Silencer Selection Instructions
Silencer Selection Instructions
SELECTION
INSTRUCTIONS
7 Silencer construction
1 Insertion Loss
Required 2 Maximum Allowable
Pressure Drop
EACH DUCT SYSTEM needs to be analyzed separately. DETERMINE how much silencer pressure drop (including
All possible sound sources and paths should be system effects) has been allowed for in the system
considered. Common paths often forgotten include duct design. Ordinarily, the silencer pressure drop (including
break-out noise and equipment noise radiated to the system effects) should not exceed 0.35” (85 Pa).1
environment through intake or exhaust louvers.
The user should always consider the added losses
It is critical that the duct system analysis begin at the due to aerodynamic system effects. That is, if the
initial sound source and continue in order, duct element silencer is located where less than ideal conditions at
by element, to the occupied space. This will ensure that the inlet and/or at the discharge of the silencer exist,
the noise level can be calculated at any point along the then the silencer’s effective pressure drop will be
system to help determine if break-out noise and/or airflow increased. (Total silencer PD = silencer PD per catalog
generated noise need to be controlled (see below). ASTM E-477-13 rating + system effect losses). In some
situations the added system effect losses can exceed
The octave band sound power levels of the noise the pressure drop of the silencer.
generating elements are summed logarithmically
(e.g. main fan or AHU, terminal boxes and airflow Figure: Effect of Silencer Location on
generated noise of ductwork, fittings, terminal devices, Pressure Drop Performance
etc.). The natural attenuation elements, such as
ductwork, plenums and fittings, etc. are subtracted. 5A
1
ASHRAE Applications Handbook, 2015, P. 48.18.
2
ASHRAE Applications Handbook, 2015, P. 48.3
THE FOLLOWING are guidelines To determine the allowable silencer catalog pressure drop for
to estimate increased pressure selection and specification purposes:
losses due to varying silencer inlet
and discharge conditions. These Allowable Catalog Silencer PD =
should be considered only as very
approximate guidelines. Substantial Total Allowable Silencer Pressure Drop including System Effects
variations can occur depending
upon the type of silencer, its internal (Inlet System Effect Factor x Outlet System Effect Factor)
geometry, size of silencer, size of
duct, airflow turbulence, etc.
Vibro-Acoustics’ V-A Select program allows the user to evaluate
Note: the factors shown do NOT include
system effects when selecting silencers. See the V-A Select Manual
pressure drops of the duct element. These must for more information.
be added separately.
Transitions D D
1
D is the diameter of round duct or equivalent diameter of rectangular duct.
no turning vanes
Centrifugal fan
D D
silencer on fan)
1
D is the diameter of round duct or equivalent diameter of rectangular duct.
Coils or filters D D
SEE DIAGRAM
1 Inlet Cone Silencer 2 Splitters designed 3 Blunt, untapered 4 Although unlikely 5 Discharge Cone 6 Blunt, untapered
must be aerodynamically so turbulent wake is splitters with either in practice, this was Silencers must be splitters do not allow
matched to fan gone before reaching radius or sharp edged chosen as the reference matched to fan pressure/velocity recovery
hub, otherwise H.P. plane of the fan blades, tails, create excess configuration. motor hub, or fan before dumping air to the
consumed increases for lowest fan noise. turbulence & fan noise H.P. can be well in room causing excessive,
considerably to 105% - from turbulence. excess of 100%! abrupt expansion
110% or more! pressure losses.
General Notes: A. If a fan consumes less horsepower, it generates less noise and therefore needs less silencing.
B. Turbulence allowed to impinge upon the plane of the axial fan blades can create 10-15 dB or more excess fan sound power.
3 Silencer
Location
Considerations for
Silencer Location
SILENCERS SHOULD generally be located as close to BEST SILENCER LOCATION IF NO FIRE DAMPER
the fan or noise source as possible. This will help contain
the noise at the source and limit potential points along
the system where the unsilenced noise may break out.
However, turbulent airflow usually exists close to noise
sources such as fans, valves, dampers, etc. Therefore
SILENCER
the user should evaluate aerodynamic system effects
(see above).
FD SILENCER
IN THE MAJORITY OF INSTALLATIONS, a concern ONCE THE ABOVE STEPS HAVE BEEN FOLLOWED,
for silencer airflow generated noise is generally DETERMINE:
unwarranted because it does not materially contribute to >> Silencer shape (Rectangular or Circular dependent on
the overall system noise level. This is particularly true if the connection shape of the ductwork).
the silencer is properly located close to the source and
pressure drops are not excessive. >> Silencer type
>> Dissipative (RD and CD): Uses acoustic grade glass
ASHRAE1 recommends that in general, airflow generated fiber protected by perforated metal.
noise should be evaluated if silencer static pressure >> Film-Faced (RFL and CFL): Dissipative type with
drops exceed 0.35” (including system effects), the noise film such as Tedlar or Mylar lining between the
criterion is below RC-35(N), or if the silencer is located perforatedmetal and the acoustical glass fiber. An
very close to or in the occupied space. acoustical spacer is used between the perforated
metal and the liner to reduce insertion loss
To roughly calculate the maximum allowable silencer degradations caused by the film liner.
generated noise when the silencer is located very close
to or in the occupied space: Subtract 5dB per octave >> No-Media (RNM, CNM and CENM): Completely void
from the room sound criterion spectrum. of absorptive media or fill of any kind.
6 Select
Silencer
COMPARE THE ACTUAL INSERTION LOSS required Vibro-Acoustics’ model numbers also include a
spectrum with the insertion loss spectrum shapes for frequency indicator (e.g. AC1, AC2, etc.). The lower the
different silencer sizes and pressure drops available “AC” numeric the better the silencer performs in the low
(see Performance Data Section or use the V-A Select or frequency range. The higher the number the better it
Quick Pick Computer Programs). Select the silencer that performs at the mid and high frequency ranges.
best fits the insertion loss required and does not exceed
the maximum allowable silencer pressure drop and Normally, the selection of a silencer is limited by the
generated noise. space available and allowable pressure drop. It should
be recognized that for a given silencer, the pressure
Ensure that the silencer length selected fits within the drop will increase as the square of the duct velocity.
allowable space and does not affect the aerodynamic Thus, at lower system velocities, more insertion loss can
system effects calculated in step 2 above. be achieved at acceptable pressure drops. In higher
velocity systems, longer silencer lengths with larger air
As a guideline, Vibro-Acoustics’ silencer model numbers passage ways may be required to maintain acceptable
include a duct velocity range indicator (i.e., ULV, LV, MV, pressure drops and achieve the required insertion loss.
HV or UHV). This can be used to narrow the multiple
silencer options: Vibro-Acoustics’ V-A Select computer program can be
used to efficiently select a silencer from the parameters
determined in steps 1 through 4 above.
CNM see LV 0-750 fpm 750-1250 fpm 1250-2000 fpm 2000-3500 fpm
Note: Silencers can always be used in systems with lower velocities than the recommended operating range.
However, more silencer length may be required to achieve the required insertion loss.