100% found this document useful (1 vote)
1K views2 pages

Earth Pit Test Report

1. The document is an earth resistance test report from Durga Switchgears conducted on January 3rd, 2009 for Samco Metals and Alloys testing the earth resistance of various equipment earth pits. 2. It lists 32 pieces of equipment such as transformers, generators, cranes, furnaces, and their individual and combined earth resistance measurements in ohms. 3. All resistance measurements were found to be well within the maximum permissible limits of 6 ohms for individual pits and 1 ohm for combined values.

Uploaded by

KOSAKA LAB
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views2 pages

Earth Pit Test Report

1. The document is an earth resistance test report from Durga Switchgears conducted on January 3rd, 2009 for Samco Metals and Alloys testing the earth resistance of various equipment earth pits. 2. It lists 32 pieces of equipment such as transformers, generators, cranes, furnaces, and their individual and combined earth resistance measurements in ohms. 3. All resistance measurements were found to be well within the maximum permissible limits of 6 ohms for individual pits and 1 ohm for combined values.

Uploaded by

KOSAKA LAB
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

TIN 33251085384 DURGA SWITCHGEARS ESB 1075

CST 872774/08-01-08 (Servicing, Repairing and Testing of all kinds of LT/HT CircuitBreakers,
AREA CODE 0 5 5 Protective relays, Transformers and High pot Test)
DEALERS FOR ANDREW YULE PRODUCTS
8/5, JOHN VASU STREET, Mobile: 9884320732
MADHAVARAM MILK COLONY, Office: 9840319105
CHENNAI – 600 051. Mail : [email protected]
DATE: 06-01-09
TO
M/S SAMCO METALS AND ALLOYS (P) LTD
KANIYAMBADI – 632 102.
VELLORE DIST , TAMIL NADU.

EARTH RESISTANCE TEST REPORT

TEST CARRIED OUT ON 03RD JANUARY 2009

S.NO DESCRIPTION Individual Combined


Resistance Resistance
in Ohms in Ohms
1 Transformer 1 Body Earth Pit 1 1.8 0.21
2 Transformer 1 Body Earth Pit 2 1.6 0.19
3 Transformer 1 Neutral Earth Pit 1.5 0.19
4 Transformer 2 Body Earth Pit 1 1.3 0.31
5 Transformer 2 Body Earth Pit 2 1.5 0.22
6 Transformer 2 Neutral Earth Pit 1.6 0.28
7 Transformer 3 Body Earth Pit 1 1.2 0.18
8 Transformer 3 Body Earth Pit 2 1.4 0.19
9 Transformer 3 Neutral Earth Pit 1.3 0.25
10 Transformer 5 Body Earth Pit 1 1.3 0.18
11 Transformer 5 Body Earth Pit 2 1.6 0.29
12 Transformer 5 Neutral Earth Pit 1.3 0.21
13 Lightning Arrestor Earth Pit 1.3 0.19
14 Kiosk Earth Pit 1.5 0.21
15 Dummy Earth 1.3 1.20
16 1250 KVA Transformer Body Earth 1.3 0.15
Pit 1
17 1250 KVA Transformer Body Earth 1.2 0.18
Pit 2
18 1250 KVA Transformer Neutral 1.4 0.12
Earth Pit 1
19 1250 KVA Transformer Neutral 1.2 0.13
Earth Pit 2
TIN 33251085384 DURGA SWITCHGEARS ESB 1075
CST 872774/08-01-08 (Servicing, Repairing and Testing of all kinds of LT/HT CircuitBreakers,
AREA CODE 0 5 5 Protective relays, Transformers and High pot Test)
DEALERS FOR ANDREW YULE PRODUCTS
8/5, JOHN VASU STREET, Mobile: 9884320732
MADHAVARAM MILK COLONY, Office: 9840319105
CHENNAI – 600 051. Mail : [email protected]
DATE: 06-01-09
TO
M/S SAMCO METALS AND ALLOYS (P) LTD
KANIYAMBADI – 632 102.
VELLORE DIST , TAMIL NADU.

EARTH RESISTANCE TEST REPORT

TEST CARRIED OUT ON 03RD JANUARY 2009

S.NO DESCRIPTION Individual Combined


Resistance Resistance
in Ohms in Ohms
20 800 KVA DG Body Earth Pit 1 1.8 0.19
21 800 KVA DGBody Earth Pit 2 1.6 0.22
22 800 KVA DG Neutral Earth Pit 1 1.5 0.23
23 800 KVA DG Neutral Earth Pit 2 1.3 0.18
24 CRANE 117 Body Earth 0.25 0.25
25 CRANE 118 Body Earth 0.28 0.28
26 Heat Furnace C 1.2 0.32
27 Heat Furnace D &Heat Furnace E 1.4 0.47
28 Crane 120 0.51 0.51
29 Crane 122 0.31 0.31
30 SHOT Blast 202 0.18 0.18
31 SHOT Blast 203 0.32 0.32
32 SHOT Blast 204 0.31 0.31

TESTED BY EARTH TESTER MAKE: WACO


SERIAL NO: 50388

NOTES:-
THE MAXIMUM PERMISSIBLE VALUES FOR INDIVIDUAL EARTH
PITS & COMBINED VALUES ARE 6 OHMS & 1 OHM RESPECTIVELY. THE
EARTH PIT RESISTANCE VALUES MEASURED AT YOUR PLANT ARE WELL
WITHIN THE LIMITS.