W1R and W2R meter readings under no-load
condition.
11. Bring back the 3-Φ Variac to its minimum position and switch off the mains.
12. Calculate Regulation and efficiency under half load, full load and no load conditions
using appropriate equations.
Page 5 of 6
G.N.I.T.S. – EEE DEPARTMENT
POWER SYSTEMS LAB
III B.Tech EEE-II Semester Experiment No:2
ABCD constants, Regulation and efficiency of 3-φ Transmission line model
TABULAR FORM:
ABCD constants
A B C D
Regulation
Half-load
Full-load
No-load
Full-load
No-load
RESULT:
Page 6 of 6