Footing Design Excel

This document provides information to design the foundations for two columns. It includes soil properties, column sizes and loads, and calculations to determine the footing depth and dimensions. The key steps are: 1. The footing depth is calculated to be 206936.64 mm based on soil properties and column loads. 2. The footing dimensions are calculated using the total required area, center-to-center spacing between columns, and equations relating the individual footing areas. 3. The resulting footing dimensions are a length of 2.5 m for column C1 and lengths determined by equations relating the individual footing areas.

Uploaded by

sujan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (5 votes)
3K views13 pages

Footing Design Excel

This document provides information to design the foundations for two columns. It includes soil properties, column sizes and loads, and calculations to determine the footing depth and dimensions. The key steps are: 1. The footing depth is calculated to be 206936.64 mm based on soil properties and column loads. 2. The footing dimensions are calculated using the total required area, center-to-center spacing between columns, and equations relating the individual footing areas. 3. The resulting footing dimensions are a length of 2.5 m for column C1 and lengths determined by equations relating the individual footing areas.

Uploaded by

sujan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 13

Given Data

Length Width
Size of column (C1) = 450 450
Size of column (C2) 500 500
Service load at C1 = 1000
Service load at C2 = 1200
Bearing capacity of soil (BCS) 200
Grade of concrete = 25
Grade of steel = 415
Distance of column center C1 from property line(i.e from column 0.5
center to footing end)
Spacing between column(C/C spacing) 3.5

Step 1
Size of combined footing = 12.1
Distance of resultant column load from column C1= 1.91
Length of footing = 4.82
Adopted footing length (L) 5
Width of footing (B) = 2.42
Adopted footing width(B) = 2.5
Final area of footing provided = 12.5

Step 2
Upward soil pressure acting on footing = 176
Factored soil pressure = 264
Upward soil pressure per unit length = 660

Step 3
Shear force and BM calculation
SF at point left of A = -330
SF at point right of A = 1170
SF at point left of B = -1140
SF at point right of B = 660
Distance of zero shear force from point A= 1.77
Distance of zero shear force from footing edge(i.e. from C) = 2.27

BM at point A = 82.5
BM at point B = 330
BM at zero shear force (BM max)= -654.545455

Step 4 Design of combined footing


1 Effective depth of footing(d) = 435.57
Considered effective depth of footing(d) = 450
Clear cover = 50
Diameter of bar = 20
Total depth (D) = 510

2a Check for two way (punching shear)at column C2


b0= 3800
Resisting area = 1710000
For two way shear(Tc=) 1.25
Vu = 1561.74
Tv = 0.91

2b Check for two way (punching shear)at column C1


b0= 3600
Resisting area = 1620000
For two way shear(Tc=) 1.25
Vu = 1286.16
Tv = 0.79

3 Reinforcement calculation(Longitudinal reinforcement)


Top reinforcement calculation
Percentage of steel (pt) = 1.09
Ast = 4925.6773
Size of rebar used = 28
Area of bar(ast) = 615.75
Spacing of bars = 125.01

Provide 28 dia bar @ 125mm c/c for top reinforcement

Bottom reinforcement calculation


Percentage of steel (pt) = 0.49
Ast = 2212.75
Size of rebar used = 20
Area of bar(ast) = 314.16
Spacing of bars = 141.98

Provide 20 dia bar @ 120mm c/c for bttom reinforcement

4 Bottom reinforcement calculation(Transverse reinforcement)


Band width under column C1 = 1.35
Upward pressure under column C1 = 600
Cantilever projection distance = 1.025
BM at column face at transverse direction = 315.19
Percentage of steel (pt) = 0.34
Ast = 2056.47
Size of rebar used = 18
Area of bar(ast) = 254.47
Spacing of bars = 123.74
Provide 18 dia bar @ 120mm c/c for bttom reinforcement

Band width under column C2 = 1.4


Upward pressure under column C2 = 720
Cantilever projection distance = 1
BM at column face at transverse direction = 360.00
Percentage of steel (pt) = 0.38
Ast = 2364.14
Size of rebar used = 20
Area of bar(ast) = 314.16
Spacing of bars = 132.89
Provide 20 dia bar @ 120mm c/c for bttom reinforcement

5 Top reinforcement calculation(Transverse reinforcement)= 540


Size of rebar used = 12
Area of bar(ast) = 113.10
Spacing of bars = 209.44
Provide 12 dia bar @ 200mm c/c for top reinforcement
mm
mm
KN
KN
KN/m2
Mpa
Mpa

Adding 10% as self wt. of footing


m 2

m
m
m
m
m
m2 OK

KN/m2
KN/m2
KN/m

KN 450 500
KN 450
KN
KN
m
m
5m
KN-m 0.5 3.5
KN-m
KN-m

1500 1800
C A B
mm
mm 660 KN/m
mm 1170
mm 660
mm


mm x −
mm2
N/mm2 -330
KN -1140
N/mm2 OK

82.5 330
mm
mm2
N/mm2
KN −
N/mm2 OK
-654.5455

%
mm2
mm
mm2
mm

%
mm2
mm
mm2
mm

m
KN/m
m
KN-m
%
mm2
mm
mm2
mm

m
KN/m
m
KN-m
%
mm2
mm
mm2
mm

mm2
mm
mm2
mm
500 2.5 m

D
KN/m
A Given data
Unit weight of soil = 20 KN/m3
Angle of repose = 30 degree
Allowable bearing capacity of soil (BCS) = 150 KN/m2
Concrete grade = 20 N/mm2
Steel grade = 415 N/mm2
C/C distance of two column (s)= 6m
Size of column L B
C1 400 400 mm
C2 500 500 mm
Service load on column C1(P1)= 1000 KN
Service load on column C2(P2)= 1500 KN
Distance from footing edge to Center of Column C1(m)= 0.2 m

B Calculation of foundation depth (h) = 206936.64

C Calculation of footing dimension


Area of footing (L1*B1)+(L2+B2)= 18.33 m2 eq 1
n= 3.6 m
Area of footing (A1) = L1*B1 m2
Area of footing (A2) = L2*B2 m2
We have
(L1*B1)*(m+n-0.5*L1)=L2*B2*(s-n)
Taking B1=B2=B
(L1*B1)*(0.2+3.6-0.5*L1)=L2*B2*(6-3.6)
3.8L1-0.5L12=2.4L2 eq2
Substituting L2 value of eq2 in eq1, We get
L1 = 2.5 m
B=B1=B2 3.6 m
L2 = 2.7 m
Width of longitudinal beam(bb) =Size of column/pedistal 0.6 mm
D Thickness of footing based on moment
Net upward ultimate soil pressure (Pu) = 200.32 KN/m2
Width of longitudinal beam(bb) =
xu/d = 0.479 for Fe415&Fe500
Maximum moment per unit width (Mu) = 225.36 KNm/m
Depth of footing from moment criteria (d) 286 mm

E Thickness of footing based on one way shear


Design of column
A Given Data
Column Dimension D B
500 400 mm
Pu = 3000 KN
Mux = 180 KNm
Muy = 200 KNm
Concrete grade (Fck) = 25 N/mm2
Steel grade(Fy) = 500 N/mm2
Length (L) = 6m

B Effective length (Leff) = 3.9 m


C Slenderness ratio = 9.75 < 12
Short column
ex = 28.67 mm
ey = 25.33 mm
0.05B = 20 mm
0.05D = 25 mm
As ex>0.05D&ey>0.05B so designed as short biaxially loaded column

D Calculation of moment along X and Y axis


Mux = 76 KNm
Muy = 86 KNm
Design moment
Mux = 180 KNm
Muy = 200 KNm

E Assuming % of steel (p)= 1.5 %


Effective cover(d') = 40 mm
d'/D = 0.1
Pu/FckBD = 0.6
p/Fck = 0.06
From IS code, SP 16 chart 48
Mux/FckB2D = 0.03
Mux = 60 KNm
d'/B = 0.1
Pu/FckBD = 0.6
p/Fck = 0.06
From IS code, SP 16 chart 48
Muy/FckBD2 = 0.03
Muy = 75 KNm
From IS code, 456 clause 39.6
n n
 M ux   M uy  ≤1
   
M 
 M uxl   uyl 
n n
 M ux   M uy 
   
M 
 M uxl   uyl 
Puz = 1125000