HDPE Pipe System Design PDF
HDPE Pipe System Design PDF
Sclairpipe ®
Systems Design
2
Contents
RULES FOR CHOICE OF PIPE WEIGHT
Pressure Class Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Design Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Summary of Rules for Pipe Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
CHEMICAL RESISTANCE
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
General Guide to Resistance of Sclairpipe to Various Chemicals . . . . . . . . . . . . . . . . . . .12
The accuracy or applicability of all information contained herein is intended as a guide and is not guaranteed. Hence, KWH Pipe assumes no obligation
or liability for this information. All tables and statements may be considered as recommendations but not as warranty. Users of our products should perform
their own tests to determine the suitability of each such product for their particular purposes. KWH Pipe’s liability for defective products is limited to the
replacement, without charge, of any product found to be defective. Under no circumstances shall it be responsible for any damages beyond the price of the
products, and in no event shall it be liable for consequential damages.
Index
3
DESIGN CRITERIA
For each pipe DR number, there is a corresponding maximum allowable continuous operating pressure at 73.4°F when
used in water service. This pressure rating varies when different pipe design hoop stress values (HDS) are substituted into
the pipe design equation. Typically, HDPE pipes are made from materials qualified as PE 3408 which means the
compound has a HDS of 800 psi.
This pipe design methodology has been checked against long term pipe strain. Strain in polyethylene pipe has been
found to govern the life of the pipe system. Operation at the design stress level should induce no greater than 3% strain
over 50 years of continuous service at 73.4°F. This is consistent with other investigations where the long term strain
design limit of 3% to 4%, incorporating a 0.5 design factor, has been designated.
Installation of 24 inch SCLAIRPIPE for a twin sewage siphon line SCLAIRPIPE used in a tailing applications at a molybdenum mine
in Victoria, B.C. The pipe is completely resistant to seawater and its in Arizona. Inclusion of 2% finely dispersed carbon black ensures
smooth surface discourages the adherence of algae and other that the pipe is resistant to ultraviolet light degradation enabling it to
marine growths. be installed at grade. Anchoring of the pipeline is achieved simply
by dumping a load of tails on the pipe at regular intervals.
Index
4
It should be noted that the above requirements are test requirements under laboratory conditions and therefore must be
adjusted by a design factor to be used for pipe pressure rating purposes. Although a basic design factor of 0.5 is used for
determining long-term (50 years) operating limits, shorter term phenomena may be related to the “safe strain limit” which
laboratory investigations demonstrate to be approximately 3% to 4%. The following maximum stress levels are therefore
recommended for protection against varying terms of pressure exposure for Sclairpipe produced from a PE3408 material:
The above recommendations are based on the assumption that the pipe will not be subjected to other imposed stresses.
They refer to phenomena which cease within the time limits given and the pipe then returns to a “normal” operating
pressure. These phenomena may be repeated with reasonable expectation that the service life expectancy of the piping
will not be significantly affected.
Regular pressure cycling, outside of hydraulic transient situations, should not be accommodated in this way. When
such cycling is expected as a regular condition of operation, the highest pressure anticipated for the majority of the
operating time should be considered as the operating pressure and treated as though it would persist continuously for the
design life of the system.
SHOCK LOADS
Hydraulic shock loads (sometimes called “water hammer”) can be difficult to calculate in complex systems, however, their
presence and cause can be predicted. For further information reference should be made to the “Waterhammer and
Hydraulic Transients” section of this manual.
It is often more economical to eliminate the cause rather than attempt to accommodate stresses by increasing the
standard pressure rating of the selected pipe. It is known that under some conditions, a lighter weight pipe will be more
resistant to damage under these conditions than a heavier weight pipe and that rigid materials and structures will increase
the magnitude of the stresses. Overpressure is not likely to be a limiting factor in design. Negative pressures, resulting
from column separation and pressure shocks resulting from the collapse of the separation, are more likely to be limiting
factors in design.
EXTERNAL LOADS
Performance limits with regard to earthloading design and external hydraulic loading follow the recommendations given
in “Earthloading - Design of Underground Piping Systems” and “Vacuum and External Hydraulic Overpressure” sections
of this manual. Strength requirements under these conditions are functions of the cube of the Dimension Ratio (DR).
ENVIRONMENTAL CONDITIONS
Temperature is the most important environmental consideration. For operation at temperatures in excess of 73.4°F, a
thermal service factor should be applied to the pressure rating as described in “Design Considerations Related to
Environment” section of this manual.
Corrosive conditions are normally not a consideration with SCLAIRPIPE, but they do occur in industrial processing
uses associated with strong oxidizing chemicals (see section on “Chemical Resistance and Permeability”). Oxidation,
which results from exposure to certain aggressive chemicals is usually manifested by embrittlement of the surface and a
significant reduction in the long-term stress resistance of the material.
The polyethylene material used in the manufacture of SCLAIRPIPE has a high resistance to environmental stress
cracking. However, when the pipe is stressed in the presence of certain surface active chemicals, e.g. wetting agents,
environmental stress cracking can take place with a detrimental effect to the products projected long-term life.
When chemical resistance is in doubt, exposure tests are recommended. Generally these tests follow the procedures
described in ASTM D543. Changes in tensile properties can be measured on ring tensile specimens in accordance with
the procedures described in ASTM D2513, paragraph 8.6. Significant variation between control specimens and those
exposed to the chemical is generally accepted as evidence of corrosive degradation and decisions as to use of SCLAIRPIPE
in this application shall be made accordingly.
Direct assistance of KWH technical personnel is recommended where further explanation and assistance is required.
Index
5
For pipelines consisting of continuously extruded SCLAIRPIPE, a Hazen Williams C-factor of 150 to 155 is generally
used in the above formula for water flowing in the pipe. This value recognizes the essentially frictionless nature of
SCLAIRPIPE, and represents about the highest permissible C-factor based on Moody’s work on “frictionless” pipe. When
standard pipe lengths are joined by butt fusion into continuous lines, the resulting fusion beads have a minor effect on
the overall friction factor and the use of a “C” value of 150 is recommended. These values have been substantiated by
test work conducted by the National Research Council in Ottawa. The testing was done using a 200 foot length of butt-
fused 4 inch SCLAIRPIPE. Tests were first done with fusion beads in the line and secondly with the fusion beads reamed
out.
Head losses in flowing systems are normally composed of two components, the retardant to flow in the pipe due to
friction at the walls and the retardant to flow due to elevation changes and directional changes at elbows, tees or valves.
For directional changes, the standard method of relating head losses to equivalent footage of pipe should be used and the
C-factor of 150 (for fusion-joined systems) should be applied to the total equivalent footage of pipe.
Over the life of the pipe, there will be no corrosion or solution effect and the interior surface will be changed only
through deposit of scale or algae, neither of which adhere tightly to polyethylene and hence, will have a very small effect
on flow.
Experimental testing for flow coefficients in forced sewage systems has been conducted by an independent engineering
consultant. Tests were done on two separate sewage forcemains, approximately 1000 and 1800 feet in length, both
constructed of 6 inch SCLAIRPIPE. The lines, carrying typical municipal sewage, had both been operating for more than
five years. Based on these tests, a long-term “C” value of 130 is recommended for forced sewage applications.
Where uneven grades may cause air entrapment or where the nature of the fluid is such that deposition of solids may
occur to a significant extent, the use of a lower C-factor may be justified. Elimination of the problem through the use of
bleedoffs, venting valves, flush-out ports and other familiar appurtenances is as practical with SCLAIRPIPE as with
conventional piping materials, and is usually less expensive that the use of overdesign as a means of correction.
Published flow loss tables are available for all sizes of SCLAIRPIPE from your local SCLAIRPIPE representative, to
simplify the procedure of selecting an appropriately sized pipeline for your application.
Index
6
Ps = ∆V
a_____
2.31 g
where:
Ps = excess pressure due to waterhammer, (psi)
∆V = change in velocity causing waterhammer, (ft/s)
g = acceleration due to gravity, (32.2 ft/s2)
a = velocity of wave travel in elastic pipe, (ft/s)
120
NOTE: ASSUMES INSTANTANEOUS
110 VELOCITY REDUCTION
FROM 5-0 f.p.s.
100
OVERPRESSURE (p.s.i.)
BURIED PIPE
90
80
70
50
40
32.5 26 21 17 15.5 13.5 11 9 7.3 6.3
The value of “a” depends on the method of anchoring. The usual installation condition for polyethylene pipe is that
in which it is anchored against movement throughout its length, as it occurs when it is buried underground. The other
installation condition is that in which the pipeline is not anchored against movement, as it occurs in free-standing pipe.
[ ]
1 + K (DR-2) 1/2
E
(Buried Pipe)
a = 4720
[ ]
1 + K (DR-2) 1/2
E
(Free-Standing Pipe)
where:
K = bulk modules of elasticity of liquid, in psi
(approx. 300,000 psi for water)
DR = dimension ratio
= outside diameter
______________
min. wall thickness
Comparative calculations show that, under similar conditions, wave velocities and the resulting overpressures in buried
SCLAIRPIPE are in the order of 1/5 of those experienced in steel pipe. (See Fig. 1). The lower overpressures in
SCLAIRPIPE are advantageous, however, due to the slower wave velocities, valve or pump operating procedures may
require modification. The time “period” of the wave is defined as twice the length of the line under consideration divided
by the wave velocity. To avoid reinforcement of the pressure waves, it is necessary to make changes in fluid column
velocity over a time interval that allows successive pressure waves to dampen out. The changes should be made over an
interval representing some 6 to 8 times the pipe “period”. For example, if the pipe period is calculated to be 4 seconds,
valve openings and closings should be restricted to a minimum interval of about 25 seconds. When pumps are involved,
a valve at the pump discharge should be in the closed position for pump startup and should be closed prior to pump
shutdown; it should also be ensured that the valve operating interval exceeds the minimum time interval.
The addition of appurtenances on the pipeline complicates calculation of the “period” and analysis of the waterhammer
situation. Graphical solutions are available, however, a full analysis of the phenomenon of hydraulic transients is very
complicated for most systems.
The design of SCLAIRPIPE provides for a shockwave overpressuring of two times the pressure rating of the pipe. If
the analysis indicates that this design limit (2 times recommended operating pressure for the pipe) will be exceeded, the
system should be designed so as to reduce or eliminate the causes of overpressuring. It is generally recommended that the
possibilities of waterhammer and its effect be investigated for pumped lines or gravity flow lines operating at velocities in
excess of five feet per second.
28 inch series 60 SCLAIRPIPE was used to replace a woodstave line SCLAIRPIPE was the material of choice for a 20 mile brine line
at a mine site in Noranda, Quebec. This 10,000 foot water supply line running from a potash mine in Sussex, N.B. to the Bay of Fundy.
had a design pressure of 50 psig and was installed in 1978. The line was installed without surge protection devices although it
included sections operating in excess of 200 psig.
Index
8
DESIGN CRITERIA
When selecting the most appropriate wall thickness or DR for Sclairpipe to resist anticipated burial conditions or when
confirming the adequacy of a selection which was made based on pressure class requirements three design criterion are
considered separately; vertical deflection, wall buckling and wall compression or crushing. The amount of deflection
which can be expected under specific burial conditions may be estimated using the form of the Iowa pipe deflection
formula presented below. The estimated vertical deflection as a percentage of the mean pipe diameter is then compared
to the safe design limits presented in Table 1. In order to verify the adequacy of the pipe-soil system against wall buckling
or collapse the safe allowable buckling load (qa) is determined using the equation presented and compared to the
anticipated applied loads. Compressive stress in the pipe walls may also be estimated and compared to the safe
compressive strength of HDPE which is conservatively estimated as 800 psi.
32.5 8.6
Lateral outward
26 6.5 movement of pipe wall
21 5.0
17 4.0
11 3.3
Figure 2: Mobilization of Enveloping Soil through Pipe Deformation
9 2.6
Index
9
Table 3
Table 2 Embedment Classes per ASTM D-2321
Vertical Soil Load in lbs./in2 Average Value of E’
Depth to Top Soil Density Soil Density Soil Density Soil Density
of Pipe in ft. 90 lbs.ft3 100 lbs.ft3 110 lbs.ft3 120 lbs.ft3
Degree of Compaction
of Embedment Material 1
(inorganic). Includes
2
Depth of Backfill (ft.)
Where: H = burial depth to the top of the pipe in ft. the following equation;
Davg = mean pipe diameter (O.D. - tmin)
= (W + W ) / (2tmin)
C C L (3.0)
For most pipe installations satisfaction of the wall
buckling requirement is assured when the following
equation is true; Satisfaction of the wall compression is assured when the
h + R (W /Davg) + Pv ≤ qa W W (2.1)W C
following equation is true;
≤ 800 psi
C (3.1)
Where; = specified weight of water (that is, 0.0361
W
Table 4
CRITICAL PRESSURES FOR PIPE WITHOUT SUPPORT
Net External
Dimension Critical Pressure (Pcr)
Ratio (psi)
32.2 1.0
26 1.9
21 3.6
17 6.8
15.5 8.9
13.5 13.5
11 25.0
9 45.7
Bedding Limitations:
• Always level the trench bottom, taking care to remove all sharp rocks and/or protrusions within 6 inches of the pipe.
• Ensure that the bedding material is worked into uniform contact with the pipe at the haunches.
• When bedding soil is non-compactible by its own weight, use mechanical compactions - DO NOT
MECHANICALLY COMPACT DIRECTLY ON TOP OF THE PIPE - PLACE ONE FOOT OF BEDDING
BEFORE COMPACTING DIRECTLY OVER THE PIPE.
• Do not allow rocks or frozen clods within a one foot bedding “envelope” around the pipe.
• See the Construction brochure for further details and burial information.
Now check:
Solution 0.0361x0.00 + 1.00x364.8/46.547 + 67.2/46.547 ≤ qa (2.2)
Part 1 Deflection; 9.281 psi ≤ 11.24 psi
WC = 7.6 x 48 = 364.8 lbs/in. Pipe selection is adequate for buckling criteria
WL = 1.4 x 48 = 67.2 lbs/in.
r = (48 - 1.453)/2 = 23.274 in. Part 2 Wall Compression; (3.0)
l = 1.4533 / 12 = 0.256 in. = (364.8 + 67.2) / (2x1.453)
C
Table 5: ESTIMATED CRITICAL EXTERNAL COLLAPSE PRESSURE (psi) - FOR UNSUPPORTED SCLAIRPIPE¤
vs TIME UNDER CONTINUOUS EXTERNAL PRESSURE LOADING AT 73.4¡F.
Initial ovality: 2% Includes: 2:1 Safety Factor
SCLAIRPIPE DR
Time Duration of Load
(Creep Modulus) 32.5 26 21 17 15.5 13.5 11 9 7.3 6.3
1 minute
(110,000 psi) 3.6 6.9 13.2 24.8 32.8 49.6 91.7 167.4 313.8 488.2
1 hour
(53,500 psi) 1.7 3.4 6.4 12.1 15.9 24.1 44.6 81.4 152.6 237.4
10 hours
(42,500 psi) 1.4 2.7 5.1 9.6 12.7 19.2 35.4 64.7 121.2 188.6
100 hours
(39,000 psi) 1.3 2.5 4.7 8.8 11.6 17.6 32.5 59.4 111.3 173.1
1,000 hours
(34,000 psi) 1.1 2.1 4.1 7.7 10.1 15.3 28.3 51.8 97.0 150.9
10,000 hours
(32,000 psi) 1.0 2.0 3.8 7.2 9.5 14.4 26.7 48.7 91.3 142.0
50 years
(30,000 psi) 1.0 1.9 3.6 6.8 8.9 13.5 25.0 45.7 85.6 133.1
Index
12
Chemical Resistance
INTRODUCTION
Outstanding resistance to both internal and external chemical attack has made the SCLAIRPIPE system the material of
choice for the transport of lower temperature (below 150°F) fluids in adverse chemical environments. High-density
polyethylene is chemically inert to a wide range of industrial chemicals.
The chemical, its concentration in the fluid, its temperature, its contact time with the piping material and other service
conditions, determines the suitability and expected service life of the SCLAIRPIPE system for the application. For most
bases, acids, inorganic salts and other chemicals, you usually apply the same design parameters as considered for water
service conditions. Chemical attack of SCLAIRPIPE may be divided into three categories: OXIDATION, STRESS-
CRACKING and PLASTICIZATION.
OXIDIZERS are the only group of materials which are capable of chemically degrading the SCLAIRPIPE system.
Some strong oxidizers have only a gradual effect on the pipe, therefore short-term effects are not measurable. If
continuous exposure is expected, chemical effects should be defined. The following oxidizers are unsuitable for long-term
contact with the SCLAIRPIPE system: Nitric acid (fuming), Sulphuric acid (fuming), Aqua Regia, wet chlorine gas and
liquid bromine. However, weaker solutions of mineral acids, such as battery acid or reagent nitric acid, do not attack the
pipe. Other common oxidizing agents, such as hydrochloric acid, hydrofluoric acid, hydrobromic acid and hydrogen
peroxide have been shown to have no measurable effects on SCLAIRPIPE after 3 or 4 years’ exposure.
STRESS CRACKING AGENTS are chemicals that accelerate the cracking of polyethylene when subjected to stress,
but have no chemical effect on the material itself. Although some polyethylenes are extremely sensitive to brittle fracture,
SCLAIRPIPE is highly resistant to this type of failure.
PLASTICIZERS are chemicals that can be absorbed to varying degrees by polyethylene, causing softening, some loss
of yield strength and some gain in impact strength. These plasticizing materials cause no chemical degradation of
polyethylene and they are not solvents for the material. SCLAIRPIPE is designed to give high resistance to this absorption
and consequent weakening, but if it is to be exposed continuously to these environments, an added safety factor should
be applied. Some of these materials are sufficiently volatile that when they are removed, the pipe will “dry out” and return
to its original strength. Intermittent exposure to these materials, therefore, has little or no effect on SCLAIRPIPE.
*The classification “variable resistance” is very broad. Depending on the nature of the chemical, its concentration, the
service temperature and pressure and the time of exposure, SCLAIRPIPE can be either very resistant or very susceptible
to attack. Therefore, when SCLAIRPIPE is said to have variable resistance to a chemical, it is strongly recommended that
caution be exercised and that the specific application be discussed with a technical representative of KWH Pipe.
Installation of this 8 inch series 125 SCLAIRPIPE tailings line called Polyethylene’s abrasion resistance and chemical inertness were
for it to be supported on a trestle to maintain grade. Note the guides prime considerations in the decision to specify SCLAIRPIPE in this
located at regular intervals to hold the pipe on the trestle during process pipe application.
thermal expansion and contraction situations.
Index
13
Index
14
Termites, etc.:
SCLAIRPIPE is not attacked by termites, ants or other burrowing insects, or by marine worms such as teredos.
Rodents:
SCLAIRPIPE can be damaged by rodents but is not preferentially attacked by them. In ground infested by gophers or
groundhogs, pipe should be placed more than 30 inches below the surface.
Toxicity:
The resin compound used in the manufacture of SCLAIRPIPE contains nothing which can be extracted by prolonged
contact with water. It imparts no taste or odours to potable water. The antioxidant added to the compound to prevent
thermal degradation during processing is of a type and in a quantity approved by Food and Drug control administrations
in Canada, the United States, Great Britain and most European countries, for contact with food and potable water.
SUNLIGHT AND WEATHER
SCLAIRPIPE contains finely divided and thoroughly dispersed carbon black which gives virtually permanent protection
against ultra-violet light. However, if pipe is intended for installation above ground, particularly in desert locations, it
should be remembered that other problems may arise related to temperature differentials rather than simple degradation.
These are discussed below under “Temperature”.
Exposure to conditions of alternating wetness and dryness or freezing and thawing does not require any special
precaution.
TEMPERATURE
Operating Temperatures:
As with all homogeneous thermoplastic piping, polyethylene pipe loses stiffness and tensile strength as its temperature
increases. SCLAIRPIPE is not normally recommended for use at temperatures in excess of 140°F. For systems where the
service temperature frequently exceeds 73°F, the rated allowable working pressure of the pipe should be decreased.
The required pipe DR rating can be selected by using the minimum pressure rating, determined from Figure 4. The
pipe chosen should have a long-term pressure rating at least as high as that determined from the following relationship:
150 65
140 60
TEMPAERATURE (F)
TEMPERATURE (C)
130 55
120 50
45
110
40
100
35
90
30
80
25
70
1.0 0.9 0.8 0.7 0.6 0.5
Figure 4: Thermal Service Factors for SCLAIRPIPE used at Service Temperatures higher than 73°F.
Index
15
For gravity pipe in which the internal pressure is effectively zero, the service temperature should not exceed 150°F. Where
there is high external stress on the pipe, the pipe DR rating may have to be selected by using the same thermal service
factor as is used for pressure pipe. If the service requirements warrant a reduced service life or a different margin of safety,
a qualified representative of KWH Pipe should be consulted for assistance.
Thermal Expansion:
The coefficient of thermal expansion for SCLAIRPIPE under completely unrestrained conditions is 8 x 10-5 in./in./°F.
(14 x 10-5cm./cm.°C). However, in most conditions of installation, some restraint is automatically provided. With pipes
of 4 inch nominal diameter or greater, simple burial under 2 feet or more of soil usually provides ample restraint. Under
these conditions, expansion or contraction due to temperature changes does not occur and no design considerations are
required to provide restraint. Pipe installed in a trench should be at the temperature of the trench bottom before
backfilling is started. The temperature differences after backfilling will not have any contraction or expansion effects
because of the friction between the soil and pipe.
Smaller diameter pipes, i.e. 1/2” to 3”, should be snaked during installation in the trench, regardless of the burial depth,
to increase the restraint available from friction with the soil.
If unrestrained, a pipeline installed above ground will tend to move laterally as a result of temperature changes,
especially if the line is empty. If space is limited, or if the line is installed on a pipe bridge, restraining supports must be
provided. When lateral movement is restricted, expansion will take place in either length or diameter, whichever is less
restrained. (See Construction brochure, Surface Installation Section, for further details).
Of particular importance in design is the condition in which pipe passes from an area of adequate restraint into an area
of poor restraint. Failures can result if the pipe and connections do not have adequate support at points of transition from
large fixed structures to less restricting conditions. (See Construction brochure, Buried Installation Section, for further
details).
Thermal Conducitivity:
Polyethylene is a relatively poor conductor of heat compared to metals. The coefficient of thermal conductivity for
SCLAIRPIPE is approximately 2.5 BTU/hr/ft 2/°F. per inch of thickness. As a result, temperatures which are unevenly
applied do not dissipate readily and thermal effects can be localized.
This property can be used to advantage in water systems in cold climates. The slow heat transfer inhibits freezing and,
if the usual precautions are taken with respect to depth of burial, accidental freezing is practically eliminated. If the pipe
does freeze, it does not burst and will resume its function upon thawing. Cyclical freezing, as in lines used for summer
service only, is well tolerated but it is recommended that such lines be depressurized at shutdown. Irrigation lines have
been operated in this way for many seasons without damage.
Localization of heated areas can cause noticeable deformation of the pipe. Solar heat, absorbed on one side of the pipe,
is not readily conducted to the other side. Lines installed on the surface of the ground, unprotected from solar exposure,
will require extensive anchoring to confine and control movement. The principle of design for such systems is to ensure
that the movement is controlled over short lengths and is confined within a convenient plane where room to
accommodate the movement can be provided.
INCIDENTAL DAMAGE
Despite its toughness and resilience, SCLAIRPIPE may be scuffed or scratched on the outside surface during handling.
This does not affect its serviceability unless severe gouging or cutting takes place. In general, specifications should call for
repair or removal of pipe which is gouged to depths greater than 10% of the wall thickness. V-shaped cuts of any depth
occurring on the inside of the pipe must be removed.
At Kirkland Lake in Northern Ontario, a gravity sanitary sewer of In this mine tailings applications, 36 inch series 60 SCLAIRPIPE is
18 inch SCLAIRPIPE is installed in a rock tunnel. Pipe is laid above installed at grade on a prepared right of way. The pipe routing
ground, tied down to wooden sleepers and secured with rock incorporates a number of gentle bends to accommodate thermal
anchors. expansion and contraction forces, minimizing the overall stresses
on the pipe.
Complete Engineering - Our Specialty
A member of
Registered to
PLASTICS
PIPE ISO 9002
INSTITUTE