FT-BS EN-F-0604b Intubatt 3 Slab Edge Horizontal Seal

This document provides installation instructions for using INTUBATT 3 to seal a perimeter slab around a concrete block/brick wall with a 150mm concrete floor. The void is 200mm wide with unlimited length and joints over 200mm require Z-clips inserted at 400mm centers. When installed correctly, INTUBATT 3 provides up to 240 minutes of fire resistance for integrity and 120 minutes for insulation, as well as an acoustic rating of 51dB.

Uploaded by

Tung Thanh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
229 views1 page

FT-BS EN-F-0604b Intubatt 3 Slab Edge Horizontal Seal

This document provides installation instructions for using INTUBATT 3 to seal a perimeter slab around a concrete block/brick wall with a 150mm concrete floor. The void is 200mm wide with unlimited length and joints over 200mm require Z-clips inserted at 400mm centers. When installed correctly, INTUBATT 3 provides up to 240 minutes of fire resistance for integrity and 120 minutes for insulation, as well as an acoustic rating of 51dB.

Uploaded by

Tung Thanh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Test: BS 476

Products: INTUBATT 3
Scenario: Perimeter slab seal
Penetrations: N/A
Construction: Nominal 150mm Concrete floor to
concrete block/brick work wall.
Where flexible curtain wall panels
are installed mechanical fixing
(Z-clips) are required to voids
above 50mm in accordance with
ADB.
Void Size: 200mm wide, unlimited length
joints exceeding 200mm install z
clip supports at 400mm centres

Movement: N/A
INSTALLATION INSTRUCTIONS
Fire Resistance: Up to 240 Integrity
CONCRETE FLOOR/FIRE
1. ENSURE WITHIN APERTURE IS CLEAN AND FREE OF Up to 120 Insulation
RATED SUBSTRATE
DEBRIS, LOOSE CEMENT, AND REMOVE ALL DUST
Acoustic: Assessed at 51dB
FROM SURFACES REQUIRING INSTALLATION.

2. CUT 100MM THICKNESS FIRETHERM INTUBATT 3 TO DETAILS CONTAINED HEREIN ARE SUITABLE FOR
THE REQUIRED SIZE, ENSURING THE MINERAL FIBRE FIRETHERM PRODUCTS ONLY
IS OVER SIZE BY A MINIMUM OF 5% COMPRESSION. INTUMASTIC IF DETAILS ARE USED FOR ANY OTHER PURPOSE
LEGAL PROCEEDINGS WILL BE FOLLOWED
3. FIT THE INTUBATT 3 IN TO THE VOID/SLAB EDGE. IF Z
CLIPS ARE REQUIRED ENSURE THESE ARE INSERTED
IN TO THE INTUBATT 3 PRIOR TO INSTALL, AS PER Z
CLIP FIXING REQUIREMENTS.
INTUBATT 3
4. APPLY INTUMASTIC TO ALL ABUTMENTS. FIRETHERM
UK
Contact: [email protected]
Client

Job Title

Drawing Title

3 hour Intubatt 3 Slab Edge and


The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from
Horizontal Seal
the instructions in any way will remove Firetherm from any design liability. Firetherm will accept no responsibility for the consequences of
using Firetherm products in applications or for the purposes not authorised by Firetherm. Expert advice should be sought where such Scale Date
applications are contemplated.
The Information contained within this drawing is believed to be correct on the date of publication, and is based upon tested and certified
solutions. The policy of Firetherm is one of constant improvement. Installers must therefore ensure that they are following the latest
NTS January 2014
published drawings and instructions. Whilst Firetherm will endeavour to keep its publications up to date, the accuracy of the information Sheet Size Drawn By
contained within this drawing may be affected by pertinent changes in the law or regulatory requirements and alterations or amendments to
the specification of Firetherm products. A3
Drawing Number Rev
Firetherm Technical Support: [email protected] FT-BS EN-F-0604b 1.0