Protection Interlock Diary
Protection Interlock Diary
1 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 2 of 125
1. MFT-FSSS 15
2. INDUCED DRAFT FAN –A 15
2.1 START PERMISSIVE 15
2.2 TRIPPING CONDITIONS 16
3. INDUCED DRAFT FAN –B 16
3.1 START PERMISSIVE 16
3.2 TRIPPING CONDITIONS 17
4. FORCED DRAFT FAN-A 17
4.1 START PERMISSIVE 18
4.2 TRIPPING CONDITIONS 18
5. FORCED DRAFT FAN –B 18
5.1 START PERMISSIVE 18
5.2 TRIPPING CONDITIONS 19
6. PRIMARY AIR FAN-A 19
6.1 START PERMISSIVE 19
6.2 TRIPPING CONDITIONS 20
7. PRIMARY AIR FAN-B 20
7.1 START PERMISSIVE 20
7.2 TRIPPING CONDITIONS 21
8. SEAL AIR FAN-A 21
8.1 START PERMISSIVE 21
8.2 STOP PERMISSIVE 21
8.3 AUTO START 21
8.4 AUTO STOP 22
8.5 PROTECTION START 22
8.6 PROTECTION STOP 22
9. SEAL AIR FAN-B 22
9.1 START PERMISSIVE 22
9.2 STOP PERMISSIVE 22
9.3 AUTO START 22
9.4 AUTO STOP 23
9.5 PROTECTION START 23
9.6 PROTECTION STOP 23
10. COAL MILL SYSTEM 23
10.1 START PERMISSIVE FOR MILL A 23
10.2 START PERMISSIVE FOR MILL B 24
10.3 START PERMISSIVE FOR MILL C 24
10.4 START PERMISSIVE FOR MILL D 25
10.5 START PERMISSIVE FOR MILL E 26
10.6 START PERMISSIVE FOR MILL F 26
10.7 TRIPPING CONDITIONS(SAME FOR ALL MILL) 27
2 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 3 of 125
3 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 4 of 125
TURBINE
TABLE OF CONTENTS PAGE NO
1. ETS 53
2. METS A 54
3. METS B 54
4. FEEDWATER SYSTEM 54
TDBFP –A 54
4.1 START PERMISSIVE 54
4.2 TRIPPING CONDITIONS 55
TDBFP –B 55
4.3 START PERMISSIVE 55
4.4 TRIPPING CONDITIONS 55
MDBFP 56
4.5 START PERMISSIVE 56
4.6 TRIPPING CONDITIONS 57
5. CONDENSATE WATER SYSTEM 58
CEP-A 58
5.1 START PERMISSIVE 58
5.2 AUTO START 58
5.3 TRIPPING CONDITIONS 58
CEP-B 59
5.4 START PERMISSIVE 59
5.5 AUTO START 59
5.6 TRIPPING CONDITIONS 59
6. CIRCULATING WATER SYSTEM 60
CWP-A 60
6.1 START PERMISSIVE 60
6.2 AUTO START 60
6.3 TRIPPING CONDITIONS 60
CWP-B 61
6.4 START PERMISSIVE 61
6.5 AUTO START 61
6.6 TRIPPING CONDITIONS 61
7. CLOSE CYLCE COOLING SYSTEM 62
CCCWP-A 62
7.1 START PERMISSIVE 62
7.2 AUTO START 62
7.3 TRIPPING CONDITIONS 62
CCCWP-B 62
7.4 START PERMISSIVE 62
7.5 AUTO START 62
4 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 5 of 125
5 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 6 of 125
6 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 7 of 125
DM PLANT
7 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 8 of 125
CHP
1. Crusher 89
1.1 Pre-condition 89
1.2 Start permissive 89
1.3 Stop permissive 89
1.4 Protection Stop 89
1.5 Interlock Stop 89
2. Roller Screen-A 90
2.1 Pre-condition 90
2.2 Start Permissive 90
2.3 Protection Stop 90
2.4 Interlock Stop 90
3. Roller Screen-B 90
3.1 Pre-condition 90
3.2 Start Permissive 90
3.3 Protection stop 91
3.4 Interlock stop 91
8 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 9 of 125
9 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 10 of 125
10 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 11 of 125
11 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 12 of 125
12 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 13 of 125
13 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 14 of 125
14 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 15 of 125
BOILER
1. FSSS SYSTEM
1. Both FD fan off
2. Both ID fan off
3. Turbine trip with delay of 10sec
4. Manual emergency trip pb ,push button on dcs console
5. All boiler feed pump stopped(BFPT A tripped& BFPT B tripped&MDBFP tripped&any oil layer
run for arming)
6. Feed water flow low low i.e. << 549 t/h with 2 out of 3 logic.
7. Furnace pressure low low i.e.< -2.5 kpa& delay of 3sec from local switchwith 2 out of 3 logic.
8. Furnace pressure high high i.e.>2.5kpa & delay of 3secfrom local switchwith 2 out of 3 logic.
9. Flame detection cooling air loss i.e.< 2.8 kpa from local switch with 2 out of 3 logic.
10. Flame failurewith 2 out of 3 logic.
11. Loss of all fuelwith 2 out of 3 logic.
12. Boiler total air flow <25% i.e. total air flow< 580 tph & delay of 25sec.
13. Both PAF off & any mill run with delay of 10sec.
14. Both APH tripped with delay of 3 sec.
2. ID FAN A
2.1 START PERMISSIVE
15 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 16 of 125
3. ID FAN B
3.1 START PERMISSIVE
16 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 17 of 125
4. FD FAN A
4.1 START PERMISSIVE
17 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 18 of 125
5. FD FAN B
5.1 START PERMISSIVE
1. Aph a running and outlet sa damper opened or ( aph b running and aph b outlet sa
damper opened and interconnct damper in fd outlet opened)
2. Not FDF B trip lockout position
3. Vane of fd fan a closed
4. FDF B motor stator coil temp not high i.e. <120 deg c
5. Motor bearing temp not high i.e. <80 deg c
6. FDF B bearing temp not high i.e. <90 deg c
7. FDF B outlet dampers closed
8. FDF B stopped
9. FDF B oil station normal
10. Idf a running or idf b running
11. FDF B motor in remote
12. Main motor FDF B electrical fault off
18 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 19 of 125
6. PA FAN A
6.1 START PERMISSIVE
19 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 20 of 125
7. PA FAN B
7.1 START PERMISSIVE
20 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 21 of 125
12. PAF B running and aph a stop with a delay of 105 sec.
13. MFT
14. PAF B running and PAF B outlet valve closed with PAF B run(set 60s) PAF B o/vlv close(1s)
15. PAF B lube oil supply pipe pre LL with alarm at 0.1 mpa & trip at 0.06 mpa with delay of
30sec.
16. PAF B level vibration hh and PAF B vertical vibration h with alarm at 4.60mm/sec & trip at
7.10mm/sec
17. PAF B level vibration h and PAF B vertical vibration hh with alarm at 4.60mm/sec & trip at
7.10mm/sec
18. PAF B motor stator winding temp hh with alarm at 120 degc & trip at 125 degc
& 3 out of 6 logic
19. PAF B motor foreside bearing temp hh with alarm at 80 degc & trip at 85 degc
20. PAF B motor rearward bearing temp hh with alarm at 80 degc & trip at 85 degc
21. PAF B foreside bearing temp hh with alarm at 90 degc & trip at 95 degc with 2 out of 3 logic
22. PAF B rearward bearing temp hh with alarm at 90 degc & trip at 95 degc with 2 out of 3
logic.
21 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 22 of 125
22 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 23 of 125
6. SAF B stopped
23 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 24 of 125
24 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 25 of 125
25 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 26 of 125
26 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 27 of 125
1. MFT
2. Mill motor lube oil pump all stop or lube oil pre LL i.e. < 0.05 mpa with delay of 5 sec.
3. Mill reducer lube oil conditions not available with alarm at 70 deg c & trip at 80 deg c &
delay of 2 sec.
4. Mill low pre oil pumps all all.
5. Mill bearing lube oil pressure ll i.e. <0.08 mpa with delay of 5sec
6. Mill pul coal pipeout temp hh stop i.e. With 2 out of 4 logic & alarm at 90 deg c, trip at 100
degc.
7. Mill discharge valve closed with 3 out of 4 logic.
8. Mill main bearing temp hh with alarm at 55 deg c, trip at 60 degc.
9. Mill motor bearing temp hh with alarm at 75 deg c, trip at 85 degc.
10. All paf stopped
11. Mill layer fire lost
12. Mill motor coil temp hh with 3 out of 6 logic, alarm at 135 deg c & trip at 145 deg c.
13. Feedeer trip to mill trip
1. Mill a outlet temp is suitable with 2 out of 4 logic & temp <50 deg c
2. Coal feeder A1 outlet no blockage
3. Coal feeder A1 inlet mov opened
4. Coal feeder A1 outlet mov opened
27 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 28 of 125
9. Mill a outlet temp is suitable with 2 out of 4 logic & temp <50 deg c
10. Coal feeder A2 outlet no blockage
11. Coal feeder A2 inlet mov opened
12. Coal feeder A2 outlet mov opened
13. Coal feeder A2 inner temp normal
14. Mill a running
15. Set coal feeder A2 speed minimum i.e. <15 rpm
16. Coal feeder A2 not tripped
1. MFT
2. Coal feeder A1 outlet blockage with delay of 5 sec.
3. Mill a stopped
4. MFT
5. Coal feeder A2 outlet blockage with delay of 5 sec
6. Mill a stopped
28 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 29 of 125
MAIN MOTOR
1. APH A guide & support brg temp not high i.e. <70 deg c
1. flue gas in air preheater a inlet temp not high i.e. <120 deg c
2. IDF A stopped
3. FDF A stopped
4. PAF A stopped
AUX MOTOR
1. APH A guide & support brg temp not high i.e. <70 deg c
1. flue gas in air preheater a inlet temp not high i.e. <120 deg c
2. IDF A stopped
3. FDF A stopped
4. PAF A stopped
Put in interlock & APH A main motor tripped with delay of 100sec
1. APH A guide & support brg temp not high & not bad i.e. <70 deg c
29 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 30 of 125
1. APH A main motor running & all (13a,13b,13c,13d,13e) flue gas damper inlet APH A opened,
sequential check of 30sec
1. ID FAN-A STOPPED with delay of 600sec or IDF A LUBE OIL STATION PRE LOW & LOP-B
RUNNING with delay of 5sec
1. INTERLOCK PERMISSIVE
a. IDF A LUBE OIL STATION LEVEL NOT LOW INTERLOCK PERMISSIVE & OPERATOR PUT
IN
b. INTERLOCK PUT IN &IDF A LUBE OIL STATION PRE LOW with delay of 2sec
2. & INTERLOCK PUT IN & IDF-A LOP-A RUNNING with delay of 2sec
3. IDF-A LOP-A NOT RUNNING
30 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 31 of 125
1. ID FAN-A STOPPED with delay of 600sec or IDF A LUBE OIL STATION PRE LOW & LOP-B
RUNNING with delay of 5sec
1. INTERLOCK PERMISSIVE
a. IDF A LUBE OIL STATION LEVEL NOT LOW INTERLOCK PERMISSIVE & OPERATOR
PUT IN
b. INTERLOCK PUT IN &IDF A LUBE OIL STATION PRE LOW with delay of 2sec&
INTERLOCK PUT IN & IDF-A LOP-A RUNNING with delay of 2sec
2. IDF-A LOP-A NOT RUNNING
31 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 32 of 125
1. ID FAN-A STOPPED with delay of 600sec or IDF B LUBE OIL STATION PRE LOW & LOP-B
RUNNING with delay of 5sec
1. INTERLOCK PERMISSIVE
a. IDF B LUBE OIL STATION LEVEL NOT LOW INTERLOCK PERMISSIVE & OPERATOR
PUT IN
b. INTERLOCK PUT IN &IDF B LUBE OIL STATION PRE LOW with delay of 2sec
2. & INTERLOCK PUT IN & IDF-A LOP-A RUNNING with delay of 2sec
3. IDF-A LOP-A NOT RUNNING
1. ID FAN-A STOPPED with delay of 600sec or IDF B LUBE OIL STATION PRE LOW & LOP-B
RUNNING with delay of 5sec
1. INTERLOCK PERMISSIVE
a. IDF B LUBE OIL STATION LEVEL NOT LOW INTERLOCK PERMISSIVE &
OPERATOR PUT IN
b. INTERLOCK PUT IN &IDF B LUBE OIL STATION PRE LOW with delay of 2sec&
INTERLOCK PUT IN & IDF-A LOP-A RUNNING with delay of 2sec
2. IDF-A LOP-A NOT RUNNING
32 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 33 of 125
1. FD FAN-A STOPPED with delay of 600sec or FDF A LUBE OIL STATION PRE LOW & LOP-B
RUNNING with delay of 5sec.
33 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 34 of 125
1. INTERLOCK PERMISSIVE
a. FDF A LUBE OIL STATION LEVEL NOT LOW i.e.>400mm
b. INTERLOCK PERMISSIVE & OPERATOR PUT IN
2. INTERLOCK PUT IN &FDF A LUBE OIL STATION PRE LOW i.e.<1 Mpa & delay of 3sec
&INTERLOCK PUT IN & FDF-A LOP-B RUNNING with delay of 2sec.
3. FDF-A LOP-B NOT RUNNING
1. FD FAN-A STOPPED with delay of 600sec or FDF A LUBE OIL STATION PRE LOW & LOP-B
RUNNING with delay of 5sec.
1. INTERLOCK PERMISSIVE
c. FDF A LUBE OIL STATION LEVEL NOT LOW i.e.>400mm
d. INTERLOCK PERMISSIVE & OPERATOR PUT IN
2. INTERLOCK PUT IN &FDF A LUBE OIL STATION PRE LOW i.e.<1 Mpa & delay of 3sec
&INTERLOCK PUT IN & FDF-A LOP-B RUNNING with delay of 2sec.
3. FDF-A LOP-B NOT RUNNING
1. FD FAN-B STOPPED with delay of 600sec or fdf b lube oil station pre low & lop-b running
with delay of 5sec.
34 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 35 of 125
1. Interlock permissive
e. Fdf b lube oil station level not low i.e.>400mm
f. Interlock permissive & operator put in
2. Interlock put in &fdf b lube oil station pre low i.e.<1 mpa & delay of 3sec &interlock put
in & fdf-a lop-b running with delay of 2sec.
3. fdf b lop-b not running
1. Fd fan-a stopped with delay of 600sec or fdf b lube oil station pre low & lop-b running
with delay of 5sec.
1. Interlock permissive
g. Fdf b lube oil station level not low i.e.>400mm
h. Interlock permissive & operator put in
2. Interlock put in &fdf b lube oil station pre low i.e.<1 mpa & delay of 3sec &interlock put
in & fdf-a lop-b running with delay of 2sec.
3. fdf a lop-b not running.
35 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 36 of 125
1. Interlock permissive
a. Paf a lube oil station level not low i.e. >500mm
2. Interlock permissive & operator put in following any conditions
a. Interlock put in & oil flow not normal of paf a lub oil with delay of 2sec , alarm at
26lpm & interlock put in & paf-a lop-b running with delay of 3sec.
b. Interlock put in &paf a lube oil station pre low i.e. <0.1 mpa with delay of 3sec &
interlock put in & paf-a lop-b running with delay of 2sec.
c. Or paf-a lop-b not running
1. Interlock permissive
a. PAF A lube oil station level not low i.e. >500mm
2. Interlock permissive & operator put in following any conditions
a. Interlock put in & oil flow not normal of paf a lub oil with delay of 2sec , alarm at
26lpm & interlock put in &PAF-A lop-b running with delay of 3sec.
b. Interlock put in &PAF A lube oil station pre low i.e. <0.1 mpa with delay of 3sec &
interlock put in &PAF-A lop-b running with delay of 2sec.
c. Or PAF-A lop-b not running
36 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 37 of 125
1. Interlock permissive
a. PAF B lube oil station level not low i.e. >500mm
2. Interlock permissive & operator put in following any conditions
a. Interlock put in & oil flow not normal of PAF B lub oil with delay of 2sec , alarm at
26lpm & interlock put in & paf-a lop-b running with delay of 3sec.
b. Interlock put in &PAF B lube oil station pre low i.e. <0.1 mpa with delay of 3sec &
interlock put in & paf-a lop-b running with delay of 2sec.
c. Or paf-a lop-b not running
1. Interlock permissive
a. PAF B lube oil station level not low i.e. >500mm
2. Interlock permissive & operator put in following any conditions
a. Interlock put in & oil flow not normal of PAF B lub oil with delay of 2sec , alarm at
26lpm & interlock put in & paf-a lop-b running with delay of 3sec.
b. Interlock put in &PAF B lube oil station pre low i.e. <0.1 mpa with delay of 3sec &
interlock put in & paf-a lop-b running with delay of 2sec.
c. Or paf-a lop-b not running
37 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 38 of 125
1. Mill a low press oil pump a running & mill a low pres oil pump b running & mill a pres of
supply oil port low with delay of 20sec.
2. Mill a stopped with delay of 120sec.
1. Mill a low press oil pump b running & mill a low pres oil pump b running & mill a pres of
supply oil port low with delay of 20sec.
2. Mill a stopped with delay of 120sec.
38 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 39 of 125
1. Any mill a low pres oil pump a or b running & mill a pres of supply oil port not low i.e. >0.12
mpa.
1. Mill a supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out of 3 logic or both
mill a low pres oil pump a & b not running
1. Any mill a low pres oil pump b or b running & mill a pres of supply oil port not low i.e. >0.12
mpa.
39 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 40 of 125
1. Mill a supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out of 3 logic or both
mill a low pres oil pump b & b not running
1. Mill B low press oil pump a running & Mill B low pres oil pump b running & Mill B pres of
supply oil port low with delay of 20sec.
2. Mill B stopped with delay of 120sec.
40 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 41 of 125
b. Interlock put in & Mill B pres of supply oil port low i.e. <0.12 mpa with delay of 2sec
1. Mill B low press oil pump b running & Mill B low pres oil pump b running & Mill B pres of
supply oil port low with delay of 20sec.
2. Mill B stopped with delay of 120sec.
1. Any Mill B low pres oil pump a or b running & Mill B pres of supply oil port not low i.e. >0.12
mpa.
41 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 42 of 125
1. Mill B supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out of 3 logic or both
Mill B low pres oil pump a & b not running
1. Any Mill B low pres oil pump b or b running & Mill B pres of supply oil port not low i.e. >0.12
mpa.
1. Mill B supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out of 3 logic or both
Mill B low pres oil pump b & b not running
42 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 43 of 125
1. Mill C low press oil pump a running &Mill C low pres oil pump b running &Mill C pres of
supply oil port low with delay of 20sec.
2. Mill C stopped with delay of 120sec.
1. Mill C low press oil pump b running & Mill C low pres oil pump b running & Mill C
pres of supply oil port low with delay of 20sec.
2. Mill C stopped with delay of 120sec.
43 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 44 of 125
1. Any Mill C low pres oil pump a or b running &Mill C pres of supply oil port not low i.e.
>0.12 mpa.
1. Mill C supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out of 3 logic or
both Mill C low pres oil pump a & b not running
1. Any Mill C low pres oil pump b or b running &Mill C pres of supply oil port not low i.e.
>0.12 mpa.
44 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 45 of 125
1. Mill C supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out of 3 logic or
both Mill C low pres oil pump b & b not running
1. Mill D low press oil pump a running & Mill D low pres oil pump b running & Mill D
pres of supply oil port low with delay of 20sec.
2. Mill D stopped with delay of 120sec.
45 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 46 of 125
1. Mill D low press oil pump b running & Mill D low pres oil pump b running &
Mill D pres of supply oil port low with delay of 20sec.
2. Mill D stopped with delay of 120sec.
1. Any Mill D low pres oil pump a or b running &Mill D pres of supply oil port
not low i.e. >0.12 mpa.
46 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 47 of 125
1. Mill D supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out of 3 logic or
both Mill D low pres oil pump a & b not running
1. Any Mill D low pres oil pump b or b running &Mill D pres of supply oil port not low i.e.
>0.12 mpa.
1. Mill D supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out of 3 logic
or both Mill D low pres oil pump b & b not running
47 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 48 of 125
1. Mill E low press oil pump a running & Mill E low pres oil pump b running &
Mill E pres of supply oil port low with delay of 20sec.
2. Mill E stopped with delay of 120sec.
1. Mill E low press oil pump b running & Mill E low pres oil pump b running &
Mill E pres of supply oil port low with delay of 20sec.
2. Mill E stopped with delay of 120sec.
48 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 49 of 125
1. Any Mill E low pres oil pump a or b running &Mill E pres of supply oil port
not low i.e. >0.12 mpa.
1. Mill E supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2 out
of 3 logic or both Mill E low pres oil pump a & b not running
1. Any Mill E low pres oil pump b or b running &Mill E pres of supply oil port
not low i.e. >0.12 mpa.
49 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 50 of 125
1. Mill E supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with 2
out of 3 logic or both Mill E low pres oil pump b & b not running
1. Mill F low press oil pump a running & Mill F low pres oil pump b
running & Mill F pres of supply oil port low with delay of 20sec.
2. Mill F stopped with delay of 120sec.
50 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 51 of 125
1. Mill F low press oil pump b running & Mill F low pres oil pump b
running & Mill F pres of supply oil port low with delay of 20sec.
2. Mill F stopped with delay of 120sec.
1. Any Mill F low pres oil pump a or b running &Mill F pres of supply oil
port not low i.e. >0.12 mpa.
1. Mill F supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa& with
2 out of 3 logic or both Mill F low pres oil pump a & b not running
51 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 52 of 125
1. Any Mill F low pres oil pump b or b running &Mill F pres of supply oil
port not low i.e. >0.12 mpa.
1. Mill F supply oil port pres low low (switch1,2,3) i.e. <0.08 mpa&
with 2 out of 3 logic or both Mill F low pres oil pump b & b not
running
52 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 53 of 125
TURBINE
1. ETS
1. Overspeed trip i.e. >=3300rpm with 2out of 3 logic.
2. Axial shaft hi hi i.e. >=+1.2mm, <=-1.6mm with 2out of 3 logic.
3. Differential expansion hi hi i.e.Hp-ip (>=+11.6 mm, <= - 6.6 mm)lp (>=+30 mm, <= -8 mm)
4. Hp bypass trouble trip i.e. Hp bp vlv pos > 5.10% & actual load <330mw
5. Msv inlet temp lo trip i.e.If main steam temperature is < temperature out of load vs temp
scale and actual load > 158.40 mw, thn ets trip, with value 427(2 out of 3) as per curve for
higher load.
6. Mft trip
7. Generator protection trip
8. Journal brg metal temp hi hi i.e.>110degc &1 out of 4 (forward thrust(t1~t4) or
(backward thrust(t1~t4)
9. Thrust bearing metal temp hi hi i.e.>110degc &1 out of 8(t1~t8)
10. Hp exhaust temp hi hi i.e.>427 deg c with 2 out of 4 logic.
11. Shaft vibration hi hi i.e.> 125mu.m &>>250mu.m ,any 1 brg h & other brg hh
12. Bearing vibration hi hi i.e. > 80mu.m &>>100mu.m, any 1 brg h & other brg hh
13. Manual push button trip
14. Deh trip
15. Vacuum A lo lo trip i.e. <= -76 kpa
16. Vacuum A lo lo alarm i.e. <= -81.3 kpa
17. Hp lp bypass trouble trip i.e.If actual load > 330 mw and hp bypass position < 5% and any lp
bypass(a or b) position > 50 %, then ets trip.
18. Vacuum B lo lo trip i.e. <= -76 kpa
19. Vacuum B lo lo alarm i.e. <= -81.3 kpa
20. Eh oil press lo lo trip i.e <= 7.8 mpa
21. Lube oil press lo lo trip i.e.<= 70 kpa
22. Lp-A exhaust cyl temp hi hi i.e.>= 107 deg c
23. Lp-B exhaust cyl temp hi hii.e.>= 107 deg c
METS – A/B
53 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 54 of 125
1. TSI Overspeed protection tripping condition initiated by 2 out of 3 logic with setpoint
>=5958rpm/min delay of 1 sec
2. Axial displacement High High tripping initiated by 1 out of 2 logic with
setpoint>=±0.07mm delay of 1sec
3. Shaft Vibration high High 1 out of 2 logic with setpoint (Any vibration high and other
than any high high ) High – 120mu.m
High High – 125mu.m
4. Bearing vibration high high 1 out of 2 logic with setpoint – high high >=70mu.m
5. Feedwater pump main protection trip initiated when BFP Trip
6. Thrust bearing return oil temperature high high initiated 1 out of 2 logic with delay 1
sec >=75Deg C
7. Front bearing return oil temperature high high initiated 1 out of 2 logic with delay of 1
sec >=75Deg C
8. Rear bearing return oil temperature high high initiated 1 out of 2 logic with delay of 1
sec >=75Deg C
9. Thrust bearing temperature high high initiated 1 out of 2 logic with delay 1 sec
>=95Deg C
10. Radial bearing temperature high high initiated 1 out of 2 logic with delay 1 sec
>=90Deg C
11. MEH Trip initiated during any condition trip
12. Eh oil Pressure low low trip initiated 2 out of 3 with delay 1 sec (9Mpa)
13. Vacuum Pressure low low trip initiated 2 out of 3 with delay 1 sec
(-60Kpa)
14. Lube oil Pressure low low trip initiated 2 out of 3 with delay 1 sec (0.3Mpa)
15. Emergency trip will be initiated by soft push button from Scada
4.FEEDWATER SYSTEM
TDBFP- A
54 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 55 of 125
1. Temp OF T-BFP-A outer thrust brass HH with temp of >120 ° &delay of 1 sec.
2. T-BFP inlet press low with pressure < 1.25 Mpa & delay of 30sec.
3. T-BFP-A free end radial bearing temp HH with temp of >100 ° &delay of 1 sec.
4. Temp of T-BFP-A inner thrust brass HH with temp of >120 ° &delay of 1 sec.
5. T-BFP-A outlet flow LLwith flow <350 tph & delay of 2 sec,and recirculation vlv <60% or
behind vlv closed& final delay of 10sec.
6. Deaerator water level LL with 2 out of 3 logic and level low low <<1050mm & delay of 10sec
7. T-BFP- A stopped
8. MFT
9. T-BFP-A driving end radial bearing temp HH with temp of >100 ° &delay of 1 sec.
TDBFP- B
1. Temp OF T-BFP-B outer thrust brass HH with temp of >120 ° & delay of 1 sec.
2. T-BFP inlet press low with pressure < 1.25 Mpa & delay of 30sec.
3. T-BFP-B free end radial bearing temp HH with temp of >100 ° & delay of 1 sec.
55 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 56 of 125
4. Temp of T-BFP-B inner thrust brass HH with temp of >120 ° & delay of 1 sec.
5. T-BFP-A outlet flow LL with flow <350 tph & delay of 2 sec, and recirculation vlv <60% or
behind vlv closed & final delay of 10sec.
6. Deaerator water level LL with 2 out of 3 logic and level low low <<1050mm & delay of 10sec
7. T-BFP- B stopped
8. MFT
9. T-BFP-A driving end radial bearing temp HH with temp of >100 ° & delay of 1 sec.
MDBFP
4.5 START PERMISSIVE
1. Mdbfp wdg temp nt high i.e. < 120 deg c with 1 out of 6 logic.
2. Shaft vib of mdbfp driving end x y nt high i.e. < 80𝛍m with 1 out of 2 logic.
3. Shaft vib of mdbfp free end x y nt high i.e. < 80𝛍m with 1 out of 2 logic.
4. Mdbfp liq coupling brg tem 1-10 nt high i.e. < 85 deg c with 1 out of 10 logic.
5. Mdbfp driving end rad brg temp nt high i.e. < 90 deg c with 1 out of 1 logic.
6. Mdbfp inner thrust brass temp nt high i.e. < 110 deg c with 1 out of 1 logic.
7. Mtr coupler & rad brg temp nt high i.e. < 75 deg c with 1 out of 1 logic.
8. Mdbfp free end rad brg temp nt high i.e. < 90 deg c with 1 out of 1 logic.
9. Mdbfp outer thrust brass temp nt high i.e. < 110 deg c with 1 out of 1 logic.
10. Mdbfp driving end rad brg temp nt high i.e. < 90 deg c with 1 out of 1 logic.
11. Mdbfp bp rnd rad brg temp nt high i.e. < 75 deg c with 1 out of 1 logic.
12. Temp of wrkng oil clr oil i/l nt high i.e. < 110 deg c with 1 out of 1 logic.
13. Temp of wrkng oil clr oil o/l nt high i.e. < 75 deg c with 1 out of 1 logic.
14. Temp of lub oil clr oil i/l nt high i.e. < 75 deg c with 1 out of 1 logic.
15. Temp of lub oil clr oil o/l nt high i.e. < 75 deg c with 1 out of 1 logic.
16. Mdbfp bp free end rad brg temp nt high i.e. < 90 deg c with 1 out of 1 logic.
17. Mdbfp a ele gate vlv opnd
18. Dea wtr lvl nt low i.e. < 2350mm with 1 out of 3 logic.
19. Mdbfp aux oil pmp mtr rung & hyd couplr hdr lub oil pre high i.e. >0.17 mpa
20. No mdbfp spd rvrse alarm
21. Mdbfp min flw cntrl vlv pos>95% & ele vlv beh mdbfp min flw device opn
22. Md vlv of pipe frm confd del pmp to hp wtr sply cls
23. Mdbfp intrlck cut in or mdbfp outlet ele gate vlv clsed
24. Mdbfp intrlock cut in or mdbfp hyd scoop tube set point <10%
25. Mdbfp nt trip frst out
26. Mdbfp temp & sv permit
27. Mdbfp remote posn
28. Mdbfp no elec fault
29. Mdbfp no trip lockout pos
56 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 57 of 125
TRIPPING CONDITIONS
1. M-BFP winding temperature hh i.e. >130 deg c with any both temp & delay of 2sec.
2. M-BFBP free end radial bearing temperature HH HH i.e. >100 Deg C with 1 out 1 logic &
delay of 2sec.
3. M-BFBP driving end radial bearing temperature HH i.e. >100 Deg C with 1 out 1 logic & delay
of 2sec.
4. Motor BFBP end radial bearing temperature HH i.e. >90 Deg C with 1 out 1 logic & delay of
2sec.
5. Motor Coupler end radial bearing temperature HH i.e. >90 Deg C with 1 out 1 logic & delay
of 2sec.
6. Temperature of hydraulic Coupler bearing 1-10 HH i.e. >85 Deg C with 1 out 10 logic & delay
of 2sec.
7. Temperature of M-BFP driving end radial bearing temperature i.e. >90 Deg C with 1 out 1
logic & delay of 2sec.
8. Temperature of M-BFP Inter Thrust brass temperature HH i.e. >100 Deg C with 1 out 1 logic
& delay of 2sec.
9. Temperature of M-BFP free end radial bearing temperature HH i.e. >100 Deg C with 1 out 1
logic & delay of 2sec.
10. Temperature of M-BFP Outer Thrust brass temperature HH i.e. >120 Deg C with 1 out 1 logic
& delay of 2sec.
11. Temperature of working oil cooler inlet temp HH i.e. >130 deg C and outlet temp HH i.e. >80
Deg C with delay of 2sec.
12. Temperature of lubricating oil cooler inlet temp HH i.e. >70 deg C and outlet temp HH i.e.
>60 Deg C with delay of 2sec.
13. M-BFP inlet valve closed
14. M-BFP running with set delay of 30sec and Pressure of M-BFP inlet LL i.e. <1.25 Mpa with on
time delay of 30sec.
15. Flow of M-BFP inlet water LL i.e. <350 Tph & M-BFP min flow RCV Pos<60% or Electric Vlv
behind M-BFP RCV Closed with 2 out of 3 logic & delay of 10sec.
16. Shaft Vibration of M-BFP driven end X Y HH with 2 out of for high & 1 out of 4 for HH, &
High>80µm & HH >120 µm WITH DELAY OF 1SEC
17. Hydraulic Coupler header lubricating pressure L & LL I.E.<0.08 Mpa with delay of 1sec.
18. Deaerator level LL i.e. <1050 mm with 2 out of 3 logic & delay of 2sec.
19. GEN in NET & MFT with 2 out of 3 logic & delay of 1 sec.
57 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 58 of 125
CEP A
CEP B
58 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 59 of 125
5.4START PERMISSIVE
CWP A
59 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 60 of 125
CWP B
6.4START PERMISSIVE
60 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 61 of 125
CCCWP-A
61 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 62 of 125
7.1START PERMISSIVE
CCCWP-B
7.1START PERMISSIVE
62 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 63 of 125
OCCWP-B
63 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 64 of 125
64 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 65 of 125
1. Winding temp of vac pmp A not h with alarm 120 deg c, any phase or both
2. Bearing temp of vac pmp A not hwith alarm 70 deg c, with 1 out of 2 logic.
3. Vac pmp A inlet pneumatic vlv closed & not open
4. Vac pmp A not trip
5. Steam wtr seperator a lvl not low i.e. >200mm.
1. Vac pmp A motor bearing temp 1 hh i.e. <80 degc with 1 out of 1 logic and delay of 2sec
2. Vac pmp A motor stator cold temp 1 hh i.e. <130 degc with any phase both temp and delay
of 2sec
65 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 66 of 125
3. Vac pmp A motor bearing temp 2 hh i.e. <80 degc with 1 out of 1 logic and delay of 2sec
VACUUM PUMP B
1. Winding temp of vac pmp B not h with alarm 120 deg c, any phase or both
2. Bearing temp of vac pmp B not hwith alarm 70 deg c, with 1 out of 2 logic.
3. Vac pmp B inlet pneumatic vlv closed & not open
4. Vac pmp B not trip
5. Steam wtr seperator a lvl not low i.e. >200mm.
66 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 67 of 125
1. Vac pmp B motor bearing temp 1 hh i.e. <80 degc with 1 out of 1 logic and
delay of 2sec
2. Vac pmp B motor stator cold temp 1 hh i.e. <130 degc with any phase both
temp and delay of 2sec
3. Vac pmp B motor bearing temp 2 hh i.e. <80 degc with 1 out of 1 logic and
delay of 2sec
VACUUM PUMP C
1. Winding temp of vac pmp C not h with alarm 120 deg c, any phase or both
2. Bearing temp of vac pmp C not hwith alarm 70 deg c, with 1 out of 2 logic.
3. Vac pmp C inlet pneumatic vlv closed & not open
4. Vac pmp C not trip
5. Steam wtr seperator a lvl not low i.e. >200mm.
67 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 68 of 125
1. Vac pmp C motor bearing temp 1 hh i.e. <80 degc with 1 out of 1 logic and delay
of 2sec
2. Vac pmp C motor stator cold temp 1 hh i.e. <130 degc with any phase both temp
and delay of 2sec
3. Vac pmp C motor bearing temp 2 hh i.e. <80 degc with 1 out of 1 logic and delay
of 2sec
1. GEN STATOR COOL WAT TANK LVL NOT LOW, Normal Press -68.6 Kpa.
1. Interlock permissive:operator put in & gen stator cool wat tank lvl not low
2. Interlock on & following any conditions:
a. Gen stator cool wat tank lvl low ,Normal operating level-100 mm with 1 out of 1
logic & delay of 1sec
b. Gen stator cool wat i/l flow low & not bad,i.e. <1274 mm with 1 out of 1 logic &
delay of 2sec
c. Gen stator cp - b stopped with delay of 1sec.
68 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 69 of 125
10.4START PERMISSIVE
1. GEN STATOR COOL WAT TANK LVL NOT LOW, Normal Press -68.6 Kpa.
10.6AUTO START
1. Interlock permissive: operator put in & gen stator cool wat tank lvl not low
2. Interlock on & following any conditions:
3. Gen stator cool wat tank lvl low ,Normal operating level-100 mm with 1 out of 1
logic & delay of 1sec
4. Gen stator cool wat i/l flow low & not bad,i.e. <1274 mm with 1 out of 1 logic &
delay of 2sec
5. Gen stator cp - A stopped with delay of 1sec.
AC PUMP A& B
1. Gen vacuum oil tank lvl not low withNormal operating level-45 mm
1. Interlock permissive
a. Operator put in & gen vacuum oil tank lvl not low with normal operating level-45 mm.
2. Interlock on & following any conditions
69 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 70 of 125
DC PUMP
1. Interlock permissive
a. Operator put in & start permit always enable
2. Interlock on & following any conditions
a. Ac seal oil pump a not running & ac seal oil pump b not running with delay of 2sec
b. Gen seal oil-gas dp low i.e.<65 kpa 7 delay of 5sec.
c. Gen seal oil pmp outlet header pres low & not bad i.e.<0.8 kpa & delay of 5sec.
1. Interlock permissive
a. Operator put in & start permit always enable
2. Interlock on & following conditions
a. Vapor extractor pump b not running with osp 2.
1. Gen vacuum oil tank lvl high i.e.>620mm with delay of 1sec.
70 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 71 of 125
EH OIL PUMP A
12.1 START PERMISSIVE
1. Interlock permissive
a. Eh oil tank temp not low i.e.>18 degC
b. Eh oil tank level not low i.e.>300mm
2. Interlock on & following any conditions
a. Eh oil pmp b not running with osp 2
b. Eh oil press low with osp 2
1. EH oil tank level LL alarm i.e. <130mm with 1out of q logic & delay of 1sec.
EH OIL PUMP B
12.4 START PERMISSIVE
71 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 72 of 125
1. Interlock permissive
a. EH oil tank temp not low i.e.>18 degC
b. EH oil tank level not low i.e.>300mm
2. Interlock on & following any conditions
c. EH oil pmp B not running with osp 2
d. EH oil press low with osp 2
1. EH oil tank level LL alarm i.e. <130mm with 1out of 1 logic & delay of 1sec.
1. EH oil tank level ll alarm i.e. <130 mm with 1out of 1 logic & delay of 1sec.
Auto start conditions are as follows:operator put in & start permit always enable
1. Interlock on & pres low i.e.<0.07 mpa of main oil pump inlet(msp)& delay 2sec
72 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 73 of 125
2. Turbine trip
3. Turbine speed low low< 2850 rpm & not bad
1. Main oil pump inlet press not low (msp) i.e. >0.07 mpa
2. Ac startup lube oil not running
3. Turbine speed hi hi i.e. >2850 rpm not bad & main oil pump inlet press not low(msp) i.e.
>0.07 mpa
1. Turbine trip
2. Main Oil Pump Oultet press low (TOP) i.e. <1.205 Mpa
3. Bearing lube oil press low (TOP) i.e. < 0.115 Mpa
4. Turbine speed low low< 2850 rpm & NOT BAD
1. Top not running & turbine speed low low< 2850 rpm & not bad with delay of 2 sec.
73 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 74 of 125
AC JOP-A
13.6 START PERMISSIVE
1. Jacking oil pump a inlet press not low i.e. >0.07 mpa
Interlock permissive: jacking oil pump a inlet press not low i.e. >0.07 mpa, & remaining any condition
1. Following conditions with operator put in & interlock &speed low i.e.<2000 rpm & not bad &
choice of start - selection high
2. Following conditions with operator put in & choice of start selection not high & speed low
i.e.<2000 rpm & not bad & jacking oil pump b not running with total delay of 2 sec.
3. Following conditions with operator put in & interlock & jacking oil pump b running & jacking
oil pump b outlet press low i.e. <7kpa & speed low i.e.<2000rpm & not bad
4. Following conditions with operator put in & interlock & jac&king oil pump b not running &
speed low i.e. <2000rpm & not bad
1. Jacking oil pump a inlet press low i.e. <0.07 mpa with delay of 5 sec.
AC JOP-B
74 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 75 of 125
1. Jacking oil pump a inlet press not low i.e. >0.07 mpa
Interlock permissive: jacking oil pump a inlet press not low i.e. >0.07 mpa, & remaining any condition
1. Following conditions with operator put in & interlock &speed low i.e.<2000 rpm & not
bad & choice of start - selection high
2. Following conditions with operator put in & choice of start selection not high & speed
low i.e.<2000 rpm & not bad & jacking oil pump b not running with total delay of 2 sec.
3. Following conditions with operator put in & interlock & jacking oil pump b running &
jacking oil pump b outlet press low i.e. <7kpa & speed low i.e.<2000rpm & not bad
4. Following conditions with operator put in & interlock & jac&king oil pump b not running
& speed low i.e. <2000rpm & not bad
1. Jacking oil pump B inlet press low i.e. <0.07 mpa with delay of 5 sec.
DC JOP
1. DC jacking oil pump inlet press not low i.e. >0.07 mpa
75 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 76 of 125
1. Jacking oil pump a running & jacking oil pump b not running&jacking oil pump a outlet press
low i.e. < 7mpa &speed low i.e. <2000 rpm & not bad with delay of 5sec.
2. Jacking oil pump b running & jacking oil pump a not running&jacking oil pump b outlet press
low i.e. < 7mpa &speed low i.e. <2000 rpm & not badwith delay of 5sec.
3. Jacking oil pump a running & jacking oil pump b running&speed low i.e. <2000 rpm& not bad
with delay of 3sec.
4. Jacking oil pump a not running & jacking oil pump b not running&speed low & not bad i.e.
<2000 rpm with delay of 3sec.
1. Turbine speed hi i.e. >2050 rpm ¬ bad with delay of >2050rpm.
13.17PROTECTION STOP
TDBFP-A
76 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 77 of 125
DC LOP
TDBFP-B
77 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 78 of 125
DC LOP
MDBFP AOP
14.9 AUTO START
1. Mdbfp running & hydraulic coupler lubricating pres low i.e. <0.15 mpa & osp 2.
2. Mdbfp not running with osp 2.
78 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 79 of 125
1. Mdbfp running & hydraulic coupler lubricating pres not lowi.e. <0.15 mpa &hydraulic
coupler lubricating pres not low i.e. >0.3 mpa with total delay of 30sec.
DM PLANT
1. Raw water A Basin Level High ≥ 3 meter & Pump in Auto & Discharge valve in
Auto
1.2 Auto Stop
1. Raw water A Basin Level Low ≤ 1.7 meter & Pump in Auto &Discharge valve in
Auto
2. Raw Water Pump B
2.1 Auto Start
1 . Raw water B Basin Level High ≥ 3 meter & Pump in Auto & Discharge valve in
Auto
1. Raw water B Basin Level Low ≤ 1.7 meter & Pump in Auto &Discharge valve in
Auto
3. Raw Water Pump C
3.1 Auto Start
1. Raw water C Basin Level High ≥ 3 meter & Pump in Auto & Discharge valve in
Auto
79 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 80 of 125
1. Raw water C Basin Level Low ≤ 1.7 meter & Pump in Auto &Discharge valve in
Auto
1. Raw water D Basin Level High ≥ 3 meter & Pump in Auto & Discharge valve in
Auto
4.2 Auto Stop
1. Raw water D Basin Level Low ≤ 1.7 meter & Pump in Auto &Discharge valve in
Auto
80 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 81 of 125
8. Hydrant Pump #1
8.1 Manual Start Permissive
81 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 82 of 125
9. Hydrant Pump #2
9.1 Manual Start Permissive
1. Auto Select
2. MCC Healthy
82 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 83 of 125
1. Auto Select
2. MCC Healthy
3. Breaker Not Trip
4. Spray Pump Not Trip
5. Breaker Not Closed
6. Emergency PB Not Operated
7. Pressure < 8.5 kg/cm2
10.3 Manual Stop Permissive
83 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 84 of 125
1. Manual Select
1. Auto Select
2. MCC Healthy
3. Breaker Not Trip
4. Jockey Pump Not Trip
5. Breaker Not Closed
6. Emergency PB Not Operated
7. Pressure <11.5 kg/cm2
8. Hydrant Pump #1 Not Running
9. Hydrant Pump #2 Not Running
10. Spray Pump Not Running
11. Diesel Hydrant Pump #1 Not Running
84 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 85 of 125
85 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 86 of 125
1. Auto Select
2. MCC Healthy
3. Breaker Not Trip
4. Jockey Pump Not Trip
5. Breaker Not Closed
6. Emergency PB Not Operated
7. Pressure <10.5 kg/cm2
8. Hydrant Pump #1 Not Running
9. Hydrant Pump #2 Not Running
10. Spray Pump Not Running
11. Diesel Hydrant Pump #1 Not Running
12. Diesel Hydrant Pump #2 Not Running
13. Diesel Spray Pump Not Running
12.3 Auto Stop Permissive
86 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 87 of 125
13. VT Pump 1
13.1 Tripping Condition
14. VT Pump 2
14.1 Tripping Condition
15. VT Pump 3
15.1 Tripping Condition
87 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 88 of 125
19. VT pump on for 260 sec and discharge valve close feedback.
20. Transformer 1 winding temp high and breaker close.
21. Transformer 2 winding temp high and breaker close.
22. Transformer 1 BUCHHOLZ relay trip.
23. Transformer 2 BUCHHOLZ relay trip.
24. Motor winding temp high (2 out of 6) alarm at 110 deg and 130 deg.
25. Pump DE bearing temp high, alarm at 75 deg and trip at 85 deg.
26. Pump NDE bearing temp high, alarm at 75 deg and trip at 85 deg.
27. Pump discharge pressure high (1.8 bar)
CRUSHER :
Pre Condition:
88 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 89 of 125
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 50sec
4. Emergency Stop not pressed
5. Safety Permissives is healthy
Stop Permissive
Protection Stop
Interlock Stop
ROLLER SCREEN - A
Pre Condition:
Start Permissive
89 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 90 of 125
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 50sec
4. Emergency Stop not pressed
5. Crusher-A should be in running condition
6. Check whether the flap gate Position either in buffer drum or crusher
Protection Stop
Interlock Stop
ROLLER SCREEN - B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 50sec
4. Emergency Stop not pressed
5. Crusher-B should be in running condition
6. Check whether the flap gate Position either in buffer drum or crusher
Protection Stop
Interlock Stop
90 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 91 of 125
ROLLER SCREEN - C
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 50sec
4. Emergency Stop not pressed
5. Crusher-C should be in running condition
6. Check whether the flap gate Position either in buffer drum or crusher
Protection Stop
Interlock Stop
CONVEYOR - 1A
Pre Condition:
91 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 92 of 125
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Flap Gate-A should be in proper condition
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal condition
Stop Permissive
1. Selected in local
2. Flap Gate -1A position should be in Proper with delay in 3sec
Protection Stop
Interlock Stop
CONVEYOR – 1B
Pre Condition:
Start Permissive
1. No Feeder Fault
92 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 93 of 125
Stop Permissive
1. Selected in local
2. Flap Gate -1B position should be in Proper with delay in 3sec
Protection Stop
Interlock Stop
CONVEYOR – 1C
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Flap Gate-1C should be in proper condition
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal condition
93 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 94 of 125
Stop Permissive
1. Selected in local
2. Flap Gate -1C position should be in Proper with delay in 3sec
Protection Stop
Interlock Stop
CONVEYOR – 1D
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Flap Gate-D should be in proper condition
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal condition
Stop Permissive
1. Selected in local
2. Flap Gate -1D position should be in Proper with delay in 3sec
Protection Stop
94 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 95 of 125
Interlock Stop
CONVEYOR – 2A
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal condition
Stop Permissive
1. Selected in local
Protection Stop
95 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 96 of 125
Interlock Stop
CONVEYOR – 2B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
CONVEYOR – 3A
Pre Condition:
96 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 97 of 125
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition
8. Flap Gate 3A position should be in proper
9. Hanging type Magnetic Separator(HTMS) in
interlock/Uninterlock
Stop Permissive
1. Selected in local
2. Flap Gate -3A position should be in proper delay on 3sec
Protection Stop
Interlock Stop
CONVEYOR – 3B
Pre Condition:
97 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 98 of 125
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition
8. Flap Gate 3B position should be in proper
9. Hanging type Magnetic Separator(HTMS) in
interlock/Uninterlock
Stop Permissive
1. Selected in local
2. Flap Gate -3B position should be in proper delay on 3sec
Protection Stop
Interlock Stop
CONVEYOR – 4A
Pre Condition:
98 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 99 of 125
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition
8. Flap Gate 4A position should be in proper
Stop Permissive
1. Selected in local
2. Flap Gate -4A position should be in proper delay on
3sec
Protection Stop
Interlock Stop
CONVEYOR – 4B
Pre Condition:
99 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 100 of 125
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal condition
8. Flap Gate 4B position should be in proper
Stop Permissive
1. Selected in local
2. Flap Gate -4B position should be in proper delay on 3sec
Protection Stop
Interlock Stop
CONVEYOR – 5A
Pre Condition:
Start Permissive
100 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 101 of 125
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal condition
8. Flap Gate 5A position should be in proper
Stop Permissive
1. Selected in local
2. Flap Gate -5A position should be in proper delay on 3sec
Protection Stop
Interlock Stop
CONVEYOR – 5B
Pre Condition:
Start Permissive
1. No Feeder Fault
101 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 102 of 125
Stop Permissive
1. Selected in local
2. Flap Gate -5B position should be in proper delay on 3sec
Protection Stop
Interlock Stop
CONVEYOR – 6A
Pre Condition:
Start Permissive
102 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 103 of 125
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
CONVEYOR – 6B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Breaker Selected in remote
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
103 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 104 of 125
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
CONVEYOR – 7A
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
8. FG-7A position should be in proper.
Stop Permissive
1. Selected in local
2. FG-7A position should be in proper delay on 3sec
104 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 105 of 125
Protection Stop
Interlock Stop
CONVEYOR – 7B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
8. FG-7B position should be in proper.
Stop Permissive
1. Selected in local
2. FG-7B position should be in proper delay on 3sec
Protection Stop
105 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 106 of 125
Interlock Stop
CONVEYOR – 7C
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
8. FG-7C position should be in proper.
Stop Permissive
1. Selected in local
2. FG-7C position should be in proper delay on 3sec
Protection Stop
Interlock Stop
CONVEYOR – 8A
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
107 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 108 of 125
CONVEYOR – 8B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be
started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
CONVEYOR – 9A
Pre Condition:
108 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 109 of 125
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
CONVEYOR – 9B
Pre Condition:
Start Permissive
1. No Feeder Fault
109 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 110 of 125
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
CONVEYOR – 10A
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
110 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 111 of 125
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
CONVEYOR – 10B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be
started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
Stop Permissive
111 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 112 of 125
1. Selected in local
Protection Stop
Interlock Stop
CONVEYOR – 11A
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be
started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in
normal condition.
Stop Permissive
1. Selected in local
Protection Stop
112 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 113 of 125
Interlock Stop
CONVEYOR – 11B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be
started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
Stop Permissive
1. Selected in local
Protection Stop
Interlock Stop
113 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 114 of 125
CONVEYOR – 12A
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
8. FG-12A Position should be in proper.
9. HTMS in interlock/uninterlock.
Stop Permissive
1. Selected in local
2. FG-12A position should be in proper Delay On 3 Sec.
Protection Stop
Interlock Stop
114 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 115 of 125
CONVEYOR – 12B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Feeder selected in remote.
3. Start Permissive from PLC Delay on 3sec
4. Emergency Stop not pressed
5. Temperature switch acts>137 Deg C
6. Safety Permissives is healthy (Hooter Should be started)
7. All PCS,BSS,ZSS,Chute Block Switch should be in normal
condition.
8. FG-12B Position should be in proper.
9. HTMS in interlock/uninterlock.
Stop Permissive
1. Selected in local
2. FG-12B position should be in proper delay on 3 sec .
Protection Stop
Interlock Stop
115 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 116 of 125
ILMS – 1A
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Emergency Stop not pressed
3. BCN – 1A should be in running condition delay on 50 sec.
Stop Permissive
Interlock Stop
ILMS – 1B
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Emergency Stop not pressed
3. BCN – 1B should be in running condition delay on 50 sec.
116 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 117 of 125
Stop Permissive
Interlock Stop
ILMS – 1C
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Emergency Stop not pressed
3. BCN – 1C should be in running condition delay on 50 sec.
Stop Permissive
Interlock Stop
117 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 118 of 125
ILMS – 1D
Pre Condition:
Start Permissive
1. No Feeder Fault
2. Emergency Stop not pressed
3. BCN – 1D should be in running condition delay on 50 sec.
Stop Permissive
Interlock Stop
FLAP GATE
Total Number of Flapper Gate -16 Nos. Following are the interlock condition for all 16Nos of
Flap Gate – 1A,1B,1C,1D,3A,3B,4A,4B,5A,5B,7A,7B,7C,12A,12B,STACKER-A,STACKER-B
Pre Condition:
118 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 119 of 125
Start Permissive
1. No Feeder Fault
2. Emergency Stop not pressed
3. Local Panel selected in remote/Local Mode
4. For Flap gate Motor reverse on required forward limit switch
5. For Flap gate Motor reverse on required reverse limit switch
6. No limit switch is coming, Flap Gate is operated both
side(operation required)
Stop Permissive
1. Selected in local
2. Emergency Push Button not operated.
Interlock Stop
METAL DETECTOR
Following are the interlock condition for all 4Nos of Metal Detector
Pre Condition:
Interlock Stop
119 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 120 of 125
Pre Condition:
Start Permit
SUMP PUMP
Start Permit
1. No feeder fault
2. To operate in local pumpmust be selected in local
mode
3. To operate pump in auto pump must be selected
in auto mode
120 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 121 of 125
Stop Permit
1. Selected in local
2. Pumps will stop for level lower than low level
3. Stop Button pressed in any mode.
Interlock Stop
PADDLE FEEDER
Start Permit
Common Fault
Long Travel
Interlock Stop
121 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 122 of 125
WAGON TIPPLER
Start Permissive
1. No feeder fault
2. Breaker selected in remote
3. Start Permissive from PMCC
4. EPB not pressed
5. Safety permissives is healthy(Hooter should be
started)
6. System is checked and found in normal operation
7. PLC Hardware/Software is normal
8. Local Emergency PB operation normal
9. Control desk PB operation normal
10. PLC is energized
11. All PLC and safety permissives are ok
12. VFD is healthy condition
13. Photocell feedback is working properly
14. Lean sensor/limit switch working properly
15. Pressure switch working properly
16. End limit switch working properly
17. CAM switch working properly
18. Entry/Exit sensor is healthy
Stop permissive
122 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 123 of 125
Interlock Stop
Pre Condition
Start Permit
Stop Permit
Protection Stop
123 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 124 of 125
Pre Condition
124 Rev.0
TALWANDI SABO POWER LIMITED
3 x 660MW POWER PLANT, MANSA.
Page 125 of 125
125 Rev.0