Daikin VRV Sheet

This document provides a schedule and specifications for a Daikin VRV air conditioning system. It lists 15 indoor units of various sizes and models to serve different rooms totaling 34.51 tons. It also specifies two outdoor units totaling 32 HP to support the indoor units. Piping, wiring, insulation and other ancillary works are detailed. Cost estimates are provided for material, labor and totals for various line items of the VRV system installation.

Uploaded by

Sridhar Reddy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
847 views6 pages

Daikin VRV Sheet

This document provides a schedule and specifications for a Daikin VRV air conditioning system. It lists 15 indoor units of various sizes and models to serve different rooms totaling 34.51 tons. It also specifies two outdoor units totaling 32 HP to support the indoor units. Piping, wiring, insulation and other ancillary works are detailed. Cost estimates are provided for material, labor and totals for various line items of the VRV system installation.

Uploaded by

Sridhar Reddy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

ANNEXURE II DAIKIN VRV EQUIPMENT SCHEDULE

S.No. Description Area (Sft) Occupancy Suggeste Daikin Qty Total TR


d TR IDU TR
3 CLSS ROOM 600 57 5.1 3 1 3
4 FOYER 166.49 3 1.5 1.65 1 1.65
5 WAITING AREA 167.61 5 1.5 1.65 1 1.65
6 ENTRANCE AREA 258.21 3 2.3 2.65 1 2.65
7 LOBBY 127.28 5 1.1 1.32 1 1.32
8 HOME THEATRE 303.86 5 2.7 2.65 1 2.65
9 SIR CABIN 320 3 2.9 2.65 1 2.65
10 LIVINGROOM 373.64 7 3.2 3.31 1 3.31
11 FAMILY LIVINGROOM 650.96 7 5.5 2.65 2 5.3
12 MOTHER BEDROOM 198.81 2 1.7 2.08 1 2.08
13 GUEST BEDROOM 243.36 2 2.1 2.65 1 2.65
14 DAUGHTER BEDROOM : 02 194.79 2 1.7 1.65 1 1.65
15 M.B. WALK IN 160.16 3 1.3 1.65 1 1.65
16 MASTER BEDROOM 285.02 2 2.4 2.65 1 2.65
34.86
CHEDULE
Equipment Model
Type of
Remote
Round Flow Cassette FXFQ100LUV1 CARDED
Round Flow Cassette FXFQ50LUV1 CORDLESS
Round Flow Cassette FXFQ50LUV1 CORDLESS
Round Flow Cassette FXFQ80LUV1 CORDLESS
Round Flow Cassette FXFQ40LUV1 CORDLESS
Round Flow Cassette FXFQ80LUV1 CORDLESS
Round Flow Cassette FXFQ80LUV1 CORDLESS
Round Flow Cassette FXFQ100LUV1 CARDED
Round Flow Cassette FXFQ80LUV1 CORDLESS
Round Flow Cassette FXFQ63LUV1 CARDED
Round Flow Cassette FXFQ80LUV1 CORDLESS
Round Flow Cassette FXFQ50LUV1 CORDLESS
Round Flow Cassette FXFQ50LUV1 CORDLESS
Round Flow Cassette FXFQ80LUV1 CORDLESS
Suggeste Daikin Type of Capacity ODU
S.No. Description Area (Sft) Occupancy d TR IDU TR Qty Total TR Equipment Model
Remote Index Total Index IDU Index ODU HP Index Diversity %
Ground Floor
6 DINING AREA 267.44 8 2.3 2.65 1 2.65 Round Flow Cassette FXFQ80LUV1 CARDED 80 80
8 FOYER 166.49 3 1.5 1.65 1 1.65 Round Flow Cassette FXFQ50LUV1 CORDLESS 50 50
9 WAITING AREA 167.61 5 1.5 1.65 1 1.65 Round Flow Cassette FXFQ50LUV1 CORDLESS 50 50
10 ENTRANCE AREA 258.21 3 2.3 2.65 1 2.65 Round Flow Cassette FXFQ80LUV1 CORDLESS 80 80
11 LOBBY 127.28 5 1.1 1.32 1 1.32 Round Flow Cassette FXFQ40LUV1 CORDLESS 40 40
12 HOME THEATRE 303.86 5 2.7 2.65 1 2.65 Round Flow Cassette FXFQ80LUV1 CARDED 80 80
13 SIR CABIN 278.16 3 2.5 2.65 1 2.65 Round Flow Cassette FXFQ80LUV1 CORDLESS 80 80
1043 32 800 130%
14 LIVINGROOM 373.64 7 3.2 3.31 1 3.31 Round Flow Cassette FXFQ100LUV1 CARDED 100 100
15 FAMILY LIVINGROOM 650.96 7 5.5 2.65 2 5.3 Round Flow Cassette FXFQ80LUV1 CORDLESS 80 160
16 MOTHER BEDROOM 198.81 2 1.7 2.08 1 2.08 Round Flow Cassette FXFQ63LUV1 CARDED 63 63
19 GUEST BEDROOM 243.36 2 2.1 2.65 1 2.65 Round Flow Cassette FXFQ80LUV1 CORDLESS 80 80
20 DAUGHTER BEDROOM : 02 194.79 2 1.7 1.65 1 1.65 Round Flow Cassette FXFQ50LUV1 CORDLESS 50 50
21 M.B. WALK IN 160.16 3 1.3 1.65 1 1.65 Round Flow Cassette FXFQ50LUV1 CORDLESS 50 50
22 MASTER BEDROOM 285.02 2 2.4 2.65 1 2.65 Round Flow Cassette FXFQ80LUV1 CORDLESS 80 80
TOTAL NO. of Indoor Units & Capacity-TR 15 34.51 1043 38

TOTAL IDU TONNAGE 34.51


TOTAL ODU HP 41.6
DIVERSITY 130%
REQUIED ODU HP 32

TOTAL INDOOR UNITS


S.No. Model TR Qty Total TR
Round Flow Cassette
1 FXFQ50LUV1 1.66 4 6.64
2 FXFQ80LUV1 2.65 8 21.2
FXFQ40LUV1 1.32 1 1.32
FXFQ100LUV1 3.34 1 3.34
FXFQ63LUV1 2.07 1 2.07
TOTAL 15 34.57
TOTAL OUTDOOR UNITS
S.No. Out door Unit HP Qty Total
1 RXYQ16TRY6 16 2 32
Note:- The Outdoor unit is provided for 34.51 TR, considering operational AC TR is not exceeding 34.51 TR at any point of time.
LOW SIDE COST FOR VRV SYSTEM EAST SMALL VILLA PO & WO
Rate Rate Rate Rate
S.NO. DESCRIPTION QTY. Unit
Material Labour Material Total Labour Total
ANCILLARY WORKS
1 Lifting, Shifting and positioning of Out door units and Indoor Units
a Lifting,Shifting,&Positioning (manually) of VRV type Outdoor Unit
consists of Compressor, Condenser coil, Condenser fan (staircase 3 Nos 4275 12825
space should be provided by the client)
2 Lifting,Shifting,& Positioning of VRV Indoor Units
a For Cassette Units 22 Nos 1710 37620

1 Copper Refrigerant Piping


Liquid Line
a Supply & installation of copper refrigerant piping, duly insulated with
nitrile insulation specified thickness (for 1/4" to 3/4" 13mm thickness
and 7/8" to 1 5/8" 19mm thickness ) and joining of copper will be 103 Rmt 314 129 32342 13287
done by brazing with nitrogen purge in order to avoid oxidation

Gas Line
b Supply & installation of copper refrigerant piping, duly insulated with
nitrile insulation specified thickness (for 1/4" to 3/4" 13mm thickness
and 7/8" to 1 5/8" 19mm thickness ) and joining of copper will be 103 Rmt 314 72 32342 7416
done by brazing with nitrogen purge in order to avoid oxidation

2 Supply and Installations of Communication and Remote Cable


a Supply & Installation of control cum transmission wiring of Copper 2 1 Lot 2565 2565
core 1.5 sqmm(cord) .

3 Drain Pipe with Insulation


a Supply & Installation PVC drain piping with suitable supports as 1 Lot 1710 1710
required & insulated with 6mm thick Nitrile rubber insulation
5 Testing and Commissioning of total VRV system
a Total VRV system will be flushed out with dry nitrogen and then hold
the entire system with nitrogen for pressure test 24 hours with 580 22 Kg 675 53 14850 1166
Psig pressure.Charging the gas with R410A.
a Total VRV system will be flushed out with dry nitrogen and then hold
the entire system with nitrogen for pressure test 24 hours with 580 1 Lot 6840 6840
Psig pressure.Charging the gas with R410A.
Tapped withAdhesive UV Tape and Coated with water proof Acrylic
6
paint R/O Rmt 91 48

SUBTOTAL 79534 83429


GST @ 18 % 14316
SERVICE TAX @18% 15017

TOTAL 93850 98446


GRAND TOTAL 192296

Note: 1. Any Variation in the lowside as per site conditions


2. Sufficient space should be provided by Client for Outdoor units Lifting (Lifting by manual only)
ANNEXURE III
DAIKIN VRV EQUIPMENT COST
Sr.No Description Qty Rate Amount
Rs Rs
1 Outdoor units VRV IV
a RXYQ20TRY6 2 182,460 364,920
Indoor Units
Supply of Round Flow Cassette Indoor Units with cordless
2 Remotes & refnet joints
1 FXFQ50LUV1 4 56,400 225,600
2 FXFQ80LUV1 6 63,800 382,800
3 FXFQ40LUV1 1 54,900 54,900
4 FXFQ100LUV1 1 62,400 62,400
5 FXFQ63LUV1 1 55,100 55,100
6 FXFQ80LUV1 2 61,100 122,200
TOTAL EQUIPMENT COST IN INR 903,000
CGST @14% 126,420
SGST @14% 126,420
TOTAL VRV EQUIPMENT COST 1,155,840

Total Cost for Equipment after Discount 1,155,840


5