Checklist
Checklist
PROYEK :
PERIODE :
CATATAN
CUSTOMER EXECUTOR
( ) ( )
LAPORAN KONDISI POMPA CHILLER ( CHWP )
PROYEK :
PERIODE :
CATATAN
CUSTOMER EXECUTOR
( ) ( )
TEHNIK UTAMA PRIMA
PERUMAHAN TAMAN ALAMANDA BLOK C 2 NO 44 RT 04/013 KELURAHAN KARANGSTRIA - TAMBUN - BEKASI
TLP : 0812 9410 867 / 0813 1671 2272
TIME ARRIVAL :
TIME DEPARATURE :
JOB COMPLETED : [ ] YES [ ] NO
CUSTOMER EXECUTOR
............................ ...............................
LAPORAN KONDISI CHILLER
PROYEK :
PERIODE :
CHILLER NO :
COMPRESSOR
NO DESCRIPTION KETERANGAN
1
1 MOTOR FAN CONDENSER & CONTACTOR
FAN 1
FAN 2
FAN 3
FAN 4
FAN 5
FAN 6
FAN 7
FAN 8
FAN 9
FAN 10
3 CONTACTOR COMPRESSOR
a. Main Contactor
b. Delta Contactor
c. Star Contactor
4 SENSOR TEMPERATURE
a. Suction temperature
b. Leaving Water Temperature
c. Return Water Temperature
5 HP SWITCH
6 LP SWITCH
7 BATTERY EXPANTION DRIVER
8 EVD DRIVER
9 FLOW SWITCH
10 MOTORIZED VALVE LEAVING WATER
11 CAPACITY TRANSDUCER
12 REFRIGERANT R 134 a
13 OIL EMKARATE RL 68
14 TRANSDUCER HP
15 TRANSDUCER LP
16 BATTERY CHARGER
17 MAIN BOARD PICO CARREL
18 DISPLAY PICO CARREL
19 CORE DRIER
20 OIL FILTER
21 PHASE MONITOR
22 FUSE COMPRESSOR
23 OVER LOAD COMPRESSOR
24 OVER LOAD FAN CONDENSER
25 FUSE CONTROL
26 ELECTRONIC EXPANTION VALVE
CUSTOMER EXECUTOR
............................. ...............................
Mc QUAY SINGLE SCREW LOG SHEET - MICROTECH II
PROYEK : DATE :
MODEL : TIME :
CHILLER NUMBER :
SERIAL NUMBER :
DESCRIPTION STANDARD COMPRESSOR
1 UNIT STATUS 1 2 3
a Unit Status ON / OFF ON
b Unit Stagging % 25 - 100
c Setpoint Source °C 6 - 10 C
2
a Ent Evap Temp °C 10 - 16 C
b Lvg Evap Temp °C 6 - 12 C
c Delta Evap Water Tem °C 2-5C
3 COMPRESSOR STATUS
a Status Auto/ Man Auto
b Compressor Stagging % 25 - 100
c Saturated Evap Pressu Bar 1.5 - 4.5
d Saturated Evap Temp °C ( - 3.3 ) - 8.6
e Saturated Cond Pressu Bar 10 - 16.0
f Saturated Cond Temp °C 40.6 - 62.8
g Suction Temperature °C 6.2 - 18.5
h Suction Superheat °C 3.0 - 8.5
i Delivery Superheat °C 30.0 - 42.5
j Expantion Position 900 - 1800
k Oil Pressure ( I/O menu Bar 11.5 - 16
l Discharge temperatur °C 60.0 - 98
m Stage Position Up/Dn/Fix/Of
4 MANUAL INSPECTION
a Inlet Water Pressure Kg/Cm² 2.0 - 4.5
b Outlet Water Pressure Kg/Cm² 2.0 - 4.5
c Delta Evap Water Pres Kg/Cm² 0.5 - 1.0
5 d Oil Level % 50 - 100
e Liquid Line Sight GlassClear / Bubbl Clear
f Fan Condenser Status n 5.
6 ELECTRICAL MEASURMENT
R AMPERE < 260
a Ampere S AMPERE < 260
T AMPERE < 260
NOTE
GALUH PAKUAN SERVICE
PERUMAHAN TAMAN ALAMANDA BLOK C 2 NO 44 RT 04/013 KELURAHAN KARANGSTRIA - TAMBUN - BEKASI
TLP : 0812 9410 867 / 0813 1671 2272
TIME ARRIVAL :
TIME DEPARATURE :
JOB COMPLETED : [ ] YES [ ] NO
SUPERVISOR EXECUTOR
........................................ ............................
SERVICE
HAN KARANGSTRIA - TAMBUN - BEKASI
2272
ORDER
DAY :
STATUS
[ ] CHARGE
[ ] FREE
[ ] WARRANTY
[ ]
[ ]
WORK DESCRIPTION
TECHNICAL ADVISE
CUSTOMER
..................................................
LAPORAN CHECKLIST HARIAN CHILLER
PROYEK DATE :
MODEL TIME :
CHILLER NUMBER :
DESCRIPTION STANDARD COMPRESSOR
1 UNIT STATUS R 407 C
a Unit Status ON / OFF ON
b Unit Stagging % 25 - 100
c Setpoint Source °C 6.0 - 10.0
2 WATER STATUS
a Ent Evap Temp °C 12.0 - 16.0
b Lvg Evap Temp °C 5.5 - 12.0
c Delta Evap Water Temp °C 2.0 - 5.0
3 COMPRESSOR STATUS
a Status Auto/ Man Auto
b Compressor Stagging % 25 - 100
c Saturated Evap Pressure Bar 3.3 - 5
d Saturated Evap Temp °C ( -1.1 ) - 8.9
e Saturated Cond Pressure Bar 16.0 - 25.0
f Saturated Cond Temp °C 40.6 - 60.0
g Suction Temperature °C 3.0 - 12.0
h Suction Superheat °C 3.0 - 6.0
I VALVE Position 1800 - 3000
k Oil Pressure ( I/O menu ) Bar 16.0 - 25.0
l Discharge temperature °C 60.0 - 95.0
m Stage Position Up/Dn/Fix/Off
4 MANUAL INSPECTION
a Inlet Water Pressure Kg/Cm² 2.0 - 3 Bar
b Outlet Water Pressure Kg/Cm² 2.0 - 3 Bar
c Delta Evap Water Pressure Kg/Cm² 0.5 - 1 Bar
5 d Oil Level % 50 - 100
e Liquid Line Sight Glass Clear / Bubble Clear
6 ELECTRICAL MEASURMENT
7 AMPERE COMPRESSOR Ampere
8 KONDISI FAN CONDENSER
9 KONDISI POMPA CHILLER CHWP 1 CHWP2 CHWP 3 CHWP 4 CHWP5
a Bearing motor
b Bearing Pompa
c Kopel
d Karet Kopel
e Ampere Motor
f Mechanical seal
g Impeller pompa
h Make Up Water
CHECKED BY SUPERVISED BY Head Of Engineering CUST0MER
LAPORAN KONDISI FCU
PROYEK :
PERIODE :
LOKASI :
FCU NO :
KONDISI
NO DESCRIPTION NILAI KETERANGAN
BAIK BERSIH RUSAK
1 COOLING COIL
2 AIR FILTER
3 BLOWER
4 STRAINNER INLET WATER
5 BLOWER
a. Kondisi Blower
b. Kondisi Motor
c. Kondisi capcitor
d. Kondisi Fan belt
b. Penambahan Grease
8 MOTORIZED TWOWAY VALVE
9 THERMOSTAT
10 BODY FCU
11 VALVE IN
12 VALVE OUT
13 PIPING INSULATION
15 MOTOR FCU
a. Ampere Motor FLA :
b. Check terminal motor
c. Retighten terminal connection
16 DRAIN SYSTEM
CATATAN :
CUSTOMER EXECUTOR
............................ ...............................
...................
PT. MULIA INTAN PERSADA
GENERAL CONTRACTORS, MECHANICAL ELECTRICAL SPECIALIST,
DESIGN & BUILD
AHU / FCU NO :
KONDISI KONDISI KONDISI KONDISI
NO DESCRIPTION NILAI
Bersih Baik Rusak Bersih Baik Rusak Bersih Baik Rusak Bersih Baik Rusak
1 COOLING COIL
2 FILTER
3 Strainner Inlet Water
4 BLOWER
a. Kondisi Blower
b. Kondisi Motor
c. Kondisi Fan belt
d. Ukuran Fan Belt
e. Kondisi bearing
f. Penambahan Grease
5 MOTORIZED Valve
6 THERMOSTAT
7 Temperatur Ruangan
8 BODY FCU
9 ISOLASI PIPA
10 MOTOR FCU
a. Ampere Motor
b. FLA Motor
c.Terminal motor
11 DRAIN SYSTEM
CATATAN :
Dengan ini menerima hasil pekerjaan yang dilakukan sesuai yang tercantum diatas
Checked By Supervised By User RSCM Head Office Engineering
LAPORAN CHECKLIST HARIAN CHILLER
PROYEK PERAWATAN CHILLER KIRANA DATE
MODEL TIME
CHILLER
NO DESCRIPTION STANDARD
1
2
3
4
CATATAN :
TEKNISI USER
Lokasi Merk Unit
Tanggal Model Unit
Jam Mulai Kapasitas Unit
Jam Selesai Refrigerant
V Dikerjakan
PEKERJAAN PERAWATAN AC SPLIT
X Tidak
INDOOR UNIT
Putuskan pasokan listrik di panel AC
Bersihkan kotoran/debu pada cover indoor
Bersihkan kotoran/debu pada blower fan indoor
Periksa skrup cover Indoor terhadap kemungkinan karat
Bersihkan kotoran pada komponen listrik dan PCB control
Bersihkan motor blower, dan periksa bearing
Bersihkan dan check kondisi saluran drain air kondensasi
Bersihkan filter dan fin Evaporator
OUTDOOR UNIT
Putuskan pasokan listrik di panel AC
Bersihkan fin Condenser dengan steam air
Perbaikan Fin Condenser jika ada yg rebah
Bersihkan body outdoor unit
Bersihkan kotoran pada komponen listrik, relay, contactor
Pemeriksaan dan pengencangan koneksi pada terminal kabel
PENGUJIAN ARUS LISTRIK
Pengukuran beban dengan tang ampere ( sebelum cleaning )
Pengukuran beban dengan tang ampere ( sesudah cleaning )
PENGUJIAN TEKANAN REFRIGERANT
Pengukuran tekanan suction dengan Manifold Gauge ( sebelum cleaning )
Pengukuran tekanan suction dengan Manifold Gauge ( sesudah cleaning )
CATATAN
Dengan ini menerima hasil pekerjaan yang dilakukan sesuai yang tercantum diatas
Checked By