Air Terminal Devices - Instalation Manual
Air Terminal Devices - Instalation Manual
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn
Germany
Phone: +49 (0) 2845 2020
Air terminal devices +49 (0) 2845 202-265
E-mail: [email protected]
http://www.troxtechnik.com
Ceiling diffusers
Product overview
A00000054447, 05/2017, © 2016 TROX GmbH
Specialist personnel
Specialist personnel are individuals who have suffi-
cient professional or technical training, knowledge
and actual experience to enable them to carry out Protective gloves protect hands from friction, abra-
their assigned duties, understand any potential haz- sions, punctures, deep cuts, and direct contact with
ards related to the work under consideration, and hot surfaces.
recognise and avoid any risks involved.
Safety shoes
Limitation of liability
The information in this manual has been compiled
with reference to the applicable standards and
guidelines, the state of the art, and our expertise
and experience of many years.
The manufacturer does not accept any liability for
damages resulting from: Safety shoes protect the feet against crushing,
falling parts, and slipping on slippery ground.
Non-compliance with this manual
Incorrect use Correct use
Operation or handling by untrained individuals Air terminal devices are used for the ventilation of
Unauthorised modifications rooms in industrial and comfort areas. The air ter-
minal devices are connected to a supply air or
The actual scope of delivery may differ from the extract air system (by others), which is typically
information in this manual for special constructions, connected to an air handling unit.
additional order options or as a result of recent
technical changes.
Air terminal devices supply cold or warm air to If the device has to be moved:
rooms (within the stated supply air to room air tem-
perature differences). Be careful when unloading or moving the
product, and pay attention to the symbols and
Installation, operation and maintenance may have information on the packaging.
to meet increased hygiene requirements for certain If possible, take the device in its transport
areas of application. packaging up to the installation location.
The installation of air terminal devices in humid Use only lifting and transport gear designed for
rooms, areas with potentially explosive atmos- the required load.
pheres or rooms with dust-laden or aggressive air Always secure the load against tipping and
has to be assessed for each individual case. falling.
Transport and storage Do not move bulky items just by yourself. Get
help to prevent injuries and damage.
Delivery check
Upon delivery, carefully remove the packaging and Storage
check the unit for transport damage and complete- Please note:
ness. In case of any damage or an incomplete ship-
ment, contact the shipping company and your sup- Store the unit only in its original packaging
plier immediately. Put the product back into its Protect the unit from the effects of weather
packaging after the delivery check to protect it from Protect the unit from humidity, dust and con-
dust and contamination. tamination
Storage temperature: –10 to 50 °C
Fixing and installation material Relative humidity: 95 % max., non-condensing
Transport on site
CAUTION!
Installation notes:
Fix the device only to load-bearing structural
elements.
Load suspension systems only with the weight
of the device. Adjacent components and con-
necting ducts must be supported separately.
Use only approved and adequately sized fixing
material (fixing material is not included in the
supply package).
Refer to the technical leaflets for product
weights and dimensions.
The diffusers must remain accessible for
cleaning even after installation.
Installation and sealing material which the
manufacturer provides is usually supplied in an
extra bag. Fig. 2: Plenum box (square/circular)
Before you install the device, take suitable precau- 1. Fix the suspension parts such as ropes,
tions to protect air distribution components from cables or metal hangers (Fig. 2/1) to the
contamination during installation (VDI 6022). If this ceiling.
is not possible, at least cover the devices or take
other precautions to protect them from contamina- 2. Use all of the available suspension points on
tion. In this case you have to ensure that the the plenum box.
devices cannot be activated. Ensure that the com-
ponents are clean before you install them. If neces-
sary, thoroughly clean them. If you have to interrupt
the installation procedure, protect all openings from
the ingress of dust or moisture.
Installation types
Electrical connection
Personnel:
Skilled qualified electrician
DANGER!
Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous
electrical voltage.
– Only skilled qualified electricians are allowed to work on the electrical system.
– Switch off the power supply before working on any electrical equipment.
Order Type Supply voltage Max. Control input Wiring diagram Diffuser
code power signal type
rating
E1 NM230A 85 – 265 V AC, 6 VA 1-wire control or 2- Fig. 10, Fig. 11, VD, VDL,
50/60 Hz wire control (3- Fig. 12 VDR, DUK
point)
E2 NM24A 24 V AC ±20%, 50/60 4 VA 1-wire control or 2- Fig. 10, Fig. 11, VD, VDL,
Hz wire control (3- Fig. 12 VDR, DUK
1.5 W point)
24 V DC ±20%
Modulating actuators
Ceiling diffusers, variant -MN - volume flow rate 4. If necessary, adjust the damper blade posi-
measurement tion with the cords.
Ceiling diffusers with universal plenum box, damper
blade and pressure tap (variant -MN) allow for Volume flow rate calculation
volume flow rate balancing even with the diffuser
face in place.