HT Panel Specification
HT Panel Specification
2 Busbar /Busduct
2.1 Busbar current rating A 1250A
2.2 Busbar short time current rating for 3 sec kA 18.4
2.3 Material of busbar Copper
2.4 Busbar insulated Yes/No Yes
Rated continuos current at 50°C (As per site
2.5 condition) A 630
2.6 Minimum distance between
2.7 ~Phase to phase mm As per IS
2.8 ~Phase to earth mm As per IS
3 Circuit breaker
3.1 Type VCB
3.2 Rating A 1250
3.3 Rated short withstand current (3 sec) kA 18.4
3.4 Arcing quenching medium Vaccum
3.5 Aux contact of breaker
3.6 ~Number (NO/NC) No 6
3.7 ~Voltage V 415
3.8 Antipumping feature provided Yes/No Yes
4 Current Transformer
Manufacturer Precise/Newtech/ECS/Pragati
Type Epoxy Resin Cast
4.1 ICOG
a) For metering
Ratio A 200/1 A
Class 1.0
Burden VA 15
b) For feeder protection
Ratio A 100/1A
Class 5P20
Burden VA 15
c) Special Class
Ratio A 175/1A
Class PS
Knee point voltage (Vk)
Magnetising current at Vk/2
Rct: secondary winding resistance at 75°C
5 Voltage transformer
Manufacturer Precise/Newtech/ECS/Pragati
Type Epoxy Resin Cast
Voltage ratio
~Primary kV 33/√3
~Secondary-1 V 110/√3
~Secondary-2 V 110/√3
Accuracy class for secondary-1 0.5
Accuracy class for secondary-2 3P
VA burden for secondary-1 VA 100
VA burden for secondary-1 VA 100
a) Feeder protection
Functions 50, 51, 50N, 51N, 94, 95 provided Yes/No Yes
Communication protocol RS485