0% found this document useful (0 votes)
338 views

Design Qcs

This document discusses design aspects for railways. It covers basic design parameters such as deflection criteria, durability requirements, and loads and load requirements. Deflection of structures cannot adversely affect functionality and must meet specified limits. Durability is a key consideration given Qatar's aggressive soil and groundwater conditions. Loads include nominal loads, design loads, dead loads, superimposed dead loads, railway loads, fatigue effects, temperature effects, wind loads, seismic loads, groundwater loads, and highway loading. Loading combinations must also be addressed.

Uploaded by

Ray Agacia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
338 views

Design Qcs

This document discusses design aspects for railways. It covers basic design parameters such as deflection criteria, durability requirements, and loads and load requirements. Deflection of structures cannot adversely affect functionality and must meet specified limits. Durability is a key consideration given Qatar's aggressive soil and groundwater conditions. Loads include nominal loads, design loads, dead loads, superimposed dead loads, railway loads, fatigue effects, temperature effects, wind loads, seismic loads, groundwater loads, and highway loading. Loading combinations must also be addressed.

Uploaded by

Ray Agacia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

QCS 2014 Section 29: Railways Page 1

Part 01: Design Aspects

1 DESIGN ASPECTS ....................................................................................... 2


1.1 BASIC DESIGN PARAMETERS .................................................................... 2
1.1.1 General 2
1.1.2 Design Philosophies 2
1.1.3 Deflection Criteria 2
1.1.4 Durability Requirements 3
1.1.5 Fire Resistance Period 4
1.1.6 Crack Width 4
1.1.7 Flexural Cracking 4
1.1.8 Early Age Thermal and Shrinkage Cracking 4
1.2 LOADS AND LOAD REQUIREMENTS.......................................................... 5
1.2.1 General 5
1.2.2 Nominal Loads 5
1.2.3 Design Loads 6
1.2.4 Dead Loads 6
1.2.5 Superimposed Dead Loads and Imposed (Live) Load 6
1.2.6 Railway Loads 7
1.2.7 Fatigue 8
1.2.8 Dynamic Effects 8
1.2.9 Derailment 8
1.2.10 Temperature 8
LQ

1.2.11 Wind 9
1.2.12 Seismic Loads 9
H

1.2.13 Groundwater and Uplift Loads 9


1.2.14 Highway Loading 10
1.2.15 Loading Combinations 10
1.3 ALIGNMENT SPECIFICATION.................................................................... 10
1.3.1 General 10
QCS 2014 Section 29: Railways Page 2
Part 01: Design Aspects

1 DESIGN ASPECTS
1.1 BASIC DESIGN PARAMETERS
1.1.1 General

1 The works shall be designed in accordance with the standards specified by the Employer’s
Requirements.

2 If no local standard exists or the applicable standard is not specified otherwise, the
appropriate and compatible internationally recognised standard or code of practice shall be
adopted.

3 A consistent set of standards that specifically apply to the design of civil and structural
elements shall be adopted.

4 The hierarchy of standards is as follows:

(a) Qatar Construction Specifications;

(b) Euro Norms (EN);

(c) National European Standards; and

(d) International Standards and Codes of Practice.


LQ

1.1.2 Design Philosophies

1 The design shall ensure and demonstrate throughout the Works that the requirements of
H

future operation and maintenance (O&M) activities have been considered and incorporated
to produce a design that is based on a whole-life approach that optimises both capital and
operating cost. Evidence of this approach shall be incorporated into the Contractor’s project
plans and, particularly, in the design documentation.

2 The design shall ensure and demonstrate throughout the Works that he has considered and
incorporated construction and O&M safety requirements into the design. Evidence of these
considerations shall be incorporated into the Contractor’s project plans.

3 The design shall ensure that both the serviceability and ultimate limit states have been
checked in accordance with the standards and codes as specified herein.

4 The design shall take full account of the prevailing soil and groundwater conditions and
those predicted to occur at the site within the design life of the Works.

1.1.3 Deflection Criteria

1 Vertical Deflection Limits

(a) The deflection of a structure or part thereof shall not adversely affect the appearance,
functionality, durability or efficiency of the structure, or associated finishes or
partitions.

(b) The deflection of the retaining walls shall comply with the applicable design codes and
standards as specified herein.
QCS 2014 Section 29: Railways Page 3
Part 01: Design Aspects

(c) The final deflection due to all loads including the effects of temperature, creep and
shrinkage shall be measured from the as-cast level of the supports of floors, roofs and
all other horizontal members and should not exceed the ratio of (span)/500.

1.1.4 Durability Requirements

1 Durability requirements shall be addressed throughout the design, construction, operation


and maintenance of all assets and shall be reflected in the Contractor’s project plans and
O&M manuals.

2 The design shall consider the highly aggressive nature of the geological units in Qatar with
regards to soluble sulphate, chloride and salt concentrations. This shall be taken into
account for durability purposes when designing the underground structures.

3 In designing structures and selecting materials for durability, reliance shall not be placed
solely on the recommendations of codes and standards, but due account shall be taken of
the environment in which the structures are situated and to the monitoring and maintenance
works required to maximise the life of the structures.

4 The primary approach to designing concrete elements for durability shall be based on the
need to achieve a high quality and relatively impermeable concrete, paying particular
attention to structural detailing. Construction joints in underground conditions are vulnerable
to deterioration by aggressive agents and shall be designed to incorporate details that
provide two lines of defence against leakages.

5 The presence of highly aggressive groundwater requires careful design of resistant concrete
LQ

mixes, increased cover to reinforcing steel, close control of flexural cracking and very careful
detailing of gaskets, water bars and hydrophilic water stops to ensure water tight, durable
H

structures.

6 Particular attention shall be given to the detailing and appropriate selection of durable tunnel
lining materials. Lining materials (concrete and reinforcement) and lining components
(gasket seals and fixings) are to be designed and specified to satisfy this durability
requirement.

7 Particular attention shall be given to the deterioration of those elements which cannot be
easily accessed for maintenance or repair during the design life, such as reinforcement
within the inaccessible faces of structures. In such a case the design shall ensure that the
durability of the element can be achieved without maintenance.

8 Where the structure interfaces with, or is in close proximity to other light rail or metro
facilities, provisions to reduce and control stray current shall be adopted to mitigate
associated corrosion problems.

9 Where particularly aggressive conditions are found, a detailed assessment should be carried
out to determine the need to install a full cathodic protection system or if a corrosion
monitoring system is needed in order to achieve the design life of the structure.

10 Cathodic protection shall be considered for all underground reinforced concrete structures.
Connection points and other necessary devices shall be provided to enable the future
installation of a cathodic protection system or electro chemical chloride extraction using
electrical techniques in retaining walls and concrete reinforcement cage continuity. For
diaphragm wall construction, special attention shall be paid to detailing in order to provide
continuity between adjacent wall panels.
QCS 2014 Section 29: Railways Page 4
Part 01: Design Aspects

11 The Design shall include analysis of thermal strains and stresses to mitigate early-age
cracking.

12 The Design shall address all physical or chemical factors such as corrosion, chloride
penetration, carbonation, sulphate cracking and corrosion of the steel reinforcement, steel
spacer, steel accessories, embedded items and similar components that adversely affect the
durability of the Works shall be identified and taken into account in the design to ensure the
specified design life is achieved.

1.1.5 Fire Resistance Period

1 All structures shall be designed for fire protection as specified by the Qatar Ministry of the
Interior General Directorate of Civil Defence and as otherwise specified by the Contract.
Materials specified for the Works shall be non-combustible and shall not emit toxic fumes
when subject to heat or fire, except where permitted under the Contract. In all cases where
there are significant fire risks materials shall be self-extinguishing, low flammability, low
smoke and low toxicity.

1.1.6 Crack Width

1 All structural concrete elements shall be designed to prevent excessive cracking due to
flexure, early age thermal phenomena and shrinkage. The maximum crack widths shall be
as specified in Table 1.1.

1.1.7 Flexural Cracking


LQ

1 Flexural crack width shall be checked in accordance with the applicable design codes and
standards as specified herein. The limits specified in the table below shall apply irrespective
of whether any additional protection, such as a waterproofing membrane, is applied to the
H

elements of the structure.

1.1.8 Early Age Thermal and Shrinkage Cracking

1 Suitable reinforcement shall be designed to prevent early-age thermal and shrinkage


cracking for walls and slabs of more than 250 millimetres in thickness if they are subjected to
internal and external restraint during construction. Thermal and shrinkage strains due to
early-age temperature differences and shrinkage shall be accounted for in the design of
reinforcement for cracking.

2 The preferred method for control of early age thermal and shrinkage cracks is to use small
diameter reinforcing bars placed at close intervals. The limits specified in table below shall
be imposed. Guidance can be sought from CIRIA Report C660 on Early Age Thermal
Control of Concrete.

3 For massive structural elements additional considerations shall be taken into account,
including the duration of hydration and the related concrete strength.
Table 1.1
Cover and Crack Width Criteria
Exposure Max. Crack Width
Element
Condition [mm]
Concrete surface direct in contact with Very severe 0.15
the ground/blinding
Underground, external concrete surfaces Very severe 0.15
protected by a waterproofing membrane
QCS 2014 Section 29: Railways Page 5
Part 01: Design Aspects

Exposure Max. Crack Width


Element
Condition [mm]
Above ground, external concrete surfaces Severe 0.2

Tension piles direct in contact with Very severe 0.2


ground
All other concrete surfaces Moderate 0.3

1.2 LOADS AND LOAD REQUIREMENTS


1.2.1 General

1 Unless specified otherwise the design of concrete and steel elements shall conform to the
following:

(a) EN 1997-1: Eurocode 7: Geotechnical Design, Part 1: General Rules;

(b) EN 1537: Execution of special geotechnical work – Ground anchors;

(c) EN 1990 Eurocode 0: Basis of Structural Design;

(d) EN 1991 Eurocode 1: Actions on structures;

(e) EN 1992 Eurocode 2: Design of concrete structures. Part 1-1 General rules of
buildings;
LQ

(f) EN 1993 Eurocode 3: Design of steel structures;


H

(g) Qatar Construction Specifications, QCS;

(h) ‘Designers’ Guide to EN 1997-1 Eurocode 7: Geotechnical design – General rules’ by


R. Frank, C. Bauduin, R. Driscoll, M. Kavvadas, N. Krebs Ovesen, T.Orr and B.
Scuppener (by Thomas Telford, 2004); and

(i) ‘Hoek – Brown Failure Criterion – 2002 Edition’, by Evert Hoek, Carlos Carranza –
Torres and Brent Corium; and.

(j) EN 1998 Eurocode 8: Design of structures for earthquake resistance.

1.2.2 Nominal Loads

1 As a minimum, for the purpose of computing stresses and deformations, the following load
types and consequential effects shall be taken into account as applicable.

Table 1.2

Loading Types

Loading Type Acronym

Dead loads (including notional loads) DL


Superimposed Dead loads SIDL
Imposed (Live) loads LL
Railway loads RL
QCS 2014 Section 29: Railways Page 6
Part 01: Design Aspects

Loading Type Acronym

Fatigue GG
Dynamic DY
Derailment DR
Wind Loads WL
Temperature loads TE
Seismic Loads EQ
Construction/Erection ER
Shrinkage SH
Creep CP
Movement/ Distortion MD
Earth Pressure EP
Surcharge SR
Hydrostatic WP
Accidental AC
Redundancy R

1.2.3 Design Loads

1 Design loads shall include:

(a) The weight of the load carrying structures themselves (‘self-weight’) and the loads
LQ

imposed on to them, both dead and live;

(b) The deformations imposed on to the structures by temperature variations, concrete


H

shrinkage and creep and other similar factors; and

(c) Inertial loading, caused by seismic actions, oscillations due to impact, explosion
loadings and machine vibrations and other similar factors.

1.2.4 Dead Loads

1 Self-weight of the materials shall be calculated in accordance with the relevant codes as
specified herein.

1.2.5 Superimposed Dead Loads and Imposed (Live) Load

1 Superimposed dead loads include the weights of all the permanent elements of the
structures (except the load bearing elements), such as floor and roof finishes, cables,
trackwork and other similar installations, to the dimensions in the Contractor’s design.

2 The self-weights of the elements in (a) above shall be assessed according to the relevant
codes and standards, by other valid sources, or by substantiated and controllable
manufacturer’s information, or by experimental measurements.

3 For live loads on all underground structures beneath green areas (such as squares, parks,
open-air recreation areas) a minimum distributed load of 10 kN/m2 on the entire surface of
the roof of the structure, at ground level, shall be assumed. For these areas a single
concentrated load of 100 kN minimum shall be assumed.

4 For all stations the minimum distributed and concentrated loads shall be in accordance with
the table below.
QCS 2014 Section 29: Railways Page 7
Part 01: Design Aspects

Table 1.3

Superimposed Dead Loads (SIDL) & Imposed (Live) Load


#1 #1
Superimposed Dead Load Imposed Load
Uniform
Area Ceiling & Concentrated
Finishes Distributed #2
Description Services Load
[kN/m²] Load
[kN/m²] [kN]
[kN/m²]
Public Area 5 1.0 5.0 5.0
#3
Non-public Area 5 1.0 3.5 5.0

Under platform 2.5 1.0 10.0 10.0

Stairs and Landings 2.5 1.0 5.0 5.0

Equipment Rooms 2.5 1.0 10.0 10.0


Surcharge Load on
10.0 100.0
Roof Slabs
#1 this is a minimum requirement. If higher loads apply due to architectural, MEP or any other
circumstances, these shall be used.
#2 concentrated load distributed on an area 300 x 300 mm.
#3 Areas like offices, staff rooms, toilets etc. (not equipment rooms).
LQ

1.2.6 Railway Loads

1 Vertical Train Live Loads


H

(a) Each component of the structure shall be designed / checked for all possible
combinations of these loads and forces. They shall resist the effect of all
combinations:
Figure 1.1
Vertical Train Live Loads

Axle loads = 16 tons

Maximum number of successive cars = 6 car or 2 units

L = max 20 m (Length of a car)

a = 2.65m for the external cars of a 3 car set and 2.35m for the
internal car of a 3 car set (Overhang)

b = 2.10m (Wheel base in a bogie)

c = 10.50m (Distance between Axle-2 and Axle-3 in the car)


QCS 2014 Section 29: Railways Page 8
Part 01: Design Aspects

(b) The maximum number of axles will be applied to the structure to arrive at the
maximum vertical force, maximum shear and maximum bending. The structure shall
be suitable for both single-track and (double) 2-tracks load conditions.

2 Horizontal Train Live Loads

(a) The braking loads shall be assumed to be 30% of the vertical loads. The traction loads
shall also be assumed to be 30% of the vertical loads. Where the structure carries two
tracks, both tracks shall be considered to be occupied simultaneously. Traction forces
shall be considered as acting on one track and braking forces acting on the other, with
both forces acting in the same direction simultaneously to produce the worst loading
condition in the rails and supporting elements. Provision shall be made in supporting
elements for the effects of horizontal and vertical forces transferred to rails.

(b) Centrifugal Force shall be considered, taking into account a design speed for various
radii of curvature as stipulated in the alignment design specification.

(c) Hunting/noising forces shall be considered in accordance with EN 1991.

1.2.7 Fatigue

1 The nominal loadings on the structures for the purposes of the Contractor’s fatigue
assessment shall comprise trains as advised by the Engineer.

2 Fatigue load histories shall be evaluated to provide valid and representative design spectra,
with stress histories analysed by the rain-flow counting algorithm or equivalent method, both
LQ

in conjunction with the projected annual tonnages of rail traffic per track. The provisions of
BS 5400 Part 10 Clause 9.3.3 or other relevant methods may be used as a rigorous method
of evaluation of compliance with fatigue criteria.
H

1.2.8 Dynamic Effects

1 Dynamic effects resulting from the operation of the metro system shall be considered in
accordance with EN 1991 and EN 1998.

1.2.9 Derailment

1 The impact loads on adjacent structures due to derailment shall be considered at all
locations.

2 The adjacent structures are to be protected by direct means (e.g., strengthening) or indirect
means (e.g., repositioning of rail alignments or providing barriers) to ensure these structures
are still functional after an impact occurs.

3 Where indirect measures are employed in the design these can be considered when
calculating the impact loads.

1.2.10 Temperature

1 The effects of temperature shall be considered in the design of the Works using the external
temperatures as stated in the Qatar Rail Development Program Definition Document.
QCS 2014 Section 29: Railways Page 9
Part 01: Design Aspects

1.2.11 Wind

1 Wind loading may affect the surface elements such as vent-shafts, cooling towers,
pedestrian bridges and entrances/exits. It is also a factor on temporary structures during
construction. As per EN 1991, wind speed of 160 km/h shall be applied to determine the
appropriate design wind loads.

2 Applied wind loads on bridges and other above ground structures shall be in accordance
with EN 1991.

1.2.12 Seismic Loads

1 The Works shall be designed to withstand a seismic acceleration (horizontal) of 0.07g.

2 Seismic effects shall be considered on all permanent structures.

3 The effects of load changes and deformation as a result of soil behaviour (eg, liquefaction)
shall be allowed for in the design.

4 The design of the tunnels final linings shall be made for static loadings and shall be checked
against the seismic loadings, by any simplified method similar or comparable to the method
developed for the San Francisco Metro (‘Earthquake Design Criteria for Subways’, ASCE,
Volume 95, No ST6, June 1969, pp 1213-1231).

5 The seismic design of bridges and other elevated structures shall comply with the
requirements of EN 1998 and the clauses of EN 1992 and EN 1993 as relevant.
LQ

1.2.13 Groundwater and Uplift Loads

1 Loads due to water pressure shall be calculated using a unit weight of 10 kN/m³ for fresh
H

water and a unit weight of 10.3 kN/m³ for brackish-water. Should liquefaction of soils be a
potential risk, then the design water table level for permanent structures shall include layers
affected by liquefaction if this is above the design groundwater levels. The effects of
temporary drawdown, seepage and base heave effects shall be considered in the design of
the temporary works, and catered for in the permanent works if there is a ‘locked-in’ effect
from transferred forces. The extent of the temporary walls shall be sufficient to mitigate the
effects of such loads during construction.

2 Groundwater level for design of the permanent structure shall be assumed at ground level. In
the event that long-term groundwater data is available and sufficient to accurately predict the
groundwater level over the design life of the structure, the Contractor may propose a revised
design ground water level based on the maximum groundwater level plus an additional 2m.
The revised design ground water level will be subject to independent verification prior to
submission to the Engineer for a approval. For Temporary Works, the design groundwater
level shall not be lower than 500 mm above the maximum present groundwater level.
3 The effects of floatation loads shall be considered in the design of both the Temporary and
Permanent Works. The Contractor shall check the structure’s stability for resistance to
buoyancy and shall design the structure such that adequate factors of safety against
buoyancy are provided. For this check overburden height less 2m for the possible excavation
for utilities in the future shall be considered. A study showing different possible scenarios for
future excavation above the stations shall be considered in the buoyancy check and
submitted to the Engineer for approval.
4 Protection against buoyancy shall comply with EN 1997.
QCS 2014 Section 29: Railways Page 10
Part 01: Design Aspects

5 Suitable measures from those listed below to counteract buoyancy forces for the Permanent
Works shall be incorporated in the Contractor’s design. The measure(s) chosen shall suit the
particular conditions and the method of construction:
(a) Toe-in of the base slab into the surrounding ground; and
(b) Increasing the dead weight of the structure.

6 Where the base slab has toe-in to the surrounding ground, a partial safety factor of 2.0 shall
be applied to the shear resistance of the ground above the toe and the adhesion factor shall
not apply. The value of the weight of ground above the toe shall be calculated as for the
backfill material.

7 If tension piles are used to counteract buoyancy forces, special precautions shall be made to
preserve the integrity of the waterproofing system and the durability of the tension pile.
These precautions shall be submitted to the Engineer for a SONO.

8 The proposed structures (primarily the stations) may act as obstructions to groundwater
movement. The Contractor shall design and subsequently allow for unobstructed movement
of the groundwater through and around these structures so that there are no changes to the
groundwater level that exceeds normal expected diurnal fluctuations.

1.2.14 Highway Loading

1 Highway loading shall not be less than that specified in EN 1991-2, LM 1.

2 Loads shall be applied for the worst-case combinations and shall be multiplied by the
LQ

specified impact coefficients. No dynamic allowance shall be added for underground


structures with an overburden greater than 1 m.
H

3 For underground structures, beneath existing or planned public roads, with a minimum cover
thickness equal to, or greater than 2.0 m, a minimum uniform live load of 20 kN/m2 shall be
applied at any position and configuration to give the worst-case loading. Whenever the
minimum cover thickness is less than 2.0 m, the live load shall be determined precisely.

1.2.15 Loading Combinations

1 The load factors and load combinations for ultimate and serviceability limit states shall
comply with EN 1991 and EN 1997.

1.3 ALIGNMENT SPECIFICATION


1.3.1 General
1 This section refers to the alignment specification defined in Qatar Rail’s document:
(a) Alignment Design Specifications P000-QRC-ALI-SPE-00001
2 The Alignment Design Build Specifications apply to the subsystems of the Qatar Rail
Development Program (QRDP) namely the High-Speed, Conventional Long Distance Rail
(LD), Freight Lines, LRT and Metro. All units of measure shall be in accordance with the
International System of Units (SI) and in metric units.
3 The operational speed is the speed with which the line will be operated.
4 The permissible speed includes the additional margins for safety, commissioning and future
upgrading of the line.

END OF PART