Installation and Maintenance Manual

ED 15100-3
Group: Controls
Part Number: ED 15100
Date: August 2015
Supersedes: ED 15100-2

MicroTech® Chiller Unit Controller


Protocol Information
BACnet® Networks (IP or Ethernet)

Unit Model Number Description


WSC Water-Cooled Centrifugal, Single-Compressor
WDC Water-Cooled Centrifugal, Dual-Compressor
WPV Water-Cooled Centrifugal, Single-Compressor
HSC Water-Cooled Single-Compressor Centrifugal, Heat Recovery
HDC Water-Cooled Dual-Compressor Centrifugal, Heat Recovery
TSC Water-Cooled Single-Compressor Centrifugal, Templifier™
WMC Water-Cooled Centrifugal, Magnetic Bearing
WCC Water-Cooled Centrifugal, Dual-Compressor Series Counter-flow
AGZ Air-Cooled Global Scroll
ACZ Air-Cooled Scroll Condensing Unit
WGZ Water-Cooled Global Scroll
AGS Air-Cooled Global Screw
WGS Water-Cooled Global Screw
TGZ Templifier™ Water Heater
Table of Contents

Table of Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Condenser Flow Switch Status . . . . . . . . . . . . . . . . . . . . . . . . . . 45


Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Condenser Leaving Water Temperature . . . . . . . . . . . . . . . . . . . 45
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Condenser Pump Run Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Software Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Condenser Refrigerant Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 47
Reference Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Condenser Saturated Refrigerant Temperature . . . . . . . . . . . . . 48
Chiller Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Condenser Water Pump Status . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Controller Data Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Cool Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Protocol Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Design RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Device Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Basic Protocol Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Entering Water Temperature . . . . . . . . . . . . . . . . . . . 52
BACnet Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Flow Switch Status . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Leaving Water Temperature for Unit . . . . . . . . . . . . . 54
BACnet Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Leaving Water Temperature for Compressor . . . . . . 55
Object Identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Pump Run Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Property Identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Refrigerant Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 57
Property Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Saturated Refrigerant Temperature . . . . . . . . . . . . . 58
Object Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Water Flow Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Property Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Water Pump Status . . . . . . . . . . . . . . . . . . . . . . . . . . 59
MicroTech II Chiller Unit Controller Device Object . . . . . . . . . . . . . . 7 Heat Recovery Entering Water Temperature . . . . . . . . . . . . . . . . 60
Device Object Identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Heat Recovery Leaving Water Temperature . . . . . . . . . . . . . . . . 60
Device Object Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Heat Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
HTTP Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Ice Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Device Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 IGV Percentage Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Alarm Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Inverter Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Clock Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Liquid Line Refrigerant Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 65
BBMD Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Liquid Line Refrigerant Temperature . . . . . . . . . . . . . . . . . . . . . . 66
Network Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Maximum RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Configuring the Unit Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Minimum RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Typical Application: Minimum Integration . . . . . . . . . . . . . . . . . . . 10 Motor Cavity Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Set Up the Unit for Network Control . . . . . . . . . . . . . . . . . . . . . . . . 10 Oil Feed Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Unit Setup for MicroTech II Centrifugal Chiller Oil Feed Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Network Control: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Oil Sump Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Setup for All Other MicroTech II Chillers Network Control: . . . . . 10 Oil Sump Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Display Important Data Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Outdoor Air Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Comprehensive Data Point Tables . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
BACnet Standard Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Pump Select . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Chiller Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Run Enabled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Chiller Alarm Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Detailed Data Point Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Alarm Classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Active Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Fault Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Actual Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Problem Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Actual RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Warning Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Capacity Limit Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 BACnet Alarm Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Capacity Limit Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Alarm Annunciation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Chiller Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Poll Multiple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Chiller Limited . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Poll Singular . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Chiller Local/Remote . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Clearing Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Chiller Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 BACnet Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Chiller Mode Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Chiller Mode Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Protocol Implementation Conformance Statement (PICS) . . . . . . . 89
Chiller ON/OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 BACnet Protocol Implementation Conformance Statement . . . . 89
Chiller Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Chiller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 BACnet Standardized Device Profile . . . . . . . . . . . . . . . . . . . . . . 89
Chiller Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 BACnet Interoperability Building Blocks (BIBBs) Supported . . . . 89
Compressor 2 Active Capacity Limit . . . . . . . . . . . . . . . . . . . . . . 28 Standard Object Types Supported . . . . . . . . . . . . . . . . . . . . . . . 89
Compressor 2 VFD Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Data Link Layer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Compressor Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Segmentation Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Compressor Discharge Temperature . . . . . . . . . . . . . . . . . . . . . 31 Device Address Binding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Compressor Percent RLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Networking Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Compressor Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Character Sets Supported . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Compressor Run Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Non-BACnet Equipment/Network(s) Support . . . . . . . . . . . . . . . 90
Compressor Select . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Compressor Starts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Compressor Suction Line Temperature . . . . . . . . . . . . . . . . . . . . 41
Compressor Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Condenser Entering Water Temperature . . . . . . . . . . . . . . . . . . . 44
Condenser Flow Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 2 www.DaikinApplied.com


Introduction

Introduction

Limited Warranty Software Revision


Consult your local Daikin Applied Representative for warranty This edition documents the following versions of the standard
details. To find your local Daikin Applied Representative, go to MicroTech® II Communication Module software and all
www.DaikinApplied.com. subsequent revisions until otherwise indicated. However, if
your software is of a later revision, some of the information in
this document may not completely describe your software.
Revision History
Software Revision
Version Release Date Description BACnet® Communication Module Application 2.00
ED 15100 June, 2006 Initial release. Software Version
ED 15100-1 September, 2009 Added TGZ model
ED 15100-2 June, 2012 Removed Minimum
Send Time, Maximum
Send Time, Receive
Heartbeat and Default
Values. These are not
used in BACnet. Addition
of data points for multiple
compressors.
ED 15100-3 June, 2015 Specified that hours are
reported at 1/10th the
actual hours. Corrected
Compressor Status
for BACnet to be an
enumerated value, not
a bit field. Removed
references to out-dated
software/firmware. Added
clarification to “Actual
Capacity” data point
for centrifugal chillers.
Changed branding.
Changed description of
Chiller On Off data point.

www.DaikinApplied.com 3 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Introduction

Reference Documents
Company Number Title Source
American Society of Heating, BACnet- A Data Communication Protocol for Building Automation
Refrigerating and Air-Conditioning ANSI/ASHRAE 135-2004 www.ashrae.org
and Control Networks
Engineers
MicroTech II Chiller Unit Controller BACnet Communication Module-
Daikin Applied IM 736 www.DaikinApplied.com
MS/TP
MicroTech II Chiller Unit Controller BACnet Communication Module-
Daikin Applied IM 837 www.DaikinApplied.com
IP or Ethernet
MicroTech II Air-Cooled Screw Chiller Installation and Maintenance
Daikin Applied IMM AGS www.DaikinApplied.com
Manual
MicroTech II Air-Cooled Condensing Unit Installation, Operation, and
Daikin Applied IOMM ACZ/AGZ www.DaikinApplied.com
Maintenance Manual
MicroTech II Air-Cooled Condensing Unit Installation, Operation, and
Daikin Applied IOMM ACZ www.DaikinApplied.com
Maintenance Manual
MicroTech II Air-Cooled Scroll Chiller Installation, Operation, and
Daikin Applied IOMM AGZ www.DaikinApplied.com
Maintenance Manual
Daikin Applied IOMM WGZ MicroTech II Water-Cooled Scroll Chiller Installation Manual www.DaikinApplied.com
MicroTech II Centrifugal Chiller Installation, Operation, and
Daikin Applied IOMM WPV www.DaikinApplied.com
Maintenance Manual
MicroTech II Chiller Unit Controller Installation, Operation, and
Daikin Applied IOMM WSCWDC www.DaikinApplied.com
Maintenance Manual
Daikin Applied OM AGS MicroTech II Air-Cooled Screw Chiller Operating Manual www.DaikinApplied.com
MicroTech II Unit Controller for Centrifugal Chillers and Templifiers
Daikin Applied OM CentrifMicro II www.DaikinApplied.com
Operating Manual
Daikin Applied OM WGS MicroTech II Water-Cooled Screw Chiller Operating Manual www.DaikinApplied.com
MicroTech II Templifier TGZ Heat Recovery Water Heaters Operating
Daikin Applied OMM TGZ www.DaikinApplied.com
Manual
MicroTech II Magnetic Bearing Compressor Chiller Operating
Daikin Applied OM WMC www.DaikinApplied.com
Manual
MicroTech II Templifier Single Compressor Centrifugal Installation,
Daikin Applied IOMM TSC www.DaikinApplied.com
Operation, and Maintenance Manual

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 4 www.DaikinApplied.com


Introduction

This document contains the necessary information to


incorporate a MicroTech II Chiller Unit Controller from Daikin
Protocol Definitions
Applied into your Building Automation System (BAS). It The MicroTech II Chiller Unit Controller can be configured in a
includes all necessary BACnet properties and corresponding interoperable BACnet network. The BACnet Communication
MicroTech II Chiller Unit Controller data points. It also contains Module communicates via BACnet IP or BACnet Ethernet. The
the BACnet Protocol Implementation and Conformance BACnet Communication Module can be setup to communicate
Statement. BACnet terms are not defined. Refer to the BACnet either Metric (SI) or English units of measurement via the
specifications and functional profile for definitions and details. HTTP interface. In order to avoid conflict, both the Chiller
keypad and BACnet Communication Module must be setup to
communicate the same units of measure (Metric or English).
Chiller Models
The following table lists the model designators of Daikin
BACnet Protocol
Applied Chiller units and the corresponding description. The BACnet protocol is a standard communication protocol for
Building Automation and Control Networks developed by the
Unit Model Number Description
American National Standards Institute and American Society
WSC Water-Cooled Centrifugal, Single-Compressor
of Heating, Refrigerating and Air-conditioning Engineers
WDC Water-Cooled Centrifugal, Dual-Compressor
(ASHRAE) specified in ANSI/ASHRAE Standard 135-2004.
WPV Water-Cooled Centrifugal, Packaged Unit
It addresses all aspects of the various systems that are
Water-Cooled Single-Compressor Centrifugal, Heat
HSC
Recovery applied to building control systems. BACnet provides the
Water-Cooled Centrifugal, Dual-Compressor, Water- communication infrastructure necessary to integrate products
HDC Cooled Dual-Compressor Centrifugal, Heat Recovery manufactured by different vendors and to integrate building
Water-Cooled Single-Compressor Centrifugal, services that are now independent.
TSC Templifier
WMC Water-Cooled Centrifugal, Magnetic Bearing
Water-Cooled Centrifugal, Dual Compressor Series
WCC Counter-flow
AGZ Air-Cooled Global Scroll
ACZ Air-Cooled Scroll, Condensing Unit
WGZ Water-Cooled Global Scroll
TGZ Templifier™ Water Heater
AGS Air-Cooled Global Screw
WGS Water-Cooled Global Screw

Controller Data Points


The MicroTech II Chiller Unit Controller contains data points or
unit variables that are accessible from as many as four user
interfaces: the unit keypad/display, the Operator Interface
Touch Screen, a BACnet IP or BACnet Ethernet network, or
the BACnet Communication Module’s HTTP interface. Not all
points are accessible from each interface. This document lists
all important data points and the corresponding path for each
network interface. Refer to the applicable Operation Manual
for keypad/display and Operator Interface Touch Screen detail
(see Reference Documents section for literature part numbers.)

www.DaikinApplied.com 5 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Basic Protocol Information

Basic Protocol Information

BACnet Networks
Compatibility The object identifier is shown in the data points listing as two
numbers. The first number is shown in the Type ID column and
The MicroTech II Chiller Unit Controller conforms to the designates the Object type enumeration. The second number
BACnet Standard (ANSI/ASHARE 135-2004) as stated in the is shown in the Instance column and designates the instance
Protocol Implementation and Conformance Statement (PICS). of that particular object type.
Refer to the Protocol Implementation Conformance Statement
(PICS) on page 89. The object identifier is a property of the object that you can
read from the object code. The name of the property is “Object_
Identifier” and the property identifier is 75. The ASHRAE BACnet
BACnet Objects specification reserves the first 128 numbers for ASHRAE
MicroTech II Chiller Unit Controllers incorporate standard defined objects. Manufactures may define additional object
BACnet object types (i.e., object types defined in the BACnet types and assign a number above 127 as long as they conform
Standard). Each object has properties that control unit to the requirements of the ASHRAE BACnet specification.
variables or data points. Some object types occur more than
Each object also has a name. Object names are character
once in the unit controller; each occurrence or instance has
strings. The object name is a property of the object that you
different property values and controls different unit variables
can read from the object. The name of the property is “Object_
or data points. Each instance is designated with a unique
Name” and the property identifier is 77.
instance index. Some properties can be from the network
adjusted (for example, read/write properties such as setpoints) Objects are sometimes referred to as an object type and
and others can only be interrogated (for example, read-only instance number as they are in the BACnet specification. The
properties such as status information). example object above would be: Analog Input, Instance 18.
Each data point accessible from a BACnet network is
described with a table that gives the Object Identifier, Property Property Identifier
Identifier, Full BACnet Reference or path, and the Name Each object has a number of properties or attributes. Each
enumeration of the property. property has a unique identifier of BACnet Property Identifier
data type. Property identifiers are an enumerated set; a
Example of BACnet Data Point number identifies each member. The value of the Property
Object Identifier Property Identifier Identifier enumeration is shown in the Property ID column. In
Type Property Property the example above the property identifier is 85.
Object Type Instance
Enumeration Name Enumeration
Analog Input 0 18 Present Value 85 Property Name
Object Name
EntCondWaterTemp Each property also has a unique name. Property names are
character strings and shown in the Property Name column.
In the example above the property name is Present Value
Object Identifier (Property Enumeration 85).

Object Identifiers are each designated with an Object type as Object Name
defined in the BACnet specification. The first column of the
data point definition gives the object type. The object in the This property is a character string that is the unique name of
example shown above happens to be the Entering Condenser the object in the BACnet device. In the example above the
Water Temperature. object name is EntCondWaterTemp.
The object identifier is a property of the object that you can
read from the object. The name of the property is “Object_
Property Values
Identifier” and the property identifier is 75. Some properties are standard data types and some are
enumerated sets. If the property value is an enumerated set,
Each object in a chiller controller has a unique identifier.
all enumerated values and corresponding meaning are given in
BACnet object identifiers are two-part numbers of BACnet
the Property Values column of the data point listing.
Object Identifier data type. The first part identifies the object
type (the first 10 bits of the 32-bit BACnet Object Identifier
[See ANSI/ASHRAE 135-2004 BACnet A Data Communication
Protocol for Building Automation and Control Networks]). The
first column of the data point definition gives the object type.
The second part identifies the instances of that particular object
type (the last 22 bits of the 32-bit BACnet Object Identifier).

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 6 www.DaikinApplied.com


Basic Protocol Information

MicroTech II Chiller Unit Controller HTTP Interface


Device Object The BACnet Communication Module uses a HTTP interface
for setting certain network variables. Figure 1 shows the HTTP
Each BACnet compatible device can only be assigned a single interface main page. This is a read-only screen that displays
BACnet Device Object. several setup parameters. The parameters that require setting
depend on the data link layer of the BAS network. Device, Date/
Time, and Alarms require settings for all BACnet networks.
Device Object Identifier BACnet via Ethernet does not require network settings.
CAUTION However, BACnet via IP does require network settings.
If another device in the network already has this object The BACnet Communication Module HTTP interface can be
identifier (instance number), you must change the instance accessed by opening Internet Explorer® and typing in the IP
number of one device object so that all devices in the network address. (NOTE: the default IP address is 172.16.5.8 and
have a unique device identifier. subnet mask is 255.255.0.0.) Follow the steps below to modify
to the BACnet Communication Module configuration:
The MicroTech II Chiller Unit Controller Device Object Identifier
1. Change the network settings (this includes the IP
uniquely specifies the unit within the network. The device
address and subnet mask.) on your computer and the
object type for all devices is fixed by ASHRAE at 8. Therefore,
options in Internet Explorer (this step is done only if
the device object instance number must be unique. The initial
your computer is not already on the same subnet as the
Device Object identifier is set at 3000 during manufacturing.
BACnet Communication Module.)
The device object identifier can be read from the unit controller.
The name of the property is “Object_Identifier” and the property 2. Access the BACnet Communication Module
identifier is 75. configuration pages to change the desired parameters.
3. Press the Save Changes button and then reboot your
Device Object Name computer.
The Device Object Name uniquely specifies a device in the 4. Switch your Internet Explorer and network settings back
network. It must be unique in the network. The device name to the original settings.
for the MicroTech II Chiller Unit Controller device is MTII Chiller
Refer to the Communication Module Installation Manual,
UC ####. The #### represents the device object instance
BACnet IP or Ethernet (IM 837) for detailed instructions.
number. The device name is the “prefix” of all object names in
the MicroTech II Chiller Unit Controller. All objects include the
device name and a period “.” (MTII Chiller UC ####.) preceding Figure 1: BACnet Communication Module HTTP Main Page
the object name. The device object instance number assigned
at the factory is 3000.
NOTE: If you change the device instance in the BACnet
Communication Module HTTP interface, you also
change the device name and thus the full reference
for all objects in the unit controller.
The Device Object name is also available to the network in
the device. The property name is “Object_Name” and property
identifier is 77.

www.DaikinApplied.com 7 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Basic Protocol Information

Below is a description of each network function controlled by Alarm Properties


the BACnet Communication Module HTTP interface:
Alarming Enabled
Device Properties The Alarming Enabled parameter indicates whether the Alarm
Annunciation method of alarm notification has been enabled
BACnet LAN Type (see BACnet Alarms section).
The BACnet LAN Type parameter identifies the Data Link/ NOTE: If the BACnet device does not recognize an Alarm
Physical layers of the BAS network. The Data Link/Physical Annunciation message, the BAS can poll the unit
layers available are BACnet Ethernet and BACnet IP. controller for alarms (see BACnet Alarms section).

BACnet IP UDP Port Alarm Destination Device Instance


BACnet IP UDP (User Datagram Protocol) Port identifies the The Alarm Destination Device Instance parameter indicates
application process in the MicroTech II Chiller Unit Controller. the BACnet device in the network receiving the alarm
notification annunciation.
Device Instance
Alarm Process ID
CAUTION
If another device in the network already has this device The Alarm Process ID parameter identifies the process that the
instance, you must change the instance number of one device device receiving the alarm notification annunciation executes
object so that all devices in the network have a unique device after it receives the alarm notification.
identifier.
Alarm Priority
The device instance identifies the BACnet Communication The Alarm Priority parameters indicate the priority for each
Module device on the BAS network. The BACnet class of alarms. Priority values range from 0 to 255. The
Communication Module ships from the factory with a default smaller the priority’s value, the higher the priority. For example,
device instance of 3000. The device instance can be changed an alarm set to a value of 1 is a higher priority alarm than an
via the BACnet Communication Module HTTP interface. alarm set to a value of 255.
NOTE: Changing the device instance of the Device Object
changes the full reference of all objects because Clock Properties
each full reference includes the instance number of
the Device Object The Clock Parameters indicate local time, the time difference
between local time and Universal Coordinated Time (UCT)
Description expressed in minutes, and whether or not the controller is in
a daylight savings period. Setting these parameters is only
The Description parameter describes the application running in necessary when the BAS network does not have a Time
the BACnet device. Master controller on the network. To change the actual date
and time, go to the Clock Setup page.
Location
NOTE: The clock must be reset any time power is lost to the
The Location parameter is a changeable property that can be chiller or if the BACnet Communication Module is
used to indicate the physical location of the MicroTech II Chiller rebooted.
Unit Controller.
Interval to Send Who-Is
APDU Timeout The Interval to send Who-Is parameter indicates the maximum
The APDU Timeout parameter indicates the amount of time rate at which the BACnet Communication Module can send
(in milliseconds) between retransmissions of an APDU Who-Is requests to identify unknown devices. This parameter
requiring acknowledgment for which no acknowledgement is an integer and the frequency is per minute.
has been received.

Number of APDU Retries


The Number of APDU Retries parameter indicates the maximum
number of times that an APDU shall be retransmitted.

Password for Restart


Password that allows the BACnet Communication Module to
be reinitialized from the network.

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 8 www.DaikinApplied.com


Basic Protocol Information

BBMD Parameters Network Considerations


IP Address for BBMD Access to Properties
The IP Address for BBMD parameter indicates the IP address To access a property via BACnet, you must specify the object
for the BACnet Broadcast Management Device (BBMD) if used. identifier, including the device object identifier or the object
name, in addition to the device object name and the property
Time-To-Live for Foreign Device Registration identifier.
The Time-To-Live for Foreign Device Registration parameter The BACnet Communication Module HTTP interface allows
indicates the time (in seconds) within which the foreign device you to read properties or read/write properties using the Test/
must re-register with the BBMD. If it does not re-register, the Test or Test/Variables pages. To perform any read or writes you
BBMD will remove (purge) it from its Foreign Device Table (FDT) must specify the Object Type (Analog, Integer, or Digital) and
and discontinue forwarding messages to the foreign device. the Index Number. For any enumerated types, the value read
from the HTTP pages correlates directly with the enumeration
BACnet IP when using BACnet. This document maps all HTTP points to
their corresponding BACnet points.
The BACnet IP parameters on the BACnet Properties and
System Configuration/Network pages indicate the Internet
Protocol parameters for the BACnet Communication Module. Configuring the Unit Controller
The UDP Port, IP address, subnet mask, and IP router The MicroTech II Chiller Unit Controller, along with the
address are variables that must be set during the BACnet BACnet Communication Module, is designed, programmed,
Communication Module configuration. The BACnet default and configured at the factory to be a chiller unit controller
UDP Port is 47808 (BAC0 in Hex). This value may be changed accessible over a BACnet network. No additional programming
at the BAS integrator’s discretion. is required to make this a chiller unit controller. The unit
controller is ready to operate with the default values of the
various parameters set at the factory. Default values may be
changed with the unit keypad or via the network. Parameters
must be adjusted in the HTTP interface to accommodate your
particular network. See the appropriate Operation Manual
for default values and keypad operating instructions and the
BACnet Communication Module Installation Manual (see
Reference Documents section for literature details.) The
Installation Manual specifies default values for variables
accessible from the network.

www.DaikinApplied.com 9 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Typical Application: Minimum Integration

Typical Application: Minimum Integration

When you have integrated the unit into your network, you can
monitor and control unit operation from your workstation. At a Display Important Data Points
minimum, you can: Typical workstation displays of MicroTech II Chiller Unit
• Display and monitor data points Controller attributes include the following significant data points
(page number of detailed description in parenthesis). Each
• Turn the unit on or off
data point is identified with a number that also references it in
• Operate the unit safely the Comprehensive Data Point Tables. These data points also
appear in boldface in the Comprehensive Data Point Tables.
Set Up the Unit for Network Control References in the text of this section also identify these data
points with a number and shading.

Unit Setup for MicroTech II Centrifugal Table 1: Significant Data Points


Chiller Network Control:
No. Configuration No. Temperatures No. Setpoints
1. Disable the chiller. The chiller should not be operating Evaporator
while performing this setup. 1 Chiller Status (26) 5 Entering Water 9 Cool Setpoint (42)
Temperature (44)
2. At the unit keypad: Evaporator
Chiller Mode Capacity Limit
2 6 Leaving Water 10
Setpoint (24) Setpoint (21)
a. In the Set Unit Setpoint screen 14, set the BAS Temperature (45)
Protocol to Modbus. Use the Manager Password Actual Capacity Condenser
3 7 Entering Water — —
of “2001.” (20) Temperature (38)
b. In the Set Unit Setpoint screen 1, set the Control Chiller Enable Condenser
4 8 Leaving Water — —
Source to Local. (22) Temperature (40)

3. Verify with the chiller/control company technician that the


chiller is operational on BAS. You can display any number of additional data points based
a. In the Set Unit Setpoint screen 1, set the Control on job requirements or individual preference. See BACnet
Source to BAS. Standard Objects for a list of all BACnet Objects available to
the network. For a more detailed description of all available
data points, see Detailed Data Point Information on page 15.
Setup for All Other MicroTech II Chillers
Network Control:
1. Set the Set Unit Setpoint screen 1 initially to Source =
Keypad.
2. Change the Protocol default to the appropriate BAS
Protocol in the applicable menu screen shown in the
table below.
3. Verify with the chiller/control company technician that the
chiller is operational on BAS.
4. Set the Set Unit Setpoint screen 1 to Source = Network.
WMC,
AGS-A, WGZ,
Model AGZ-A ACZ-A AGZ-B ACZ-B AGS-C AGS-D WGS WSC,
B, DP TGZ
WDC
Menu
7 6 10 7 12 16 17 15 14 10
Screen
Pass-
2001 2001 2001 2001 8945 8453 8745 8745 2001 2001
word
NOTE: Models AGZ-A/B, ACZ-A/B, WGZ, and TGZ have one unit controller, while models
AGS-B/C and WGS have one unit controller and multiple circuit controllers. Unit settings for
AGS-B/C and WGS models are adjusted on the unit controller.

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 10 www.DaikinApplied.com


Comprehensive Data Point Tables

Comprehensive Data Point Tables

BACnet Standard Objects


Chiller Variables

Object Type

Object Type
& Instance1
Network Control Property

W = Write
R = Read

Interface
Instance
Object
Keypad attributes available as BACnet

HTTP
Page
Standard Objects for network control of
the unit Description2
Active Setpoint 17 R AI 7 A2 -40°–199°F
*Actual Capacity (3) 17 R AI 9 A 10 0–160%
Actual RPM 0–32678
Compressor #1 18 R AI 56 I 118
Compressor #2 AI 60 I 122
*Capacity Limit (Output) (10) 19 R AI 8 A 42 0–160%
*Capacity Limit Setpoint (10) 19 W AO 32 A3 0 to 160%; Default=100%
*Chiller Enable (Input) (4) 20 W BV 41 D1 0=Request Chiller Off, 1=Request Chiller On, Default=Off
Chiller Limited 21 R BI 39 D6 0=Not Limited, 1=Limited
Chiller Local/Remote 22 R BI 38 D5 0=OFF, 1=ON
Chiller Mode Output 23 R MSI 44 I 19 1=Ice, 2=Cool, 3=Heat, Default=Cool
Chiller Mode Setpoint 24 W MSO 45 I 17 1=Ice, 2=Cool, 3=Heat, Default=Cool
Chiller ON OFF 25 R BI 33 D2 0=Chiller OFF, 1=Chiller ON
Chiller Power 25 R AI 67 I 116 Totalized compressor kilowatts.
*Chiller Status BACnet (1) 26 R MSI 43 I 18 1=Off, 2=Start, 3=Run, 4=Pre Shutdown, 5=Service
1=AGZS, 2=AGZD, 3=WGZD/TGZ, 4=WSC/WDC, 5=AGSU,
Chiller Type 27 R MSI 48 I 28 6=ACZS, 7=ACZD, 8=WMC, 9=WGSD, 10=AGSD, 11=AGZS,
12=AGZDU, 13=WGZU, 14=ACZSU, 15=ACZDU
Compressor 2 Active Capacity Limit 28 R AI 88 A 107
Compressor 2 VFD Speed 28 R AI 80 A 99
Compressor Current 0 –65,535
Compressor Select AI 51 A 26
Compressor #2 AI 76 A 95
Compressor #3 29 R AI 95 A 109
Compressor #4 AI 103 A 114
Compressor #5 AI 111 A 119
Compressor #6 AI 117 A124
Compressor Discharge Temperature -460°–621°F
Compressor Select 31 R AI 18 A 19
Compressor #2 AI 72 A 91
Compressor Percent RLA -3276.8–3276.7
Compressor Select AI 24 A 25
Compressor #2 AI 75 A 94
Compressor #3 32 R AI 94 A 108
Compressor #4 AI 102 A 113
Compressor #5 AI 110 A 118
Compressor #6 AI 116 A 123
Compressor Power 0–65,535
Compressor Select AI 54 A 27
Compressor #2 AI 77 A 96
Compressor #3 34 R AI 96 A 110
Compressor #4 AI 104 A 115
Compressor #5 AI 112 A 120
Compressor #6 AI 118 A 125
1. A=Analog, I=Integer and D=Digital (Binary).
2. Property Values between the BACnet points and the HTTP points are the same.
* Boldface denotes data points for typical minimum integration.

www.DaikinApplied.com 11 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Comprehensive Data Point Tables

Object Type

Object Type
& Instance1
Network Control Property

W = Write
R = Read

Interface
Instance
Object
Keypad attributes available as BACnet

HTTP
Page
Standard Objects for network control of
the unit Description2
Compressor Run Hours 0 –65,535; Hours reported at 1/10th the actual hours.
Compressor Select AI 26 I 46
Compressor #2 36 R AI 93 I 107
Compressor #3 AI 101 I 110
Compressor #4 AI 109 I 113
Compressor Select 37 W MSO 46 I 32 1=Comp1, 2=Comp2, 3=Comp3, 4=Comp4, 5=Comp5, 6=Comp6
Compressor Starts 0 –65,535
Compressor Select AI 25 I 45
Compressor #2 38 R AI 92 I 107
Compressor #3 AI 100 I 110
Compressor #4 AI 108 I 113
Compressor Status Bitwise logic:
Compressor Select AI 123 I 45 Bit 0=OFF
Compressor #2 AI 91 I 105 Bit 1=Start Oil Pump
Compressor #3 39 R AI 99 I 108 Bit 2=Interlock/Prelube
Compressor #4 AI 107 I 111 Bit 3=Run
Bit 4=Shutdown
Compressor #5 AI 115 I 114
Bit 5=Postlube
Compressor #6 AI 121 I 115
Compressor Suction Line Temperature -40°–244°F
Compressor Select 41 R AI 15 A 15
Compressor #2 AI 69 A 88
Compressor Voltage 0–65,535
Compressor Select AI 52 A 29
Compressor #2 AI 79 A 98
Compressor #3 42 R AI 98 A 112
Compressor #4 AI 106 A 117
Compressor #5 AI 114 A 122
Compressor #6 AI 120 A 127
*Condenser Entering Water 44 R AI 3 A7 -40°–244°F
Temperature (7)
Condenser Flow Rate 44 R AI 50 A 24 Flow Rate in GPM Centrifugals Only
Condenser Flow Switch Status 45 R BI 35 D8 0=No Flow, 1=Flow
*Condenser Leaving Water Temperature 45 R AI 4 A8 -40°–244°F
(8)
Condenser Pump Run Hours 0–65,535; Hours reported at 1/10th the actual hours.
Pump Select 46 R AI 28 I 48
Pump #2 AI 90 I 104
Condenser Refrigerant Pressure -3276.8–3276.7
Compressor Select 47 R AI 16 A 21
Compressor #2 AI 74 A 93
Condenser Saturated Refrigerant -40°–244°F
Temperature
48 R AI 17 A 20
Compressor Select
Compressor #2 AI 73 A 92
Condenser Water Pump Status 49 R BI 37 D 31 0=No Flow, 1=Flow
*Cool Setpoint (9) 50 W AO 29 A1 10 – 120°F; Default=44°F
Design RPM 0-32678
Compressor #1 51 R AI 63 I 125
Compressor #2 AI 64 I 126
*Evaporator Entering Water 52 R AI 1 A4 -40°–244°F
Temperature (5)
Evaporator Flow Switch Status 53 R BI 34 D7 0=No Flow, 1=Flow
*Evaporator Leaving Water 54 R AI 2 A6 -40°–244°F
Temperature for Unit (6)
1. A=Analog, I=Integer and D=Digital (Binary).
2. Property Values between the BACnet points and the HTTP points are the same.
* Boldface denotes data points for typical minimum integration.

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 12 www.DaikinApplied.com


Comprehensive Data Point Tables

Object Type

Object Type
& Instance1
Network Control Property

W = Write
R = Read

Interface
Instance
Object
Keypad attributes available as BACnet

HTTP
Page
Standard Objects for network control of
the unit Description2
Evaporator Leaving Water Temperature for -40°–244°F
Compressor AI 23 A 14
Compressor Select 55 R
Compressor #2 AI 68 A 87
Evaporator Pump Run Hours 0–65,535; Hours reported at 1/10th the actual hours.
Pump Select 56 R AI 27 I 47
Pump #2 AI 89 I 103
Evaporator Refrigerant Pressure -3276.8–3276.7
Compressor Select 57 R AI 13 A 17
Compressor #2 AI 71 A 90
Evaporator Saturated Refrigerant -40°–244°F
Temperature
Compressor Select 58 R AI 14 A 16
Compressor #2 AI 70 A 89
Evaporator Water Flow Rate 59 R AI 49 A 18 Flow Rate in GPM Centrifugals Only
Evaporator Water Pump Status 59 R BI 36 D 29 0=No Flow, 1=Flow
Heat Recovery Entering Water 60 R AI 5 A 22 -40°–244°F
Temperature
Heat Recovery Leaving Water 60 R AI 6 A 23 -40°–244°F
Temperature
Heat Setpoint 61 W AO 31 A5 50–150°F, Default=95°F
Ice Setpoint 62 W AO 30 A 50 15–35°F, Default=25°F
IGV Percentage Open 0–110%
Compressor #1 63 R AI 58 I 120
Compressor #2 AI 62 I 124
Inverter Temperature 32.0–212.0°F
Compressor #1 64 R AI 66 A 86
Compressor #2 AI 87 A 106
Liquid Line Refrigerant Pressure 65 R AI 12 A 38 -22592–22591 psi
Liquid Line Refrigerant Temperature -40°–244°F
Compressor Select 66 R AI 11 A 36
Compressor #2 AI 85 A 104
Maximum RPM 0–32678
Compressor #1 67 R AI 55 I 117
Compressor #2 AI 59 I 121
Minimum RPM 0–32678
Compressor #1 68 R AI 57 I 119
Compressor #2 AI 61 I 123
Motor Cavity Temperature
Compressor #1 69 R AI 65 A 85
Compressor #2 AI 86 A 105
Oil Feed Pressure -22592–22591 psi
Compressor Select 70 R AI 19 A 32
Compressor #2 AI 81 A100
Oil Feed Temperature -40°–244°F
Compressor Select 71 R AI 21 A 34
Compressor #2 AI 83 A 102
Oil Sump Pressure -22592–22591 psi
Compressor Select 72 R AI 20 A 33
Compressor #2 AI 82 A 101
Oil Sump Temperature -40°–244°F
Compressor Select 73 R AI 22 A 35
Compressor #2 AI 84 A 103
Outdoor Air Temperature 74 R AI 10 A 39 -40°F–244°F
1. A=Analog, I=Integer and D=Digital (Binary).
2. Property Values between the BACnet points and the HTTP points are the same.
* Boldface denotes data points for typical minimum integration.

www.DaikinApplied.com 13 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Comprehensive Data Point Tables

Object Type

Object Type
& Instance1
Network Control Property

W = Write
R = Read

Interface
Instance
Object
Keypad attributes available as BACnet

HTTP
Page
Standard Objects for network control of
the unit Description2
Power Factor -99– +100
Compressor Select AI 53 A 28
Compressor #2 AI 78 A 97
Compressor #3 75 R AI 97 A 111
Compressor #4 AI 105 A 116
Compressor #5 AI 113 A121
Compressor #6 AI 119 A126
Pump Select 76 W MSO 47 D 19 1=Pump No. 1, 2=Pump No. 2; Default=1
Run Enabled 77 R BI 33 D2 0=OFF, 1=Run Allowed
1. A=Analog, I=Integer and D=Digital (Binary).
2. Property Values between the BACnet points and the HTTP points are the same.
* Boldface denotes data points for typical minimum integration.

Chiller Alarm Objects


Object Type

Object Type
& Instance
Network Control Property
W = Write
R = Read

Interface
Instance
Object

Keypad attributes available as BACnet


HTTP
Page

Standard Objects for network control of the


unit Description
Warning Alarms, Analog Input Object (11) 79 R AI 902 N/A Alarm Index
Problem Alarms, Analog Input Object (11) 79 R AI 900 N/A Alarm Index
Fault Alarms, Analog Input Object (11) 79 R AI 901 N/A Alarm Index
Warning Alarms, Multi-state Input Object (11) 80 R MSI 902 N/A Alarm Index and Alarm Text (30 characters max)
Problem Alarms, Multi-state Input Object (11) 80 R MSI 900 N/A Alarm Index and Alarm Text (30 characters max)
Fault Alarms, Multi-state Input Object (11) 81 R MSI 901 N/A Alarm Index and Alarm Text (30 characters max)
Alarm Digital Output (11) 81 R BI 40 D3 0-No Alarm, 1=Alarm
BACnet Clear Alarm (12) 82 W BV 42 D 24 0= Normal, 1=Clear Alarm

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 14 www.DaikinApplied.com


Detailed Data Point Information

Detailed Data Point Information

This section lists the information (the data) that is available to


the BAS via the BACnet network. This information is used to
safely operate and log the performance of the chiller. The BAS
system integrator also uses this information when creating
custom graphics.
The information needed to access these points through the
HTTP interface is also included. The HTTP interface allows
you to read/write these data points using their Analog, Integer
and Digital designations along with an index number for each
variable. For the Property Values definitions of the HTTP data
points, refer to that same points BACnet variable description.

Table 2: Data Points for Chiller Models


WSC, WDC,
WPV, HSC,
HDC, TSC,
Data Point WMC, WCC AGZ ACZ AGS WGZ, TGZ WGS
Active Setpoint X X X X X
Actual Capacity X X X X X
Actual RPM X*****
Capacity Limit Output X X* X* X X X
Capacity Limit Setpoint X X* X* X X X
Cavity Temperature X*****
Chiller Enable X X X X X X
Chiller Limited X X* X* X X X
Chiller Local/Remote X X X X X X
Chiller Location X X X X X X
Chiller Mode Output X X X X X
Chiller Mode Setpoint X X X X X
Chiller On Off X X X X X X
Chiller Status X X X X X X
Chiller Type X X X X X
Compressor Current** X X
Compressor Discharge Temperature X X X
Compressor Percent RLA X X
Compressor Power** X X
Compressor Run Hours X X X X X X
Compressor Select X X X X X X
Compressor Starts X X X X X X
Compressor Suction Line Temperature X X X X
Compressor Voltage** X X
Condenser Entering Water Temperature X X X
Condenser Flow Switch Status X X X
Condenser Leaving Water Temperature X X X
Condenser Pump Run Hours X
Condenser Refrigerant Pressure X X X X X X
Condenser Saturated Refrigerant Temperature X X X X X X
Condenser Water Flow Rate X X
Condenser Water Pump Status X X X
Cool Setpoint X X X X X
Current Alarm X X X X X X
Design RPM X*****
Device Object X X X X X X
Evaporator Entering Water Temperature X X X X
Evaporator Flow Switch Status X X X X X X
Evaporator Leaving Water Temperature for Unit X X X X X
* Dual Circuit Only
** Optional Solid State Starter Required. Voltage, Power and Current are per compressor
*** Not available on the WMC
**** AGS A and B vintage only
***** WMC only

www.DaikinApplied.com 15 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

WSC, WDC,
WPV, HSC,
HDC, TSC,
Data Point WMC, WCC AGZ ACZ AGS WGZ, TGZ WGS
Evaporator Leaving Water Temperature for X X X
Compressor
Evaporator Pump Run Hours X
Evaporator Refrigerant Pressure X X X X X X
Evaporator Saturated Refrigerant Temperature X X X X X X
Evaporator Water Flow Rate X X
Evaporator Water Pump Status X X X X X
Fault Alarms, Analog Input Object X X X X X X
Fault Alarms, Multi-state Input Object X X X X X X
Heat Recovery Entering Water Temperature X
Heat Recovery Leaving Water Temperature X
Heat Setpoint X
Ice Setpoint X X X X X
IGV Percentage Open X*****
Inverter Temperature X*****
Liquid Line Refrigerant Pressure X****
Liquid Line Refrigerant Temperature X X**** X
Maximum RPM X*****
Minimum RPM X*****
Network Clear Alarm X X X X X
Oil Feed Pressure*** X
Oil Feed Temperature*** X
Oil Sump Pressure*** X
Oil Sump Temperature*** X
Outdoor Air Temperature X X X
Power Factor
Problem Alarms, Analog Input Object X X X X X X
Problem Alarms, Multi-state Input Object X X X X X X
Pump Select X
Run Enabled X X X X X X
Warning Alarms, Analog Input Object X X X X X X
Warning Alarms, Multi-state Input Object X X X X X X
* Dual Circuit Only
** Optional Solid State Starter Required. Voltage, Power and Current are per compressor
*** Not available on the WMC
**** AGS A and B vintage only
***** WMC only

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 16 www.DaikinApplied.com


Detailed Data Point Information

Active Setpoint
Keypad Menu Path: This output network variable indicates the current value of the setpoint temperature used to control the
Menu temperature of the Leaving Chilled Water or Leaving Hot Water. Based on the operating mode of the
\Set chiller, this value is derived from the Cool Setpoint, Heat Setpoint, or Ice Setpoint. The default mode is
\Unit SPs (3) Cooling and is used unless changed by the Mode input. (A2)

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–199° F/-40°-93°C NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 7 Present Value 85
Object Name
ActiveLvgWaterTarget

HTTP Interface
Variable Details

Variable Type Index


Analog 2

Actual Capacity
Keypad Menu Path: This output network variable indicates the percent of capacity the chiller is currently producing. It may
No Keypad Equivalent be more or less than the nominal capacity of the chiller. For Centrifugal chillers, this is the combined
percent RLA of the compressors. For positive displacement chillers (those using screw and scroll
compressors) this is a percentage of total compressors running. (A10)

Measurement Units Data Type Valid Range Default Value


Percent of chiller capacity NA Real 0% to 160% NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 9 Present Value 85
Object Name
ChillerCapacity

HTTP Interface
Variable Details

Variable Type Index


Analog 10

www.DaikinApplied.com 17 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Actual RPM
Keypad Menu Path: This variable indicates the actual speed of the compressor. (I118 & I122)
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Revolutions per Minute BACnet: RPM BACnet: Real BACnet: 0-32678 NA

BACnet
Compressor #1
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 56 Present Value 85
Object Name
Comp1ActualRPM

Compressor #2
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 60 Present Value 85
Object Name
Comp2ActualRPM

HTTP Interface
Variable Details

Compressor Variable Type Index


1 Integer 118
1 Integer 122

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 18 www.DaikinApplied.com


Detailed Data Point Information

Capacity Limit Output


Keypad Menu Path: This output variable is a measure of the ratio of operating capacity to full capacity expressed in percent.
No Keypad Equivalent This output variable indicates the current value of the Capacity Limit. (A42)

Measurement Units Data Type Valid Range Default Value


Percent of maximum capacity NA Real 0% to 160%. NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 8 Present Value 85
Object Name
ActiveCapacityLimit

HTTP Interface
Variable Details

Variable Type Index


Analog 42

Capacity Limit Setpoint


Keypad Menu Path: Capacity Limit is a measure of the ratio of operating capacity to full capacity expressed in percent. This
No Keypad Equivalent level may be adjusted via an operator workstation or other network device, but cannot be adjusted
above a factory-specified limit. The input network variable sets the operating value (input). Refer to the
appropriate Operation Manual for suitable variable values. (A3)

Measurement Units Data Type Valid Range Default Value


Percent of maximum capacity NA Real 0% to 160%. See Below

BACnet
This read or read/write property sets the maximum capacity limit of the chiller. This level may be adjusted, but cannot be adjusted
above a factory-specified limit.

Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Output 1 32 Present Value 85
Object Name
NetworkCapacityLimitPct

Default Value (Relinquish_Default) 100%

HTTP Interface
Variable Details

Variable Type Index


Analog 3

www.DaikinApplied.com 19 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Chiller Enable
Keypad Menu Path: The Chiller Enable data point starts the chiller in a particular way. This is a commandable property. Refer
Menu to the appropriate Operating Manual for suitable variable values. (D1)
\Set
\Unit SP (1)

Measurement Units Data Type Valid Range Default Value


Chiller State NA Enumerated See Below See Below

BACnet
This read or read/write property enables (starts) the chiller to run if the operating conditions are satisfied, or disables (stops) the
chiller from running. When this property is read, it indicates the current operating state of the chiller.

Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Value 5 41 Present Value 85
Object Name
ChillerEnable
Property Values
0 = Disable (Inactive)
1 = Enable (Active)

Default Value (Relinquish_Default) 0 = Request Chiller OFF

HTTP Interface
Variable Details

Variable Type Index


Digital 1

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 20 www.DaikinApplied.com


Detailed Data Point Information

Chiller Limited
Keypad Menu Path: This output network variable indicates the main running mode and states of the chiller. The Limited
No Keypad Equivalent network variable indicates whether conditions exist that prevent the chiller from reaching setpoint. (D6)

Measurement Units Data Type Valid Range Default Value


Status NA Enumerated See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 39 Present Value 85
Object Name
ChillerLimited
Property Values
0 = Not Limited (Inactive)
1 = Limited (Active)

HTTP Interface
Variable Details

Variable Type Index


Digital 6

www.DaikinApplied.com 21 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Chiller Local/Remote
Keypad Menu Path: The Local/Remote network variable indicates whether the chiller is in local control or allowed to be
No Keypad Equivalent controlled remotely over the network. (D5)

Measurement Units Data Type Valid Range Default Value


Mode NA Enumerated See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 38 Present Value 85
Object Name
ChillerLocalRemote
Property Values
0 = OFF (Inactive)
1= ON (Active)

HTTP Interface
Variable Details

Variable Type Index


Digital 5

Chiller Location
Keypad Menu Path: This configuration network parameter provides a description of the location of the chiller.
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Any NUL terminated ASCII
NA NA Structure ASCII string of zeros + NUL
string up to 31 bytes.

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 22 www.DaikinApplied.com


Detailed Data Point Information

Chiller Mode Output


Keypad Menu Path: This output data point indicates the current operating mode of the chiller. (I19)
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


HVAC Mode NA Unsigned Integer See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 44 Present Value 85
Object Name
ActiveMode
Property Values
1. ICE
2. COOL
3. HEAT

HTTP Interface
Variable Details

Variable Type Index


Integer 19

www.DaikinApplied.com 23 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Chiller Mode Setpoint


Keypad Menu Path: The Chiller Mode data point determines the mode of operation of the chiller. This is a commandable
Menu property of a Multi-state Output object. Refer to the appropriate Operating Manual for suitable variable
\Set values. (I17)
\Unit SP (1)

Measurement Units Data Type Valid Range Default Value


HVAC Mode NA Unsigned Integer See Below See Below

BACnet
This commandable property sets the mode of operation of the chiller and provides the ability for another node on the network to
place a chiller in another mode.

Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Output 14 45 Present Value 85
Object Name
ChillerOperationMode
Property Values
1. ICE
2. COOL
3. HEAT

Default Value (Relinquish_Default) 2

HTTP Interface
Variable Details

Variable Type Index


Integer 17

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 24 www.DaikinApplied.com


Detailed Data Point Information

Chiller ON/OFF
Keypad Menu Path: This output network variable indicates the current run-allowed state of the chiller. The OFF state is
Menu represented by state = FALSE and value = 0. The other discrete states are represented by state =
\View TRUE and value > 0. (D2) It is normally recommended to monitor the “Chiller Status” data point for the
\Unit current operating state of the chiller.
\Status

Measurement Units Data Type Valid Range Default Value


Chiller State NA Enumerated See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 33 Present Value 85
Object Name
UnitOFF
Property Values
0 = OFF
1 = Run Allowed

HTTP Interface
Variable Details

Variable Type Index


Digital 2

Chiller Power
Keypad Menu Path: This variable indicates the totalized compressor kilowatts. (I116).
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


BACnet: Real
Percent of chiller capacity NA LONWORKS: Fixed-Point 0–160% NA
Scalar signed long

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 67 Present Value 85
Object Name
TotalChillerKW

HTTP Interface
Variable Details

Variable Type Index


Integer 116

www.DaikinApplied.com 25 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Chiller Status
Keypad Menu Path: This output network variable indicates the main running mode and states of the chiller. The mode
Menu provides the primary running states of a chiller and the state provides an indicator of other conditions
\View present. (I18)
\Unit
\Status

Measurement Units Data Type Valid Range Default Value


State NA Unsigned Integer See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 43 Present Value 85
Object Name
UnitStatus
Property Values
1 = OFF
2 = Start
3 = Run
4 = Pre Shutdown
5 = Service

HTTP Interface
Variable Details

Variable Type Index


Integer 18

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 26 www.DaikinApplied.com


Detailed Data Point Information

Chiller Type
Keypad Menu Path: This output network variable indicates the type of chiller connected to this unit controller. (I28)
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Event Count NA Unsigned Integer See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 48 Present Value 85
Full Reference
DaikinChillerType
Property Values
1 = AGZS 6 = ACZS 11 = AGZS
2 = AGZD 7 = ACZD 12 = AGZDU
3 = WGZD 8 = WMC 13 = WGZ/TGZ
4 = WSC/WDC 9 = WGSD 14 = ACZSU
5 = AGSU 10 = AGSD 15 = ACZDU

HTTP Interface
Variable Details

Variable Type Index


Integer 28

www.DaikinApplied.com 27 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor 2 Active Capacity Limit


Keypad Menu Path:
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Percent BACnet: Percent BACnet: Real BACnet: 0–100% NA

BACnet
Compressor #2
This variable indicates the active capacity limit for compressor 2. (A107)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 88 Present Value 85
Object Name
Comp2ActiveCapLimit

HTTP Interface
Variable Details

Variable Type Index


Analog 107

Compressor 2 VFD Speed


Keypad Menu Path:
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Percent BACnet: Percent BACnet: Real BACnet: 0–100% NA

BACnet
Compressor #2
This variable indicates the VFD speed for compressor 2. (A99)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 80 Present Value 85
Object Name
Comp2Speed

HTTP Interface
Variable Details

Variable Type Index


Analog 99

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 28 www.DaikinApplied.com


Detailed Data Point Information

Compressor Current
Keypad Menu Path:
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Electric Current Amperes Real -3276.8-3276.7 NA

BACnet
Compressor Select
This output network variable indicates the current compressor amperes of the compressor selected with Compressor Select on
page 37. (A26)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 51 Present Value 85
Object Name
Current

Compressor #2
This variable indicates the current compressor amperes of compressor 2. (A95)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 76 Present Value 85
Object Name
Comp2Current

Compressor #3
This variable indicates the current compressor amperes of compressor 3. (A109)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 95 Present Value 85
Object Name
Comp3Current

Compressor #4
This variable indicates the current compressor amperes of compressor 4. (A114)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 103 Present Value 85
Object Name
Comp4Current

Compressor #5
This variable indicates the current compressor amperes of compressor 5. (A119)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 111 Present Value 85
Object Name
Comp5Current

www.DaikinApplied.com 29 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor #6
This variable indicates the current compressor amperes of compressor 6. (A124)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 117 Present Value 85
Object Name
Comp6Current

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 26
Compressor #2 Analog 95
Compressor #3 Analog 109
Compressor #4 Analog 114
Compressor #5 Analog 119
Compressor #6 Analog 124

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 30 www.DaikinApplied.com


Detailed Data Point Information

Compressor Discharge Temperature


Keypad Menu Path:
Menu
\View
\Comp (5)

Measurement Units Data Type Valid Range Default Value


-460°–621°F
Temperature °F/ °C Real NA
-273.17°–327.66°C

BACnet
Compressor Select
This output network variable indicates the current compressor refrigerant temperature of the compressor selected with Compressor
Select on page 37. (A19)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 18 Present Value 85
Object Name
DischargeTemp

Compressor #2
This output network variable indicates the current compressor 2 refrigerant temperature. (A91)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 72 Present Value 85
Object Name
Comp2DischargeTmp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 19
Compressor #2 Analog 91

www.DaikinApplied.com 31 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor Percent RLA


Keypad Menu Path:
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Percent RLA Percent Real 0% to 160% NA

BACnet
Compressor Select
This output network variable indicates the current motor current for the compressor motor of the compressor selected with
Compressor Select on page 37. (A25)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 24 Present Value 85
Object Name
CompMotorCurrentPercent

Compressor #2
This variable indicates the current motor current for compressor 2. (A94)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 75 Present Value 85
Object Name
Comp2MotorCurrentPercent

Compressor #3
This variable indicates the current motor current for compressor 3. (A108)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 94 Present Value 85
Object Name
Comp3MotorCurrentPercent

Compressor #4
This variable indicates the current motor current for compressor 4. (A113)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 102 Present Value 85
Object Name
Comp4MotorCurrentPercent

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 32 www.DaikinApplied.com


Detailed Data Point Information

Compressor #5
This variable indicates the current motor current for compressor 5. (A118)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 110 Present Value 85
Object Name
Comp5MotorCurrentPercent

Compressor #6
This variable indicates the current motor current for compressor 6. (A123)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 116 Present Value 85
Object Name
Comp6MotorCurrentPercent

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 25
Compressor #2 Analog 94
Compressor #3 Analog 108
Compressor #4 Analog 113
Compressor #5 Analog 118
Compressor #6 Analog 123

www.DaikinApplied.com 33 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor Power
Keypad Menu Path:
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Power kiloWatts Real 0-6553.5 NA

BACnet
Compressor Select
This output network variable indicates the current power for the compressor motor of the compressor selected with Compressor
Select on page 37. (A27)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 54 Present Value 85
Object Name
Kilowatts

Compressor #2
This variable indicates the current power for the compressor motor of compressor 2 (A96).
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 77 Present Value 85
Object Name
Comp2Kilowatts

Compressor #3
This variable indicates the current power for the compressor motor of compressor 3 (A110).
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 96 Present Value 85
Object Name
Comp3Kilowatts

Compressor #4
This variable indicates the current power for the compressor motor of compressor 4 (A115).
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 104 Present Value 85
Object Name
Comp4Kilowatts

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 34 www.DaikinApplied.com


Detailed Data Point Information

Compressor #5
This variable indicates the current power for the compressor motor of compressor 5 (A120).
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 112 Present Value 85
Object Name
Comp5Kilowatts

Compressor #6
This variable indicates the current power for the compressor motor of compressor 6 (A125).
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 118 Present Value 85
Object Name
Comp6Kilowatts

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 27
Compressor #2 Analog 96
Compressor #3 Analog 110
Compressor #4 Analog 115
Compressor #5 Analog 120
Compressor #6 Analog 125

www.DaikinApplied.com 35 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor Run Hours


Keypad Menu Path: NOTE: Value returned must be multiplied by 10 to give run hours.
Menu
\View
\Compressor

Measurement Units Data Type Valid Range Default Value


Event Count Hours Real 0–65,535 NA

BACnet
Compressor Select
This output network variable indicates the number of hours that the compressor motor of the compressor selected with Compressor
Select on page 37. Compressor 1 is the default selection. Value is Hrs/10. (I46)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 26 Present Value 85
Object Name
CompHours

Compressor #2
This variable indicates the number of hours for compressor 2. This variable is not available on all chiller models. Value is Hrs/10. (I107)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 93 Present Value 85
Object Name
Comp2Hours

Compressor #3
This variable indicates the number of hours for compressor 3. This variable is not available on all chiller models. Value is Hrs/10. (I110)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 101 Present Value 85
Object Name
Comp3Hours

Compressor #4
This variable indicates the number of hours for compressor 4. This variable is not available on all chiller models. Value is Hrs/10. (I113)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 109 Present Value 85
Object Name
Comp4Hours

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Integer 46
Compressor #2 Integer 107
Compressor #3 Integer 110
Compressor #4 Integer 113

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 36 www.DaikinApplied.com


Detailed Data Point Information

Compressor Select
Keypad Menu Path: This input network variable selects the compressor/circuit (number 1, 2, 3, 4, 5 or 6) that is interrogated.
No Keypad Equivalent The controller returns the information for the selected compressor/circuit. You must first select a
compressor/circuit, then interrogate the selected compressor/circuit. This variable selects a compressor/
circuit for the following variables. See Table 2: Data Points for Chiller Models on page 15 to determine
which of these variables will be available. (I32)
Name Page
Compressor Current 28
Compressor Discharge Temperature 29
Compressor Percent RLA 29
Compressor Power 31
Compressor Run Hours 32
Compressor Starts 34
Compressor Suction Line Temperature 37
Compressor Voltage 37
Condenser Refrigerant Pressure 41
Condenser Saturated Refrigerant Temperature 41
Evaporator Leaving Water Temperature for Compressor 45
Evaporator Refrigerant Pressure 46
Evaporator Saturated Refrigerant Temperature 47
Oil Feed Pressure 54
Oil Feed Temperature 55
Oil Sump Pressure 56
Oil Sump Temperature 56

Measurement Units Data Type Valid Range Default Value


Event Count NA Unsigned Integer 0–65,535 Comp No. 1

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Output 14 46 Present Value 85
Object Name
CompSelect
Property Values
1 = Comp/Circuit No. 1
2 = Comp/Circuit No. 2
3 = Comp/Circuit No. 3 (Circuit No. 1 on Scroll Chillers and Condensing Units)
4 = Comp/Circuit No. 4 (Circuit No. 2 on Scroll Chillers and Condensing Units)
5 = Comp No. 5 (Circuit No. 1 on Scroll Chillers and Condensing Units)
6 = Comp No. 6 (Circuit No. 2 on Scroll Chillers and Condensing Units)

HTTP Interface
Variable Details

Variable Type Index


Integer 32

www.DaikinApplied.com 37 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor Starts
Keypad Menu Path:
Menu
\View
\Compressor

Measurement Units Data Type Valid Range Default Value


Event Count NA Real 0–65,535 NA

BACnet
Compressor Select
This output network variable indicates the number of times the compressor motor of the compressor selected with Compressor
Select on page 37 has started. (I45)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 25 Present Value 85
Object Name
CompStarts

Compressor #2
This variable indicates the number of times the compressor 2 motor has started. (I106)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 92 Present Value 85
Object Name
Comp2Starts

Compressor #3
This variable indicates the number of times the compressor 3 motor has started. (I109)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 100 Present Value 85
Object Name
Comp3Starts

Compressor #4
This variable indicates the number of times the compressor 4 motor has started. (I112)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 108 Present Value 85
Object Name
Comp4Starts

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Integer 45
Compressor #2 Integer 106
Compressor #3 Integer 109
Compressor #4 Integer 112

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 38 www.DaikinApplied.com


Detailed Data Point Information

Compressor Status
This output network variable indicates the number status of the compressor.
Measurement Units Data Type Valid Range Default Value
BACnet: Real
Event Count NA LONWORKS: Fixed Point 0-31 NA
Scalar - unsigned long

BACnet
Compressor Select
This output network variable indicates the compressor status of the compressor selected with Compressor Select on page 37. (I44)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 123 Present Value 85
Object Name
CompressorStatus
0=OFF
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown

Compressor #2
This output network variable indicates the compressor status of the compressor 2. (I105)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 91 Present Value 85
Object Name
Comp2Status
0=OFF
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown

Compressor #3
This output network variable indicates the compressor status of the compressor 3. (I108)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 99 Present Value 85
Object Name
Comp3Status
0=OFF
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown

www.DaikinApplied.com 39 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor #4
This output network variable indicates the compressor status of the compressor 42. (I111)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 107 Present Value 85
Object Name
Comp4Status
0=OFF
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown

Compressor #5
This output network variable indicates the compressor status of the compressor 5. (I114)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 115 Present Value 85
Object Name
Comp5Status
0=OFF
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown

Compressor #6
This output network variable indicates the compressor status of the compressor 6. (I115)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 121 Present Value 85
Object Name
Comp6Status
0=OFF
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Integer 45
Compressor #2 Integer 105
Compressor #3 Integer 108
Compressor #4 Integer 111
Compressor #5 Integer 114
Compressor #6 Integer 115

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 40 www.DaikinApplied.com


Detailed Data Point Information

Compressor Suction Line Temperature


Keypad Menu Path:
Menu
\View
\Unit
\Refrigerant (2)

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-40°–118°C NA

BACnet
Compressor Select
This output network variable indicates the current suction line refrigerant temperature. There is a separate output for each
compressor. See Compressor Select on page 37. (A15)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 15 Present Value 85
Object Name
SuctionTemp

Compressor #2
This variable indicates the current suction line refrigerant temperature for compressor 2. This variable is not available on all chiller
models. (A88)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 69 Present Value 85
Object Name
Comp2SuctTemp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 15
Compressor #2 Analog 88

www.DaikinApplied.com 41 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor Voltage
Keypad Menu Path:
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Electric Voltage VAC Real 0-65,534 NA

BACnet
Compressor Select
This output network variable indicates the current compressor voltage. There is a separate output for each compressor. See
Compressor Select on page 37. (A29)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 52 Present Value 85
Object Name
Voltage

Compressor #2
This variable indicates the current compressor voltage for compressor 2. It is available via BACnet only. (A98)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 79 Present Value 85
Object Name
Comp2Voltage

Compressor #3
This variable indicates the current compressor voltage for compressor 3. It is available via BACnet only. (A112)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 98 Present Value 85
Object Name
Comp3Voltage

Compressor #4
This variable indicates the current compressor voltage for compressor 4. It is available via BACnet only. (A117)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 106 Present Value 85
Object Name
Comp4Voltage

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 42 www.DaikinApplied.com


Detailed Data Point Information

Compressor #5
This variable indicates the current compressor voltage for compressor 5. It is available via BACnet only. (A122)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 114 Present Value 85
Object Name
Comp5Voltage

Compressor #6
This variable indicates the current compressor voltage for compressor 6. It is available via BACnet only. (A127)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 120 Present Value 85
Object Name
Comp6Voltage

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 29
Compressor #2 Analog 98
Compressor #3 Analog 112
Compressor #4 Analog 117
Compressor #5 Analog 122
Compressor #6 Analog 127

www.DaikinApplied.com 43 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Condenser Entering Water Temperature


Keypad Menu Path: This output network variable indicates the current temperature of the entering condenser water. (A7)
Menu
\View
\Unit
\Water

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-40°–118°C NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 3 Present Value 85
Object Name
EntCondWaterTemp

HTTP Interface
Variable Details

Variable Type Index


Analog 7

Condenser Flow Rate


Keypad Menu Path: This output network variable indicates the rate of the water flow through the condenser. (A24)
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Flow Volume GPM / L/S Real 0–65,534 NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 50 Present Value 85
Object Name
CondWaterFlowRate

HTTP Interface
Variable Details

Variable Type Index


Analog 24

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 44 www.DaikinApplied.com


Detailed Data Point Information

Condenser Flow Switch Status


Keypad Menu Path: This output network variable indicates the status of the water flow through the condenser. (D8)
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Flow State NA Enumerated See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 35 Present Value 85
Object Name
CondWaterFlowStatus
Property Values
0 = No Flow (Inactive)
1 = Flow (Active)

HTTP Interface
Variable Details

Variable Type Index


Digital 8

Condenser Leaving Water Temperature


Keypad Menu Path: This output network variable indicates the current temperature of the leaving condenser water. (A8)
Menu
\View
\Unit Water

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-40°–118°C NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 4 Present Value 85
Object Name
LvgCondWaterTemp

HTTP Interface
Variable Details

Variable Type Index


Analog 8

www.DaikinApplied.com 45 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Condenser Pump Run Hours


Keypad Menu Path: NOTE: Value returned must be multiplied by 10 to give run hours.
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Event Count NA Real 0–65,535 NA

BACnet
Pump Select
This output network variable indicates the number of hours that the selected condenser pump motor has been turned on. See
Pump Select on page 76. Value is Hrs/10. (I48)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 28 Present Value 85
Object Name
CondPumpOperHours

Pump #2
This output network variable indicates the number of hours that the selected condenser pump motor for compressor 2 has been
turned on. This variable is not available on all chiller models. Value is Hrs/10. (I104)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 90 Present Value 85
Object Name
CondPmp2Hrs

HTTP Interface

Variable Details
Variable Variable Type Index
Pump Select Integer 48
Pump #2 Integer 104

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 46 www.DaikinApplied.com


Detailed Data Point Information

Condenser Refrigerant Pressure


Keypad Menu Path:
Menu
\View
\Unit
\Refrigerant (1)

Measurement Units Data Type Valid Range Default Value


-22592–22591 psi /
Pressure (gauge) Psi/kPa Real NA
-3,276.8–3,276.7 kPA

BACnet
Compressor Select
This output network variable indicates the current refrigerant pressure in the selected condenser. There is a separate output for
each compressor. See Compressor Select on page 37. (A21)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 16 Present Value 85
Object Name
CondPressure

Compressor #2
This variable indicates the current refrigerant pressure for compressor 2. This variable is not available on all chiller models. (A93)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 74 Present Value 85
Object Name
Comp2CondPress

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 21
Compressor #2 Analog 93

www.DaikinApplied.com 47 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Condenser Saturated Refrigerant Temperature


Keypad Menu Path:
Menu
\Unit
\Refrigerant (1)

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-40°–118°C NA

BACnet
Compressor Select
This output network variable indicates the current saturated refrigerant temperature in the condenser. There is a separate output for
each compressor. See Compressor Select on page 37. (A20)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 17 Present Value 85
Object Name
CondSatTemp

Compressor #2
This variable indicates the current saturated refrigerant temperature in the condenser for compressor 2. This variable is not
available on all chiller models. (A92)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 73 Present Value 85
Object Name
Comp2CondSatTemp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 20
Compressor #2 Analog 92

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 48 www.DaikinApplied.com


Detailed Data Point Information

Condenser Water Pump Status


Keypad Menu Path: This output network variable indicates whether the selected pump has been commanded ON or OFF.
No Keypad Equivalent See Pump Select on page 76.(D31)

Measurement Units Data Type Valid Range Default Value


Flow State NA Enumerated See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 37 Present Value 85
Object Name
CondPumpState
Property Values
0 = OFF (Inactive)
1 = ON (Active)

HTTP Interface
Variable Details

Variable Type Index


Digital 31

www.DaikinApplied.com 49 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Cool Setpoint
Keypad Menu Path: The Cool Setpoint data point determines the temperature of the Leaving Chilled Water. This is a
Menu commandable property of an Analog Output object. Refer to the appropriate Operation Manual for
\Set suitable variable values. (A1)
\Unit SPs (3)

Measurement Units Data Type Valid Range Default Value


Dependent on Chiller mode
Temperature °F/°C Real See below
and model

BACnet
This commandable property sets the temperature of the Leaving Chilled Water. This level may be adjusted via an operator
workstation or other network device.

Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Output 1 29 Present Value 85
Object Name
NetworkCoolTempSetpoint

Default Value (Relinquish_Default) 44°F

HTTP Interface
Variable Details

Variable Type Index


Analog 1

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 50 www.DaikinApplied.com


Detailed Data Point Information

Design RPM
Keypad Menu Path: This output network variable indicates the Turbocor compressors calculated speed target based on
No Keypad Equivalent conditions and request demand. (I125 & I126)

Measurement Units Data Type Valid Range Default Value


Revolutions per Minute BACnet: RPM BACnet: Real BACnet: 0–32678 NA

BACnet
Compressor #1
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 63 Present Value 85
Object Name
Comp1DesignRPM

Compressor #2
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 64 Present Value 85
Object Name
Comp2DesignRPM

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor #1 Integer 125
Compressor #2 Integer 126

Device Object
CAUTION
If another device in the network has the same object identifier
(instance number), you must change the instance number of
one device object so that all devices in the network have a
unique device instance.

Keypad Menu Path: Each BACnet compatible device must have a single BACnet Device Object. The device object contains
No Keypad Equivalent all required properties. All properties of the device object may be read, but cannot be changed over the
network. The initial instance of the MicroTech II Chiller device object is 3000. All critical properties of the
device object can be changed in the HTTP interface.

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Device 8 3000
Object Name
MTII Chiller UC 3000

www.DaikinApplied.com 51 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Evaporator Entering Water Temperature


Keypad Menu Path: This output attribute indicates the temperature of the evaporator entering water temperature. (A4)
Menu
\View
\Unit
\Water

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40–245°F/-40°–118°C NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 1 Present Value 85
Object Name
EntEvapWaterTemp

HTTP Interface
Variable Details

Variable Type Index


Analog 4

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 52 www.DaikinApplied.com


Detailed Data Point Information

Evaporator Flow Switch Status


Keypad Menu Path: This output network variable indicates the status of water flow through the evaporator. (D7)
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Flow State NA Enumerated See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 34 Present Value 85
Object Name
EvapWaterFlowStatus
Property Values
0 = No Flow (Inactive)
1 = Flow (Active)

HTTP Interface
Variable Details

Variable Type Index


Digital 7

www.DaikinApplied.com 53 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Evaporator Leaving Water Temperature for Unit


Keypad Menu Path: This output network variable indicates the current temperature of the evaporator leaving chilled water. (A6)
Menu
\View
\Unit Water
or
Menu
\View
Comp (2)

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-4°–118°C NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 2 Present Value 85
Object Name
LvgEvapWaterTempUnit

HTTP Interface
Variable Details

Variable Type Index


Analog 6

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 54 www.DaikinApplied.com


Detailed Data Point Information

Evaporator Leaving Water Temperature for Compressor


Keypad Menu Path:
Menu
\View
\Comp

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-40°–118°C NA

BACnet
Compressor Select
This output network variable indicates the current temperature of the Evaporator leaving chilled water temperature of the
compressor selected with Compressor Select on page 37.(Centrifugals only). (A14)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 23 Present Value 85
Object Name
LvgEvapWaterTempComp

Compressor #2
This variable indicates the current temperature of the Evaporator leaving chilled water temperature of compressor 2. This variable
is not available on all chiller models. (A87)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 68 Present Value 85
Object Name
Comp2EvapLvgWTmp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 14
Compressor #2 Analog 87

www.DaikinApplied.com 55 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Evaporator Pump Run Hours


Keypad Menu Path: NOTE: Value returned must be multiplied by 10 to give run hours.
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Event Count NA Real 0–65,535 NA

BACnet
Pump Select
This output network variable indicates the number of hours that the selected evaporator pump has been turned on. There is a
separate output for each pump. See Pump Select on page 76. Value is Hrs/10. (I47)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 27 Present Value 85
Object Name
EvapPumpOperHours

Pump #2
This variable indicates the number of hours for pump 2. This variable is not available on all chiller models. Value is Hrs/10. (I103)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 89 Present Value 85
Object Name
EvapPmp2Hrs

HTTP Interface
Variable Details

Variable Variable Type Index


Pump Select Integer 47
Pump #2 Integer 103

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 56 www.DaikinApplied.com


Detailed Data Point Information

Evaporator Refrigerant Pressure


Keypad Menu Path:
Menu
\View
\Comp (2)

Measurement Units Data Type Valid Range Default Value


-22592–22591 psi /
Pressure (gauge) Psi/kPa Real NA
-3,276.8–3,276.7 kPa

BACnet
Compressor Select
This output network variable indicates the current refrigerant pressure in the evaporator. There is a separate output for each
compressor. See Compressor Select on page 37. (A17)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 13 Present Value 85
Object Name
EvapPressure

Compressor #2
This variable indicates the current refrigerant pressure in the evaporator for compressor 2. This variable is not available on all
chiller models. (A90)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 71 Present Value 85
Object Name
Comp2EvapPress

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 17
Compressor #2 Analog 90

www.DaikinApplied.com 57 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Evaporator Saturated Refrigerant Temperature


Keypad Menu Path:
Menu
\Unit
\Refrigerant (1)

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-40°–118°C NA

BACnet
Compressor Select
This output network variable indicates the current saturated refrigerant temperature in the evaporator. There is a separate output
for each compressor. See Compressor Select on page 37. (A16)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 14 Present Value 85
Object Name
EvapSatTemp

Compressor #2
This output network variable indicates the current saturated refrigerant temperature in the evaporator for compressor 2. (A89) This
variable is not available on all chiller models.
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 70 Present Value 85
Object Name
Comp2EvapSatRTmp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 16
Compressor #2 Analog 89

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 58 www.DaikinApplied.com


Detailed Data Point Information

Evaporator Water Flow Rate


Keypad Menu Path: This output network variable indicates the current evaporator water flow rate. (A18)
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


Flow Volume GPM / L/S Real 0–65,534 NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 49 Present Value 85
Object Name
EvapWaterFlowRate

HTTP Interface
Variable Details

Variable Type Index


Analog 18

Evaporator Water Pump Status


Keypad Menu Path: This output network variable indicates whether the selected pump has been commanded ON or OFF.
No Keypad Equivalent See Pump Select on page 76. (D29)

Measurement Units Data Type Valid Range Default Value


Flow State NA Enumerated See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 36 Present Value 85
Object Name
EvapPumpState
Property Values
0 = Commanded OFF (Inactive)
1 = Commanded ON (Active)

HTTP Interface
Variable Details

Variable Type Index


Digital 29

www.DaikinApplied.com 59 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Heat Recovery Entering Water Temperature


Keypad Menu Path: This output network variable indicates the current temperature of the water entering the heat recovery
No Keypad Equivalent section. (A22)

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-40°–118°C NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 5 Present Value 85
Object Name
HeatRecEntWaterTemp

HTTP Interface
Variable Details

Variable Type Index


Analog 22

Heat Recovery Leaving Water Temperature


Keypad Menu Path: This output network variable indicates the current temperature of the water leaving the heat recovery
No Keypad Equivalent section. (A23)

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real -40°–244°F/-40°–118°C NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 6 Present Value 85
Object Name
HeatRecLvgWaterTemp

HTTP Interface
Variable Details

Variable Type Index


Analog 23

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 60 www.DaikinApplied.com


Detailed Data Point Information

Heat Setpoint
Keypad Menu Path: This input network variable provides the heating setpoint when the chiller is operating in the heat
Menu mode. The value is ignored if the controller is in cooling mode. The BACnet property is a commandable
\Set property of a Multi-state Output object. Refer to the appropriate Operation Manual for suitable variable
\Unit SPs (3) values. (A5)

Measurement Units Data Type Valid Range Default Value


Temperature °F/°C Real 100°–150°F/37.8°–65.6°C See Below

BACnet
This commandable property sets the temperature of the Leaving Chilled Water when it is in the heating mode.

Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Output 0 31 Present Value 85
Object Name
NetworkHeatTempSetpoint

Default Value (Relinquish_Default) 100°F

HTTP Interface
Variable Details

Variable Type Index


Analog 5

www.DaikinApplied.com 61 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Ice Setpoint
Keypad Menu Path: The Ice Setpoint data point determines the temperature of the Leaving Chilled Water. This is a
Menu commandable property of a Analog Output object. Refer to the appropriate Operation Manual for
\Set suitable variable values. (A50)
\Unit SPs (3)

Measurement Units Data Type Valid Range Default Value


Dependent on Chiller Mode
Temperature °F/ °C Real See below
and Model

BACnet
This commandable property sets the temperature of the Leaving Chilled Water. This level may be adjusted via an operator
workstation or other network device. When this property is read, it indicates the current value of the temperature of the Leaving
Chilled Water.

Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Output 1 30 Present Value 85
Object Name
NetworkIceTempSetpoint

Default Value (Relinquish_Default) 25°F

HTTP Interface
Variable Details

Variable Type Index


Analog 50

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 62 www.DaikinApplied.com


Detailed Data Point Information

IGV Percentage Open


Keypad Menu Path: This output network variable indicates current percent of vanes open for each compressor (0%=closed,
No Keypad Equivalent 110%=full capacity-open) (I120 & I124)

Measurement Units Data Type Valid Range Default Value


Percent BACnet: % BACnet: Real BACnet: 0–110 NA

BACnet
Compressor #1
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 58 Present Value 85
Object Name
Comp1IGVPercentOpen

Compressor #2
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 62 Present Value 85
Object Name
Comp2IGVPercentOpen

HTTP Interface
Variable Details

Compressor Variable Type Index


Compressor #1 Integer 120
Compressor #2 Integer 124

www.DaikinApplied.com 63 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Inverter Temperature
Keypad Menu Path: This output network variable the current drive temperature. There is one variable for each compressor.
No Keypad Equivalent (A86 & A106)

Measurement Units Data Type Valid Range Default Value


Temperature BACnet: °F BACnet: Real BACnet: 32°–212°F NA

BACnet
Compressor #1
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 66 Present Value 85
Object Name
Comp1InverterTmp

Compressor #2
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 87 Present Value 85
Object Name
Comp2InverterTmp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor #1 Analog 86
Compressor #2 Analog 106

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 64 www.DaikinApplied.com


Detailed Data Point Information

Liquid Line Refrigerant Pressure


Keypad Menu Path: This output network variable indicates the current liquid line refrigerant pressure. There is a separate
No Keypad Equivalent output for each compressor/circuit. See Compressor Select on page 37. (A38)

Measurement Units Data Type Valid Range Default Value


-22592–22591 psi /
Pressure Psi/kPa Real NA
-3,276.8…3,276.7 kPa

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 12 Present Value 85
Object Name
LiquidLinePress

HTTP Interface
Variable Details

Variable Type Index


Analog 38

www.DaikinApplied.com 65 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Liquid Line Refrigerant Temperature


Keypad Menu Path:
Menu
\View
\Unit \Refrg (2)
Liquid Line=

Measurement Units Data Type Valid Range Default Value


-40°–244°F
Temperature °F/ °C Real NA
-40°–118°C

BACnet
Compressor Select
This output network variable indicates the current liquid line refrigerant temperature. There is a separate output for each
compressor/circuit. See Compressor Select on page 37. (A36)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 11 Present Value 85
Object Name
LiquidLineTemp

Compressor #2
This variable indicates the current liquid line refrigerant temperature for compressor 2. This variable is not available on all chiller
models. (A104)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 85 Present Value 85
Object Name
Comp2LiqLineTemp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 36
Compressor #2 Analog 104

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 66 www.DaikinApplied.com


Detailed Data Point Information

Maximum RPM
Keypad Menu Path: This output data point indicates the maximum (choke) RPM. This is the speed the Turbocor compressor
No Keypad Equivalent calculates above which the efficiency of the compressor falls off. (I117 & I121)

Measurement Units Data Type Valid Range Default Value


Revolutions per Minute BACnet: RPM BACnet: Real BACnet: 0–32678 NA

BACnet
Compressor #1
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 55 Present Value 85
Object Name
Comp1MaxRPM

Compressor #2
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 59 Present Value 85
Object Name
Comp2MaxRPM

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor #1 Integer 117
Compressor #2 Integer 121

www.DaikinApplied.com 67 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Minimum RPM
Keypad Menu Path: This output data point indicates the minimum (surge) RPM. This is the speed the Turbocor compressor
No Keypad Equivalent calculates is the minimum safe operating speed above onset of stall. (I119 & I123)

Measurement Units Data Type Valid Range Default Value


Revolutions per Minute BACnet: RPM BACnet: Real BACnet: 0–32678 NA

BACnet
Compressor #1
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 57 Present Value 85
Object Name
Comp1MinRPM

Compressor #2
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 61 Present Value 85
Object Name
Comp2MinRPM

HTTP Interface
Variable Details

Compressor Variable Type Index


1 Integer 119
2 Integer 123

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 68 www.DaikinApplied.com


Detailed Data Point Information

Motor Cavity Temperature


Keypad Menu Path: This output data point indicates the current temperature of the compressor’s motor stator cavity. (A85 &
No Keypad Equivalent A105)

Measurement Units Data Type Valid Range Default Value


Temperature BACnet: °F BACnet: Real BACnet: -4°–212°F NA

BACnet
Compressor #1
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 65 Present Value 85
Object Name
Comp1MotorCavityTmp

Compressor #2
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 86 Present Value 85
Object Name
Comp2MotorCavityTmp

HTTP Interface
Variable Details

Compressor Variable Type Index


1 Integer 119
2 Integer 123

www.DaikinApplied.com 69 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Oil Feed Pressure


Keypad Menu Path:
Menu
\View
\Comp (3)

Measurement Units Data Type Valid Range Default Value


-22592–22591 psi
Pressure psi/kPa Real NA
-3,276.8…3,276.7 kPa

BACnet
Compressor Select
This output network variable indicates the current compressor oil feed pressure. There is a separate output for each compressor.
See Compressor Select on page 37. (A32)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 19 Present Value 85
Object Name
OilFeedPressure

Compressor #2
This variable indicates the current oil feed pressure for compressor 2. This variable is not available on all chiller models. (A100)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 81 Present Value 85
Object Name
Comp2OilFeedPress

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 32
Compressor #2 Analog 100

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 70 www.DaikinApplied.com


Detailed Data Point Information

Oil Feed Temperature


Keypad Menu Path:
Menu
\View
\Comp (4)

Measurement Units Data Type Valid Range Default Value


-40°–244°F
Temperature °F/ °C Real NA
-40°–118°C

BACnet
Compressor Select
This output network variable indicates the current compressor oil feed temperature. There is a separate output for each
compressor. See Compressor Select on page 37. (A34)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 21 Present Value 85
Object Name
OilFeedTemp

Compressor #2
This output network variable indicates the current compressor oil feed temperature for compressor 2. This variable is not available
on all chiller models. (A102)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 83 Present Value 85
Object Name
Comp2OilFeedTemp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 34
Compressor #2 Analog 102

www.DaikinApplied.com 71 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Oil Sump Pressure


Keypad Menu Path:
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


-22592–22591 psi
Pressure psi/kPa Real NA
-3,276.8…3,276.7 kPa

BACnet
Compressor Select
This output network variable indicates the current compressor oil sump pressure. There is a separate output for each compressor.
See Compressor Select on page 37. (A33)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 20 Present Value 85
Object Name
OilSumpPressure

Compressor #2
This variable indicates the current compressor oil sump pressure for compressor 2. This variable is not available on all chiller
models. (A101)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 82 Present Value 85
Object Name
Comp2OilSumpPress

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 33
Compressor #2 Analog 101

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 72 www.DaikinApplied.com


Detailed Data Point Information

Oil Sump Temperature


Keypad Menu Path:
Menu
\View
\Comp (4)

Measurement Units Data Type Valid Range Default Value


-40°–244°F
Temperature °F/ °C Real NA
-40°–118°C

BACnet
Compressor Select
This output network variable indicates the current compressor oil sump temperature. There is a separate output for each
compressor. See Compressor Select on page 37. (A35)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 22 Present Value 85
Object Name
OilSumpTemp

Compressor #2
This output network variable indicates the current compressor oil sump temperature for compressor 2. This variable is not available
on all chiller models. (A103)
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 84 Present Value 85
Object Name
Comp2OilSumpTemp

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 35
Compressor #2 Analog 103

www.DaikinApplied.com 73 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Outdoor Air Temperature


Keypad Menu Path: This output network variable indicates the current outdoor air temperature. (A39)
No Keypad Equivalent

Measurement Units Data Type Valid Range Default Value


-40°–244°F
Temperature °F/ °C Real NA
-40°–118°C

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 10 Present Value 85
Object Name
OutdoorAirTemp

HTTP Interface
Variable Details

Variable Type Index


Analog 39

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 74 www.DaikinApplied.com


Detailed Data Point Information

Power Factor
Keypad Menu Path: Power factor is a read-only point that defines the cosine of the phase angle between the voltage applied
No Keypad Equivalent to a load and the current passing through the load. The power factor is assigned an analog value scaled
by 0.01 (i.e. a value of +95 corresponds to a power factor of 0.95). For a more detailed description of
power factor, see Application Guide AG 31-002, available on www.DaikinApplied.com

Measurement Units Data Type Valid Range Default Value


Power Factor Power Factor Real -99 – +100 N/A

BACnet
Compressor Select
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 53 Present Value 85
Object Name
PowerFactor

Compressor #2
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 78 Present Value 85
Object Name
Comp2PowerFactor

Compressor #3
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 97 Present Value 85
Object Name
Comp3PowerFactor

Compressor #4
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 105 Present Value 85
Object Name
Comp4PowerFactor

Compressor #5
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 113 Present Value 85
Object Name
Comp4PowerFactor

www.DaikinApplied.com 75 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Detailed Data Point Information

Compressor #6
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 119 Present Value 85
Object Name
Comp4PowerFactor

HTTP Interface
Variable Details

Variable Variable Type Index


Compressor Select Analog 28
Compressor #2 Analog 97
Compressor #3 Analog 111
Compressor #4 Analog 116
Compressor #5 Analog 121
Compressor #6 Analog 1126

Pump Select
Keypad Menu Path: This input network variable selects which pump (Number 1 or Number 2) supplies the data. The Chiller
No Keypad Equivalent Unit Controller returns the information for the appropriate Condenser or Evaporator pump. You must first
select a pump and then interrogate the selected pump. See Condenser Pump Run Hours on page 46
and Evaporator Pump Run Hours on page 56. (D19)

Measurement Units Data Type Valid Range Default Value


Event Count NA Unsigned Integer See Below 1 = Pump No. 1

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Output 14 47 Present Value 85
Object Name
PumpSelect
Property Values
1 = Pump #1
2 = Pump #2

HTTP Interface
Variable Details

Variable Type Index


Digital 19

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 76 www.DaikinApplied.com


Detailed Data Point Information

Run Enabled
Keypad Menu Path: This output network variable indicates that the chiller can start if operating conditions are met. See
Menu Chiller Status on page 26 for details (D2).

Measurement Units Data Type Valid Range Default Value


Chiller Status NA Enumerated See Below NA

BACnet
Variable Details
Object Identifier Property Identifier
Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 33 Present Value 85
Object Name
UnitOFF
Property Values
0 = OFF (Inactive)
1 = Run Allowed (Active)

HTTP Interface
Variable Details

Variable Type Index


Digital 2

www.DaikinApplied.com 77 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Alarms

Alarms

Alarm Classes BACnet Alarm Handling


BACnet alarms in a MicroTech II Chiller Unit Controller are The BACnet Communication Module has three methods for
divided into three classes: Faults, Problems, and Warnings. handling BACnet alarms: Alarm Annunciation, Poll Multiple,
Fault alarms have the highest severity level. Problem alarms and Poll Singular.
have medium severity level. Warning alarms have the lowest
severity level. Alarm Annunciation
This method of alarm notification sends a BACnet
Fault Alarms ConfirmedEventNotification to a single BACnet device
Fault alarms require an acknowledgment from the operator. specified in the HTTP interface.
These alarms indicate that the compressor is shut down. The ConfirmedEventNotification Service includes the
fields identifed in Table 3. Refer to ANSI/ASHRAE 135-
Problem Alarms 2004, BACnet-A Data Communication Protocol for Building
Problem alarms do not cause compressor shutdown but limit Automation and Control Networks for detailed definitions.
operation of the chiller in some way. Not all BACnet devices can receive an alarm message of this
type. A BAS integrator may not want to use this method to
Warning Alarms handle alarms. If either case is true, the BAS integrator can
A warning is enunciated whenever an abnormal condition use the Poll Multiple or Poll Singular method.
exists which does not affect chiller operation.

Table 3: Event Notification Service Details


Field Source
Process Identifier Device Instance Process ID in the HTTP interface.
Initiating Device Identifier Device Instance of the BACnet Communication Module as specified in the HTTP interface.
Object Instance that generated the Alarm. (Subtract 1000 from this value to get the instance of the of the object in the BACnet
Event Object Identifier Communication Module.)
Time Stamp The time the BACnet Communication Module detected the alarm initially.
P = Problems
Notification Class W = Warnings
F = Faults
Priority Priority specified in the HTTP interface.
Event Type Complex Event.
Message Text Alarm Message Text as shown in Table 4: BACnet Alarms on page 83.
Notify Type ALARM
AckRequired Notification Requirement as shown in the Ack column of Table 4.
From State The Event State of the BACnet Communication Module before the occurrence of the event that caused Alarm.
To State The Event State of the BACnet Communication Module after the occurrence of the event that caused the Alarm.
Conditions in the BACnet Communication Module at the time of the alarm. Each number in the Event Values column of Table 4 is the
Event Values instance number of an object in the BACnet Communication Module that displays its present value in this field of the Event Notification
message.

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 78 www.DaikinApplied.com


Alarms

Poll Multiple
The Poll Multiple method requires that three objects in
the BACnet Communication Module be polled for alarm
notification: one object indicates Warning Alarms, one indicates
Problem Alarms, and one indicates Fault Alarms. The BACnet
Communication Module includes three Analog Input and three
Multi-state objects that contain the alarm information. The
Analog Input objects return a number for an alarm condition.
The number is found in the Index column of Table 4. The Multi-
state object returns the same number for the alarm condition
and the text of the alarm message found in the Alarm Message
Text column of Table 4: BACnet Alarms on page 83.

Warning Alarms, Analog Input Object


This BACnet object indicates the index number of warning
alarms. If the present value is zero, no alarm has occurred (see
Table 4.)
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 902 Present Value 85
Object Name
AIWarningAlarm

Problem Alarms, Analog Input Object


This BACnet object indicates the index number of problem
alarms. If the present value is zero, no alarm has occurred (see
Table 4.)
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 900 Present Value 85
Object Name
AIProblemAlarm

Fault Alarms, Analog Input Object


This BACnet object indicates the index number of fault alarms. If
the present value is zero, no alarm has occurred (see Table 4.)
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Analog Input 0 901 Present Value 85
Object Name
AIFaultAlarm

www.DaikinApplied.com 79 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Alarms

Warning Alarms, Multi-state Input Object


This BACnet object indicates the index number of warning
alarms in the present value property and the text of the alarm
message in the state text property. If the present value is zero,
no alarm has occurred (see Table 4)
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 902 Present Value 85
Object Name
MSIWarningAlarm

Measurement Units Data Type Valid Range Default Value


NA NA Character String NA NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 902 State Text 110
Object Name
MSIWarningAlarm

Problem Alarms, Multi-state Input Object


This BACnet object indicates the index number of problem
alarms in the present value property and the text of the alarm
message in the state text property. If the present value is zero,
no alarm has occurred (see Table 4.)
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 900 Present Value 85
Object Name
MSIProblemAlarm

Measurement Units Data Type Valid Range Default Value


NA NA Character String NA NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 900 State Text 110
Object Name
MSIProblemAlarm

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 80 www.DaikinApplied.com


Alarms

Fault Alarms, Multi-state Input Object


This BACnet object indicates the index number of Fault
Alarms in the present value property and the text of the alarm
message in the state text property. If the present value is zero,
no alarm has occurred (see Table 4.)
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 901 Present Value 85
Object Name
MSIFaultAlarm

Measurement Units Data Type Valid Range Default Value


NA NA Character String NA NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Multi-state Input 13 901 State Text 110
Object Name
MSIFaultAlarm

Poll Singular
Alarm Digital Output
The Poll Singular method requires that one Binary Input object
in the BACnet Communication Module be polled for alarm
notification. This object indicates whether an alarm condition has
occurred. The operator interface displays the alarm text. (D3)
Measurement Units Data Type Valid Range Default Value
NA NA Integer Enumerated NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Input 3 40 Present Value 85
Object Name
AlarmDigitalOutput
Property Values
0 = No Alarm
1 = Alarm

www.DaikinApplied.com 81 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Clearing Alarms

Clearing Alarms

This BACnet object clears all active alarms. However, it cannot


clear all alarms in the Fault category (i.e. alarms that shut
down the chiller). Fault alarms must be cleared at the chiller
panel. The following are alarms can be cleared at the chiller
but not over the network: (D24)
• Low Evaporator Pressure
• High Condenser Pressure (by pressure sensor)
• High Condenser Pressure (by pressure switch)
• Low Oil Pressure
• Freeze Protection
• High Motor Temperature
NOTE: The above list pertains only to centrifugal chillers.
The Flow Loss alarm is the only alarm that can be
cleared remotely on all other chiller types.

Measurement Units Data Type Valid Range Default Value


NA NA Integer Enumerated NA

Object Identifier Property Identifier


Object Type Type Enumeration Instance Property Name Property Enumeration
Binary Value 5 42 Present Value 85
Object Name
ClearAlarm
Property Values
0 = Normal
1 = Clear Alarm

HTTP Interface
Variable Details

Variable Type Index


Digital 24

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 82 www.DaikinApplied.com


Clearing Alarms

BACnet Alarm Messages


The following table identifies each alarm, class, whether an
acknowledgement is required, the alarm text, and indicates
system parameters at the time of the alarm.

Table 4: BACnet Alarms


WSC
WDC
WPV
HSC
HDC
TSC
WMC WGZ
Alarm Class Description Event Values WCC AGZ ACZ TGZ AGS WGS
NO ACTION – Condenser Entering Water Temperature Sensor
1 W 1,2,3,4,9 X
Failure
NO ACTION – Evaporator Entering Water Temperature Sensor
2 W 1,2,3,4,9,10 X X X X
Failure
NO ACTION - Liquid Line Refrigerant Temperature Sensor
3 W 1,2,3,4,9 X X
Failure
NO ACTION (STOP if Heat) - Condenser Leaving Water
4 W Temperature Sensor Failure 1,2,3,4,9 X X

5 P RESTART DELAYED - Power Loss While Running #1 1,2,9,10 X X


6 P RESTART DELAYED - Power Loss While Running #2 1,2,9,10 X X
7 P RESTART DELAYED - Power Loss While Running #3 1,2,9,10 X2
9 W Expansion Alarm – Warning 1,2,9,10 X X
10 P START INHIBITED - Ambient Temperature Low 1,2,3,4,9,10 X X X X X
11 P INHIBIT LOAD – Condenser Pressure High #1 1,2,9,10 X5 X3 X X X
12 P INHIBIT LOAD – Condenser Pressure High #2 1,2,9,10 X5 X3 X X X
13 P INHIBIT LOAD – Condenser Pressure High #3 1,2,9,10 X2
15 P UNLOAD – Condenser Pressure High 1,2,9,10 X X
16 P UNLOAD – Condenser Pressure High #1 1,2,3,4,9,10 X5 X3 X X X
17 P UNLOAD – Condenser Pressure High #2 1,2,3,4,9,10 X5 X3 X X X
18 P UNLOAD – Condenser Pressure High #3 1,2,3,4,9,10 X2
CONDENSER PUMP ON - Condenser Water Freeze
20 P 1,2,3,4,9 X X
Protection #1
CONDENSER PUMP ON - Condenser Water Freeze
21 P 1,2,3,4,9 X X
Protection #2
CONDENSER PUMP ON - Condenser Water Freeze
22 P 1,2,3,4,9 X X
Protection #3
CONDENSER PUMP ON - Condenser Water Freeze
23 P 1,2,3,4,9 X X
Protection #4
24 P PUMP #2 START ATTEMPTED - Condenser Pump #1 Failure 1,2,3,4,9 X
25 P PUMP #1 START ATTEMPTED - Condenser Pump #2 Failure 1,2,3,4,9 X
26 P LOAD - Discharge Temperature High #1 1,2,3,4,9 X
27 P LOAD - Discharge Temperature High #2 1,2,3,4,9 X
28 P LOAD - Discharge Temperature High #3 1,2,3,4,9 X
29 P LOAD - Discharge Temperature High #4 1,2,3,4,9 X
NO EWT RESET - Entering Evaporator Temperature Sensor
30 P 1,2,3,4,9 X
Failure
31 P INHIBIT LOAD - Evaporator Pressure Low 1,2,3,4,9,10 X6 X4
32 P INHIBIT LOAD - Evaporator Pressure Low #1 1,2,3,4,9,10 X X5 X3 X X X
33 P INHIBIT LOAD - Evaporator Pressure Low #2 1,2,3,4,9,10 X X5 X3 X X X
34 P INHIBIT LOAD - Evaporator Pressure Low #3 1,2,3,4,9,10 X2
36 P UNLOAD - Evaporator Pressure Low 1,2,3,4,9,10 X X6 X4
37 P UNLOAD - Evaporator Pressure Low #1 1,2,3,4,9,10 X X5 X3 X X X
38 P UNLOAD - Evaporator Pressure Low #2 1,2,3,4,9,10 X X5 X3 X X X
39 P UNLOAD - Evaporator Pressure Low #3 1,2,3,4,9,10 X2
41 P UNLOAD - Compressor Motor Current High #1 1,2,3,4,9,10 X
1-AGS ‘C’ Vintage Only (two circuits only)
2-AGS ‘B’ Vintage Only (up to three circuits)
3-ACZ Dual Circuit Only
4-ACZ Single Circuit Only
5-AGZ Dual Circuit Only
6-AGZ Single Circuit Only
7-Solid State Starter Option required. Not available on WMC.
8- WMC Only.

www.DaikinApplied.com 83 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Clearing Alarms

WSC
WDC
WPV
HSC
HDC
TSC
WMC WGZ
Alarm Class Description Event Values WCC AGZ ACZ TGZ AGS WGS
42 P UNLOAD - Compressor Motor Current High #2 1,2,3,4,9,10 X
43 P UNLOAD - Compressor Motor Current High #3 1,2,3,4,9,10 X2
EVAPORATOR PUMP ON - Evaporator Water Freeze
45 P 1,2,3,4,9 X
Protection Comp #1
EVAPORATOR PUMP ON - Evaporator Water Freeze
46 P 1,2,3,4,9 X
Protection Comp #2
EVAPORATOR PUMP ON - Evaporator Water Freeze
47 P 1,2,3,4,9 X
Protection Comp #3
EVAPORATOR PUMP ON - Evaporator Water Freeze
48 P 1,2,3,4,9 X
Protection Comp #4
49 P PUMP #2 START ATTEMPTED - Evaporator Pump #1 Failure 1,2,3,4,9 X
50 P PUMP #1 START ATTEMPTED - Evaporator Pump #2 Failure 1,2,3,4,9 X
51 P (Check Chiller Display for Cause) 1,2,3,4,9,10 X X X X X X
COMPRESSOR SHUTDOWN - Outside Air Temperature
52 F 1,2,3,4,9,10 X X X X X
Sensor Fault
53 F COMPRESSOR SHUTDOWN - Current Overload Trip #1 1,2,3,4,9,10 X X X
54 F COMPRESSOR SHUTDOWN – Current Overload Trip #2 1,2,3,4,9,10 X X X
55 F COMPRESSOR SHUTDOWN – Current Overload Trip #3 1,2,3,4,9,10 X2
57 F COMPRESSOR SHUTDOWN – Motor Current Imbalance #1 1,2,3,4,9,10 X X1 X
58 F COMPRESSOR SHUTDOWN – Motor Current Imbalance #2 1,2,3,4,9,10 X X1 X
61 F COMPRESSOR SHUTDOWN – Low Motor Current #1 1,2,3,4,9,10 X
62 F COMPRESSOR SHUTDOWN – Low Motor Current #2 1,2,3,4,9,10 X
65 F UNIT SHUTDOWN - Motor Protector Trip 1,2,3,4,9,10 X6 X4
66 F COMPRESSOR SHUTDOWN - Motor Protector Trip #1 1,2,3,4,9,10 X5 X3 X
67 F COMPRESSOR SHUTDOWN - Motor Protector Trip #2 1,2,3,4,9,10 X5 X3 X
68 F COMPRESSOR SHUTDOWN - Motor Temperature High #1 1,2,3,4,9,10 X X1 X
69 F COMPRESSOR SHUTDOWN - Motor Temperature High #2 1,2,3,4,9,10 X X1 X
70 F COMPRESSOR SHUTDOWN - Motor Temperature High #3 1,2,3,4,9,10 X2
72 F COMPRESSOR SHUTDOWN - Phase Loss #1 1,2,3,4,9,10 X7 X5 X3 X1 X
73 F COMPRESSOR SHUTDOWN - Phase Loss #2 1,2,3,4,9,10 X7 X5 X3 X1 X
74 F COMPRESSOR SHUTDOWN - Phase Loss #3 1,2,3,4,9,10 X2
76 F COMPRESSOR SHUTDOWN - Phase Reversal #1 1,2,9,10 X7 X1 X
77 F COMPRESSOR SHUTDOWN - Phase Reversal #2 1,2,9,10 X7 X1 X
78 F COMPRESSOR SHUTDOWN - Phase Reversal #3 1,2,9,10 X2
80 F COMPRESSOR SHUTDOWN - Overvoltage #1 1,2,9,10 X7 X1 X
81 F COMPRESSOR SHUTDOWN - Overvoltage #2 1,2,9,10 X7 X1 X
82 F COMPRESSOR SHUTDOWN - Overvoltage #3 1,2,9,10 X2
84 F COMPRESSOR SHUTDOWN - Undervoltage #1 1,2,9,10 X7 X1 X
85 F COMPRESSOR SHUTDOWN - Undervoltage #2 1,2,9,10 X7 X1 X
86 F COMPRESSOR SHUTDOWN - Undervoltage #3 1,2,9,10 X2
COMPRESSOR SHUTDOWN - Condenser Pressure Sensor
88 F 1,2,3,4,9,10 X6 X4
Fault
COMPRESSOR SHUTDOWN - Condenser Pressure Sensor
89 F 1,2,3,4,9,10 X X5 X3 X X X
Fault #1
COMPRESSOR SHUTDOWN - Condenser Pressure Sensor
90 F 1,2,3,4,9,10 X X5 X3 X X X
Fault #2
COMPRESSOR SHUTDOWN - Condenser Pressure Sensor
91 F 1,2,3,4,9,10 X2
Fault #3
93 F COMPRESSOR SHUTDOWN - Condenser Water Flow Loss 1,2,3,4,9 X
94 F COMPRESSOR SHUTDOWN - Condenser Pressure High 1,2,3,4,9,10 X X6 X4
95 F COMPRESSOR SHUTDOWN - Condenser Pressure High #1 1,2,3,4,9,10 X X5 X3 X X X
96 F COMPRESSOR SHUTDOWN - Condenser Pressure High #2 1,2,3,4,9,10 X X5 X3 X X X
1-AGS ‘C’ Vintage Only (two circuits only)
2-AGS ‘B’ Vintage Only (up to three circuits)
3-ACZ Dual Circuit Only
4-ACZ Single Circuit Only
5-AGZ Dual Circuit Only
6-AGZ Single Circuit Only
7-Solid State Starter Option required. Not available on WMC.
8- WMC Only.

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 84 www.DaikinApplied.com


Clearing Alarms

WSC
WDC
WPV
HSC
HDC
TSC
WMC WGZ
Alarm Class Description Event Values WCC AGZ ACZ TGZ AGS WGS
97 F COMPRESSOR SHUTDOWN - Condenser Pressure High #3 1,2,3,4,9,10 X2
99 F COMPRESSOR OFF - Current High with Compressor OFF #1 1,2,3,4,9 X
100 F COMPRESSOR OFF - Current High with Compressor OFF #2 1,2,3,4,9 X
101 F COMPRESSOR OFF - Current High with Compressor OFF #3 1,2,3,4,9 X
102 F COMPRESSOR OFF - Current High with Compressor OFF #4 1,2,3,4,9 X
COMPRESSOR SHUTDOWN - Discharge Temperature
103 F 1,2,3,4,9,10 X X X
Sensor Fault #1
COMPRESSOR SHUTDOWN - Discharge Temperature
104 F 1,2,3,4,9,10 X X X
Sensor Fault #2
COMPRESSOR SHUTDOWN - Discharge Temperature
105 F 1,2,3,4,9,10 X2
Sensor Fault #3
COMPRESSOR SHUTDOWN - Discharge Temperature High
107 F 1,2,3,4,9,10 X X X
#1
COMPRESSOR SHUTDOWN - Discharge Temperature High
108 F 1,2,3,4,9,10 X X X
#2
COMPRESSOR SHUTDOWN - Discharge Temperature High
109 F 1,2,3,4,9,10 X2
#3
COMPRESSOR SHUTDOWN - Condenser Entering Water
111 F 1,2,3,4,9,10 X X
Temperature Sensor Fault
112 F COMPRESSOR SHUTDOWN - Evaporator Water Flow Loss 1,2,3,4,9,10 X X X X X X
COMPRESSOR SHUTDOWN - Evaporator Leaving Water
113 F 1,2,3,4,9,10 X X X X
Temperature Low (Freeze)
114 F COMPRESSOR SHUTDOWN - Evaporator Pressure Low 1,2,3,4,9,10 X6 X4
115 F COMPRESSOR SHUTDOWN - Evaporator Pressure Low #1 1,2,3,4,9,10 X X5 X3 X X X
116 F COMPRESSOR SHUTDOWN - Evaporator Pressure Low #2 1,2,3,4,9,10 X X5 X3 X X X
117 F COMPRESSOR SHUTDOWN - Evaporator Pressure Low #3 1,2,3,4,9,10 X2
COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor
119 F 1,2,3,4,9,10 X6 X4
Fault
COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor
120 F 1,2,3,4,9,10 X X5 X3 X X X
Fault #1
COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor
121 F 1,2,3,4,9,10 X X5 X3 X X X
Fault #2
COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor
122 F 1,2,3,4,9,10 X2
Fault #3
124 F COMPRESSOR SHUTDOWN - Ground Fault Trip #1 1,2,3,4,9,10 X7 X6 X3 X X1 X
125 F COMPRESSOR SHUTDOWN - Ground Fault Trip #2 1,2,3,4,9,10 X7 X6 X3 X X1 X
126 F COMPRESSOR SHUTDOWN - Ground Fault Trip #3 1,2,3,4,9,10 X2
128 F COMPRESSOR SHUTDOWN - Lift Pressure Low #1 1,2,9,10 X X
129 F COMPRESSOR SHUTDOWN - Lift Pressure Low #2 1,2,9,10 X X
130 F COMPRESSOR SHUTDOWN - Lift Pressure Low #3 1,2,9,10 X2
COMPRESSOR SHUTDOWN - Liquid Line Pressure Sensor
132 F 1,2,9,10 X
Fault #1
COMPRESSOR SHUTDOWN - Liquid Line Pressure Sensor
133 F 1,2,9,10 X
Fault #2
COMPRESSOR SHUTDOWN - Liquid Line Pressure Sensor
134 F 1,2,9,10 X2
Fault #3
COMPRESSOR SHUTDOWN - Liquid Line Temperature
136 F 1,2,9,10 X
Sensor Fault #1
COMPRESSOR SHUTDOWN - Liquid Line Temperature
137 F 1,2,9,10 X
Sensor Fault #2
COMPRESSOR SHUTDOWN - Liquid Line Temperature
138 F 1,2,9,10 X2
Sensor Fault #3
140 F UNIT LOCKOUT - Number of Allowed Re-Starts Exceeded 1,2,9,10 X6 X4
COMPRESSOR LOCKOUT - Number of Allowed Re-Starts
141 F 1,2,3,4,9,10 X5 X3 X X1 X
Exceeded #1
1-AGS ‘C’ Vintage Only (two circuits only)
2-AGS ‘B’ Vintage Only (up to three circuits)
3-ACZ Dual Circuit Only
4-ACZ Single Circuit Only
5-AGZ Dual Circuit Only
6-AGZ Single Circuit Only
7-Solid State Starter Option required. Not available on WMC.
8- WMC Only.

www.DaikinApplied.com 85 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Clearing Alarms

WSC
WDC
WPV
HSC
HDC
TSC
WMC WGZ
Alarm Class Description Event Values WCC AGZ ACZ TGZ AGS WGS
COMPRESSOR LOCKOUT - Number of Allowed Re-Starts
142 F 1,2,3,4,9,10 X5 X3 X X1 X
Exceeded #2
COMPRESSOR LOCKOUT - Number of Allowed Re-Starts
143 F 1,2,3,4,9,10 X2
Exceeded #3
COMPRESSOR SHUTDOWN - Evaporator Leaving Water
145 F 1,2,3,4,9,10 X X X X
Temperature Sensor Fault
COMPRESSOR SHUTDOWN - Evaporator Leaving Water
146 F 1,2,3,4,9 X
Temperature Sensor Fault #1
COMPRESSOR SHUTDOWN - Evaporator Leaving Water
147 F 1,2,3,4,9 X
Temperature Sensor Fault #2
COMPRESSOR SHUTDOWN - Evaporator Leaving Water
148 F 1,2,3,4,9 X
Temperature Sensor Fault #3
COMPRESSOR SHUTDOWN - Evaporator Leaving Water
149 F 1,2,3,4,9 X
Temperature Sensor Fault #4
150 F UNIT STOP - Mechanical High Pressure Trip 1,2,9,10 X6 X4
COMPRESSOR SHUTDOWN - Mechanical High Pressure
151 F 1,2,3,4,9,10 X X5 X3 X X X
Trip #1
COMPRESSOR SHUTDOWN - Mechanical High Pressure
152 F 1,2,3,4,9,10 X X5 X3 X X X
Trip #2
COMPRESSOR SHUTDOWN - Mechanical High Pressure
153 F 1,2,3,4,9,10 X2
Trip #3
155 F COMPRESSOR SHUTDOWN - Oil Net Pressure Low #1 1,2,3,4,9 X
156 F COMPRESSOR SHUTDOWN - Oil Net Pressure Low #2 1,2,3,4,9 X
157 F COMPRESSOR SHUTDOWN - Oil Net Pressure Low #3 1,2,3,4,9 X
158 F COMPRESSOR SHUTDOWN - Oil Net Pressure Low #4 1,2,3,4,9 X
159 F COMPRESSOR SHUTDOWN - Oil Feed Temperature High #1 1,2,3,4,9 X
160 F COMPRESSOR SHUTDOWN - Oil Feed Temperature High #2 1,2,3,4,9 X
161 F COMPRESSOR SHUTDOWN - Oil Feed Temperature High #3 1,2,3,4,9 X
162 F COMPRESSOR SHUTDOWN - Oil Feed Temperature High #4 1,2,3,4,9 X
163 F COMPRESSOR SHUTDOWN - Oil Feed Temperature Low #1 1,2,3,4,9 X
164 F COMPRESSOR SHUTDOWN - Oil Feed Temperature Low #2 1,2,3,4,9 X
165 F COMPRESSOR SHUTDOWN - Oil Feed Temperature Low #3 1,2,3,4,9 X
166 F COMPRESSOR SHUTDOWN - Oil Feed Temperature Low #4 1,2,3,4,9 X
COMPRESSOR SHUTDOWN - Oil Feed Temperature Sensor
167 F 1,2,3,4,9 X
Fault #1
COMPRESSOR SHUTDOWN - Oil Feed Temperature Sensor
168 F 1,2,3,4,9 X
Fault #2
COMPRESSOR SHUTDOWN - Oil Feed Temperature Sensor
169 F 1,2,3,4,9 X
Fault #3
COMPRESSOR SHUTDOWN - Oil Feed Temperature Sensor
170 F 1,2,3,4,9 X
Fault #4
171 F COMPRESSOR SHUTDOWN - Oil Level Low #1 1,2,9,10 X X
172 F COMPRESSOR SHUTDOWN - Oil Level Low #2 1,2,9,10 X X
173 F COMPRESSOR SHUTDOWN - Oil Level Low #3 1,2,9,10 X2
COMPRESSOR SHUTDOWN - Oil Filter Delta Pressure High
175 F 1,2,9,10 X X
#1
COMPRESSOR SHUTDOWN - Oil Filter Delta Pressure High
176 F 1,2,9,10 X X
#2
COMPRESSOR SHUTDOWN - Oil Filter Delta Pressure High
177 F 1,2,9,10 X2
#3
COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor
179 F 1,2,3,4,9 X
Fault #1
COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor
180 F 1,2,3,4,9 X
Fault #2
COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor
181 F 1,2,3,4,9 X
Fault #3
1-AGS ‘C’ Vintage Only (two circuits only)
2-AGS ‘B’ Vintage Only (up to three circuits)
3-ACZ Dual Circuit Only
4-ACZ Single Circuit Only
5-AGZ Dual Circuit Only
6-AGZ Single Circuit Only
7-Solid State Starter Option required. Not available on WMC.
8- WMC Only.

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 86 www.DaikinApplied.com


Clearing Alarms

WSC
WDC
WPV
HSC
HDC
TSC
WMC WGZ
Alarm Class Description Event Values WCC AGZ ACZ TGZ AGS WGS
COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor
182 F 1,2,3,4,9 X
Fault #4
COMPRESSOR SHUTDOWN - Oil Sump Pressure Sensor
183 F 1,2,3,4,9 X
Fault #1
COMPRESSOR SHUTDOWN - Oil Sump Pressure Sensor
184 F 1,2,3,4,9 X
Fault #2
COMPRESSOR SHUTDOWN - Oil Sump Pressure Sensor
185 F 1,2,3,4,9 X
Fault #3
COMPRESSOR SHUTDOWN - Oil Sump Pressure Sensor
186 F 1,2,3,4,9 X
Fault #4
COMPRESSOR SHUTDOWN - Oil Sump Temperature Sensor
187 F 1,2,3,4,9 X
Fault #1
COMPRESSOR SHUTDOWN - Oil Sump Temperature Sensor
188 F 1,2,3,4,9 X
Fault #2
COMPRESSOR SHUTDOWN - Oil Sump Temperature Sensor
189 F 1,2,3,4,9 X
Fault #3
COMPRESSOR SHUTDOWN - Oil Sump Temperature Sensor
190 F 1,2,3,4,9 X
Fault #4
191 F SHUTDOWN – Phase Voltage Protection 1,2,9,10 X6 X4
192 F COMPRESSOR SHUTDOWN - Starter Fault Compressor #1 1,2,3,4,9,10 X X X X
193 F COMPRESSOR SHUTDOWN - Starter Fault Compressor #2 1,2,3,4,9,10 X X X X
194 F COMPRESSOR SHUTDOWN - Starter Fault Compressor #3 1,2,3,4,9,10 X2
196 F COMPRESSOR SHUTDOWN - No Starter Transition #1 1,2,3,4,9 X X1
197 F COMPRESSOR SHUTDOWN - No Starter Transition #2 1,2,3,4,9 X X1
198 F COMPRESSOR SHUTDOWN - No Starter Transition #3 1,2,3,4,9 X X1
199 F COMPRESSOR SHUTDOWN - No Starter Transition #4 1,2,3,4,9 X X1
200 F COMPRESSOR START ABORT - Oil Pressure Low #1 1,2,3,4,9 X
201 F COMPRESSOR START ABORT - Oil Pressure Low #2 1,2,3,4,9 X
202 F COMPRESSOR START ABORT - Oil Pressure Low #3 1,2,3,4,9 X
203 F COMPRESSOR START ABORT - Oil Pressure Low #4 1,2,3,4,9 X
204 F COMPRESSOR SHUTDOWN - Subcooling Low #1 1,2,9,10 X2 X
205 F COMPRESSOR SHUTDOWN - Subcooling Low #2 1,2,9,10 X2 X
206 F COMPRESSOR SHUTDOWN - Subcooling Low #3 1,2,9,10 X2
COMPRESSOR SHUTDOWN - Surge Suction Superheat
208 F 1,2,3,4,9 X
High-Running #1
COMPRESSOR SHUTDOWN - Surge Suction Superheat
209 F 1,2,3,4,9 X
High-Running #2
COMPRESSOR SHUTDOWN - Surge Suction Superheat
210 F 1,2,3,4,9 X
High-Running #3
COMPRESSOR SHUTDOWN - Surge Suction Superheat
211 F 1,2,3,4,9 X
High-Running #4
COMPRESSOR SHUTDOWN - Surge Suction Superheat
212 F 1,2,3,4,9 X
High-Starting #1
COMPRESSOR SHUTDOWN - Surge Suction Superheat
213 F 1,2,3,4,9 X
High-Starting #2
COMPRESSOR SHUTDOWN - Surge Suction Superheat
214 F 1,2,3,4,9 X
High-Starting #3
COMPRESSOR SHUTDOWN - Surge Suction Superheat
215 F 1,2,3,4,9 X
High-Starting #4
COMPRESSOR SHUTDOWN - Suction Temperature Sensor
216 F 1,2,3,4,9,10 X X X
Fault #1
COMPRESSOR SHUTDOWN - Suction Temperature Sensor
217 F 1,2,3,4,9,10 X X X
Fault #2
COMPRESSOR SHUTDOWN - Suction Temperature Sensor
218 F 1,2,3,4,9,10 X2
Fault #3
1-AGS ‘C’ Vintage Only (two circuits only)
2-AGS ‘B’ Vintage Only (up to three circuits)
3-ACZ Dual Circuit Only
4-ACZ Single Circuit Only
5-AGZ Dual Circuit Only
6-AGZ Single Circuit Only
7-Solid State Starter Option required. Not available on WMC.
8- WMC Only.

www.DaikinApplied.com 87 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Clearing Alarms

WSC
WDC
WPV
HSC
HDC
TSC
WMC WGZ
Alarm Class Description Event Values WCC AGZ ACZ TGZ AGS WGS
COMPRESSOR START ABORT - Vanes Open OR No Start –
220 F 1,2,3,4,9 X
Interlock Switch #1
COMPRESSOR START ABORT - Vanes Open OR No Start –
221 F 1,2,3,4,9 X
Interlock Switch #2
COMPRESSOR START ABORT - Vanes Open OR No Start –
222 F 1,2,3,4,9 X
Interlock Switch #3
COMPRESSOR START ABORT - Vanes Open OR No Start –
223 F 1,2,3,4,9 X
Interlock Switch #4
COMPRESSOR SHUTDOWN - (Check Chiller Display for
224 F 1,2,3,4,9,10 X X X
Cause)
225 F C-Stop - General Comp Fault#1 1,2,3,4,9,10 X8
226 F C-Stop - General Comp Fault#2 1,2,3,4,9,10 X8
227 F C-Stop - Communication Fault #1 1,2,3,4,9,10 X8
228 F C-Stop - Communication Fault #2 1,2,3,4,9,10 X8
229 F C-Stop - Interlock Fault #1 1,2,3,4,9,10 X8
230 F C-Stop - Interlock Fault #2 1,2,3,4,9,10 X8
231 F C-Stop - Bearing Fault #1 1,2,3,4,9,10 X8
232 F C-Stop - Bearing Fault #2 1,2,3,4,9,10 X8
233 F C-Stop - Motor Fault #1 1,2,3,4,9,10 X8
234 F C-Stop - Motor Fault #2 1,2,3,4,9,10 X8
235 F C-Stop - Drive Fault #1 1,2,3,4,9,10 X8
236 F C-Stop - Drive Fault #2 1,2,3,4,9,10 X8
237 F C-Stop - Internal Control Err#1 1,2,3,4,9,10 X8
238 F C-Stop - Internal Control Err#2 1,2,3,4,9,10 X8
239 W Warn-Chiller Capacity Limited 1,2,3,4,9,10 X8
240 F U-Stop - Check Valve Fault #1 1,2,3,4,9,10 X8
241 F U-Stop - Check Valve Fault #2 1,2,3,4,9,10 X8
242 F U-Stop - LB Valve Fault #1 1,2,3,4,9,10 X8
243 F U-Stop - LB Valve Fault #2 1,2,3,4,9,10 X8
1-AGS ‘C’ Vintage Only (two circuits only)
2-AGS ‘B’ Vintage Only (up to three circuits)
3-ACZ Dual Circuit Only
4-ACZ Single Circuit Only
5-AGZ Dual Circuit Only
6-AGZ Single Circuit Only
7-Solid State Starter Option required. Not available on WMC.
8- WMC Only.

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 88 www.DaikinApplied.com


Appendix A

Appendix A

Protocol Implementation Conformance Statement (PICS)


This section contains the Protocol Implementation BACnet Interoperability Building Blocks
Conformance Statement (PICS) for the MicroTech II Chiller
Unit Controller of Daikin Applied as required by ANSI/ASHRAE (BIBBs) Supported
Standard 135-2004, BACnet: A Data Communication Protocol BIBB Name Designation
for Building Automation and Control Networks. Data Sharing – ReadProperty – B DS-RP-B
Data Sharing – ReadPropertyMultiple – B DS-RPM-B
BACnet Protocol Implementation Data Sharing – WriteProperty – B DS-WP-B

Conformance Statement Data Sharing – WritePropertyMultiple – B DS-WPM-B


Alarm and Event – Notification Internal – B AE-N-I-B
Date: June 2015 Alarm and Event – ACK – B AE-ACK-B
Vendor Name: Daikin Applied Alarm and Event – Information – B AE-INFO-B
MicroTech II Chiller Unit Device Management – Dynamic Device Binding – A DM-DDB-A
Product Name: Device Management – Dynamic Device Binding – B DM-DDB-B
Controller
Device Management – Dynamic Object Binding – B DM-DOB-B
Product Model Number: MTII Chiller UC
Device Management – DeviceCommunicationControl – B DM-DCC-B
Applications Software
2.0 Device Management – TimeSynchronization – B DM-TS-B
Version:
Device Management – UTCTimeSynchronization – B DM-UTC-B
Firmware Revision: Device Management – ReinitializeDevice – B DM-RD-B
Version 1 Device Management – Restart – B DM-R-B
BACnet Protocol Revision:
Revision 4
Standard Object Types Supported
Product Description Writeable

Dynamically

Dynamically
Properties

Deleteable
Creatable
The MicroTech II Chiller Unit Controller with optional BACnet not
Optional Required
Communication Module is a microprocessor-based controller Properties to be Proprietary
designed to operate Daikin Applied chillers and be integrated Object-Type Supported Writeable Properties
into BACnet building automation systems. Analog Input □ □ Description
Reliability
Read_Only1

BACnet Standardized Device Profile Analog Output □ □ Description


Reliability
Relinquish
Default Read_Only1

 BACnet Operator Workstation (B-OWS) Description

 BACnet Building Controller (B-BC) Binary Input □ □ Reliability


Inactive_Text
Read_Only1

 BACnet Advanced Application Specific Controller Active_Text


(B-AAC) Description
Reliability
Present
 BACnet Application Specific Controller (B-ASC)
 BACnet Smart Sensor (B-SS)
Binary Value □ □ Inactive_Text
Active_Text
Value
Relinquish Read_Only1
Default
Priority Array
 BACnet Smart Actuator (B-SA) Relinquish Default
Description
Location
Local_Time
Device □ □ Local_Date Location
UTC_Offset
Daylight_Savings_
Status
Description
Multi-state
Input □ □ Reliability
State_Text
Read_Only1

Description
Multi-state
Output □ □ Reliability
State_Text
Relinquish
Default Read_Only1

1. Read_Ony is a read only proprietary property used to indicate whether the


Present_Value is read-only (0), writeable but not commandable (1) or writeable
and commandable (2).

www.DaikinApplied.com 89 ED 15100-3 • MICROTECH II CHILLER CONTROLLER


Appendix A

Data Link Layer Options Networking Options


 BACnet IP, (Annex J)  Router, Clause 6
 ISO 8802-3, Ethernet (Clause 7) Routing Configurations:
 MS/TP master (Clause 9), baud rate(s):  Annex H, BACnet Tunneling Router over IP
 BACnet/IP Broadcast Management Device (BBMD)
Registrations by Foreign Devices?  Yes
Segmentation Capability
 No
 Segmented requests supported Window Size:
 Segmented responses supported Window Size:
Character Sets Supported
 ANSI X3.4  IBM®/Microsoft® DBCS
Device Address Binding
 ISO 8859-1  ISO 10646 (UCS-2)
Static Device Binding  Yes
 ISO 10646 (UCS-4)  JIS C 6226
 No
NOTE: Support for multiple character sets does not imply
they can be supported simultaneously.

Non-BACnet Equipment/Network(s)
Support
 Communication Gateway
Non-BACnet equipment/networks(s):

ED 15100-3 • MICROTECH II CHILLER CONTROLLER 90 www.DaikinApplied.com


Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high
priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com
and click on Training, or call 540-248-9646 and ask for the Training Department.

Warranty

All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied representative for warranty details. To find your
local Daikin Applied representative, go to www.DaikinApplied.com.

Aftermarket Services

To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.

Products manufactured in an ISO Certified Facility.

ED 15100-3 (08/15) ©2015 Daikin Applied | (800) 432–1342 | www.DaikinApplied.com

You might also like