Liebert APM With Modular Battery User Manual v2.9 PDF
Liebert APM With Modular Battery User Manual v2.9 PDF
1.1 Introduction
This chapter introduces the relevant requirements for positioning and cabling of the LIEBERT APM UPS Rack
System and related equipment.
Because each site has its requirements, it is not the aim of this chapter to provide step-by-step installation
instructions, but to act as a guide for the general procedures and practices that should be observed by the installing
engineer.
Do not apply electrical power to the UPS equipment before the commissioning engineer arrives at installation site.
The UPS should be installed by a qualified engineer in accordance with the information contained in this chapter. All the
equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation information.
The standard LIEBERT APM UPS system of Emerson can be connected to TN, TT and IT AC distribution system (IEC60364-3)
of 3-phase 4-wire, and a 3-wire to 4-wire conversion transformer is provided as an optional part.If the system is connected to IT AC
distribution system, its input needs to be fitted with a 4-pole circuit breaker in accordance with relevant IT system standard.
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH THIS EQUIPMENT.
When connecting the battery, the battery terminal voltage will exceed 400Vdc and is potentially lethal.
Eye protection should be worn to prevent injury from accidental electrical arcs.
Remove rings, watches and all metal objects.
Only use tools with insulated handles.
Wear rubber gloves.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid
and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.
1.3 Location
The UPS is intended for indoor installation and should be located in a cool, dry and clean environment with adequate
ventilation to keep the environmental parameters within the specified operating range (see Tab. 9-2).
Chapter 2 Battery installation 7
The LIEBERT APM series UPS uses forced convection cooling by internal fans. Cooling air enters the module
through ventilation grills located at the front part of the cabinet and exhausted through grills located in the rear part of
the cabinet. Please do not block the ventilation holes.
If necessary, a system of extractor fans should be installed to aid cooling-air flow. An air filter should be used when
the UPS is to operate in a dirty environment and should be regularly cleaned to maintain airflow.
The cooling capacity of air conditioner should be selected according to the power loss data of UPS specified in Tab.
9-3: Normal mode (VFI SS 111 double-conversion UPS)
Note: The UPS should be installed on a cement surface or other surface that is not combustible.
The battery will generate some amount of hydrogen and oxygen at the end of charging, so the fresh air volume of the
battery installation environment must meet EN50272-2001 requirements.
The ambient temperature of the battery must be stable. Ambient temperature is a major factor in determining the
battery capacity and life. The nominal operating temperature of battery is 20°C. Operating above this temperature will
reduce the battery life, and operation below this temperature will reduce the battery capacity. If the average operating
temperature of battery is increased from 20ºC to 30ºC, then the service life of the battery will be reduced by 50%. If
the operating temperature of the battery is above 40ºC, then the battery service life will be decreased in exponent
rate. In a normal installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away
from heat sources or air outlets.
If external batteries are to be used, the battery circuit breakers (or fuses) must be mounted as close as possible to
the batteries, and the connecting cables should be as short as possible.
1.3.3 Storing
Should the equipment not be installed immediately, it must be stored in a room so as to protect it Protection from
excessive humidity and heat sources (see Tab. 9-2).The battery needs to be stored in dry and cool place with good
ventilation. The most suitable storage temperature is 20 ºC to 25ºC.
Should the UPS remains unpowered for a prolonged period of time while the battery are connected, the batteryes may deeply
discharge and being so permanently damaged .In such cases it is therefore reccomented to leave the battery circuit breaker(s)
open. During storage in any case, periodically charge the battery according to the battery user manuals.
1.4 Positioning
When the equipment has been finally positioned, ensure the UPS will remain stationary and stable. To prolong the
service life, the choosen installation site must guarantee:
Space for easy operation on the UPS
Sufficient air to dispel the heat produced by the UPS
Protection from atmospheric agents
Protection from excessive humidity and heat sources
Protection against dust
Compliancy to the local fire prevention requirements
An operating environment temperature within +20°C to +25°C. The batteries are at maximum efficiency in this
temperature range (for information about the battery storage and transportation as well as the environment,
refer toTable 8-2 )
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
Chapter 1 Installation Of UPS Rack System 8
A UPS system can comprise an UPS rack system, external battery cabinet, depending on the specific system
requirement.
All the UPS system cabinets used in the same installation site are of the same height and should be positioned
side-by-side to achieve an aesthetically appealing effect.
Refer to Chapter 7 Installation Drawing for the positioning of UPS cabinet.
Warning
Ensure that any lifting equipment used in moving the UPS cabinet has sufficient lifting capacity.
The UPS is fitted with castors – take care to prevent movement when unbolting the equipment from its shipping pallet. Ensure
adequate personnel and lifting aids are available when removing the shipping pallet.
Ensure that the UPS weight is within the weight loading capacity range of any hoisting equipment. See Tab. 1-1 for
UPS weight.
UPS and optional cabinets can be handled by means of a fork lift or similar equipment. The UPS cabinet can also be
moved by its castors when moving in a short distance.
Note: Care must be taken when handling units fitted with batteries. Keep such moves to a minimum.
Note :
The unit can be shipped whit 1, 2 or 3 power modules installed but not with 4 or 5 ( to be ship separate), and cannot
be with any battery modules installed
As LIEBERT APM series UPS has no ventilation grills at either sides, no clearances are required for the sides.
To enable routine tightening of power terminations within the UPS, it is recommended that clearance around the front
of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important
to leave a distance of 350mm in the rear side of the rack to permit adequate circulation of air coming out of the unit.
If the UPS make use of internal modular battery sufficient clearing shall be given at the back site to allow personnel to
operate the battery circuit breakers (~ 600mm)
The component layout of the UPS rack system supports front access and repairing the UPS, thus reducing the space
requirement for side and rear access.
When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS will remain
stationary and stable.
Installation diagrams in Chapter 4 of this manual identify the location of the holes in the base plate through which
the equipment can be bolted to the floor. If the UPS is to be located on a raised floor, it should be mounted on a
pedestal suitably designed to accept the UPS point loading (more than 1000 kg). Refer to the bottom view in Fig. 4-7
to design this pedestal and stable.
Chapter 2 Battery installation 9
The UPS structure is shown in Fig. 1-1 The UPS configuration is provided in Tab. 1-1
The number and possible installation positions of the Power Modules and Battery Modules may vary according to
the chosen factory configuration. Thanks to the different mounting depth it’s not possible to install a power module
instead of a battery module and vice versa.
Please install the power modules and Battery modules from bottom to top, so as to avoid cabinet toppling due to high
gravity center.
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
Chapter 1 Installation Of UPS Rack System 10
When installing power modules always work from the lower available space upwards to prevent raising the center of
gravity.
1. Use the DIP switch on the front panel of the module to set the module address. The setting range is from 1 to 5.
The module address should be exclusive. The setting method is shown in Tab. 1-2
2. Place the ready switch on the front panel of the module to the up position (i.e., in unready state).
3. Insert the module in the installation position, and push it into the cabinet.
4. Secure the module to the cabinet through the fixing holes on both sides of the front panel of the module.
5. Place the ready switch to the down position (i.e., in ready state).
Ready switch
DETAIL A
Cables can enter the LIEBERT APM series UPS rack system and battery cabinet from below. Cable entry is made
possible through a blanking plate fitted at the bottom of the equipment. The recommended installation practice is to
install glands to prevent foreign material or vermin entering the cabinet.
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
Chapter 1 Installation Of UPS Rack System 12
Over currents
Install suitable protective devices in the distribution unit of the incoming mains supply, considering the power cable
current-carrying capacity and overload capacity of the system (see Tab. 9-7).
Generally it is recommended a magnetic circuit breaker with IEC60947-2 tripping curve C (normal) rated at the 125%
of the current listed in Tab. 9-7.
Split bypass: In case a split bypass is used, separate protective devices should be installed for the rectifier input and
bypass input in the incoming mains distribution panel.
Note
The rectifier input and bypass input must use the same neutral line.
Note
For IT power network system, 4-pole protective device must be installed on the external input distribution and external output
distribution of the UPS.
When using the RCD in the split bypass system or parallel system, the RCD should be installed in the upstream of
the input distribution to avoid wrong alarm.
The residual current introduced by RFI filter in the UPS is between 3.5mA and 1000mA. It is recommended to confirm
the sensitivity of each RCD of upstream input distribution and downstream distribution (to load).
The DC compatible circuit breaker provides over current protection for UPS system and battery, which is provided by
the external battery cabinet. See Appendix A for a selection guide
Chapter 2 Battery installation 13
In the eventuality that an external distribution panel is used for load distribution, the selection of protective devices
must provide discrimination with those that are used at the input to the UPS (see Tab. 9-7).
Warning
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN EMI, ELECTRIC SHOCK HAZARD, OR RISK
OF FIRE, SHOULD AN EARTH FAULT OCCUR.
Warning
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN EMI, ELECTRIC SHOCK HAZARD OR RISK
OF FIRE, SHOULD AN EARTH FAULT OCCUR.
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
Chapter 1 Installation Of UPS Rack System 14
Note
The operations described in this section must be performed by authorized electricians or qualified technical personnel.. If you have
any difficulties, do not hesitate to contact our Customer Service & Support department at the address given at the beginning of this
manual.
After the equipment has been finally positioned and secured, refer to Chapter 4 Installation Drawing to connect the
power cables as described in the following procedures:
1. Verify that all the external input distribution switches of the UPS are completely opened and the UPS internal
maintenance bypass switch is opened. Attach necessary warning signs to these switches to prevent unauthorized
operation.
2. Open the doors of the UPS, remove the front protective cover and then the power connection buses are visible.
3. Connect the protective earth and any necessary grounding cables to the enclosure of the cabinet at the bottom
part of the UPS rack (close to the cabinet side where the output connection terminal strips are located).The cabinet
for the UPS must be connected to the user’s ground connection.
Note: The grounding cable and neutral cable must be connected in accordance with local and national codes
practice.
Identify and make power connections for incoming cables according to one of the two procedures below, depending
on the type of installation:
Common Input Connections
4. For common bypass and rectifier inputs, connect the AC input supply cables to the UPS input terminals
(mA-mB-mC-mN) Refer to
Fig. 4-11 and tighten the connections to 5 Nm (M6 Bolt).ENSURE CORRECT PHASE ROTATION.
5. If a 'split-bypass' configuration is used, connect the AC input supply cables to the rectifier input terminals
(mA-mB-mC-mN) Refer to
Fig. 4-11 and the AC bypass supply cables to the bypass input terminals (bA-bB-bC-bN) and tighten the connections
to 5 Nm (M6 Bolt). ENSURE CORRECT PHASE ROTATION.
Note: For split Bypass operation ensure that the busbars between Bypass and Rectifier inputs are removed. The
neutral line of bypass input must be connected to that of the rectifier input.
Frequency Converter Mode
If the frequency converter configuration is used, connect the AC input cables to the rectifier input terminals
(mA-mB-mC-mN) Refer to
Fig. 4-11 and tighten the connections to 5Nm (M6 bolt), or to 13Nm (M8 bolt) or to 26Nm (M10 bolt).ENSURE
CORRECT PHASE ROTATION AND TIGHTEN CONNECTION TERMINALS. No need to connect the bypass input
cables to bypass input terminals (bA-bB-bC-bN).
Chapter 1 Installation Of UPS Rack System 20
Note
The precautions for battery installation, use and maintenance are to be provided by the batteryes manufacturers. The precautions
in this section include the key issues that must be considered during the installation design, which may be adjusted according to
the specific local situations.
• The battery shall be installed and stored in a clean, cool and dry environment.
• Do not install the battery in a sealed battery chamber or sealed room. The battery room ventilation shall at least meet
the requirement of EN50272-2001. Otherwise, battery bulging, fire and even human injury may be caused.
• The battery shall be installed far away from the heating source (e.g. transformer). Do not use or store the battery in the
place near the heating source or burn the battery or place it into fire. Otherwise, battery leakage, bulging, fire or
explosion may be caused.
• Batteries shall be placed in such a manner that two bare live parts with the potential difference of more than 150V shall
not be contacted at the same time. If it is unavoidable, insulated terminal cover and insulated cables shall be used for
connection.
• If external batteries are to be used, the battery circuit breakers (or fuses) must be mounted as close as possible to the
batteries, and the connecting cables should be as short as possible..
Battery Handling
When connecting the battery, follow the precautions for high-voltage operation
• Before accepting and using the battery, check the appearance the battery. If the package is damaged, or the battery
terminal is dirty, corroded or rusted or the shell is broken, deformed or has leakage, replace it with new product.
Otherwise, battery capacity reduction, electric leakage or fire may be caused.
o Before operating the battery, remove the finger ring, watch, necklace, bracelet and any other metal jewelry
o Wear rubber gloves.
o Eye protection should be worn to prevent injury from accidental electrical arcs.
o Only use tools (e.g. wrench) with insulated handles.
• The batteryes is very heavy. Please handle and lift the battery with proper method to prevent any human injury or
damage to the battery terminal.
• Do not decompose, modify or damage the battery. Otherwise, battery short circuit, leakage or even human injury may
be caused.
• The battery contains sulfuric acid. In normal operation, all the sulfuric acid is attached to the separation board and plate
in the battery. However, when the battery case is broken, the acid will leak from the battery.Therefore, be sure to wear a
pair of protective glasses, rubber gloves and skirt when operating the battery. Otherwise, you may become blind if acid
enters your eyes and your skin may be damaged by the acid.
• At the end of battery life, the battery may have internal short circuit, drain of electrolytic and erosion of positive/negative
plates.If this condition continues, the battery may have temperature out of control, swell or leak. Be sure to replace the
battery before these phenomena happen.
• If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to
sulfuric acid and disposed of in accordance with local regulations.
• If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.
Chapter 2 Battery installation 21
Note
• The battery modules, regardless if they are mounted internally to the UPS or in the MBC, make
uses of strings of 30 batteries.
• The Traditional external battery cabinet can make use of each even number of battery per string
between 30 and 40.
• The default factory setting, if the unit is ordered w/o internal battery is 40.
• The cabinet is only for valve regulated maintenance-free lead-acid battery.
2.3 Safety
Warning
• When handling the battery modules please refer to the label on it on how to operate
• Please use insulated glove to move battery modules.
• Do not to OPEN the battery boxes.
• Voltage between points 1 and 2 ( Fig. 2-1) may exceed 150V DC, so they must not be touched
and the cover shall be kept on when not installed
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
Chapter 1 Installation Of UPS Rack System 22
Battery boxes should be stored in a cool place with the protective cover on . Hot and humid place will cause damage
to Battery boxes.
Only the qualified engineers are allowed to install and maintain mounted in a traditional battery cabinet or shelf. To
ensure safety, install the external battery in a locked cabinet or dedicated battery room accessible just to service
qualified personnel
Please note that number of cells set via software must be consistent with the actual number of cells.
A minimum space of 10mm must be reserved on all vertical sides of the battery block to permit free air movement
around the cells.
A certain clearance should be reserved between the top of the cells and the underside of the shelf above as this is
necessary for monitoring and servicing the cells.
When installing the batteries always work from the bottom shelf upwards to prevent raising the center of gravity.
Install the batteries reliably and avoid vibration and mechanical bumping.
The bending radius of cable should be more than 10D, where "D" is the outer diameter of cable.
When connecting the cable, do not cross the battery cables and do not bind the battery cables together
The battery connection must be firm and reliable. After the connection, all the connections between the wiring
terminals and the batteries must be corrected to meet the torque requirement provided in the specifications and user
manuals of the battery manufacturers.
Each battery terminal should be insulated after its connection has been made.
Check if the battery is unexpectedly grounded. If the battery is unexpectedly grounded, remove the earth power
supply. Contacting any part of the grounded earth may be subject to electric shock
Measure the battery voltage, and carry out battery voltage calibration after the UPS is started.
When using a traditional battery solution, always comply with the following precautions:
• Disconnect the charging power before connecting or disconnecting the cable of the battery terminals.
• Do not connect the cables between the UPS battery terminals and the batteries before getting the approval from the
commissioning engineer.
• When connecting the cables between the battery terminals and the circuit breaker, always connect the circuit breaker end of
the cable first.
• Be sure to connect the positive/negative terminals of the batteries to those of the circuit breakers and those of the circuit
beakers to those of the UPS respectively with reference to the markings of positive/negative terminals. Reverse connection of
battery polarities will result in explosion, fire accident, the damage of batteries and UPS, and human injury.
• The battery connecting terminal shall not subject to any external force, such as the pulling force or twisting force of the cable.
Otherwise, the internal connection of the battery may be damaged, and in severe case, the battery may catch fire.
• Do not connect power until the total voltage of the battery string is verified correct through measurement.
• Do not connect any conductor between the positive and negative terminals of the battery.
• Do not close the battery circuit breakers before getting the approval from the commissioning engineer.
Chapter 2 Battery installation 23
• Check to ensure that all the safety devices are in place and function normally. Check if the battery management parameter
setting is normal particularly.
• Measure and record the air temperature in the battery room.
• Check if the battery terminals are damaged or have the symptom of heating, and if the shell or cover is damaged.
• Please fasten every bolt on the terminal according to the fastening torque specified in the table below .
• After 1-2 months of service, recheck to make sure that each screw has been fastened according to the specified torque.
Otherwise there is risk of fire.
• CAUTION: Use the battery with the same capacity and type, if battery is replaced by an incorrect type, it can cause explosion.
• CAUTION: Dispose of used battery according to the local instructions
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
30 Chapter 3 Installation Drawing
1
1. power module
2. Battery module
3. Bypass module
4. Power input/output
5. Battery Module CB
2
Fig. 4-3: 150kVA UPS module system, front view whit open door and back view without doors
1. Blanking plate
2. battery module
3. battery input
5. battery module CB
Fig. 4-4: Modular Battery Cabinet: front view with open door and back view without doors
Chapter 3 Installation Drawing 31
1996
600 1100
600 1100
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
32 Chapter 3 Installation Drawing
16
12
485
396
340
DETAIL A
847
985
1081
Fig. 4-7: UPS and BC bottom view show the position of casters and fixing holes
460
80
Fig. 4-8: UPS and BC bottom view show the cable entry area
Chapter 3 Installation Drawing 33
mA mB mC mN
mN
PE oA
oB oC
bA bB bC
oN
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
34 Chapter 3 Installation Drawing
25
M8(all)
286
256
238
203
200
183
40
42
40 40 45
40 45
40
M10
M8
25
269
183
80 80
1. Battery Box
2. Battery Boxes Terminals
3. Battery Module Terminals
4. Circuit Breaker
5. Battery Tray
According to the selected configuration, the LIEBERT APM can house from none to 9 battery modules connected in
parallel.
Each Modular Battery Cabinet can house additional 10 modules of battery
Each module is made of 3 battery boxes and a battery tray. Each battery box contains ten 9AH/12V batteries and
each battery tray has one 50A DC current limiting circuit breaker. The maximum discharging current of each layer of
battery is 45A. Over charging current will trip the circuit breaker and the monitoring unit will display the alarm.
Note
When using modular battery it is important to install at least 2 battery module per each power module installed.Not doing that will
result in the CB tripping before the battery reaches the EOD.
Note
Battery housed in the external Modular Battery Cabinet must be of the same kind of the internal ones.
Chapter 5 Operating Instructions 43
Warning: Hazardous mains voltage and/or battery voltage present behind the protective cover
The components that can only be accessed by opening the protective cover with tools cannot be operated by user.
Only qualified service personnel are authorised to remove such covers.
6.1 Introduction
The LIEBERT APM UPS operates in the following 3 modes listed in Tab. 6-1. This section describes various kinds of
operating procedures under each operating mode, including transfer between operating modes, UPS setting and
procedures for turning on/off inverter.
The UPS rack system only has a maintenance bypass isolating switch, and all the other transfers are processed
automatically by internal control logics.
This procedure must be followed when turning on the UPS from a fully powered down condition.
The operating procedures are as follows:
1. Open the external power switch. Open the UPS door, connect the power supply cables and ensure the correct
phase rotation.
Warning
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
44 Chapter 5 Operating Instructions
2. Close the external circuit breakers and connect the mains power.
The LCD starts up at this time. The Rectifier indicator flashes during the startup of rectifier. The rectifier enters normal
operation state, and after about 30s, the rectifier indicator goes steady green. After initialization, the bypass static
switch closes. The UPS Mimic LEDs will indicate as following:
LED Status
Rectifier indicator Green
Battery indicator Off
Bypass indicator Green
Inverter indicator Off
Load indicator Green
Status indicator Amber
Note
In bypass mode, the load is directly fed by the mains power instead of the pure AC power from the inverter.
6.4 Procedure For Switching The UPS Into A Maintenance Bypass From
Normal Mode
This procedure can transfer the load from the UPS inverter output to the maintenance bypass supply, but the
precondition is that the UPS is in normal mode before the transfer.
Caution
Before making this operation, read messages on display to be sure that bypass supply is regular and the inverter is synchronous
with it, so as not to risk a short interruption in powering the load.
1. Press the INVERTER OFF switch on the right side of the operator control panel for longer than two seconds (if
system is a interrupt transfer, there is a prompt to alarm and you must confirm the interrupt transfer). The UPS Mimic
indicator Inverter ON will extinguish and also the Status Indicator (6) will turn amber and will be accompanied by an
audible alarm. The load transfers to static bypass, and the inverter shuts down.
Note
Pressing the Alarm Silence ON/OFF button cancels the audible alarm but leaves the warning message displayed until the alarm
condition is rectified.
2. Open the UPS door, close the maintenance bypass switch on the right bottom of the unit from OFF to ON position.
The load power supply is provided by the manual maintenance bypass.
Warning
If you need to maintain the module, wait for 10 minutes to let the DC bus capacitor fully discharge before removing corresponding
module.
When the maintenance bypass switch is on position of ON, some part of the UPS circuit still has hazardous voltage. Therefore,
only qualified person can maintain the UPS.
Caution
When the UPS is in maintenance bypass mode, the load is not protected against abnormal mains supply.
Warning
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
46 Chapter 5 Operating Instructions
Note
The rectifier will be turned on automatically when the overtemprature fault disappears at 5 minutes after the disappearance of
overtemprature signals.
After pressing the EPO button, if the UPS mains input has been disconnected, the UPS is completely powered down.
When the mains input is restored, the EPO condition will be cleared and the UPS system will enable static bypass
mode to restore the output.
Warning
If the maintenance bypass isolatingswitch is put to ON and the UPS has mains input, then the UPS output is emergised.
The UPS module needs 10 minutes to discharge to safe voltage, do not operate on the UPS during this time.
7.1 Introduction
The operator control and display panel is located on the front panel of the UPS. Through this LCD panel, the operator
can operate and control the UPS, and check all measured parameters, UPS and battery status and event and alarm
logs. The operator control panel is divided into three functional areas from left to right: mimic current path, LCD
display & menu keys, and control and operation keys.
The LEDs shown on the mini current path represent the various UPS power paths and show the current UPS
operating status.
Steady Green Load on Rectifier
Flashing Green Utility Normal, but rectifier not operating
Steady Red Rectifier fault
Off Rectifier has no fault, and utility abnormal
Battery or battery converter abnormal (Battery Failure, No Battery, Battery Reverse, battery converter
Steady Red
fault, battery converter over temperature, battery converter over current)
Off Battery and converter have no fault, and battery is charging
The LCD display is a 320 × 240 dots graphic display that is friendly to user. The LCD can display alarm information in
real time. 1024 historical records can be stored and retrieved for reference and diagnosis.
Through the graphic LCD display and a user-friendly menu-driven operator system, the user can easily browse the
parameters for input, output, load and batteries and the current UPS status and warnings are always put forward
automatically for quick reference. The versions of converter firmware, inverter firmware, bypass firmware and internal
monitor firmware can be displayed on the LCD.
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
52 Chapter 6 Operator Control And Display Panel
Five menu buttons are used for selecting the menu to be displayed.
Button F1 F2 F3 F4 F5
Function 1 ESC
Home Exit Move left Move right Confirm
Function 2
Move up Move down
Softkey functions
The icons above the F1 to F5 buttons clearly explain the meaning of each button. As shown in Fig. 7-2 pressing F1
can move the cursor (at AC Output) from menu window (2) to the current event log window (4), and firstly move the
cursor to “Close rectifier input circuit breaker”. Pressing F2 can move the cursor from “AC Output” menu to “Bypass
Input” menu.
Chapter 6 Operator Control And Display Panel 53
The LCD menu tree is shown below. Please refer to Tab. 7-13: UPS event log
Rectifier input Bypass input AC output Load of this UPS Load of parallel system Battery data
Phase current (V) Phase current (V) Apparent power (kVA) Apparent power (kVA)
Phase voltage (A) Phase current (V) Phase voltage (A) Active power (kW) Active power (kW)
Frequency (Hz) Frequency (Hz) Frequency (Hz) Reactive power (kVAR) Reactive power (kVAR) Battery voltage (V)
Line voltage (V) Line voltage (V) Line voltage (V) Load % Single UPS system has Battery current (A)
Crest factor no parallel system data Battery temperature (ºC)
PF PF
Remaining time (Min)
Battery capacity (%)
Battery in boost charging
Battery in float charging
Battery not connected
Current log History log Language Function setting Test command UPS version
The LCD menu tree shown in Fig. 7-2 is described in details below.
UPS information window: Display basic information of UPS, including current time, date, UPS name, configuration
and status. This window displays the UPS basic information and is not necessary for the user to operate. The
information of this window is given in the following table.
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
54 Chapter 6 Operator Control And Display Panel
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
56 Chapter 6 Operator Control And Display Panel
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
62 Chapter 9 Product Specifications
Battery Mode $ % 96
Heat Losses & Air Exchange
Rated Power kVA 30 60 90 120 150
Normal Mode kW 1.2 2.4 3.6 4.8 6
No Load kW 0.6 1.2 1.8 2.4 3
Maximum forced air cooling (front
L/sec 48 96 144 192 239
intake, rear exhaust)
Intermediate DC circuit
Rated Power, kVA Unit 30~150
Nominal: 432V (VRLA Float charge is 540V) 36 jars of 12V VRLA
Battery bus voltage Vdc
Range: 400V ~ 616V
Nominal 216=[36x6cell (12V)blocks]
Quantity of
Maximum 240=[40x6cell (12V)blocks]
lead-acid cells
Minimum 180=[30x6cell (12V)blocks]
2.25 V/cell (selectable from 2.2 –2.3V/cell), Constant current and constant
Float Voltage V/cell (VRLA)
voltage charge mode
Temperature
mV/C° - 3.0 (selectable 0 to – 5.0 around 25°C or 30°C or inhibit)
compensation
Ripple Voltage % V float ≤1
Ripple Current ~ C10 ≤5
Boost charge 2.35 V/cell (selectable from 2.30-2.40V/cell)
VRLA
Voltage Constant current and constant voltage charge mode
- float-boost current trigger 0.050 C10 (selectable 0.030-0.070)
- boost-float current trigger 0.010 C10 (selectable 0.005-0.025)
Boost Control -
24 hr safety time-out (selectable 8-30 hr)
boost charge mode inhibit also selectable
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
64 Chapter 9 Product Specifications
Frequency2 Hz 50/60
Synchronous transfer: (< 2ms
Transfer time (between
ms Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz)
Bypass and Inverter)
or 40, 60, 80, 100 ms selectable
Upper limit: +10, +15 or +20, default +15
Bypass voltage
%Vac Lower limit –10, -20, -30 or -40, default: -20 (delay time to accept steady bypass voltage: 10
tolerance
sec)
Bypass frequency
% ±10 or ±20, default ±10
tolerance
Synchronisation -
Hz Rated frequency ± 2 Hz (selectable ± 0.5 to ± 3Hz)
Window
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual