This document provides the design calculations for an outlet chamber including: 1) The side wall is designed to withstand bending moments of 1.18 kNm and 0.98 kNm with a minimum reinforcement of 8F bars at 230 c/c on both faces. 2) The base slab is designed as a two-way slab with a thickness of 150mm and reinforcement of 8F bars at 230 c/c at the top and bottom. 3) The wall is also designed as a beam with a reinforcement of 12F-2 nos bars at the bottom and 8F bars at 230 c/c on each face.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
329 views

Design of Outlet Chamber

This document provides the design calculations for an outlet chamber including: 1) The side wall is designed to withstand bending moments of 1.18 kNm and 0.98 kNm with a minimum reinforcement of 8F bars at 230 c/c on both faces. 2) The base slab is designed as a two-way slab with a thickness of 150mm and reinforcement of 8F bars at 230 c/c at the top and bottom. 3) The wall is also designed as a beam with a reinforcement of 12F-2 nos bars at the bottom and 8F bars at 230 c/c on each face.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 7

OUTLET CHAMBER THERMAX LTD.

:DESIGN OF OUTLET CHAMBER :

DESIGN DATA :
Top level of Chamber = EL 354.840
Bottom level of Chamber = EL 353.340
Size of chamber = 1.50 m
Design SWD = 1.50 m
Safe bearing capacity = 100 kN/m2
Grade of concrete = M20

DESIGN CALCULATIONS :

1. DESIGN OF SIDE WALL :


The wall is designed considering three edges fixed and top edge free.
The coefficients (bending moment & hoop tension) considered for the design
are taken from the tables of IS3370 (Part IV), published by `Concrete
Association of India'.

Design Liquid depth = a = 1.50 m


Width of wall = b = 1.50 m
Wall thickness assumed = t = 150 mm
b/a = 1.0

Bending Moment - [coeff. as per tables of IS 3370 (PART IV), TABLE III]
Coefficient for Bending Moment, Mx = k1 = 0.035 @ y = 0
Coefficient for Bending Moment, My = k2 = 0.029 @ y = b/2
Maximum Vertical Bending Moment,
BMmax = k1 x 10 x a3 = 1.18 kNm
Maximum Horizontal Bending Moment,
BMmax = k1 x 10 x a3 = 0.98 kNm

Check for thickness -


Total thk reqd. = BMmax x 106 = 62.03 mm
(Uncracked section) 0.307 x 1000 OK

Area of Reinforcement -
Astreqd = BMmax = 76.09 mm2
(Vert. reinf. on 150 x 0.9 x d
liquid face)

Astreqd = BMmax = 63.04 mm2


(Horz. reinf. on 150 x 0.9 x d
liquid face)

KPCL, RPTS. 1
OUTLET CHAMBER THERMAX LTD.

Minimum steel reqd. as per IS 3370 on each face,


% Steel = 0.114286 %
Ast min = 171.4 mm2
Provide 8F @ 230 c/c on both faces in vertical direction throughout.
(Astprov = 218.55 mm2).
Provide 8F @ 230 c/c on each face.
(Astprov = 218.55 mm2).

2. DESIGN OF BASE SLAB:

Structural Configuration :
lx = 1.5 m
ly = 1.5 m
ly = 1.00 < 2.0
lx Design slab as two-way
b = ly/lx

Loadings:-
Assume slab thickness = t = 150 mm
1. Self weight of slab = 25 x t = 3.75 kN/m2
2. Load of water = 15.00 kN/m2
Total dead load = 18.75 kN/m2

Bending Moments - (Refer IS 456:2000, Table 26, Case 3)


Along Long/Short span :
-ve BM at support = 0.037 x w1 x lx2 = 1.56 kNm
+ve BM at midspan = 0.028 x w1 x lx 2
= 1.01 kNm

Design BM = Mmax = 1.56 kNm

Thk. reqd. for = Mmax x 106 = 71.28 mm


Uncracked section Q x 103 T'fore OK
(Q= 0.307 N/mm ) 2

Effective depth provided = d = 121 mm

Reinforcement -
Along Long/Short span :
Ast reqd. for -ve BM = 1.56 x 106 = 95.50 mm2
(at top) 150 x 0.9 x 121

Ast reqd. for +ve BM = 1.01 x 106 = 61.83 mm2


(at bottom) 150 x 0.9 x 121

KPCL, RPTS. 2
OUTLET CHAMBER THERMAX LTD.

Minimum steel reqd. as per IS 3370 in each direction


% Steel = 0.1142857 %
Ast min = 171.4 mm2

Provide 8F @ 230 c/c (= 217.4 mm2) bothways at top and bottom


3. WALL DESIGNED AS BEAM:

Span of beam = 1500 mm


Size of beam = 150 mm
Depth of beam = 1500 mm

Load from slab = w x lx = 9.375 kN/m


3
Self weight of beam = 25 x b x d = 5.625 kN/m

Total load on beam = 15 kN/m

Maximum moment = w x l2 = 4.219 kN-m


8

As per clause 29.2 of IS 456,


For continuous Beam,
Ratio L/D = 1.00
Lever arm, Z = 0.2 x ( L + 1.5 D ) = 750 mm

Reinforcement at bottom = M x 106 = 37.50 mm2


150 * Z

Provide 12F-2 nos. (Ast = 226.19 mm2)

Side face reinforcement:


As per clause 32.5 of IS 456;
Astmin = 0.0012 x b x d = 270 mm2

Provide 8F @ 230 c/c (Ast = 218.55 mm2) on each face.

4. LOAD ON COLUMN:

Size of column,b = 0.23 m


l = 0.23 m
Length of column = 3.89 m

Reaction from beam = wxl = 0.938 kN


24

KPCL, RPTS. 3
OUTLET CHAMBER THERMAX LTD.

Load on column = 2 x 0.938 = 1.875 kN

Self weight of column = 5.145 kN

Total load on column = 7.020 kN

Column is designed as per working stress method.

5. DESIGN OF RAFT FOUNDATION:

Projection beyond column = l = 260 mm


Width of base slab = 0.75 m
Length of base slab = 1.80 m
Assumed thickness of base slab = 250 mm
Width of raft beam = 230 mm
Depth of raft beam = 350 mm
Loading -

Area of Footing = 1.35 m2


Thickness of footing = 0.25 m
Self weight of footing = 8.44 kN
Load from column = 7.02 kN
Self weight raft beam = 2.70 kN
Total Load = 18.15 kN

Bending Stress = Load/Area = 13.45 kN/m2


< 100 kN/m2
OK
Bending Moment = 2.36 kNm

Effective depth = Mmax3 x 100 = 51.21 mm


Q x 1000
Total Thk. Assumed = 250 mm

Ast required = 2.36 x 106 = 53.03 mm2


230 x 0.9 x 215

Provide 10F @ 150c/c bothways at top & bottom( Ast = 523.598 mm 2)

6. DESIGN OF RAFT BEAM:

Width of raft beam = 230 mm

KPCL, RPTS. 4
OUTLET CHAMBER THERMAX LTD.

Depth of raft beam = 350 mm


Loading:
Uniform load on beam = 10.09 kN/m
Total load on beam = 10.09 kN/m

Maximun bending moment = w x l2 = 2.264 kN-m


8

Thk. reqd. for = Mmax x 106 = 49.88 mm


Cracked section Q x 103 T'fore OK
(Q= 0.91 N/mm2)

Ast required = 2.264 x 106 = 53.23 mm2


230 x 0.9 x 315

Provide 10F -2 nos. at top & bottom( Ast = 157.08 mm2)


Provide 8F-2L stirrups @ 150 c/c throughout the beam
(Ast = 335.103 mm2)

KPCL, RPTS. 5
THERMAX LTD.
OUTLET CHAMBER

DESIGN OF COLUMN BELOW SLAB:

SR. DESCRIPTION NOTA- UNIT FORMULA COLUMN


NO. -TION C1/C2
I DESIGN DATA

a) Axial load on Column P kN 7.02


b) Moment @ Major Axis Mx kNm 0.14
c) Moment @ Minor Axis My kNm 0.14
d) Width of Column b mm 230
Depth of Column D mm 230
e1) Dia of bar F mm 12
f1) No. of bars no. 4
e1) Dia of bar F mm 0
f1) No. of bars no. 0
g) Longi.reinf.in Column Asc mm2 452
h) Unsupported length of Column
(Length x 1.2) @ Major Axis lex mm 4668
@ Minor Axis ley mm 4668
i) Grade of Concrete fck N/mm2 M20 20
j) Grade of Steel fy N/mm2 Fe415 415
k) Clear cover d' mm 30
l) Modular ratio m 13.33

2 a) Slenderness Ratio @Major Axis SRx lex/D 20.30


b) Slenderness Ratio @Minor Axis SRy ley/b 20.30
c) As S.R.is > 12 @ Major Axis,
therefore Column is........... LONG COL
d) As S.R.is > 12 @ Minor Axis,
therefore Column is........... LONG COL

3 Reduction factor for stress @ Major axis Crx 1.25 -(lex/(48xD) 0.83
Reduction factor for stress @ Minor axis Cry 1.25 -(ley/(48xb) 0.83
Direct stress (Permissible) s cc perm N/mm 2 6 or 6 x Cr 6.00
4 Bending stress(Permissible) scbc perm N/mm2 8.5 or 8.5 x Cr 8.50
Compressive stress (Permissible) ssc perm N/mm 2 175 or 175 x Cr 144.76
5 Load carrying capacity of column P kN scc Ac + ssc Asc 380.17
SAFE
6 Properties of column section
a) Equivalent Area Ae mm2 Ac+1.5mAsc 6.15E+04
b) Moment of Inertia @ Major Axis Ixx mm 4
bD /12
3
2.33E+08
c) Moment of Inertia @ Minor Axis Iyy mm4 Db3/12 2.33E+08

d) Section Modulus @ Major axis Zxx mm3 Ixx/( D/2) 2.03E+06


e) Section Modulus @ Minor axis Zyy mm 3 Iyy/( b/2) 2.03E+06

KPCL, RPTS. 6
THERMAX LTD.
OUTLET CHAMBER

SR. DESCRIPTION NOTA- UNIT FORMULA COLUMN


NO. -TION C1/C2
II CHECK FOR STRESSES
Direct stress scc cal N/mm2 P/Ae 0.11
Bending stress @ Major Axis scbc cal N/mm2 Mx / Zxx 0.07
Bending stress @ Minor Axis scbc cal N/mm2 My / Zyy 0.07
scc cal scbcx cal scbcy cal < 1 0.04
scc perm scbc perm scbc perm < 1 SAFE

Tensile stress = scbcx cal + scbcy cal - scc cal N/mm2 0.02

0.35 ( scc cal + scbcx cal + scbcy cal ) or N/mm2 0.09


0.25 ( scc cal + Max of ( scbcx cal or scbcy cal )) safe
3/4 (Modulus of rupture at 7days) N/mm2 1.80

III COLUMN SECTION TO BE PROVIDED


a) Provide Width of Column as b mm 230
Provide Depth of Column as D mm 230
b1) Provide Longi. Reinf. as dia mm 12
c1) Provide No. of bars as Nos. 4

IV CONFINING REINF. AS PER IS13920


Dk mm D - 2xd' + Fx2 186
bk mm b - 2xd' + Fx2 186
b) Gross area Ag mm 2
bxD 41547.6
c) Core area Ak mm2 bk x Dk 34596.0
d) Diam. Of confining reinf. dc mm 8
e) Area of confining reinf. Ash mm2 p/4 x dc2 50.3
f) Spacing of confining reinf. s mm Ash/(0.18x h x fck/fy 310.1
x (Ag/Ak - 1) )