TBSS Sppic 06 MS Cvl-Pda

This document provides a method statement for conducting a pile dynamic analysis test at a solar farm project site. It outlines the job scope, safety analysis, work program, list of workers and equipment. The method statement describes mobilizing equipment, unloading piles, conducting the test procedure, and test arrangement. It explains the roles and responsibilities of workers, safety measures to implement, and control risks associated with the work.

Uploaded by

Izza Halim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
136 views32 pages

TBSS Sppic 06 MS Cvl-Pda

This document provides a method statement for conducting a pile dynamic analysis test at a solar farm project site. It outlines the job scope, safety analysis, work program, list of workers and equipment. The method statement describes mobilizing equipment, unloading piles, conducting the test procedure, and test arrangement. It explains the roles and responsibilities of workers, safety measures to implement, and control risks associated with the work.

Uploaded by

Izza Halim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 32

TNB Bukit Selambau Solar

CLIENT Sdn. Bhd 31st Floor, PJX HM


Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52, 46050
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah

CONTRACT NO. TBSS 01/2018

PROJECT TITLE 30MW LARGE SCALE SOLAR PHOTOVOLTAIC PLANT AT LOT 2556, LOT 2557, LOT 3774 & LOT 3776 BUKIT
SELAMBAU, KULA MUDA, KEDAH DARUL AMAN.
DESIGN, SUPPLY, ERECTION & COMMISSIONING OF 132KV SINGLE CIRCUIT TRANSMISSION LINE FROM
BUKIT SELAMBAU SOLAR FARM TO PMU BUKIT SELAMBAU, KUALA MUDA, KEDAH DARUL AMAN.

DOCUMENT NO. TBSS SPPIC 06 MS/CVL-PDA

CLIENT DOCUMENT NO. TBSS SPPIC 06 MS CVL-PDA

METHOD STATEMENT FOR

PILE DYNAMIC ANALYSIS TEST

Date Issuance Prepared By Reviewed By

13/11/2019 1st issue. Rev.0 NAQIU AZIZI


TNB Bukit Selambau Solar Sdn.
CLIENT Bhd 31st Floor, PJX HM Shah
Tower, 16A, Jalan Persiaran
Barat, Pjs 52, 46050 Petaling
Jaya, Selangor.
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah
Alam

CONTENTS:

1. JOB SCOPE
2. JOB SAFETY ANALYSIS/RISK ANALYSIS
3. WORK PROGRAMME
4. LIST OF WORKERS
5. LIST OF EQUIPMENT
6. WORK PROCEDURE
7. PICTURES
8. COPY OF CIDB/NTSP CERTIFICATION OF WORKERS
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52, 46050
Petaling Jaya, Selangor.
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri
Business Park, Persiaran Sukan, 40100
Shah Alam

1. JOB SCOPE:

 The scope of this method statement is to conduct Dynamic Load Test one point per location
which is AP3A (point 1) and AP3B (point 6) by following all safety rules.
 This method statement also covers Mobilization, Unloading, Dynamic Load Test procedure
and Test arrangement.
 It explains the duties of workers involved, machinery used and methodology based on
standards.

Taking into consideration the nature of the work, working site conditions and safety requirement,

this method of statement is prepared as a general guide line to carry-out the works. This method of

statement illustrates on working methods and general safety measures. This method of statement

is only mean for general guide line and its suitability can vary depending on situation.
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52, 46050
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah
Alam

2.0 Job Safety Analysis / Risk Analysis

IMPLEMENTATION AND CONTROL OF RISK

Hazard & Person In


No. Detail Description of Activities Method of Control Remarks
Potential Risk Charge

1. Prepare workforce for the - Inexperience  All workers must be inducted Site
responsibility and work area workers before commencing work Engineer
- Unfamiliar with  To conduct safety briefing
the area  Discuss their duty of care to Site
-Weather each other Supervisor
 Competent people to do
specific work Site Safety
 All workers must wear proper Supervisor
PPE
 Stop work incase bad weather

2. Vehicle movement in / out from Minor Accident  Ensure slow speed (below
location 20km/h) when moving in or Site
out from the location of work Engineer
or site area.
Site
 Only personnel with valid Supervisor
driving license are allowed to
drive. Site Safety
Supervisor

3. Test Pile Installation Works  Set the crane lorry on firm


 Crane lorry ground. On slope area, make
a) Unloading Pile a flat by cutting and on soft
ground, use steel plate as
platform for the operation of
the equipment.
 Supervisor to use whistle to Site
alert on impending or potential Engineer
dangers.
 Workers must not step into the Site
rotating range of the arm of Supervisor
the machine.
 Precautions shall be taken to Site Safety
maintain enough clearance Supervisor
from the conductors while the
crane is moving under the line
 Unfamiliar and raising its boom while
operators working.

 Operator to be registered with


TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri
Business Park, Persiaran Sukan,
40100 Shah Alam

DOSH.
 Ensure clear communication
 Falling between operator and the rest
Object of the team – only one (1)
worker/supervisor can give
instruction to the operator to
 Electrical avoid miscommunication.
shock
caused by  Ensure that the area below
induction the load while lifting is clear
and all loads are properly
secured prior lifting.
 All workers must wear proper
PPE.

 Movement of all workers


should be in allowed
area
 Precautions should be taken
while work under live lines
 Stop work incase heavy rain
or lightning

b) Pile driving  Piling  Set the piling machine on the


machine firm ground
 Maintain the piling frame at
height of 10m
 Precaution shall be taken to
maintain enough clearance Site
from the conductors while the Engineer
 Pile Hacking piling machine is moving
under the line Site
 Wear proper safety Supervisor
 Unfamiliar harness while hacking the
operators piles
Site Safety
 Operator to be registered with Supervisor
DOSH.
 Ensure clear communication
between operator and the rest
of the team – only one (1)
worker/supervisor can give
instruction to the operator to
avoid miscommunication.
 Falling Object

 Piling machine to be in good


condition
 Wear proper safety harness

 Flash over on  Ensure that the area below Site


piling frame the load while lifting is clear Engineer
and all loads are properly
secured prior lifting. Site
 All workers must wear proper Supervisor
TNB Bukit Selambau Solar Sdn.
CLIENT Bhd 31st Floor, PJX HM Shah
Tower, 16A, Jalan Persiaran
Barat, Pjs 52, 46050 Petaling
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah Alam

PPE.
Site Safety
Supervisor
 Discharge wire must be
attached all the time to the
piling machine. Make sure all
tools, machinery and
workers follow the safety
clearance requirement for
the piling machine to move,
swing and lift piles.

4. Setting up Dynamic Load


Test Arrangement
-Workers
-To verify the proposed accident with
compression test location against exposed sharp /  Working only at areas under
any obstacles/hazards at site. harmful / PTW.
unseen
equipment  Safety briefing need to be
before any activity
-Workers begins.
accidentally fall
/ pin / stab  Use proper PPE.
during work as
a result of  Ensure safety of access road Site
carelessness. for crane to move. Engineer

Site
-Induction Supervisor
Voltage due to  Maintain the clearance to the
insufficient live parts. Site Safety
working Supervisor
clearance.

-Unstable  Properly parked the piling


position of lorry rig and check the proper
crane. accessibility.

 Check the belt and


-Improper accessories
indication to condition.
piling rig
operator may  Experience person only to
create give indication to lorry crane
confusion. operator.
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri
Business Park, Persiaran Sukan,

5. Barricade the work area

-To provide caution tape barricade -Workers


- Working only at areas under
to demarcate the working area. accidentally fall
/ pin / stab PTW. Site
during work as (Confine the work place with Engineer
a result of proper barricades / signage).
carelessness. Site
-The barricade should not be Supervisor
-Working at the removed until work completion.
area exposed to Site Safety
high voltage Supervisor
hazard. -Use proper PPE.

-Competent engineer / SHO shall


check and supervise the work.

6. House keeping -Site access -Housekeeping is to be maintained


blocked. throughout the work. Site
Engineer
-Progress general worker to be Site
appointed to perform daily Supervisor
housekeeping.
Site Safety
-All unwanted materials must be Supervisor
removed from time to time.

-Ensure emergency access is


clear from materials and debris.
TNB Bukit Selambau Solar Sdn. Bhd 31st Floor, PJX
CLIENT HM Shah Tower, 16A, Jalan Persiaran Barat, Pjs 52,
46050 Petaling Jaya, Selangor.

SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park, Persiaran Sukan,
40100 Shah Alam

2.1 HAZARD IDENTIFICATION RISK ASSESSMENT & DETERMINING CONTROL (HIRADC):-

PILING WORKS
IDENTIFY ASSESMENT CONTROL
Activities R/NR PIC
Risk Further
Hazard Consequences Current Risk Control Likelihood Severity Type of Control
Level Action/Control
Access & R  No proper  Major injury  Proper access & close 1 2 2  Administrative Supervisor
Egress access  Minor injury monitoring of access  PPE
 Soft soil  Signage/barricade
 Maintenance of
vehicles & machineries
 Competent driver
& operator
 Safe driving
 Use of steel plate at
unstable/soft ground

Mobilization R  Improper  Fall of  To monitor access & 1 4 4  Administrative Supervisor


and unloading machine – major egress using  PPE
demobilizatio technique injury experienced
n of piling  Soft soil operator/worker
 Topple of
machine and  Close supervision
other machinery – major
& barricade
machineries injury  PPE,TBM, SWP & PTW
 Overhead Electrocution  Maintenance of
utilities the machineries
 Signage

Piling works R  Soft soil Collapse of  Use of steel plate at 1 3 3  Administrative Supervisor
machinery soft/unstable  PPE
 Unauthorized  Hit by ground
personnel machinery major  Maintenance of
injury machineries
 Competent operator
 TBM & SWP
TNB Bukit Selambau Solar Sdn. Bhd 31st Floor, PJX HM Shah
CLIENT Tower, 16A, Jalan Persiaran Barat, Pjs 52, 46050 Petaling
Jaya, Selangor.

SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park, Persiaran Sukan, 40100
Shah Alam

 Wear proper clothing &


PPE

Housekeeping R  Improper  Minor injury  TBM 1 2 2  Administrative Supervisor


storage  Regular housekeeping  PPE
 No rubbish  Proper stacking & storage
bins of material & equipment
TRANSPORT TO SITE
IDENTIFY ASSESMENT CONTROL
Activities R/NR PIC
Risk Further
Hazard Consequences Current Risk Control Likelihood Severity Type of Control
Level Action/Control
Movement of material R  Improper Knocked by lorry  Have path for workers 1 3 3  Administrative Supervisor
to site walkway away from road  PPE
Fall of material, access
 collapse of lorry
Poor access,  Provide proper access
uneven & close monitoring of
Fall of material,
ground lorry topples access
 Overloading  Signage & barricade
 Conscientious and
competent driver
 Maintenance of vehicle
& machineries
 Follow speed limit
 Use of steel plate
for unstable ground
Unloading of material R  Improper Fall of material  Use proper equipment 1 3 3  Administrative Supervisor
unloading, not onto person for unloading, never  PPE
using the right Back strain on use manual labor
manual labor
equipment for  Ensure lorry is parked
Load hits onto
unloading person on stable ground
 Barricade area until
unloading is done or
use
signalman
TNB Bukit Selambau Solar Sdn. Bhd 31st Floor, PJX
CLIENT HM Shah Tower, 16A, Jalan Persiaran Barat, Pjs 52,
46050 Petaling Jaya, Selangor.

SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park, Persiaran Sukan,
40100 Shah Alam

VISITORS TO SITE
IDENTIFY ASSESMENT CONTROL
Activities R/NR PIC
Risk Further
Hazard Consequences Current Risk Control Likelihood Severity Type of Control
Level Action/Control
Access & Egress R  Improper  Slip, trip  Provide proper access 1 3 3  Administrative Supervisor
walkway and fall/hit by & close monitoring of  PPE
 Uneven vehicle access
ground  Park vehicle  Signage & barricade
and walk is path is  Maintenance of vehicle
uneven or soggy & machineries
 Competent driver
& operator
 Follow speed limit
 Use of steel plate
for unstable ground
 Wear proper clothing &
PPE

Walkabout at site R  Poor material  Slip trip and  Stack materials in 1 3 3  Administrative Supervisor
stacking fall proper manner  PPE
 Heat  Heat Stress  Keep rehydrated at
all times
 Bitten by  Major  Wear proper clothing &
Snake/Centipe Safety boots. Walk on
de clear paths
TNB Bukit Selambau Solar Sdn. Bhd 31st Floor, PJX
CLIENT HM Shah Tower, 16A, Jalan Persiaran Barat, Pjs 52,
46050 Petaling Jaya, Selangor.

SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park, Persiaran Sukan,
40100 Shah Alam

Severity (S) Rating Likelihood (L) Rating LxS Description & Action
Catastrophic – Numerous Most likely – The most likely A risk identified as LOW may be considered as acceptable and further reduction may
Low Risk
fatalities, irrecoverable. Property 5 result of the hazard/event being 5 not be necessary. However, if the risk can be resolved quickly and efficiently, control
damage and productivity released
1–4
measures should be implemented and recorded.
Fatal – Approximately one single Possible – Has a good change of Medium A MEDIUM risk requires a planned approach to controlling the hazard and applies
fatality and major property 4 occurring and is not unusual 4 Risk temporary measure if required. Actions taken must be documented on the risk
damage (within 5 years) 5 – 12 assessment form including date for completion.
Conceivable – Might be occur at A HIGH risk requires immediate action to control the hazard as detailed in the
Serious major – Non fatal injury, High Risk
3 some time in future (within 5 – 10 3 hierarchy of control. Actions taken must be documented on the risk assessment form
permanent disability
years)
15 – 25
including date for completion.
Minor – Disabling but not Remote – Has not been known to
2 2 R Routine
permanent injury occur after 10 years
Inconceivable – Is practically
Negligible – Minor abrasion, cut
1 impossible and has never 1 NR Non Routine
and bruises. First aid injury
occurred
TNB Bukit Selambau Solar Sdn.
CLIENT Bhd 31st Floor, PJX HM Shah
Tower, 16A, Jalan Persiaran Barat,
Pjs 52, 46050 Petaling Jaya,
Selangor.
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park,
Persiaran Sukan, 40100 Shah Alam

3.0 Work Program

Days

S.NO DESCRIPTION

1. Mobilization

2 Dynamic Load Test Setting up

3 Dynamic Load Test

4 Demobilization
TNB Bukit Selambau Solar Sdn.
CLIENT Bhd 31st Floor, PJX HM Shah
Tower, 16A, Jalan Persiaran Barat,
Pjs 52, 46050 Petaling Jaya,
Selangor.
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park,
Persiaran Sukan, 40100 Shah Alam

4.0 List of Workers

CIDB
PERMIT CIDB EXP NTSP EXP
NO NAME PASSPORT NO. CITIZENSNIP CIDB PERSONNEL ID CARD NTSP
EXPIRY DATE DATE
NO
1 THANGADURAI N1985622 INDIA 31/01/2020 1940601IND1900125407 2615344 TNB004693C 31/01/2020 16/02/2022
KAMAR
2 INDIA
BHUNESHWAR M9547146 30-Jan-20 1880101IND1900125405 2615346 TNB004669C 30-Jan-20 16-Feb-22
3 KAMAR JHARI S5390420 INDIA 30-Jan-20 1880101IND1900125433 2615318 TNB004665C 30-Jan-20 16-Feb-22
MAHTO
4 INDIA
BHUNESHWAR S5388741 30-Jan-20 1890820IND1900125432 2615319 TNB004664C 30-Jan-20 16-Feb-22
TNB Bukit Selambau Solar Sdn.
CLIENT Bhd 31st Floor, PJX HM Shah
Tower, 16A, Jalan Persiaran Barat,
Pjs 52, 46050 Petaling Jaya,
Selangor.
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park,
Persiaran Sukan, 40100 Shah Alam

5.0.1 List of Equipment & Machineries to Be Used as Follows: -

NO EQUIPMENT AND TOOLS QUANTITY


1 Hand Tools 1 Set
2 Pile rig 1
3 Hammer 3tonne 1
4 Pile Driving Analyzer 1 Set

5.0.2 List of PPE To Be Used as Follows: -

NO PPE QUANTITY

1 Safety helmet 1 Nos per Person

2 Safety boots 1 Nos per Person

3 Safety vest 1 Nos per Person


6. Work Procedure

PILE LOAD TEST :-

Transportation piles to site: According to location and transportation conditional at site, piles will be delivered by Lorry
Crane from the casting yard.

Unload piles at site: Unload pile is strictly following site’s safety regulation. To convenience, piles will be placed on the
ground directly, however must avoid the cracking in the middle of piles by the way to put it in the flat ground. Depend
on the request of Consultant (or Owner), piling worker will mark on the piles body about 50 – 100 cm to confirm the
length by chalk or paint.

PILE DRIVING/INSTALLATION:
The pile installation system shall be capable of adjustment to provide an axial, non-eccentric application of the
installation force. Pre-cast concrete piles shall be used for this testing. Pre-cast piles 250x250mmx6m . shall be used
and shall be driven in vertical position. Piling rig or Excavator mounted Piling machine shall be used for installation of
any type of piles. The leader of the piling machine shall be at least 14m height. While shifting the piling machine the
leader shall be properly mounted on the machine and precautions shall be taken to maintain enough clearance while
working near the existing live line. Before beginning piling work, piling point shall be marked properly as per the
approved foundation drawing. Piles shall be driven to required depth as per design specification. While lifting piles,
precautions shall be taken to prevent the piles from getting damaged. The recommended hammer size shall be used.
Piles driven shall be set to depth or up to refusal according to the design provided for proposed test location piling
location and/or approved by Client. The pile should be driven within the allowed tolerances. Take the records of the
penetration rate at all times during driving.

DYNAMIC LOAD TESTING: -


Dynamic load testing (DLT) of piles is a fast and effective method of assessing foundation bearing capacity that
requires instrumenting a deep foundation with accelerometers and strain transducers and analyzing data collected by
these sensors. The procedure is based on the case method of pile testing and is standardized by ASTM D4945-00
Standard Test Method for High Strain Dynamic Testing of Piles. It may be performed on driven piles, drilled shafts and
other cast in place foundations.

Adequate time should be allowed for soil stabilization before testing Dynamic load testing (DLT) is carried out with two
identical bolt-on strain and acceleration transducers (sensor) attached to a section of pile. On concrete pile, the
sensors are connected to the pile with anchor bolts. The pile driving analyzer (PDA) will be used for testing. The pile is
then struck with a driving hammer or a separate drop weight. A hammer mass of about 1 to 2% of the test load is
generally sufficient. The generated compressive stress wave travels down the piles and reflects from the pile toe
upward. The stress waves, which are picked up by the transducers, are processed and automatically stored in the
computer for further analysis and reporting. The analysis is carried out using the signal matching program CAPWAP.
Pile and soil data are modeled and a response is calculated based on one dimensional wave equation theory. The
signal matching process utilizes an iterative method in which the results of each analysis are compared to the actual
measured pile behavior. Appropriate dynamic soil parameters are refined until a satisfactory match is achieved. The
mobilized static shaft and toe resistance of the pile can hence be derived. The signal matching program also provides a
prediction of the static load displacement performance of the pile on the basis of the refined pile and soil model.
7.1 PILE RECORD SHEET AND GRAPH SET:
TNB Bukit Selambau Solar Sdn.
CLIENT Bhd 31st Floor, PJX HM Shah
Tower, 16A, Jalan Persiaran Barat,
Pjs 52, 46050 Petaling Jaya,
Selangor.
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd.


CONTRACTOR ENERTRA SDN BHD.
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park,
Persiaran Sukan, 40100 Shah Alam
TNB Bukit Selambau Solar Sdn.
CLIENT Bhd 31st Floor, PJX HM Shah
Tower, 16A, Jalan Persiaran
Barat, Pjs 52, 46050 Petaling
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah
Alam
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah
Alam
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah
Alam
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah
Alam
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah
Alam
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran
Barat, 46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business
Park, Persiaran Sukan, 40100 Shah
Alam
TNB Bukit Selambau Solar Sdn. Bhd 31st Floor, PJX HM Shah Tower, 16A, Jalan
CLIENT Persiaran Barat, Pjs 52, 46050 Petaling Jaya, Selangor.

SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. Level 18, Amcorp ENERTRA SDN BHD.
CONTRACTOR
Mall, Persiaran Barat, 46000 Petaling Jaya, Selangor.
Unit 440, Block 6, Laman Seri Business Park, Persiaran Sukan,
40100 Shah Alam

7.2 PROPOSE PILE POINT

PILE POINT NO.1


TNB Bukit Selambau Solar Sdn. Bhd 31st Floor, PJX HM Shah Tower, 16A, Jalan
CLIENT Persiaran Ba rat, Pjs 52, 46050 Petaling Jaya, Selangor.

SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. Level 18, Amcorp ENERTRA SDN BHD.
CONTRACTOR
Mall, Persiaran Barat, 46000 Petaling Jaya, Selangor.
Unit 440, Block 6, Laman Seri Business Park, Persiaran Sukan,
40100 Shah Alam

PILE POINT NO.6


TNB Bukit Selambau Solar Sdn.
CLIENT Bhd 31st Floor, PJX HM Shah
Tower, 16A, Jalan Persiaran Barat,
Pjs 52, 46050 Petaling Jaya,
Selangor.
SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


CONTRACTOR
Level 18, Amcorp Mall, Persiaran Barat,
46000 Petaling Jaya, Selangor. Unit 440, Block 6, Laman Seri Business Park,
Persiaran Sukan, 40100 Shah Alam

7.2.1 AP3A PILE POINT NO.1

7.2.1 AP3B PILE POINT NO.6


TNB Bukit Selambau Solar Sdn. Bhd
31st Floor, PJX HM Shah Tower,
CLIENT :
16A, Jalan Persiaran Barat, Pjs 52,
46050 Petaling Jaya, Selangor

CONTRACTOR : SUB-CONTRACTOR :

TNB Engineering Corporation Sdn. Bhd. ENERTRA SDN BHD.


Level 18, Amcorp Mall, Persiaran Barat, Unit 440, Block 6, Laman Seri Business Park,
46000 Petaling Jaya, Selangor Persiaran Sukan, 40100 Shah Alam

7.3 PDA TEST ARRANGEMENT


TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation


CONTRACTOR ENERTRA SDN BHD.
Sdn. Bhd. Level 18, Amcorp
Mall, Persiaran Barat, 46000 Unit 440, Block 6, Laman Seri Business Park,
Petaling Jaya, Selangor. Persiaran Sukan, 40100 Shah Alam

8.0 CIDB & NTSP CERTIFICATION OF WORKERS


TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52, 46050
SUB-CONTRACTOR :

TNB Engineering Corporation


CONTRACTOR ENERTRA SDN BHD.
Sdn. Bhd. Level 18, Amcorp Mall,
Persiaran Barat, 46000 Petaling Unit 440, Block 6, Laman Seri Business Park,
Jaya, Selangor. Persiaran Sukan, 40100 Shah Alam
TNB Bukit Selambau Solar
CLIENT Sdn. Bhd 31st Floor, PJX HM
Shah Tower, 16A, Jalan
Persiaran Barat, Pjs 52,
SUB-CONTRACTOR :

TNB Engineering Corporation


CONTRACTOR ENERTRA SDN BHD.
Sdn. Bhd. Level 18, Amcorp Mall,
Persiaran Barat, 46000 Petaling Unit 440, Block 6, Laman Seri Business Park,
Jaya, Selangor. Persiaran Sukan, 40100 Shah Alam

You might also like