C 4 Ffa
C 4 Ffa
SCBA
1200ltrs of air or 30min service duration of air
EEBD
10 minutes service duration
PORTABLE FIRE EXTINGUISHERS
Powder or CO2 – 5kgs
Foam – 9 Ltrs capacity
Total Weight Maximum 23 kgs each.
Portable foam applicator liquid 20Ltrs + 20 Ltrs spare
Nozzle capacity 1.5 cu.m / min
FIXED FIRE FIGHTING SYSTEM
Pre Discharge ALARM to sound for at least 20sec or for the time required to evacuate space
before medium is released.
CO2 SYSTEM
30% of largest cargo space
35% of largest machinery space
85% of gas to be discharged into the machinery space within the 2 minutes
EMERGENCY FIRE PUMPS
Capacity 40% of total capacity of required Fire Pumps
But not less than
25 cu.m per hour for Passenger Ships
15 cu.m per hour for Cargo Ships
Consecutive starts for diesel engine driven Emg Fire Pumps
6 in 30 minutes
2 in first 10 minutes
Fuel in service tank for 3 hrs full load and outside machinery space of category A for 15 hrs full
load operation of the Emg Fire Pump.
Onboard maintenance and inspections should be carried out in accordance with the ship’s maintenance plan. Certain
maintenance procedures and inspections may be performed by competent crew members who have completed an advanced
fire-fighting training course, while others should be performed by persons specially trained in the maintenance of such
systems. The on board maintenance plan should indicate which parts of the recommended inspections and maintenance are
to be completed by trained personnel.
Inspections should be carried out by the crew to ensure that the indicated weekly, monthly, quarterly, annual, two-year,
five-year and ten-year actions are taken for the specified equipment, if provided. Records of the inspections should be
carried on board the ship, and may be computer-based. In cases where the inspections and maintenance tasks are carried
out by trained service technicians other than the ship’s crew, inspection reports should be provided at the completion of
the testing and retained. In addition to the onboard maintenance and inspections stated in these Guidelines, manufacturer’s
maintenance and inspection guidelines should be followed.
The fire detection and alarm systems, fire doors, low location lighting, and sprinkler systems should be functional and
should be operated by lamp or indicator switch.
The working of fixed gas fire-extinguishing systems must be verified by the correct positions of control and sectional
valves.
The breathing apparatus should be in the correct pressure range.
2. Monthly Testing and Inspections:
Equipment like fire mains, pumps, hoses, nozzles, and fire hydrants should be properly arranged and be in good
condition.
Fixed gas fire extinguisher system and foam fire extinguishing systems should be closed and in proper position and their
pressure gauges should be in the proper range and free from leakages.
Firefighters outfits and the inventory must be well equipped and in good condition.
3. Quarterly Testing and Inspections:
Fixed gas fire extinguisher systems should be weighed to confirm that the contents are above 95% of the nominal charge
or containers must be refilled.
Fixed dry chemical powder systems must be inspected by a service agent.
6. Five-year Testing and Inspections:
Fixed gas fire extinguishing system, foam fire extinguishing systems and water sprinklers should be inspected for the
functioning control valves.
It should supply freshwater and that should be tested too.
Breathing apparatus should be tested and replaced.
7. Ten-year Testing and Inspections:
Fixed aerosol extinguishing systems must be tested and renewed in accordance with the manufacturer.
Fixed dry chemical powder systems should be tested by an accredited service agent.
It is thus necessary for fire protection systems to be serviced and examined as part of their maintenance from time to
time. This has also been stated in the guidelines provided by IMO.
Fire-fighting appliance providers and repairers like SHM Shipcare provide fire-fighting appliance maintenance
services that involve efficient testing and maintenance of the fire-fighting equipment.
Trained personnel, skilled at examining and servicing fire-fighting equipment perform an inspection of portable and
non-portable fire extinguishers, breathing apparatus, foam applicators, compressor air quality test, and foam
concentrate analysis.
The firefighting system and fire extinguisher types on board ships can be classified into three
category –
Class A: These types of fire extinguishers are used in fires which are a result of the burning of
wood, glass fibre, upholstery, and furnishing. Usually, Water, DCP and Foam fire extinguishers
smother the Class A fire by removing the heating factor of the fire triangle. Foam agents also
help in separating the oxygen part from the other aspects.
Class B: These fire extinguishers are used for fires which occur from fluids such as lubricating
oils, fuels, paints, cooking oil etc. A portable co2 fire extinguisher or a portable dcp extinguisher
can be used in this class.
Class C: Fires resulting from involvement of energized electrical equipment such as motors,
switches, wiring etc are extinguished by Class C type of fire extinguishers. Usually, CO2 or DCP
portable fire extinguisher is used in such fires.
For extinguishing this class of fire, Dry Powder extinguishers are used which is similar to dry
chemical besides they extinguish the fire by isolating the oxygen from the fuel or by eliminating
the heat factor of the fire triangle.
The dry powder extinguishers are only used for class D fires and they cannot be used for other
classification of fire on board ship.
Class E: This type of fire extinguisher on a ship is used for subsiding fire resulting from any of
the above-mentioned materials along with high voltage electricity. Hence, if a portable
extinguisher with a conductive agent is used for fighting the class E fire, it may lead to a risk of
shock to the operator. CO2 or DCP portable fire extinguisher is used in such fires.
The portable type onboard fire extinguisher used in the marine or maritime setup is also known
as plunger type fire extinguishers because of the plunger mechanism used to release the
extinguishing agent. There are five main types of fire extinguishers used on ships:
1. Soda Acid Fire Extinguisher
2. Water Extinguisher
3. Foam Extinguisher – Chemical and Mechanical
4. Carbon Dioxide Extinguisher
5. Dry Powder Extinguisher
Sodium bicarbonate (soda) and sulphuric acid are the prime components of the extinguisher.
They combine to form a chemical reaction to produce carbon dioxide gas, which is used to
smother the fire.
The arrangement of the extinguishers comprises of a container which holds the sodium
bicarbonate solution. A small glass bottle (phial) containing sulphuric acid is placed below a
plunger mechanism, which is covered by a safety glass along with a screw and cap at the top.
When the plunger is struck hard, the glass bottle breaks, resulting in mixing of acid and soda, a
chemical reaction takes place which produces carbon dioxide gas.
The carbon dioxide gas pressurises the space above the liquid (used for extinguishing the fire)
and forces it out through the internal pipe of the nozzle.
Note: As the CO2, which is used in soda acid fire extinguisher, may create a toxic effect in
confined spaces, Soda Acid Extinguishers are now banned on ships.
2. Water Extinguisher
To counter the A-Class fire, portable water type fire extinguisher of 9Ltr are used. The outer
container is filled with water and fitted with a CO2 Cartridge (inner container) which forces the
water out of the container with pressure.
To operate the extinguisher, first, the safety pin/clip is released. When pressure is applied on
the plunger, the CO2 cartridge ruptures and forces the water out of the extinguisher.
Chemical foam extinguisher – The chemicals used in this foam type fire extinguisher are
sodium bicarbonate and aluminium sulphate. The main container is filled with sodium
bicarbonate, whereas the inner container is filled with aluminium sulphate.
The plunger is turned to release the cap and the extinguisher is then inverted for both the
chemicals to mix. Carbon dioxide is produced from the chemical reaction which pressurizes the
container from inside and forces out the foam.
This type of portable foam fire extinguisher chemical equation is shown below:
Note: Chemical Foam Extinguishers are now banned on ships because of the poisonous
effect which the gas can create.
Mechanical foam – This extinguisher type also consists of two containers- the outer one is
filled with water, whereas the central one has carbon dioxide charge and foam solution. The
mechanical foam fire extinguisher uses a long hosepipe connected to the dip tube inside the
internal structure of fire extinguisher which allows it to use the foam portable fire extinguisher
upright.
mechanical foam type fire extinguisher diagram showing different foam extinguisher parts:
The central container has a plunger mechanism at the top which when depressed releases the
carbon dioxide and allows foam and water to mix.
The foam and water come out of the nozzle, creating mechanical foam. This extinguisher is
operated in an upright position.
Related Read: 10 Precautions To Take After Using Fixed Foam Fire Fighting System On Ships
Dry powder extinguisher contains sodium bicarbonate powder in the outer container.
A small container with carbon dioxide is placed beneath the plunger mechanism.
When the plunger is pushed, it releases the carbon dioxide gas, which in turn forces the dry
powder out of the discharge nozzle.
As they are heavier to lift, it is provided with a wheel-trolley arrangement which can be dragged
to a nearby fire location. These can be a semi-portable foam fire extinguisher or semi-portable
DCP type fire extinguisher.
These extinguishers are kept onboard on that location which has a higher risk of fire. E.g. The
semi-portable type fire extinguisher is located near the boiler and incinerator in the engine room
and also in the galley. The galley fire fighting system in a ship may include a small CO2 fixed
firefighting setup apart from the portable galley fire extinguisher.
The portable extinguishers are a type of pressure vessels and should be routinely checked
for leakage etc.
The operating mechanism of the portable fire extinguishers should be regularly checked
(where possible) every 3 months.
The vent holes to be checked for clearance.
All the cap threads should be lightly greased. There are holes provided in the screw on
caps to release any excess pressure. Ensure these holes are clear.
The plunger should be checked for free movement, and any missing or damaged plunger
should be replaced.
Depending upon the types of fire on board ship, the flag state and class requirement
accordingly determines the number, types, and locations of these portable fire fighting
extinguishers as per SOLAS.
The ship’s officer must ensure all the fire fighting equipment, including the fire
extinguishers, are always in the state of readiness. Any problem or defect in the fire
extinguisher to be reported immediately to the master.
Check all the markings on portable fire extinguisher are visible including the inspection
dates.
The recharging of the extinguisher to be done as per the instruction supplied by the
manufacturer only.
For DCP, invert the extinguisher once in a while to ensure the powder inside it is agitated.
Hydraulic tests of all the extinguishers with propellent cartridges to be performed at an
interval, not more than 10 years.
This type of portable fire fighting unit consist of a portable foam tank carrying foam-forming
liquid of at least 20l capacity with foam applicator connected to an inductor type nozzle
designed to be connected to the fire main by a hose. One spare tank of foam making liquid is
also provided.
The nozzle shall be capable of producing the rate of at least 1.5 m3/m of foam for extinguishing
an oil fire,
CTC fire extinguisher: The CTC extinguisher used to be very effective extinguisher for
combating the small fire, However, due to its tendency to emit harmful toxic phosgene gas, it is
no more used on ships. The CTC fire extinguisher full form is – Carbon Tetrachloride fire
extinguisher.
Fires on board ships can be prevented by finding and rectifying leakages of fuel oil, lubricating
oil, and exhaust gases.
In a ship’s generator room, the biggest danger of fire is from a leaky high pressure fuel pipe. Oil
leaking from such pipe can fall on high temperature exhaust manifold or on indicator cocks,
which are sensitive points for catching fire.
In modern marine engines, there is push-type cover concealing the indicator cocks; however in
old engines there is no such provision available which makes it quite difficult to provide lagging
to indicator cocks.
These days fuel high pressure pipes are sheathed and the leakage finds its way to a small tank
at the bottom of the engine known as fuel leak off tank. It is imperative to keep this system in
good order by regularly testing the tank alarm – fuel leak off tank high level alarm.
Leakages are mainly caused because of pipes breaking due to vibrations, clamps rubbing
against pipes to create holes, pipe connections behind the pressure gauges getting damaged
due to ageing (we generally do not look here), leakages from fittings at boiler furnace front and
incinerator front etc. These leakages are some of the most common “hot spots” for fire.
Moreover, careful and periodical checks are also required on boiler smoke side and incinerator
uptake.
Fires can be largely prevented by providing effective laggings to hot surfaces such as
generator turbocharger bellows, main engine exhaust uptakes after the turbocharger, various
steam pipes and pipes carrying hot oil. Laggings can be done by ship staff but these days
specialist contractors are available to carry out this work more aesthetically. Also, whenever
lagging is removed, a habit should be cultivated to put it back after the work is finished.
Apart from this, it is also important to check/test fire detectors on regular basis. Some of the
main types of detectors used on ships are:
Flame detectors
Light produced by a flame has a characteristic flicker frequency of about 25Hz. The spectrum in
the infra red or ultra violet range can be monitored to give an alarm. Oil fires generally do not
give off much smoke and this type of sensor is preferred, especially near fuel handling
equipment or boilers to give an early warning.
Heat detectors
Heat detectors are of various types such as rate of rise type, which has bi-metallic type
detecting elements – a thick strip and a thin strip. The thin strip is more sensitive to temperature
rise than the thicker one. If there is a sudden rise in temperature, the thin one bends faster than
the thicker one, bringing both of them in contact.
During normal temperature rise both strips will deflect about the same amount and thus show no
reaction. Normally if rate of rise is less than 10 deg C in half an hour, the detector will not give
any alarm. If the rate should rise to 75 degree Celsius, or more, the two strips come in contact,
thus triggering the alarm.
Smoke detectors
2) Ionization type Liquid or gas fires may not give off smoke initially but will catch fire
spontaneously. Thus smoke detectors are not effective for such fires. These detectors are
mostly used in accommodation areas.
In engine room, waste bins used for storing oily rags must have lids (covers). Oily rags
should not stay lying around or stuck at unnecessary places. Receptacles with covers
should be provided at each floor and on both sides.
High pressure fuel oil pipes should not be tightened to control a leakage while the engine
is running. Also, oil shouldn’t be taken in to turbochargers during operation.
Short sounding pipes should be kept shut with plugs. Never should they be left in open
position for the sake of convenience. Cases have been reported wherein oil has spilled out
from these short sounding pipes leading to accidents.
Loose pet cocks /small cocks on common rail pipes should be checked for.
Ship’s crew should be careful about galley fires, especially by keeping electrical
equipment in good order. Senior officers should keep an eye in the galley when provision
is being received because this is the time when galley remains unattended for a long time.
One of the patent methods of fire prevention is effective and regular fire patrol. There is no
method that can beat physical monitoring.
Fire caused by cigarettes is still one of the most common causes of fire. All care should be
taken to dispose cigarettes (using self closing ashtrays) and never should one smoke in
bed.
Fires have also caused during loading and unloading of cargo such as coal. For this
reason, ship personnel must always discuss the characteristics of the cargo and
preventive methods to be taken during safety meetings and weekly drills.
Hazards Related to Electric Cable
Insulation in Case of Fire
The insulation of the electric cable is generally made up of rubber or plastic. The amount of
smoke generated by the plastic in case of fire is dependent on factors like nature of plastic, type
of additive used, flame of fire and ventilation arrangement. In general most plastics produce a
very dense smoke when heated. In this article we will learn about the hazards related to electric
cable insulation in case of fire.
Some plastic burns very clearly when subjected to heat and flame, producing very less smoke.
If insulation used is of urethane foam it produces a very dense smoke and visibility in the room
is lost in a minute. Some plastic contains Poly Vinyl Chloride (PVC) which produces hydro
chloride gas as a product of combustion. This is a very deadly gas and has a pungent, irritating
odor.
Rubber when used for insulation produces a dense black, oily smoke and has some toxic
qualities. The most common gases produced during combustion of rubber are hydrogen
sulphide and sulphur dioxide. These gases are both dangerous and can be fatal in certain
cases.
Cables having E.P.R (Ethylene Propylene Rubber) insulation with necessary sheathing of
Polychloroprene or Chloro Sulphonated Polyethylene ( PCP or CSP) may be used to protect the
insulation against fire.
G.i armor may be used to protect insulation from fire and needs to be earthed.
By using cables having high oxygen index number, the number allotted to material depending
on minimum percentage of oxygen required to sustain combustion. If the material used is having
oxygen index number 27, it means that minimum percentage of oxygen required to burn the
material is 27 % which is well above the normal atmospheric oxygen percentage of 21 %. Thus,
the insulation material will not catch fire.
It is noted that the maximum number fires on ships initiates in the ship’s accommodation area
due to negligence of the ship’s staff. The accommodation area of the ship is vulnerable to fire as
it comprises substance such as wood, cardboard, and other personal fire-sensitive things used
by the ship’s crew onboard.
A ship accommodation is an area where the crew member’s cabin is located along with galley,
recreational room, meeting room etc. The best way to avoid incidents of fire on ship is to take
preventive measures than to suffer later.
Do not smoke cigarette sitting or lying on the bed and also, do not keep or throw live
smoking buds in the dust bins.
Try not to use essence stick or candles inside the cabins. If they are used, make sure they
are lit up during your own presence and while your going out of the cabin, are blown off
Never use hot plate or heater for cooking purpose inside the cabin.
Always make sure electrical circuit is never overloaded i.e. too many connection in one
socket.
Do not bring oily rags inside your boiler suit pocket into the cabin.
Never leave iron unattended when ironing clothes in laundry room.
Always make sure all the electrical circuits in accommodation are in sound condition to
avoid short circuit fire.
Chief cook should make sure that galley is always attended when hot plate is on.
If any welding or gas cutting operation is carried out inside accommodation, all the
precaution that are necessary, must be taken.
In tanker ship, accommodation ventilation suction should be away from cargo holds as
their vapour can enter inside the accommodation and create a flammable atmosphere.
All the visitors coming on board when the ship is at port must be briefed about the fire
hazards.
Following are the most common areas covered by water mist system:
Incinerator room
Auxiliary boiler room
Auxiliary generators
Main engine cylinder head platform
Purifier room
Inert gas generator room
Steering gear room
A fresh water pump takes suction from fresh water tank to supply high-pressure water to the
sprinkler system. Each area is isolated by valves, which can be opened during emergency
situations involving fire. The system is kept at constant stage of readiness.
High-pressure water is injected through a special nozzle working within pressure range of 4 to
10 MPa (depending upon the design of the system), which breaks the water droplets into fine
mist. The diameter of the water mist particle range from 50 to 200 µm which improves the fire
extinguishing effect and efficiency of the system. The distance between any two nozzles is very
critical as area covered by one nozzle must be such that no space is left unsprayed in the fire
affected area.
Operating Procedure:
The system start select switch on the main control panel must always be set to AUTO &
MANUAL position for automatic start. (The automatic activation with the fire alarm system is
possible only in this mode.)
Starting:
Automatic Start: Water mist system will be automatically released into the protected area
where fire is detected by the fire alarm system (both smoke and flame detectors), and an
audible and visible alarm is activated in that protected area.
Manual Start: Water mist system can be started manually from the control panel and from the
local points whenever needed, independent of the fire alarm system.
The following conditions must be maintained at all times to ensure hyper mist system is on
stand by for operation:
Stopping:
After confirming extinction of a fire, the water mist system can be stopped manually by
cancelling the signal from the fire alarm system and pressing the STOP button on the control
panel or local point.
However, an emergency can occur any time and therefore it is important that the ship’s crew is
aware of the design and operation of the fixed firefighting system installed on board.
Fixed foam firefighting system non-lethal in nature and can be used even when there are human
present inside the fire affected room/room. This makes the initial time duration for application of
fire fighting system shorter as compared to the CO2 system which requires evacuation of
personnel before operation.
Once the fire is extinguished, the ship’s crew has to make a re-entry in the affected place to
assess the damage to the ship’s equipment.
Following common precautions and procedures need to be considered for all fixed fire fighting
systems installed on ship:
Never enter a place soon after extinguishing of fire, especially pump room, engine room
etc. due to high temperature. Allow time to cool down
Ensure breathing apparatus, explosion proof lights and gas analyzers are present for
making an entry
Once it is confirmed that the fire has extinguished, remove all chances of re-ignition and
ensure the room is cool enough. Exchange air inside the room by using forced air blowers
Keep checking the level of oxygen and other gases when working/ assessing inside the
room
The oxygen analyzer and gas detectors should be of explosion proof type
When entering the room, enter as a team (of 2 people). A stand by team needs to be
ready for evacuation with breathing apparatus (BA) and other safety equipment if
something goes wrong
Following precautions and checks need to carried out once the foam fixed fire fighting system is
used for fire extinguishing purpose:
1. The place will be acquired with plenty of drainage which is a mixture of water and foam.
Use pumps to remove the drain mixture
2. Ensure there are no gases present in the room and pumps are in good working condition
before using as it may lead to secondary accidents such as explosion or electrical shocks
3. Use fresh water mist while cleaning the foam from the room
4. Keep checking the gas content in the room as during cleaning, foam may contain
poisonous gases which was produced during the fire
5. The electric machinery and systems covered with foam should be wiped out using cloth
6. All the machinery to be inspected prior cleaning is finished. If internal electric parts or
panels are still moist, use hot air blow to clean the same
7. After complete use of foam system, drain out foam solution lines and liquid lines by air
blow
8. Check the level of the foam liquid tank and refill it to the required level
9. Check the foam discharge nozzle in the fire area and foam generator for any fire damages
10. Check all the valves involved in the discharging of foam are set to normal ready-to-use
position. If the foam discharged is done manually, set the manual button to normal ready-
to-use position
The above points are required to ensure the affected space is checked and cleaned, and the
machinery in that space is ready for further usage. The foam system needs to be made normal
as soon as possible to ensure it is ready for any other emergency situation in near future.
Note: The above mentioned is not an exhaustive list but mentions all important points for
precautions and checks while using fire fighting system. Do you know any other important point
that should be added to the list? Let’s know in the comments below.
In case of a major engine room fire on merchant ships, CO2 fixed fire extinguishing system is
the most common method used for fire fighting. The chief engineer of the ship is responsible for
operating the CO2 extinguishing system,after taking all precautionary measures regarding
handling of engine room machinery.
There have been several cases in the past, wherein people have lost lives in the engine room
not because of the fire but because of suffocation after CO2 was released in the engine room.
Suffocation of the crew combined with re-ignition of fire due to lack of air tight engine room has
resulted in gruesome condition, as the CO2 system is the last resort for fighting fire and no more
firefighting method is available after using that (CO2 system can be used only once).
The CO2 operator in-charge i.e. Chief engineer (or 2nd engineer in C/E’s absence) has to be
extremely careful when it comes to following procedure to avoid fire from spreading or any
casualty. Following steps are to be followed without fail for extinguishing major find in engine
room.
1. On outbreak of fire, the fire alarm will sound and the bridge officer will know the location of
fire. If the fire is big enough to fight with portable extinguishers, all crew should be gathered in
muster station for a head count.
2. Inform the wheel house about the situation of the fire. The chief engineer should take the
decision in consent with the master to flood the engine room with CO2 for extinguishing the fire.
3. The Emergency generator should be started as CO2 flooding requires all engine room
machinery, including the auxiliary power generator to be stopped.
4. Reduce ship speed and stop the main engine at a safe location. Captain should inform the
nearest coastal authority if the ship is inside a coastal zone.
5. Open the cabinet of the CO2 operating system in the fire station with the “Key” provided
nearby in the glass case. This will give an audible CO2 Alarm in the engine room.
6. Some systems and machinery like engine room blowers and fans etc. will trip with opening of
CO2 cabinet. Counter check all the tripped system for surety.
7. Make sure there is no one left inside the engine room by repeating the head count.
8. Operate all remote closing switches for quick closing valve, funnel flaps, fire flaps, engine
room pumps and machinery, water tight doors etc.
10. Close all the entrance doors of the engine room and make sure the room is air tight.
11. Operate the control and master valve in the CO2 cabinet. This will sound another alarm and
after 60 seconds time delay CO2 will be released for fire extinguishing.
12. If there is a need to enter the engine room for rescuing a person (which must be avoided),
SCBA sets and life lines should be used. Safety of personnel should be of the highest priority
during such incidences.
Graphic Symbol
The graphical symbols used in the fire control plan should be as per fighting equipment symbols
set out in IMO Assembly Resolution A.654(16). It is duty of each and every member of ship’s
crew to know the meaning of the symbols used in this plan.
Language
The fire plan should be available in the working language of the crew on board and also in
English.
At least one copy of the fire control plan shall be available ashore at the offices of the Company.
Copies of the fire control plan must be provided to each of the members of the fire patrol team in
a passenger ship and also posted at each continuously manned central control station.
A copy of Fire Control Plan should be permanently stored in prominently marked weathertight
enclosures outside deckhouse for assistance of shore side fire fighting system in case the ship
is in port or in dry-dock.
Also with the permission of Administration i.e classification society, the details can be set out in
the form of booklet and a copy of it shall be supplied to each officer onboard. One copy of the
same should be available on board and be easily accessible. These plans should be kept up-to-
date and if alterations are made shall be recorded as soon as possible. The fire plan should be
available in the working language of the crew on board and also in English language.
Renewal, update of Fire control plan
It comes under the responsibility of the master, ship owner and ship management team at shore
to ensure that the fire control plan is kept up to date and if alterations are made shall be
recorded as soon as possible.
Following are the cases when renewal or update in the fire control plan is required:
Change in the fire fighting system, alarm system, escape route design or anything related
to current fire plan takes place. The new system or design must be included and approval
should be taken from the classification society
Modification In ship structure or ship particulars which effect the current fire plan must be
added to the new plan with approval of the classification society
In case of revision of statutes related to fire control plan under SOLAS done by IMO or
similar authority, the new fire plan to be provided and the fire fighting system or equipment
must be as per the new revised plan
When change of flag in a ship happens, the assigned classification society must review
the ship fire control plan
During the change of classification society, the fire control plan must be reviewed
Survey Requirement
The Classification society surveyor must ensure that there shall are discrepancies between the
content of the fire control and the record of approved cargo ship (or passenger ship) safety
equipment carried on board. In addition, the various entries in the record should correspond to
the particulars of the equipment carried on board and with the associated service and
maintenance reports and records.
Annual Survey: The fire control plan survey comes under the continuous ship safety equipment
survey (CSSE) which is performed annually.
Renewal Survey: If the CSSE certificate is under renewal period requiring a survey, the fire
control plan will require this survey.
The attending surveyor is required and expected to make a specific and explicit statement in the
report of the relevant survey as to whether he has examined and has verified that the content of
fire control plan found on board are in a readable state, updated, approved (or examined for
compliance) and in accordance with the requirements of Regulations under SOLAS.
Importance of Fire control Plan
The Fire control plan is not just a paper requirement for the classification society or
the port state control. It is a useful document to understand:
The location of various firefighting and safety equipment onboard for new joiners
Location of nearest and safest fire fighting equipment and escape route when fighting fire
on ship
The port fire fighting station team has no clue about the ship arrangement. The fire control
plan is extremely useful and easy to read document to tackle major fire on ship by port
Fire fighters
Fire control plan is an important part of safety management plan of the ship and any
discrepancy may lead to non conformities against the SMS
Copy of Fire control plans kept the shore officer is also inspected while issuing/ re-issuing
the document of compliance (DOC) and safety management certificate (SMC) to the
company
Expert Tip:
It is advisable for the master or the ship management team to provide a Fire control plan to the
Fire Fighting station of the port authority of that Port where the ship is regular for cargo
exchange.
The fire fighter outfit is mandatory on every ship. The outfit consists of the following things:-
1) Breathing apparatus
3) Safety shoes
4) Hand Gloves
5) Rigid Helmet
6) Electric intrinsically safe hand lamp that lasts for about three hours duration
7) Fire Axe
As per SOLAS
According to Chapter II-2, regulation 10.10.2, the minimum number of fire fighter outfit required
on board are as follows:-
2) Additional fire-fighter’s outfit will be needed for passenger vessels depending on the design
of the ship; i.e. length of passenger spaces, number of decks, vertical zones and number of
passengers etc.
3) For tanker ships, additional two numbers of fire fighter’s outfit should be kept onboard
The fire fighter outfit is stored in the fire control room and in places that are easily accessible
during emergencies.
Requirement for Self Contained Breathing Apparatus (SCBA) used in Fire Fighter Outfit
2) It should be capable of working 30 minutes & provided with one face mask.
3) Fire proof line with the snap hook of at least 3 meters should be there and must have
enough length to reach any part of the space to be entered. The line should have a breaking
strength of 500 kg.
6) It should have a pressure gauge with an anti bursting orifice in a high pressure air supply
system.
7) Maximum weight should not increase above 19 kg including lifeline, safety belt, and
harness.
9) For ships carryings 5 sets or more, the total spare capacity of free air is 9600 liters or if
charging facility is available, free air is 4800 liters.
10) It must give an audible warning when 20 % of air is left in the bottle.
14) SCBA cylinders should be hydraulic pressure tested at intervals not exceeding 5 years and
hydrostatic test date must be permanently marked on the bottles.
What is SOLAS requirements for Portable fire fighting equipments on
board?
SOLAS requirements for Portable fire fighting equipments on board:
Min capacity of powder and CO2 is 5kg.
Min capacity of foam is 9l.
Max mass of all portable not to exceed 23kg and shall have a fire fighting capacity of a 9l liquid
extinguisher.
Accommodation spaces, service spaces and control stations to be provided with PFE.
1000GRT + must have at least 5 PFE.
Extinguisher intended to be used in a space must be near its entrance.
Co2 not to be placed in accommodation spaces.
Spare charges to be available for 100% of the first 10 and 50% of the remaining. Max spare
charges to be 60. Same stats for non rechargeable.
Self Contained Breathing Apparatus, also known as SCBA, is a necessary protective gear that
is worn by paramedics, firemen, and people working on ships and oil rigs. As the name goes,
the breathing apparatus has all necessary equipment fitted into it that will allow the rescue
professionals to carry out their work without any interruption and with utmost safety.
There are two major types of SCBA that are in use today – the Open Circuit SCBA and the
Closed Circuit SCBA. The main difference between the two is that the former one is used for
rescue operations that tend to be very long. In this type of SCBA, the air is continuously re-
processed or recycled so that the wearer of the SCBA gets a continuous supply of air. In the
second variety, the oxygen is compressed to fit into air cylinders. These varieties of SCBA are
used for shorter rescue operations.
The SCBA used onboard ship is of the open circuit type mostly. In this, the exhaled air is
discharged to the atmosphere while air from the cylinder is made available for inhalation. The
equipment consists of:
Air Cylinders
The first and foremost presence in the air breathing apparatus is that of Air Cylinders. In the
open circuit SCBA, the air cylinder is known as the re-breather which recycles the air (as
mentioned above). Air cylinders, on the other hand, are filled with oxygen in a compressed form
that enables a rescue professional to go into areas that are filled with smoke and fire and free
the trapped people successfully. The air cylinders in the breathing apparatus need to be
continuously checked after the rescue operation is carried out so that they do not end up to be
empty the next time a rescue operation needs to be carried out. There are also extra air
cylinders that are provided for the people who have been trapped and rescued.
Protective Hood
The second-most important presence is that of a Protective Hood. Such hoods are designed in
a way that they cover all the parts of the face, have an eye-covering (visor) that enables a
person to see and also allow the required oxygen to pass continuously. They also have tubes
attached to ensure that the air passes continuously.
The Portable Transporting Bag is also an important equipment of the breathing apparatus. It can
be filled with air cylinders, hoods and any other protective equipment that would be necessary
for the rescue operations. The bag is made up of a material that would be resistant to damage-
causing factors and thus can be effectively used in any sort of emergency situation.
The final breathing apparatus equipment is the Portable Hauling Bag. The main difference
between this type of carrying bag and the one mentioned previously is that in this bag, an extra
weight of the necessary items can be carried. It is used for the purpose of getting the SCBA
equipment from the headquarters of the rescue professionals to the place where the incident
has actually occurred. It is in only in the accident site that the equipments are transferred from
this bigger bag to the Portable Transporting Bag.
A breathing apparatus has changed the entire rescue operation process, making it simpler and
safer. More and more lives can be saved because of the portability factor of SCBA. It therefore
becomes important and relevant to acknowledge and appreciate the worth of the SCBA in
today’s times.
1. The cylinders contain about 1240 litres of compressed air at 200 atmosphere pressure.
This gives the wearer around 31 minutes of air supply for full usage or about 21 minutes
for working conditions (person breathes heavily during work hence there is more
consumption of air and that is why the time is lesser)
2. The reducing valve reduces the pressure by about 4 bars which is further reduced by the
demand valve which is attached to the mask
3. The demand valve is the one that supplies the air to the wearer when inhaling
4. The exhalation valve releases the air from the facemask
5. When the air left inside the apparatus will last about 10 minutes (40-45 bar pressure), a
warning whistle is soundedd continuously till the cylinder gets emptied. The start of this
whistle is an indication for the wearer to move out of the space he’s in to fight fire or
whatever purpose it is used for
6. The face mask is of soft moulded nature rubber and five adjustable head straps and a
nylon lanyard or neck strap. It has a foam filled or air cushion seal and a full vision visor.
For correct positioning of the mask, the straps should be tightened in the sequence where
the first two upper straps then the middle pair and finally the lower pair are tightened. Care
should be taken to not over tighten them causing discomfort to the wearer. The mask is
made of rubber and plastic with a shatterproof visor. It has an exhalation port with a
speech diaphragm and a nose guard
7. The wearer should have a good, clear field of vision through the visor
8. A gauge is provided, clipped or attached to the harness that carries the cylinder and it
monitors the pressure within the cylinder, It is positioned to be visible to the wearer
9. Spare cylinders must be provided for each set of breathing apparatus and a small air
compressor provided onboard to refill the cylinders with compressed air
10. In case that the facemask is dislodged in a toxic atmosphere, the wearer should hold his
breath and position the mask correctly. Any inlet of such toxic air can be highly dangerous
40
We subtract 10 as 10 minutes is when the alarm starts ringing and it is a safe period which must
be taken into account. So a 1200 litres cylinder will last for 1200/40 = 30 minutes minus the 10 =
20 minutes
Nervousness and excitement can cause an increased demand of oxygen and a proportionate
increase of respiration rate.
Assembly Instructions
Open the cylinder cradle by squeezing the two sides of the cradle lever and open the cylinder
strap. Line up the cylinder valve with reducer valve hand wheel and turn handwheel
counterclockwise until hand tight. Hook cylinder strap over cylinder and pull down the operating
lever onto the tension spring to be clipped to place.
To attach demand valve assembly to facemask- line up assembly with the red by pass valve
knob upwards with the centreline of facemask and turn assembly clockwise through 90 degrees
until it clicks into place
Donning Instructions
During Use
After Use
The SCBA sets must be checked routinely and maintained to keep them in working order at all
times. Check the backplate and the shoulder/waist straps for any damage and keep these
straps and belts fully stretched. Check the facemask straps and other rubber parts for any
deterioration. Wipe the mask with a mild disinfectant and rinse under running water. Wipe dry,
always. Perform pre use checks after every maintenance.
Alarm Testing
The SCBA is a vital piece of equipment which must be given very high importance to in terms of
maintenance. Whether it be fire fighting or entry into enclosed spaces, the SCBA is what comes
hand in such situations. Visual inspection must be carried out thoroughly every month on these
sets. Every year all the valves, sealing and speech membranes must be checked. The
exhalation disc must be replaced every two years and every five years the complete apparatus
should be submitted for a full service check for overhauling.