85 Ea e 78923 - 00
85 Ea e 78923 - 00
Sheet 1 of 16 Rev. 00
ORDER N° 527572
DATE : 02-07-10
This document is the property of Saipem who will safeguard its right according to the civil and penal provision of law
AFAM – RIVERS STATE GOVERNMENT
OPEN CYCLE POWER PLANT
INDEX
SMOKE DETECTOR 3
DISCHARGE RED FLASHING BEACON & ACOUSTIC ALARM 3
MANUAL CALL POINT 3
H2 GAS DETECTOR 4
GAS HORN 4
I.S. SMOKE DETECTOR 4
AM1000 CENTRAL REVELATION 5
CENTRAL MINIGAS 5
LFAP PANEL 5
MICROPROCESSOR FOR AUTO/MAN/INHIBIT 5
FM200 CYLINDER 6
DISCHARGE VALVE, W/ PRIMARY TRIM, Sv SERIES 7
MANUAL VALVE ACTUATOR 8
SWITCH LOW PRESSURE SUPERVISORY, Sv 9
ELECTRIC VALVE ACTUATOR 10
GAUGE ASSEMBLY PRESSURE, FM-200, Mv & Lv SERIES 11
FLEX HOSE 12
VALVE CHECK, 1-1/4” F-NPT, Sv SERIES 13
RADIAL NOZZLE, 360° - 4 ORIFICIES 14
SWITCH, DISCHARGE PRESSURE 15
MULTIPLE CYLINDER ARRANGEMENT, Sv SERIES 16
2 of 16
AFAM – RIVERS STATE GOVERNMENT
OPEN CYCLE POWER PLANT
3 of 16
AFAM – RIVERS STATE GOVERNMENT
OPEN CYCLE POWER PLANT
H2 GAS DETECTOR:
Installed quantity N° 2
Make NOTIFIER
Model VGS.AD-H2
Voltage range 12 to 24 Vdc -20% +15%
Absorbed current 140 mA medium – 180 mA max
Storage temperature -25°C to +60°C
range
Operating temperature -10°C to +55°C
range
Humidity 20 to 90% (without condensate)
Weight 400g
ATEX certificate CESI01ATEX053 in compliance with EN50014; EN50018
GAS HORN:
Installed quantity N° 1
Make NOTIFIER
Model EMA24RS2R/4R
Voltage range 24 Vdc±20%
Power supply 100mA
Temperature range -25°C to +55°C
IP Rating IP 66
Reference rules EN 54-3
4 of 16
AFAM – RIVERS STATE GOVERNMENT
OPEN CYCLE POWER PLANT
CENTRAL MINIGAS:
Installed quantity N° 1
Make NOTIFIER
Model MINIGAS
Voltage supply 220Vac
Battery Max 2x12V – 7Ah
Stand-by time 18 hours
LFAP PANEL:
Installed quantity N° 4
Make NOTIFIER
Model UDS-3
Voltage range 230 Vac +10% -15%
Frequency 50/60 Hz
Main current 0.7 Aac
Battery 2x12V – 7Ah
Operating temperature range -5°C to +40°C
Storage temperature range -10°C to +50°C
Reference rules EN 11294-1, 54-2 e 54-4
5 of 16
AFAM – RIVERS STATE GOVERNMENT
OPEN CYCLE POWER PLANT