Pfisterer Non Ceramic Insulators PI EN
Pfisterer Non Ceramic Insulators PI EN
www.pfisterer.com
Non Ceramic Insulators
2 NCI-15B www.pfisterer.com
Facts & Figures
1957 1997
Foundation of PFISTERER “Schweizerische Supply of 525 kV insulator sets and spacer dampers
Elektrotechnische Fabrik AG” for South America
1959 1998
Component manufacturing for PFISTERER’s product Supply of the 1st generation of non ceramic horizontal
portfolio Vee configuration for the world’s first 420 kV compact
line in Switzerland
1965
Development and manufacturing of components for 1999
T&D for the Swiss energy market Introduction of polymeric arrester and railway insulator
production with Silicone Rubber HTV-technology
1975
Design and manufacture of the first hollow core 2000
non ceramic insulator Non ceramic insulators for 400 kV HVDC transmission
line of PPC in Greece
1979
First installation of railway non ceramic insulators in 2007
the Swiss Lötschberg Tunnel Supply of 3rd generation of 420 kV horizontal Vee to
DEWA in Dubai
1986
Installation of the first non ceramic insulators in the 2008
Swiss Transmission Network Supply of post insulators for 800 kV HVDC Project
Yunnan/Guangdong in China
1987
Line hardware department including design and 2009
engineering services established Supply of 500 kV HVDC insulators to Fingrid
1988 2010
Design and manufacture of PFISTERER’s insulator Supply of complete insulator sets for TenneT’s 420 kV
set and line hardware program started compact line Windtrack in the Netherlands
1989 2012
Supply of 420 kV insulator sets and spacer dampers Supply of complete insulator sets for Energinet’s 420 kV
for Middle East compact line in Denmark
1990 2013
Supply of 420 kV non ceramic insulators for Successful testing of a 420 kV diamond string
NOK Switzerland configuration of the National Grid in UK
1993 2014
Complete service available for vibration issues including Supply of complete non ceramic insulator sets to
damper and recorder supply, field measurements and ESKOM's 765 kV transmission lines
analytical investigations
1995
Design and supply of components for 220 kV double
circuit line including tubular poles
www.pfisterer.com NCI-15B 3
Technical Facts
Corona shed as an innovative solution
The patented corona shed solution combines
Housing
experiences of casting and overmoulding:
The primary sealing system is silicone gel, proven
Rod
through decades of use
Embedded fitting reduces the electrical field stress
HTV - Corona shed
The conical shape reduces the electric field stress in
RTV/
HTV* HTV* HTV*
LSR**
* using high pressure injection moulding ** using low pressure injection moulding
4 NCI-15B www.pfisterer.com
Transmission Insulators
Catalog Numbering System
A B – C D – E F G – H I J – K L
Insulator Type SML Rating [klb] Ground End Fitting Line End Fitting Section Length (in)* Leakage Distance (in)* Corona Ring
Type Type
Ground Line
S = Socket S = Socket
* Section length and leakage distance must be indicated with three digits and rounded.
www.pfisterer.com NCI-15B 5
Transmission Insulators 25klb
Ball (B) Oval Eye (E) Tongue (T) Clevis (C) Socket (S) Y-Clevis (Y)
Y-Clevis (Y)
+0 [+0] +1.77 [+45] +0.59 [+15] +0.59 [+15] +0.51 [+13] +1.26 [+32]
YB YE YT YC YS YY
Socket (S)
-0.75 [-19] +1.02 [+26] -0.16 [-4] -0.16 [-4] -0.24 [-6] +0.51 [+13]
SB SE ST SC SS SY
Clevis (C)
-0.67 [-17] +1.1 [+28] -0.08 [-2] -0.08 [-2] -0.16 [-4] +0.59 [+15]
CB CE CT CC CS CY
Tongue (T)
-0.67 [-17] +1.1 [+28] -0.08 [-2] -0.08 [-2] -0.16 [-4] +0.59 [+15]
TB TE TT TC TS TY
Ball (B)
-1.26 [-32] +0.51 [+13] -0.67 [-17] -0.67 [-17] -0.75 [-19] +0 [+0]
BB BE BT BC BS BY
6 NCI-15B www.pfisterer.com
Typical Line Voltage (kV) Catalog No. Section Arcing Leakage Electrical Flashover (kV) Weight
Length* Distance Distance 60 Hz CIFO
69 115 138 161 230 345 500 in in in Dry Wet Pos Neg Ibs kg
* All section lengths are based on Y-Clevis & Ball end fittings
Electrical data shown for insulators without corona rings. PFISTERER recommends corona rings to be installed at 138kV and above.
Additional section lengths and leakage distances are available. Contact Victor-PFISTERER sales agent for details.
www.pfisterer.com NCI-15B 7
Transmission Insulators 30klb
Ball (B) Oval Eye (E) Tongue (T) Clevis (C) Socket (S) Y-Clevis (Y)
Y-Clevis (Y)
+0 [+0] +1.77 [+45] +0.59 [+15] +0.59 [+15] +0.51 [+13] +1.26 [+32]
YB YE YT YC YS YY
Socket (S)
-0.75 [-19] +1.02 [+26] -0.16 [-4] -0.16 [-4] -0.24 [-6] +0.51 [+13]
SB SE ST SC SS SY
Clevis (C)
-0.67 [-17] +1.1 [+28] -0.08 [-2] -0.08 [-2] -0.16 [-4] +0.59 [+15]
CB CE CT CC CS CY
Tongue (T)
-0.67 [-17] +1.1 [+28] -0.08 [-2] -0.08 [-2] -0.16 [-4] +0.59 [+15]
TB TE TT TC TS TY
Ball (B)
-1.26 [-32] +0.51 [+13] -0.67 [-17] -0.67 [-17] -0.75 [-19] +0 [+0]
BB BE BT BC BS BY
8 NCI-15B www.pfisterer.com
Typical Line Voltage (kV) Catalog No. Section Arcing Leakage Electrical Flashover (kV) Weight
Length* Distance Distance 60 Hz CIFO
69 115 138 161 230 345 500 in in in Dry Wet Pos Neg Ibs kg
* All section lengths are based on Y-Clevis & Ball end fittings
Electrical data shown for insulators without corona rings. PFISTERER recommends corona rings to be installed at 138kV and above.
Additional section lengths and leakage distances are available. Contact Victor-PFISTERER sales agent for details.
www.pfisterer.com NCI-15B 9
Transmission Insulators 50klb
Ball (B) Oval Eye (E) Tongue (T) Clevis (C) Socket (S) Y-Clevis (Y)
Y-Clevis (Y)
+0 [+0] +1.97 [+50] +0.39 [+10] +0.39 [+10] +0.79 [+20] +1.18 [+30]
YB YE YT YC YS YY
Socket (S)
-0.39 [-10] +1.57 [+40] +0 [+0] +0 [+0] +0.39 [+10] +0.79 [+20]
SB SE ST SC SS SY
Clevis (C)
-0.79 [-20] +1.18 [+30] -0.39 [-10] -0.39 [-10] +0 [+0] +0.39 [+10]
CB CE CT CC CS CY
Tongue (T)
-0.79 [-20] +1.18 [+30] -0.39 [-10] -0.39 [-10] +0 [+0] +0.39 [+10]
TB TE TT TC TS TY
Ball (B)
-1.18 [-30] +0.79 [+20] -0.79 [-20] -0.79 [-20] -0.39 [-10] +0 [+0]
BB BE BT BC BS BY
10 NCI-15B www.pfisterer.com
Typical Line Voltage (kV) Catalog No. Section Arcing Leakage Electrical Flashover (kV) Weight
Length* Distance Distance 60 Hz CIFO
69 115 138 161 230 345 500 in in in Dry Wet Pos Neg Ibs kg
* All section lengths are based on Y-Clevis & Ball end fittings
Electrical data shown for insulators without corona rings. PFISTERER recommends corona rings to be installed at 138kV and above.
Additional section lengths and leakage distances are available. Contact Victor-PFISTERER sales agent for details.
www.pfisterer.com NCI-15B 11
Transmission Insulators 100klb
EB EE ES
Socket (S)
-1.77 [-45] +0.39 [+10] -1.38 [-35]
SB SE SS
Ball (B)
-2.17 [-55] +0 [+0] -1.77 [-45]
BB BE BS
12 NCI-15B www.pfisterer.com
Typical Line Voltage (kV) Catalog No. Section Arcing Leakage Electrical Flashover (kV) Weight
Length* Distance Distance 60 Hz CIFO
230 345 500 in in in Dry Wet Pos Neg Ibs kg
* All section lengths are based on Oval Eye & Ball end fittings
Electrical data shown for insulators without corona rings. PFISTERER recommends corona rings to be installed at 230kV and above.
Additional section lengths and leakage distances are available. Contact Victor-PFISTERER sales agent for details.
www.pfisterer.com NCI-15B 13
Line Post Insulators
Catalog Number System
A – B C D – E F G – H I J – K L
Insulator Type Rod Diameter (in) Ground End Fitting Type Line End Fitting Type Section Length (in)* Leakage Distance (in)* Corona Ring
HP = Horizontal Post 1 = 2.5" Rod A = Cast Curved 12° A = Two Round Hole Tongue X = None
VP = Vertical Post B = Cast Flat 12° B = Standard Drop Tongue A = Dia. 12"
C = Gain Base 12°, 12" Spacing C = Extended Drop Eye B = Dia. 15"
G = Flange Base
H = Stud Base/Vertical
* Section length and leakage distance must be indicated with three digits and rounded.
14 NCI-15B www.pfisterer.com
Typical Line Voltage (kV) Catalog No. Section Arcing Leakage Electrical Flashover (kV) Weight
Length* Distance Distance 60 Hz CIFO
69 115 138 161 230 345 in in in Dry Wet Pos Neg Ibs kg
* All section lengths are based on standard bendable gain base & drop tongue end fittings.
Electrical data shown for insulators without corona rings and mounted horizontally.
PFISTERER recommends corona rings to be installed at 230kV and above.
Various section lengths and leakage distances are available. Contact Victor-PFISTERER sales agent for details.
Corona Rings
Transmission Insulator
When corona rings are used, the arcing distance must be adjusted –
see specific insulator drawing for details.
www.pfisterer.com NCI-15B 15
PFISTERER SEFAG AG
EN 042 394 510 I 01/2016 © PFISTERER SEFAG AG, 2015 We accept no liability for printing errors / Subject to technical modifications
Werkstrasse 7
6102 Malters, Luzern
Switzerland
Phone +41 41 499 72 72
Fax +41 41 497 22 69
E-Mail [email protected]
www.pfisterer.com