EE251 Notes0 - Power System Models PDF
EE251 Notes0 - Power System Models PDF
EE 251
Fault Studies
Review Notes
Power System Models
1
Transmission & Distribution Lines
Sequence Impedance
2
Geometric Mean Distance
Typical three-phase line configurations
D12 D23
D31
D12
D12 D23
D31
Dm 3 D12D23D31
Ds Dscd
Ds 1.09 4 Dscd3
Note: Dsc=GMR of a single conductor
3
Aluminum Conductors
Aluminum is preferred over copper as a material
for transmission lines due to:
• lower cost
• lighter weight
• larger diameter for the same resistance*
Stranded Conductors
Alternate layers of wire of a Steel
stranded conductor are
spiraled in opposite directions
to prevent unwinding and
make the outer radius of one
layer coincide with the inner Aluminum
radius of the next.
The number of strands depends on the number
of layers and on whether all the strands are of
the same diameter. The total number of strands
of uniform diameter in a concentrically stranded
cable is 7, 19, 37, 61, 91, etc.
4
Example: Each conductor of the 345 kV bundled
three-phase line shown is 1272 MCM ACSR 54/19
Pheasant. Assuming complete transposition and a
total length of 80 miles, determine the positive-
sequence impedance of the line. Assume d=45 cm
and D=8 meters.
d
We get
Dm 3 8(8)(16) 10.08 m
Ds 0.0142(0.45) 0.08 m
The total resistance per phase
R1 0.0821(80)(0.5) 3.28
The total reactance per phase
10.08
X1 2.02 x 10-3(60)(80) ln 46.9
0.08
The positive (or negative) sequence impedance of
the line
Z1 Z2 3.28 j46.9 / phase
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 10
5
Transmission Line Inductance
The total self-inductance of a cylindrical conductor
consists of an internal inductance and an external
inductance.
Internal Inductance:
c
Lint Henry/meter
8
Note: c is the permeability of the conductor.For
a non-ferrous conductor such as copper or
aluminum,
c 4 x 10-7 Henry/meter
External Inductance:
The external inductance may be approximated by
m 2s
Lext (ln 1) Henry/meter
2 r
where
m = permeability of the medium surrounding
the conductor
r = radius of the conductor
6
Self Inductance:
c m 2s
L (ln 1) Henry/meter
8 2 r
For a non-ferrous conductor in air, we get
2s
L 2 x 10-7 (ln 1) Henry/meter
Ds
Mutual Inductance:
The mutual inductance between two conductors is
2s
M 2 x 10-7 (ln 1) Henry/meter
Dm
where Dm is the geometric mean distance
between the conductors
Note: For any unit of length,
2s
L k (ln 1) Henry/unit length
Ds
2s
M k (ln 1) Henry/unit length
Dm
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 14
7
Carson’s Line
Carson examined a single overhead conductor
whose remote end is connected to earth.
za a
a a’
+
Local Remote
Earth
Va Ia za d Earth
-
Fictitious
REF Vd 0 Return
d d’ Conductor
Id zd d
The current returns through a fictitious earth
conductor whose GMR is assumed to be 1 foot (or
1 meter and is located a distance Dad from the
overhead conductor.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 15
8
Primitive Impedances:
2s
za a ra jL a ra jk(ln 1)
Dsa
2s
zdd rd jk(ln 1)
Dsd
2s
za d jM jk(ln 1)
Da d
ra, rd = resistances of overhead conductor and
fictitious ground wire, respectively
Dsa, Dsd = GMRs of overhead conductor and
fictitious ground wire, respectively
Note: Dsd is arbitrarily set to 1 unit length
Earth Resistance:
Carson derived an empirical formula for the earth
resistance.
Note : At 60 Hz,
rd 0.09528 /mile
9
Equivalent Impedance:
Substitute the primitive impedances into
za a za a zdd 2za d
We get 2
D
za a (ra rd ) jk ln a d
DsaDsd
Note: 1. Dsd=1 unit length
2
D
2. Define De a d
Dsd
We get
De
za a (ra rd ) jk ln /unit length
Dsa
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 19
10
Three-Phase Line Impedances
Extend Carson’s
analysis to a three-phase line
Ia za a
a a’
Ib zb b za b zca b’
b
+
+ Ic zcc zb c
Va c c’
All wires
- Vb + za d grounded
- Vc zb d here
- zcd
REF
Vd 0
d d’
Id zd d
1 unit length
11
The voltage equation for the fictitious ground
conductor
is
Vd Vd' zadIa zbdIb zcd Ic zddId
which can be re-written as
Vd' zadIa zbdIb zcd Ic zdd(Ia Ib Ic )
Combining terms, we get
Vd' (zad zdd)Ia (zbd zdd)Ib (zcd zdd)Ic
Following a similar procedure, the voltage
equation
for phase a can be shown to be
Va Va' (zaa zad)Ia (zab zad)Ib
(zac zad)Ic
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 23
12
We can also subtract the voltage equation of the
ground conductor from the equations of phases b
and c. The resulting matrix equation is
Va za a za b za c I
a
Vb = za b zbb zbc Ib V/unit length
Vc za c zbc zcc Ic
Self Impedances:
za a za a 2za d zdd /unit length
zbb zbb 2zbd zdd /unit length
zcc zcc 2zcd zdd /unit length
Mutual Impedances:
za b za b za d zbd zdd /unit length
zbc zbc zbd zcd zdd /unit length
za c za c za d zcd zdd /unit length
Primitive Impedances:
2s
zx x rx jk(ln 1) /unit length
Dsx x=a,b,c,d
2s
zx y jk(ln 1) /unit length
Dx y xy=ab,bc,ca,ad,bd,cd
13
Assumptions:
1. Identical phase conductors
Dsc=0.01668 ft @ 60 Hz a b c
De
za a zbb zcc (ra rd ) jk ln
Ds
(0.278 0.095) j0.121 ln 0.01668
2790
14
za b zbc 0.095 j0.121 ln 2790
10
0.095 j0.683 /mile
Za b 3.81 j27.33
Za c 3.81 j23.97
We get
Line Transposition
Line transposition is used to make the mutual
impedances identical.
Ia
Phase c
Pos.1
Ib
Phase a
Pos.2
Ic
Phase b
Pos.3
s1 s2 s3
Section 1 Section 2 Section 3
15
Voltage equation for Section 1
Va Z111 Z121 Z131 I
a
Vb = Z211 Z221 Z231 Ib volts
Vc Z311 Z321 Z331 Ic
16
Va (Z111 Z222 Z333 )Ia
(Z121 Z232 Z313 )Ib
(Z131 Z212 Z323 )Ic
By a similar procedure, we get for phases b and c
Vb (Z211 Z322 Z133 )Ia
(Z221 Z332 Z113 )Ib
(Z231 Z312 Z123 )Ic
Vc (Z311 Z122 Z233 )Ia
(Z321 Z132 Z213 )Ib
(Z331 Z112 Z223 )Ic
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 33
17
Define f1, f2 and f3 as as the ratios of s1, s2 and s3
to the total length s, respectively. We get
Va (f1Z11 f2Z22 f3Z33)Ia
(f1Z12 f2Z23 f3Z31)Ib
(f1Z13 f2Z21 f3Z32)Ic
Vb (f1Z21 f2Z32 f3Z13)Ia
(f1Z22 f2Z33 f3Z11)Ib
(f1Z23 f2Z31 f3Z12)Ic
Vc (f1Z31 f2Z12 f3Z23)Ia
(f1Z32 f2Z13 f3Z21)Ib
(f1Z33 f2Z11 f3Z22)Ic
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 35
Define:
18
It can be shown that
De
Zs (ra rd )s jks ln
Ds
D D D
Zk1 rds jks f1ln e f2 ln e f3 ln e
D12 D23 D31
D D D
Zk2 rds jks f1ln e f2 ln e f3 ln e
D31 D12 D23
D D D
Zk3 rds jks f1ln e f2 ln e f3 ln e
D23 D31 D12
19
Solving for the mutual impedances, we get
Zk1 f1Z12 f2Z23 f3Z13
0.2(3.81 j27.33) 0.3(3.81 j27.33)
0.5(3.81 j23.97)
3.81 j25.65
Similarly, we get
20
Example: For the same line assume the
following transposition cycle:
s1=16 miles s2=24 miles s3=0
21
Example: For the same line assume a complete
transposition cycle.
10’ 10’
The GMD is
a b c
Dm 3 10(10)(20) 12.6 feet
We get the average of the mutual impedances.
Zm 3.81 j26.21
The impedance of the transposed line is
Phase- to Sequence-Impedances
Consider a transmission line that is described by
the following voltage equation:
Va Za a Za b Za c I
a
Vb = Za b Zbb Zbc Ib volts
Vc Za c Zbc Zcc Ic
or
Va bc Za bcIa bc
From symmetrical components, we have
Va bc AV012 and Ia bc A I012
22
Substitution gives
AV012 Za bcA I012
or 1
V012 A Za bcA I012
which implies that
Z012 A 1ZabcA
Performing the multiplication, we get
Z0 Zs0 2Zm0 Zs2 Zm2 Zs1 Zm1
Z1 = Zs1 Zm1 Zs0 Zm0 Zs2 2Zm2
Z2 Zs2 Zm2 Zs1 2Zm1 Zs0 Zm0
Note: Z012 is not symmetric.
Zs0 1
3
(Za a Zbb Zcc )
Zs1 1
3
(Zaa aZbb a2Zcc )
Zs2 1
3
(Zaa a2Zbb aZcc )
Zm0 1
3
(Za b Zbc Zca )
Zm1 1
3
(a2Zab Zbc aZca )
Zm2 1
3
(aZab Zbc a2Zca )
23
If the line is completely transposed,
Zs0 Zs Zm0 Zm
Zs1 Zs2 0 Zm1 Zm2 0
The sequence impedance matrix reduces to
Z0 Zs 2Zm 0 0
Z1 = 0 Zs Zm 0
Z2 0 0 Zs Zm
24
Example: For the same line and assuming a
complete transposition cycle, find the sequence
impedances of the line.
10’ 10’
25
Incomplete Transposition
The resulting circuit unbalance due to incomplete
transposition is measured in terms of the zero-
and negative-sequence line currents that arise
when positive-sequence voltages are applied at
the sending end.
For a partially-transposed transmission line,
Va zs zk1 zk 2 I
a
Vb = zk1 zs zk 3 Ib V/unit length
Vc zk 2 zk3 zs Ic
or
Va bc za bcIa bc
where
De
zs (ra rd ) jk ln
Ds
D D D
zk1 rd jk f1ln e f2 ln e f3 ln e
D12 D23 D31
D D D
zk 2 rd jk f1ln e f2 ln e f3 ln e
D31 D12 D23
D D D
zk 3 rd jk f1ln e f2 ln e f3 ln e
D23 D31 D12
26
Transform the phase impedances into sequence
impedances.
z012 A 1zabcA
which gives
z0 zs 2zm0 zm2 zm1
z1 = zm1 zs zm0 2zm2
z2 zm2 2zm1 zs zm0
where
zm0 1
3
(zk1 zk 2 zk 3 )
zm1 1
3
(a2zk1 azk2 zk3 )
zm2 1
3
(azk1 a2zk2 zk3 )
27
Assume that balanced voltages are applied at the
sending end;
that is
Va0 0 and Va2 0
We can re-write the voltage equation
Va0 z00 z01 z02 Ia0
Va1 = z10 z11 z12 I
a1
Va2 z20 z21 z22 Ia2
into
0 z00Ia0 z01Ia1 z02Ia2
Va1 z10Ia0 z11Ia1 z12Ia2
0 z20Ia0 z21Ia1 z22Ia2
The unbalanced
factor are defined as:
I I
m0 a0 and m2 a2
Ia1 Ia1
It can be shown that
z02z21 z01z22
m0
z00z22 z20z02
z20z01 z00z21
m2
z00z22 z20z02
Note: For the untransposed 40-mile line,
m0 1.05472.68o %
m2 6.624139.14o %
28
Lines with Overhead Ground Wire
Ia za a
a
a’
Ib zb b za b zca
b
b’
+ Ic zcc zb c
c
c’
Va + I zww za d
- Vb + w w w’
-
Vc + zb d All wires
- Vw zcd grounded
- here
REF
Vd 0
d’
d
Id zd d
1 unit length
29
The last equation may be written as
Vd' zdaIa zdbIb zdcIc zdwIw
zdd(Ia Ib Ic Iw )
or
Vd' (zda zdd)Ia (zdb zdd)Ib
(zdc zdd)Ic (zdw zdd)Iw
Following the same procedure, the equation for
phase a can be expressed as
Va Va' (zaa zad)Ia (zab zad)Ib
(zac zad)Ic (zaw zad)Iw
30
We get
Va za a za b za c za w I
a
Vb zba zbb zbc zbw Ib
=
Vc zca zcb zcc zcw I
c
Vw zwa zwb zwc zww Iw
where Vw 0 and
De
zx x (rx rd ) jk ln x=a,b,c,w
Dsx
De
zx y rd jk ln xy=ab,ac,aw,
Dx y bc,bw,cw
Kron’s Reduction
Consider the matrix equation
V1 Z1 Z2 I1
=
0 Z3 Z4 I2
31
From eq. 2, we get
1
I2 Z4 Z3I1
which is substituted in eq. 1 to get
1
V1 Z1I1 Z2 (Z4 Z3I1 )
or
1
V1 (Z1 Z2Z4 Z3 )I1
Go back to the voltage equation of the line.
Va za a za b za c za w I
a
Vb zba zbb zbc zbw Ib
=
Vc zca zcb zcc zcw I
c
0 zwa zwb zwc zww Iw
We wish to eliminate Iw , where
za a za b za c za w
T
Z1 = zba zbb zbc Z2 = zbw = Z3
zca zcb zcc zcw
Z4 zww
We get
za wzwa za wzwb za wzwc
za a za b za c
zww zww zww
z z z z z z
z a b c = zba bw wa
zww
zbb bw wb
zww
zbc bw wc
zww
z z z z z z
zca cw wa zcb cw wb zcc cw wc
zww zww zww
32
Example: Find the equivalent impedance of the
69-kV line shown. The phase conductors are the
same as in the previous examples. The overhead
ground wires have the following characteristics:
rw=4.0 /mile @ 25oC w
Dsw=0.001 ft @ 60 Hz
For the ground wire, we get 15’
D
zww (rw rd ) jk ln e 10’ 10’
Dsw a b c
(4.0 0.095) j0.121 ln 2790
0.001
De
za w zcw rd jk ln
Da w
0.095 j0.121 ln 18.03
2790
/mile
Za w Zcw 3.81 j24.47
zbw 0.095 j0.121 ln 2790
15 /mile
Zbw 3.81 j25.36
From a previous example, we got
33
Using the ground wire impedances, we also get
3.81 j24.47
T
Z2 = 3.81 j25.36 = Z3
3.81 j24.47 Z4 163.8 j72
Current Division
How much current is flowing in the overhead
ground wire? Under zero-sequence condition,
Ia Ib Ic Ia0
The primitive voltage equation reduces to
Va Va' za a za b za c za w za d Ia0
Vb Vb' zba zbb zbc zbw zbd Ia0
V/unit
Vc Vc' = zca zcb zcc zcw zcd Ia0
length
0 Vw' zwa zwb zwc zww zwd Iw
0 Vd' zda zdb zdc zdw zdd Id
34
From KCL, we get
Id Iw 3Ia0
The last equation may be written as
Vd' (zda zdb zdc)Ia0 zdwIw zddId
Similarly, for the overhead ground wire
Vw' (zwa zwb zwc )Ia0 zww Iw zwd Id
Subtracting the two equations, we get
0 [(zwa zwb zwc ) (zda zdb zdc)]Ia0
(zww zdw)Iw (zwd zdd)Id
Since Id (3Ia0 Iw ) , we get
0 [(zwa zwb zwc ) (zda zdb zdc)]Ia0
(zww zdw)Iw (zwd zdd)(3Ia0 Iw )
Combine
common terms and get the ratio of Iw to
3Ia0 . We get
Iw (zwa zwb zwc ) (zda zdb zdc ) 3(zdd zwd )
3Ia0 3(zww zwd zdw zdd)
Recall that
zwx zwx zwd zdx zdd x=a,b,c,w
35
Substitution gives
Iw zwa zwb zwc
(a)
3Ia0 3zww
From Id Iw 3Ia0 , we get
Id I
1 w
3Ia0 3Ia0
Substitute eq. (a) to get
Id z zwb zwc
(b) 1 wa
3Ia0 3zww
36
Line Transposition
Consider a transmission line with one overhead
ground wire. Assume that the line is transposed.
Ground wire
Ia
Phase c
Pos.
Ib
Phase a
Pos.
Ic
Phase b
Pos.
s1 s2 s3
Section 1 Section 2 Section 3
The impedance matrix for each section can be
found using Kron’s reduction.
37
Similarly, for Sections 3, we get
z wzw z wzw z wzw
z z z
zww zww zww
z wzw z z z wzw
z f 3 = z z w w z
zww zww zww
zwzw zwzw zwzw
z z z
zww zww zww
It can be shown that
Va I
a
Vb s(f1Zf1 f2Zf 2 f3Zf 3 ) Ib
Vc Ic
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 75
z s zm z m
z a b c = zm z s z m /unit length
z m zm z s
38
The off-diagonal elements are
zm 13 (z z z )
z z z z z z
13 w w w w w w
zww zww zww
The sequence impedance matrix will be diagonal.
z00 0 0
z012 = 0 z11 0 /unit length
0 0 z22
where
z00 zs 2zm and z11 z22 zs zm
39
The last two terms can be shown to be equal to
(k)2 M
1
3
z ww
where
De 2 D D
M (ln ) (ln e )2 (ln e )2
Dw Dw Dw
D D D D
(ln e )(ln e ) (ln e )(ln e )
Dw Dw Dw Dw
De D
(ln )(ln e )
Dw Dw
Likewise,
De
zww (rw rd ) jk ln
Dww
For most transmission line configurations,
Dm
z11 ra jk ln /unit length
Ds
Note: This is the formula for the positive sequence
impedance of a transposed line without ground
wires.
40
The zero-sequence impedance can be shown to be
2
z0(m)
z00 z0(a) /unit length
z0(g)
where
3
De
z0(a) (ra 3rd ) jk ln 2
DsDm
De
z0(m) 3rd j3k ln
3 DwDwDw
z0(g) 3zww
41
Zm 13 [2(6.48 j25.0) 6.38 j21.7]
6.45 j23.9
17.57 j56.06 6.45 j23.9 6.45 j23.9
Zabc= 6.45 j23.9 17.57 j56.06 6.45 j23.9
6.45 j23.9 6.45 j23.9 17.57 j56.06
For comparison, Zabc below is for a completely
transposed line without the overhead ground wire.
Z00 Zs 2Zm
30.47 j103.86
Z11 Z22 Zs Zm
11.12 j32.17
Note: When the effect of the ground wire was not
taken into account, we got
Z0 22.55 j110.8
Z1 11.12 j32.17
42
Steel Ground Wires
The overhead Grade E.B.B. 7 Strands
3/8 inch Diameter
ground wires are 10-3 15
Resistance (/mile)
10-7 11
some alloy of GMR
steel. This poses a 10-9 9
problem since the 10-11 7
resistance and 5
10-13
GMR of these Resistance
conductors vary 10-15 3
with current. 10-17 1
10-19
0 10 20 30 40 50 60
Amperes per Cable
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 85
43
The zero-sequence impedance of the ground wire
De
z0(g) 3zww 3(rw rd ) j3k ln
Dww
The resistance and GMR of the ground wire is a
function of the current. For 1A, 30A and 60A, we
get for E.B.B.
rw= 3.5 /mile at 1A
= 7.8 /mile at 30A
= 6.0 /mile at 60A
Dsw= 10-3 ft at 1A
= 5 x 10-12 ft at 30A
= 1.5 x 10-10 ft at 60A
44
The zero-sequence mutual impedance is
De
z0(m) 3rd j3k ln
Dag
2790
3(0.095) j3(0.121) ln
16.96
0.29 j1.86 /mile
Z0(m) 11.43 j74.28
Substitution gives
Z00 31.0 j102.65 at 1A
Z00 18.86 j107.06 at 30A
Z00 27.21 j105.89 at 60A
Note: For comparison, we got the following zero-
sequence impedances from previous examples:
No overhead ground wire:
45
Parallel Multicircuit Lines
Consider the double-circuit transmission line
shown. One circuit is designated abc and the
other a’b’c’. Each circuit may be untransposed or
partially transposed.
m Ia bc n
Za b c
Ia'b'c'
Za'b'c'
46
Using matrix notation, we get
Va b c Zaa Zaa' Ia b c
=
Va'b'c' Za'a Za'a' Ia'b'c'
47
Performing the transformation, we get
I A 1Ya aA A 1Ya a'A V012
012 =
I0'1'2' A 1Ya'aA A 1Ya'a'A V0'1'2'
Assume that the voltages at both ends of the line
contain positive sequence components only. We
get
0 0
Va1 1
V012 0 0
= = Va1
V0'1'2' 0 0
Va'1 1
0 0
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 95
Note that Va1 Va'1 since the lines are bused at
both
ends. Substitution gives
Ia0 Y00 Y01 Y02 Y00' Y01' Y02' 0
I Y10 Y11 Y12 Y10' Y11' Y12' 1
a1
I Y Y21 Y22 Y20' Y21' Y22' 0
a2 = 20 Va1
Ia'0 Y0'0 Y0'1 Y0'2 Y0'0' Y0'1' Y0'2' 0
I Y1'0 Y1'1 Y1'2 Y1'0' Y1'1' Y1'2' 1
a'1
Ia'2 Y2'0 Y2'1 Y2'2 Y2'0' Y2'1' Z2'2' 0
Solving for the sequence currents, we get
Ia0 (Y01 Y01' )(Va1 )
Ia2 (Y21 Y21' )(Va1 )
Ia1 (Y11 Y11' )(Va1 )
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 96
48
Ia'0 (Y0'1 Y0'1' )(Va1 )
Ia'2 (Y2'1 Y2'1' )(Va1 )
Ia'1 (Y1'1 Y1'1' )(Va1 )
Define the net through unbalance factors as
I Ia'0
m0t a0 per unit
Ia1 Ia'1
I Ia'2
m2t a2 per unit
Ia1 Ia'1
Define the net circulating current unbalance factors
as Ia0 Ia'0
m0c per unit
Ia1 Ia'1
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 97
Ia2 Ia'2
m2c per unit
Ia1 Ia'1
Solving for the unbalance factors, we get
m0t (Y01 Y01' Y0'1 Y0'1' ) / Y1
m2t (Y21 Y21' Y2'1 Y2'1' ) / Y1
m0c (Y01 Y01' Y0'1 Y0'1' ) / Y1
m2c (Y21 Y21' Y2'1 Y2'1' ) / Y1
where
Y1 Y11 Y11' Y1'1 Y1'1'
49
Electric Field of a Long Conductor
Consider a long, isolated cylindrical conductor with
a uniform positive charge density q and located in
a homogeneous medium.
The flux density at a distance x from the center is
q q
D âr Coul/m2 +
2x x
âr
The electric field intensity is
D q
E âr Volt/m
2x
Sequence Capacitance
50
Voltage Due to Charged Conductor
Consider two points P1 and P2 which are located at
distances D1 and D2 from the center of the
conductor.
D1 P1
The voltage drop from
P1 to P2 is P2
D2 D2
v12 D1
E dx
q
D2
D1 2x dx
q D
ln 2 Volts
2 D1
51
Due to charge qb, we also get the voltage drop vba.
qb D
vba ln
2 rb
or q D q r
va b b ln b ln b
2 rb 2 D
Applying superposition, we get the total voltage
drop from charge qa to charge qb.
qa D q r
va b ln b ln b
2 ra 2 D
Since qa+qb=0, we get
qa D2
vab ln Volts
2 rarb
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 103
2
Ca n Cbn 2Ca b Farad/meter
D
ln
r
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 104
52
Three-Phase Line
Consider a three-phase trans- qb
mission line with equilateral
spacing. Assume identical
phase conductors and neglect D D
the effect of ground. Assume
qa qb qc 0 qa D qc
1 D D r
vac qa ln qb ln qc ln
2 r D D
Adding the two equations, we get
1 D r
vab vac 2q ln (q q ) ln
2 D
a b c
r
Since qa=-(qb+qc), we get
3qa D
vab vac ln Volts
2 r
53
Phasor Diagram:
Vca Vcn Va b
Va b Va n( 330o )
Va c Va n( 3 30o ) Va n
Vab Vac 3Van
Vbn Va c
We get
qa D
van ln
2 r Vbc
The capacitance to neutral is
qa 2 Farad/meter,
Ca n Cbn Ccn
va n D to neutral
ln
r
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 107
qa Phase c
Pos.1
qb Phase a
Pos.2
qc Phase b
Pos.3
1
3
s 1
3
s 1
3
s
Section 1 Section 2 Section 3
54
For section 1, we get b
D12 D23
a D31 c
1 D12 r D
v a b1 qa ln qb ln qc ln 23
2 r D12 D31
1 D31 D r
vac1 qa ln qb ln 23 qc ln
2 r D12 D31
D12 D23
c D31 b
1 D23 r D31
v ab2 q
a ln qb ln qc ln
2 r D23 D12
1 D12 D r
v a c2 qa ln qb ln 31 qc ln
2 r D23 D12
55
For section 3, we get c
D12 D23
b D31 a
1 D31 r D
v a b3 qa ln qb ln qc ln 12
2 r D31 D23
1 D23 D r
v a c3 qa ln qb ln 12 qc ln
2 r D31 D23
1 Dm r
va b qa ln qb ln
2 r Dm
56
Similarly, we get
1 Dm r
va c q
a ln qc ln
2 r Dm
Taking summation, we get
1 Dm r
va b va c 2qa ln (qb qc ) ln
2 r Dm
3 D
3van qa ln m Volts
2 r
or
1 D
van qa ln m Volts
2 r
The capacitance of phase a to neutral is
qa 2 Farad/meter,
Ca n
va n D to neutral
ln m
r
Since the line is completely transposed,
Ca n Cbn Ccn
57
Capacitive Reactance
1
xc
2fC
2.862 D -meter,
x 109 ln m
f r to neutral
1.779 D -mile, to
x 106 ln m neutral
f r
Note: To get the total capacitive reactance, divide
xc by the total length of the line.
Equivalent Circuit
A lumped-parameter representation is used for
short and medium-length lines. For long lines, a
distributed-parameter model is used.
Short Line: Up to 80 kilometers (50 miles)
Z=R+jL
+
+
Vs Is VR
- -
Vs Z Is VR
58
Medium-Length Line: From 80 km (50 mi) to
240 km (150 mi)
Z=R+jL
+ +
I IR
Vs s 1
2
YC jC
1
2
1
2
YC VR
- -
Dm 3
2(23.8)3 30 ft
30
x1 0.121 ln 0.812 /mi
0.0373
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 118
59
Z1 0.1284 j0.812 /mi
Z1 12.84 j0.81.16
1.779 D -mile, to
xC x 106 ln m neutral
f r
1.779 30
x 106 ln 1
60 24
(1.108)
192,034 -mile, to neutral
XC 1,920.34 , to neutral
1
YC j j520.74 x 10-6 -1
XC
Mutual Capacitance
In capacitance calculations, the earth is assumed
as a perfectly conducting plane. The electric field
that results is the same if an image conductor is
used for every conductor above ground.
+qb
Dab +qc
Dac
Dan +qn
+qa
Haa
Hab Hac Han
-qa
-qn
-qc
-qb
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 120
60
The voltage drop from conductor a to ground is
va v a a'
1
2
1 H H H
(qa ln a a qb ln a b ... qn ln a n
4 ra Da b Da n
ra D D
qa ln qb ln a b ... qn ln a n )
Ha a Ha b Ha n
Combining common terms, we get
1 H H H
va (qa ln a a qb ln a b ... qn ln a n )
2 ra Da b Da n
va Pa a Pa b Pa c ... Pa n qa
vb Pba Pbb Pbc ... Pbn qb
=
…
…
…
61
where
1 H
Pk k ln k k
2 rk
1 H
Pk j ln k j
2 Dk j
Inversion of matrix P gives
Ca a Ca b Ca c ... Ca n
Cba Cbb Cbc ... Cbn
C =
…
62
For a purely capacitive system, we get
…
jCna jCnb jCnc ... jCnn
63
Transposed Three-Phase Line
qa Phase c
Pos.1
qb Phase a
Pos.2
qc Phase b
Pos.3
1
3
s 1
3
s 1
3
s
Section 1 Section 2 Section 3
va Pa a Pa b Pa c qa
vb = Pba Pbb Pbc qb Volts
vc Pca Pcb Pcc qc
64
Since the line is completely transposed, the mutual
and ground capacitances are averaged values.
Average Mutual Capacitance
65
Sequence Capacitance
Using matrix notation, we have
Iabc YabcVabc
Iabc jCabcVabc
From Vabc AV012 and Ia bc A I012, we get
A I012 jCabcAV012
or 1
I012 jA CabcAV012
Thus, we have
C012 A 1CabcA
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 131
66
Example: Determine the phase and sequence
capacitances of the transmission line shown. The
phase conductors are 477 MCM ACSR 26/7 whose
radius is 0.0357 ft. The line is 50 miles long and is
completely transposed.
14’ 14’
Calculate distances
a b c
Haa=Hbb=Hcc=80 ft
Hab=Hbc=81.2 ft 40’
Hac=84.8 ft
Find the P matrix
1 H
Pa a Pbb Pcc ln a a
20 ra
For air,
1
0 x 10-9 Farad/meter
36
Substitution gives
80
Paa 18 x 109 ln
0.0357
138.86 x 109 Meter/Farad
86.29 x 106 Mile/Farad
Similarly, we get
1 H
Pa b Pbc ln a b
20 Da b
19.66 x 106 Mile/Farad
67
The P matrix can be shown to be
68
The self- and mutual capacitances are
Cs0 13 (Ca a Cbb Ccc ) 0.62 F
Cm0 13 (Ca b Cbc Cca ) 0.105 F
The sequence capacitances are b
Cm0
C0 Cs0 2Cm0 Cm0
a Cm0
0.41 F c
Cg0 Cg0
C1 C2 Cs0 Cm0 Cg0
0.725 F
69
The voltage equation for section 1 is
va Pa a Pa b Pa c Pa w qa
vb Pba Pbb Pbc Pbw qb
=
vc Pca Pcb Pcc Pcw qc
vw Pwa Pwb Pwc Pww qw
where vw=0 and the elements of P are
1 H
Pk k ln k k k=a,b,c,w
2 rk
1 H kj=ab,ac,aw,
Pk j ln k j
2 Dk j bc,bw,cw
70
Example: Determine the phase and sequence
capacitances of the transmission line shown. The
phase conductors are 477 MCM ACSR 26/7 whose
radius is 0.0357 ft. The overhead ground wires
are 3/8 inch E.B.B. steel. The line is 50 miles long
and is completely transposed. w u
71
It can be shown that the P matrix is
P1 P2
P=
P3 P4
where
86.3 19.7 12.4
P1 = 19.7 86.3 19.7 x 106 mi/F
12.4 19.7 86.3
14.8 19.6
P2 = P3 = 19.6 19.6
T x 106 mi/F
19.6 14.8
99.1 23.1
P4 = x 106 mi/F
23.1 99.1
72
Using Kron’s reduction,
1
Pa bc P1 P2P4 P3
or
81.30 14.15 7.69
Pabc = 14.15 80.02 14.15 x 106 mi/F
7.69 14.15 81.30
Capacitances to ground
73
Assuming a complete transposition cycle,
Electrostatic Unbalance
In the system shown, assume Va n , Vbn and Vcn
are positive-sequence voltages. The line is not
transposed.
a
Ia
a’
+
Va n Ib Ca b
b
Vcn - -
Vbn b’
+ + Cbc C ca
c
Ic
c’
+
+ + +
Vn Va Vb Vc Ccg Cbg Cag
- - -
-
74
The charging
current
at no-load
condition
Iabc jCabcVabc jBabcVabc
Transforming to sequence components, we get
I012 jA 1CabcAV012 jB012V012
From KVL, we get
Van Va Vn Vbn Vb Vn
Vcn Vc Vn
or
V 1
an
Va bc = Vbn + 1 Vn
Vcn 1
75
Expanding, we get
Ia0 jB00Vn jB01Van
Ia1 jB10Vn jB11Van
Ia2 jB20Vn jB21Van
Case 1: Neutral Ungrounded
If the neutral is ungrounded, Ia0 0. Electrostatic
unbalance is defined in terms of the sequence
voltages. It can be shown that
V V C
d0 a0 n 00
Va1 Va n C01
76
Case 2: Neutral Grounded
If the neutral is grounded, Vn 0. Electrostatic
unbalance is defined in terms of the sequence
currents. It can be shown that
2
Ia0 Ca g a Cbg aCcg
d0
Ia1 3(Cg0 3Cm0 )
Note: Electrostatic unbalance may be reduced by
Transformers
Sequence Impedance
77
Ideal Two-Winding Transformer
NH NX
+ +
I IX
VH H VX
_ _
VH N
Voltage Equation: H
VX NX
The voltage drop from the polarity-marked
terminal to the non-polarity-marked terminal of
the H winding is in phase with the voltage drop
from the polarity-marked terminal to the non-
polarity-marked terminal of the X winding.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 155
Current Equation: NHIH NX IX
The current that enters the H winding through the
polarity-marked terminal is in phase with the
current that leaves the X winding through the
polarity-marked terminal.
Note: Balancing ampere-turns must be satisfied at
all times.
78
Ideal Autotransformer
IH nS
VH nC
IC IX VX
79
Transformer Polarity
H1 H2 H1 H2
Subtractive Additive
X1 X2 X2 X1
Practical Transformer
1. The H and X coils have a small resistance.
2. There are leakage fluxes in the H and X coils.
3. There is resistance loss in the iron core.
4. The permeability of the iron is not infinite.
iH iX
+ +
vH eH eX vX
- NH NX -
iron
core
80
Equivalent Circuit
RH jXH Ie x NH NX R X jXX
+ + + +
IH R IX
VH c jXm EH EX VX
- - - -
H winding Ideal X winding
+ + + +
IH IX
VH EH EX VX
- - - -
81
Three-Winding Transformer
NX
NH +
+ IX VX
IH _
VH +
_
NY IY VY
_
VH N VH N VX N
H H X
VX NX VY NY VY NY
NHIH NX IX NY IY
Three-Winding Autotransformer
+
I
NY Y V
IH _Y
VH NH
NX IX V
X
VH N VH N VX N
H H X
VX NX VY NY VY NY
NHIH NX IX NY IY
82
Equivalent Circuit
From 3 short-circuit tests, get
ZHX=impedance measured at the H side when the
X winding is short-circuited and the Y winding
is open-circuited
ZHY=impedance measured at the H side when the
Y winding is short-circuited and the X winding
is open-circuited
ZXY=impedance measured at the X side when the
Y winding is short-circuited and the H winding
is open-circuited
Note: When expressed in ohms, the impedances
must be referred to the same side.
ZX
ZH +
+
ZY +
VX
VH
- VY -
-
ZHX ZH ZX
ZXY ZX ZY
ZHY ZH ZY
or
ZH 1
2
(ZHX ZHY ZXY )
ZX 1
2
(ZHX ZHY ZXY )
ZY 1
2
(ZHX ZHY ZXY )
83
Example: A three-winding three-phase transformer
has the following nameplate rating:
H: 30 MVA 140 kV
X: 30 MVA 48 kV Y:
10.5 MVA 4.8 kV
Short circuit tests yield the following impedances:
ZHX = 63.37 @ the H side
ZHY = 106.21 @ the H side
ZXY = 4.41 @ the X side
Find the equivalent circuit in ohms, referred to the
H side.
ZXY (140
48
)2(4.41) 37.52
2.66
66.03 +
+
+ VX
VH 40.18
- VY -
-
84
Angular Displacement
ANSI/IEEEC57.12.00-1993: The angular displace-
ment of a three-phase transformer is the time
angle (expressed in degrees) between the line-to-
neutral voltage of the high-voltage terminal
marked H1 and the the line-to-neutral voltage of
the low-voltage terminal marked X1.
Vector Diagrams
H2 X2 H2
X2
X1
X1 X3
H1 H3 H1 H3 X3
- Connection Y- Connection
H2 X2 H2 X2
X1
X1 X3 X3
H1 H3 H1 H3
Y-Y Connection -Y Connection
85
Wye-Wye Connection
HV side LV side
H2 X2
N n
H1 H3 X1 X3
VH2N
VX 2n
VX1n VX3n
VH1N VH3N
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 171
VH1N VH3N VAN VC N
VX 2n Vbn
Va n and VAN
are in phase.
VX1n VX3n Va n Vcn
86
Let H1=A, H2=B and H3=C. Also let X1=c, X2=a
and X3=b.
VH2N VBN
VH1N VH3N VAN VC N
VX 2n Va n
Va n lags VAN
by 120o.
VX1n VX3n Vcn Vbn
VH1N VH3N VAN VC N
VX 2n Vcn
Va n lags VAN
by 240o.
VX1n VX3n Vbn Va n
87
Wye-Wye Connection
HV side LV side
H2 X2
N n
H1 H3 X1 X3
VH2N
VX3n VX1n
VH1N VH3N VX 2n
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 175
VH1N VH3N VAN VC N
VX3n VX1n Vcn Va n
Va n lags VAN
by 180o.
VX 2n Vbn
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 176
88
Let H1=A, H2=B and H3=C. Also let X1=c, X2=a
and X3=b.
VH2N VBN
VH1N VH3N VAN VC N
VX3n VX1n Vbn Vcn
Va n lags VAN
by 300o.
VX 2n Va n
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 177
VH1N VH3N VAN VC N
VX3n VX1n Va n Vbn
Va n lags VAN
by 60o.
VX 2n Vcn
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 178
89
IEC Designation
The International Electrotechnical Commission
(IEC) uses the face of a clock in identifying the
phase shift. 0
IEC Designation for -
10 2
Dd0 Dd2 Dd4
Dd6 Dd6 Dd10
8 4
IEC Designation for Y-Y
Yy0 Yy6 6
90
Consider a set of balanced 3-phase line-to-neutral
voltages with asequence
a-c-b. From
Vab Van Vnb Vcn
we get
Vab Van Vbn
Va n
Similarly, weget
Vbc Vbn Vcn Vbn
Vca Vcn Van
Va b Vcn Vca
Va n leads Va b by 30o
Va n
Vbn leads Vb c by 30o
Vbn
Vcn leads Vca by 30o
Vb c
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 181
91
Y- and -Y Transformers
H2 H2
X2 X2
X1 X1
H1 H3 X3 X3
H1 H3
HV Y – LV
H2 X2
H2 X2
X1
X1
X3
H1 H3
H1 H3
X3
HV - LV Y
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 183
HV Wye – LV Delta
H1 X1
H2 X2
N
H3 X3
VH2N
VX1X2 VX 2n
Sequence
1-2-3 VX1n
VX 2X 3
VX3X1
VH1N VH3N
VX3n
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 184
92
The choice of phases A, B and C is arbitrary. Let
H1=A, H2=B, H3=C. Also let X1=a, X2=b, X3=c.
VH2N VBN
VH1N VH3N VAN VC N
VX 2n Vbn
VX1X2 Va b
VX1n Va n lags VAN
VX 2X 3 Va n Vb c by 30o
VX3X1 Vca
VX3n Vcn
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 185
VH1N VH3N VAN VC N
VX 2n Vcn
VX1X2 Vb c
VX1n
V Va n lags VAN
VX 2X 3 bn Vca by 270o
VX3X1 Va b
VX3n Va n
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 186
93
Let H1=A, H2=B, H3=C. Also let X1=c, X2=a,
X3=b.
VH2N VBN
VH1N VH3N VAN VC N
VX 2n Va n
VX1X2 Vca
VX1n Va n lags VAN
VX 2X 3 Vcn Va b by 150o
VX3X1
Vb c
VX3n Vbn
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 187
HV Wye – LV Delta
H1 X1
H2 X2
N
H3 X3
VH3N VX3n
Sequence VX 3X2
3-2-1 VX1X3 VX 2n
VH1N VH2N VX2X1
VX1n
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 188
94
The choice of phases A, B and C is arbitrary. Let
H1=C, H2=B, H3=A. Also let X1=c, X2=b, X3=a.
VH3N VAN
VH1N VH2N VC N VBN
VX3n
Va n
VX 3X2
Va b
VX1X3
Va n leads VAN
VX 2n Vca Vbn by 30o
VX2X1
VX1n Vb c
Vcn
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 189
VH1N VH2N VC N VBN
VX3n Vbn
VX 3X2 Vb c
VX1X3 VX 2n Va b Vcn Va n leads VAN
by 150o
VX2X1 Vca
VX1n Va n
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 190
95
Let H1=C, H2=B, H3=A. Also let X1=b, X2=a,
X3=c.
V H3N VAN
VH1N VH2N VC N VBN
VX3n Vcn
VX 3X2 Vca
Va n lags VAN
VX1X3 VX 2n Vb c Va n by 90o
VX2X1 Va b
VX1n Vbn
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 191
C H3 X3 b A H3 X3 b
B H2 X2 a B H2 X2 c
A H1 X1 c C H1 X1 a
Van lags VAN by 150o Van lags VAN by 210o
A H3 X3 c C H3 X3 a
B H2 X2 a B H2 X2 c
C H1 X1 b A H1 X1 b
Van lags VAN by 90o Van lags VAN by 270o
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 192
96
IEC Designation
The International Electrotechnical Commission
(IEC) uses the face of a clock in identifying the
phase shift.
11 1
IEC Designation for Y-
HV Delta– LV Wye
H3 X3
H2 X2
n
H1 X1
VH2N VX 2n
Sequence
VH1H2
1-2-3 VH2H3 VX n
1
VH1N V
H3H1
VH3N VX3n
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 194
97
HV Delta– LV Wye
H3 X3
C c
H2 X2
B b
n
H1 X1
A a
VBN Vbn
VAB VBC Va n Va n lags VAN
by 30o
VAN VC A VC N Vcn
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 195
Positive–Sequence Voltages
Consider a Y- transformer with a 30o phase shift.
B b
H2 X2
X1
N
A H3 X3 c
H1
C a
VBN1 Vbn1
(A-B-C) Va b1
Va n1 lags VAN1
Va n1 Vbc1
by 30o
Vca1
VAN1 VC N1
Vcn1
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 196
98
Negative–Sequence Voltages
Consider a Y- transformer with a 30o phase shift.
B b
H2 X2
X1
N
A H3 X3 c
H1
C a
VC N2 Vcn2
Va n2 leads VAN2
(A-C-B) Vcb2
by 30o
Va c2 Vbn2
Vba2
VAN2 VBN2 Va n2
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 197
Positive–Sequence Currents
Consider a Y- transformer
with a 30o phase shift.
B H2
Iba1 b
X2
IB1 X1
Ib1
Icb1
IA1 Ic1
A H3 Ia c1 X3
c
IC1 H1 Ia1
C a
Icb1 Ib1
IB1 (A-B-C)
Ia1 lags IA1
Ia1 by 30o
IA1 IC1 Iba1 Ia c1
Electrical & Electronics Engineering Institute
Ic1 EE 251 – Fault Studies
University of the Philippines Diliman 198
99
Negative–Sequence Currents
Consider a Y- transformer
with a 30o phase shift.
B H2
Iba2 b
X2
Ib2
IB2 X1
Icb2
IA2 Ic2
A H3 Iac2 X3
c
IC2 H1 Ia2
C a
Ic2 Ia c2
IC2
(A-C-B) Ia2 leads IA2
Ib2 by 30o
Iba2 Icb2
IA2 IB2
Ia2
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 199
100
The Base Currents
Base MVA3 x 1000
Base I
3 Base kVL
100,000
251 A at the 230 kV side
3 (230)
100,000
2,887 A at the 20 kV side
3 (20)
The Per-Unit Phase Fault Currents
IA 3.0 p.u.
IB IC 0
IA1 13 (IA a IB a2 IC ) 1.0 p.u.
IA2 13 (IA a2 IB a IC ) 1.0 p.u.
101
The Line Currents at the 20-kV side
Ia Ia0 Ia1 Ia2 1.732 p.u.
Ib Ia0 a2 Ia1 a Ia2 1.732 p.u.
2
Ic Ia0 a Ia1 a Ia2 0
The Line Currents in Amperes
Ia Ib 5,000 A I 0
c N
Check ampere turns: NHIH NX IX or H IH IX
NX
230 / 3
(753) 5,000 (Check)
20
Shell Type
102
Three-Legged Transformer Core
The 3-legged core type three-phase transformer
uses the minimum amount of core material. For
balanced three-phase condition, the sum of the
fluxes is zero.
30
Note: The zero-sequence
flux leaks out of the core
and returns through the
0 0 0
transformer tank.
3-Legged Core Type
103
Positive Sequence Impedance
Whether a bank of single-phase units or a three-
phase transformer unit (core type or shell type),
the equivalent impedance is the same.
Using per-unit values, the positive-sequence
equivalent circuit is
Z1 R1 jX1
+ + Note: The negative-
I I sequence impedance is
VH H X VX equal to the positive-
- - sequence impedance.
Z0 Z1
+
+
VH VX
- -
104
Zero Sequence Impedance*
Transformer Connection Zero-Sequence Network
Z0 Z1
+
+
VH VX
- -
Z0 Z1
+
+
VH VX
- -
Z0 Z1
+
+
VH VX
- -
105
Zero Sequence Impedance*
Transformer Connection Zero-Sequence Network
XH XX
+
+
VH Xm VX
- -
XH
+
+
VH Xm VX
- -
XH XX
+
+
VH Xm VX
- -
106
Zero Sequence Impedance*
Transformer Connection Zero-Sequence Network
XH XX
+
+
VH Xm VX
- -
XH XX
+
+
VH Xm VX
- -
107
Example: A three-winding three-phase transformer
has the following nameplate rating: 150/150/45
MVA 138YG-69YG-13.8 kV (Yy0d1).
H-X @ 150 MVA = 14.8%
H-Y @ 45 MVA = 21.0%
X-Y @ 45 MVA = 36.9%
Draw the positive and zero-sequence equivalent
circuits. Use 100 MVA and the transformer voltage
ratings as bases.
At the chosen MVA base,
ZHX 0.148(100 / 150) 0.10 p.u.
ZHY 0.21(100 / 45) 0.47 p.u.
ZXY 0.369(100 / 45) 0.82 p.u.
We get
ZH 12 (0.10 0.47 0.82) 0.125 p.u.
ZX 12 (0.10 0.47 0.82) 0.225 p.u.
ZY 12 (0.10 0.47 0.82) 0.595 p.u.
Positive/Negative Zero Sequence
Sequence Network Network
ZX ZX
ZH + ZH +
+ +
ZY + VX ZY + VX
VH VH
-
VY - -
VY -
- -
108
Generators
Sequence Impedance
109
Negative Sequence Impedance
IEEE Std 115-1995: Determination of the negative-
sequence reactance (Method 1)
The machine is operated at rated speed with its
field winding short-circuited. Symmetrical
sinusoidal three-phase currents of negative phase
sequence are applied to the stator. Two or more
tests should be made with current values above
and below rated current, to permit interpolation.
The line-to-line voltages, line currents and electric
power input are measured and expressed in per-
unit.
110
Zero Sequence Impedance
IEEE Std 115-1995: Determination of the zero-
sequence reactance (Method 1)
The machine is operated at rated speed with its
field winding short-circuited. A single-phase voltage
is applied between the line terminals and the
neutral point.
Measure the applied
voltage, current and V
electric power.
E A W
Field
111
Positive Sequence Impedance
The AC RMS component of the current following a
three-phase short circuit at no-load condition with
constant exciter voltage and neglecting the
armature resistance is given by
E E E t
I(t) exp
X ds X d ' X ds '
d
E E t
exp
X
d " X '
d "
d
112
IEEE Std 115-1995: Determination of the transient
and subtransient direct axis reactances (Method 1)
The direct-axis transient reactance is determined
from the current waves of a three-phase short
circuit suddenly applied to the machine operating
open-circuited at rated speed. For each test run,
oscillograms should be taken showing the short
circuit current in each phase.
The direct-axis transient reactance is equal to the
ratio of the open-circuit voltage to the value of the
armature current obtained by the extrapolation of
the envelope of the AC component of the armature
current wave, neglecting the rapid variation during
the first few cycles.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 225
113
Example: Calculation of transient and subtransient
reactances for a synchronous machine
Phase 1 Phase 2 Phase 3 Ave
(1) Initial voltage 1.0
(2) Steady-state Current 1.4 1.4 1.4
(3) Initial Transient Current 8.3 9.1 8.6
(4) I’ = (2)+(3) 9.7 10.5 10.0 10.07
(5) Xd’ = (1)(4) 0.0993
(6) Init. Subtransient Current 3.8 5.6 4.4
(7) I” = (4)+(6) 13.5 16.1 14.4 14.67
(8) Xd” = (1)(7) 0.0682
14
12 +
10 +++ Curve B
Current in phase 1 (per unit)
+
8 ++
+ ++
++
6 + ++
Line C
++
5 ++
++
+ +
4 ++
+ +
+ + ++
3
+
2.0
+ Line A
1.5
+
+
1.0
+
0.8
0.6 +
+ Curve A
0.4 +
0 10 20 30 40 50 60
Time in half-cycles
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 228
114
Average Generator Reactances
Reactance Turbo Water-Wheel Synchronous
Generators Generators Motors
Xd 1.10 1.15 1.20
Xq 1.08 0.75 0.90
X d‘ 0.23 0.37 0.35
X q‘ 0.23 0.75 0.90
X d” 0.12 0.24 0.30
X q” 0.15 0.34 0.40
X2 0.12 0.24 0.35
Ungrounded Generator
If the generator is connected ungrounded-wye or
delta, no zero-sequence current can flow. The
sequence networks for the generator are shown
below.
F1 F2 F0
jX1
+ jX2 jX0
Eg
-
N1 N2 N0
Positive Negative Zero
Sequence Sequence Sequence
115
Grounded-Wye Generator
The sequence networks for the grounded-wye
generator are shown below.
F1 F2 F0
jX1
+ jX2 jX0
Eg
-
N1 N2 N0
F1 F2 F0
jX1 jX0
+ jX2
Eg 3Zg
-
N1 N2 N0
116
Electric Utility (Power Grid)
Thevenin’s Theorem
Any linear active network with output terminals AB can
be replaced by a single voltage source Vth in series with
a single impedance Zth
A A
Linear + Zth
Active Vth
Network -
B B
117
Utility Fault MVA
Electric Utilities conduct
Electric short circuit analysis at the
Utility Connection Point of their
Grid customers
IF
Fault Customers obtain the Fault
Data at the Connection Point
to represent the Utility Grid
for their power system
analysis
Customer
Facilities
118
Equivalent Circuit of Utility
I TPF
Vf
S TPF V f I TPF
V
f
2
Z1 Z1
Where, Z1 and Z2 are the
equivalent positive-
Z1
kV
2
sequence and
Z 2 negative-sequence
Fault MVA3 impedances of the
utility
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 237
I SLGF
3V f
S SLGF V f I SLGF
3Vf
2
Z1 Z 2 Z0 2Z 1 Z 0
Z1 Z 2
2Z 1 Z 0
3Vf
2
119
Equivalent Circuit of Utility
Example:
Z1 Z 2
kV 2
69
2
1.3603
Fault MVA3 3500
In Per Unit,
Z actual 1.3603
Z1 Z 2 0.0286 p.u.
Z base 47.61
or
100MVABASE
Z1 Z 2 0.0286 p.u.
3500MVAFAULT
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 240
120
Equivalent Circuit of Utility
Solving for the Resistance and Reactance,
2Z 1 Z 0
3Vf
2
31.0
2
0.1
S SLGF 30
Re al2 Z 1 Z 0 0.1cos tan-1 20 0.004994 p.u.
Im ag2 Z 1 Z 0 0.1sintan -1
20 0.099875 p.u.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 242
121
Equivalent Circuit of Utility
2 Z 1 Z 0 0.004994 j0.099875
Z 0 0.004994 j0.099875 20.0013 j0.028571
0.003694 j0.042733 p.u.
+ + +
0.0013+j0.028571
+ 0.0013+j0.028571 0.003694 j0.042733
V f 10
-
- - -
Positive Negative Zero
Sequence Sequence Sequence
122
Equivalent Circuit of Utility
The equivalent sequence networks of the Electric
Utility Grid are:
+ + +
R1 +jX1
+ R2 +jX2 R0 +jX0
Eg
-
- - -
Positive Negative Zero
Sequence Sequence Sequence
Utility Thevenin Equivalent Circuits
123