Engine Room Fire Hydrant System
Engine Room Fire Hydrant System
HB
FD020F
Frame 70 Casing
HB HB
4th Deck FD019F
FD642F
Upper Deck
Engine Room
Compressed
Air Charging Set: 0.99MPa
HB HB HB
Start: 0.8MPa
Stop: 0.9MPa FD018F FD014F FD025F
2nd Deck
Auto
ST/SP
PI PI Hydro- HB HB HB
phore FD017F FD013F FD024F
Tank 3rd Deck
(2m3) For No.1
FD041F PIAL PS Bilge & Gas FD042F HB
FD001F FD002F Pump Auto FD026F
Fire Line Pressurising Start
Jockey Pump
(2m3/h x 0.9MPa)
PI HB HB HB
FD016F FD012F FD023F 4th Deck
To Bilge To Bilge
Holding Tank Holding Tank
To Soot Drain HB HB HB
To Bilge Well
Eductor Driving FD015F FD011F FD022F
FD102F Water Service Floor
To Ballast Eductor
Overboard Line
FD101F
BA153F FD005F FD051F FD050F BA152F FD004F
FD100F
PI PI PI
Bilge, Fire and
MC
No.1 General Service Pumps No.2
MC Water Spray MC
PP026
Self-priming PP025
Pump CF025
Fire Main
Sea Water
WS050F WS052F BG117F BG115F BG114F BG112F WS051F WS053F
Fresh Water
Compressed Air
From Main From Fresh Water From Direct Fire Hose and
Bilge Line Tank for Water Bilge Suction HB
Nozzle
Spray Line Rinsing
Emergency Fire Pump In addition, both bilge, fire and GS pumps can provide standby services to the The lift pump motor is driven by high pressure oil delivered from a hydraulic
Manufacturer: Naniwa following: pump located next to the fire pump. The fire pump diesel drive also drives the
hydraulic lift pump.
No. of sets: 1 • Drive for the ballast stripping eductor and soot drain eductor.
Type: Vertical, centrifugal, motor-driven • Deck water spray system. The engine room fire main consists of two main risers opposite each other,
Model: FBWHV-250 with hydrants provided at each principal level of the machinery space, a total
Capacity: 560m3/h at 110MWC The bilge, fire and GS pumps are normally left lined-up for operation on of 18 fire hydrants serve the engine room. The starboard side riser terminates
the fire main with the discharge and suction valves kept open, except when at the base of the funnel; the port side 200mm riser continues on to supply the
Motor rating: 280kW, 440V, 60Hz, 1,750 rpm
being used on other services. Both of these pumps take their suction from the deck fire main system. 40mm branch lines are taken off the risers to supply
sea water crossover main and can be started and stopped from the following the hydrants in the engine room. A 200mm branch line off the main pump
Forward Fire Pump locations: discharge line serves as a back-up supply to the water spray system. Deck
isolating valve FD587F allows the deck and engine room systems to be isolated
Manufacturer: ?? • Locally.
if circumstances dictate. This valve must always be left open during normal
No. of sets: 1 • Fire control station. operating conditions and is operated from an extended spindle located on the
Type: Diesel, hydraulic-driven • Bridge. trunk deck.
Model: ??
Capacity: 180m3/h at 90MWC The sea water fire main and deck wash system is maintained under a constant WARNING
Motor rating: ?? pressure of up to 0.9MPa by a 2.0m3 hydrophore unit and its associated All valves on the fire main system and associated pumps MUST be
jockey pump. The hydrophore unit is used to maintain the system pressure and operated on a regular basis to prevent seizure. It should be possible to
accommodate and replace any small losses in the system. By this means, the operate all of these valves by hand without the use of wheelkeys.
fire main and deck wash system is maintained under operational pressure to
supply water to any of the hydrants. Adjacent to each fire hydrant in the engine room is a hose reel and a jet/spray
nozzle.
The fire main and deck wash system supplies the hydrants located in the engine
room, around the accommodation block and out on deck. If a hydrant valve is