In order to use the chiller correctly and efficiently, please read the
1. Installation requirements:
Site requirements:
Air-cooled chiller must be installed way from walls more than 1 meter,
Remarks:
Confirm all of the plumbing connected well and keep the inlet and
Before start the pump, confirm the built-in tank with full of chilled
water or other type coolant. (Note: please choose the chilled medium
according to requirements.)
3. Operation sequence
1. Open all water inlet and outlet valves, and ensure the waterways
unblocked.
3. Only for Water cooled chiller: if cooling tower and the cooling
4.1 Instructions:
○
1 main interface:
○
2 Alarm interface:
○
3 Fault checking /Reset:
Note:After check out the fault, firstly shooting the fault and then Rest
items.
Remarks:
○
1 User settings: parameter settings and meaning, please reference 5.1
○
2 Unit status: If the part is running, the circle is filled; if not, it is blank. And
○
3 History list: check the latest alarm, press for 2 seconds, history
○
4 Utilization rate: each compressor running time in total
○
5 System version: It is the version of the control system.
4.3 Power on :
○
1 Turn on the air switch , chiller unit is connected with power.
○
2 Press , when the indicator on the key is lightening, the
added the temperature variation data, the axil fan or the cooling water
pump will be started running after 10 seconds time delay, and another 10
and 10 seconds time delay, the chilled water pump will be stopped
automatically finally; then the indicator of key is put out; and press
automatically;
stopped automatically;
○
2 Chiller with two compressors:
started automatically.
automatically
Remark
If the chiller unit is in idle for long time, please turn off the air switch
, and discharge the water/fluid in the tank, shell and tube, or plate
heat exchanger.
○
1 User settings table
Item Default Setting Range Note
Lock T. set NO Yes / No Lock the set temperature
Set
12.0℃ -30~99.9℃ Limited within the setting range
temperature
Contrast 32 20~44 Adjust LCD screen contrast
Local/
ON/OFF Remote: remote control the unit
Local Local+remote/Re
TYPE start/stop
mote
Backlight On 0 0~255 min 0: Back light off
○
2 User data settings
○
1 Parameter table of Manufacturer settings
Item Description Data set Set Range Remark
invalid.
Auto start-up Forbid Forbid /Use condition before power off after
restart
Keep when Keep when mute/stop output alarm info when mute.
Alarm output
mute when mute Stop when mute:relay stop
Pump input rating 0.3A 0~25.0A FORBID, these three data are
temperature +1C
temperature -1C
Temperature
50.0℃ 12.0~100.0℃
setpoint max
Set temperature range limited
Temperature
7.0℃ -30.0~12.0℃
setpoint min
auto reset.
be auto reset.
compressor.
pressure input.
invalid.
Compressor
N.O N.C/N.O
overload
Configuration
guide Water level switch N.C N.C/N.O Switching input method choice.
○
2 Enter into Manufacturer settings functional menu
put in. With key and to choose the correct number, and press
key to confirm the data and move to the next number. After
manufacturer settings.
Remarks:
○
3 Manufacturer settings
○
4 Manufacturer debug
3phase power source, 7 alarm outputs and 4 relay outputs can be tested
by this function. If chiller running well, that means wiring and settings are
normal, if any alarm, that means some settings are not correct or wiring not
○
5 Configure guide
reference 5.2 ○
1 manufacturer settings table.
6.Fault instructions
Detection
Fault Result Instruction
condition
Compressor high
pressure
pressure or not
Detect when
Compressor
Compressor Compressor
overload
running stopped, cooling
Compressor high Detect compressor rated current setting is
fan/pump
current reasonable or not.
stopped after
Compressor current
time delay. Detect compressor wiring is normal or not.
low
alarm Chiller running higher than set point of temperature high alarm
Chilled pump Detect when Chiller unit Detect input same with switching input settings
Chilled pump high running Detect rated current setting of chilled pump
Detect when Chiller unit Detect 3phase power phase reverse or phase
Power failure
power on stopped lacking
Chiller unit
Water flow fault
Detect when stopped
chilled pump Chiller stopped Detect input same with switching input settings
happened
After stopped, it
Chiller needs Detect when Compressor total running time is over the set
cannot be
maintenance running time
running
7. Trouble shootings
Fault Reason/possibilities Solution
Power normal
but chiller
Controller fault change a new controller
cannot be
started
1 Circuit short
○ ○1 check out the short circuit and the reason, solve the problem
2 Main circuit over load
○ ○2 Check the load of each and find out the reason, avoid circuit
Power switch
tripped
3 Breaker fault
○ over load running, if the breaker rated current is too small,
change a bigger one.
○3 change a new breaker
○
1 Chilled pump cannot be start if storage tank without water; (For
chiller model above 7.5 HP, water level protector will be installed in the
tank. When tank with lower level water or empty, chilled pump will be
stopped automatically, the chiller will display water level fault and
alarm.)
○
2 Please do not frequently operate the power switch.
○
3 While processing water temperature is decreased to the set
○
4 Do not set temperature below 5C. It is to avoid coolant freezed in
If the chiller is not in use for long time, please discharge the
○
5 To ensure the chiller with best performance, please clean the
Remark: Stop the chiller once there is alarm, check and solve the
the operating current increased; While high pressure of the air cooled chiller
kg/cm2, the compressor can be trip-out under the protection of the high
pressure switch and stop running because of bad cooling, high pressure
overload, and it will display fault code or fault indication, then please check
that the circulating water in the cooling tower is running well, the temperature
of cooling water is not over-high, the fan of the cooling tower and the water
pump are running, and the cooling water valve is fully open (If it is an air
cooled chiller, please confirm that the radiator is not dirty or choked.). All the
stated come back to normal, the chiller can be running well after restarting by
refrigerant , firstly the leak should be filled, the dryer filter should be
2. While leaking part in water, please stop the chiller immediately, and
discharge water of the water tank quickly. In order to avoid that the
chiller is damaged badly for the compressor suck water, please notify
best state while it displays high pressure within the scope of 12.5 kg/cm2 to 15
kg/cm2 (while for the air cooled chiller, it is best within the scope of 14~17
kg/cm2 ), but it should not be above 19.5 kg/cm2. If the pressure of the water
cooled chiller is above 19.5 kg/cm2, or the pressure of the air cooled chiller is
above 24 kg/cm2, the high pressure switch will turn off by itself, then please
deal with it according to Footnote(1). It is the best state when the low pressure
is within the scope of 3.1 kg/cm2 to 4.5 kg/cm2, but it could not be lower than
2 kg/cm2. If the low pressure is below 2 kg/cm2, the switch of the low pressure
will turn off by itself, please deal with it according to Footnote (2).
they are equal, while the compressor is running, that means the valve of the
immediately and notify the company to deal with the problem. Please be
aware that the stated conditions would happen when the compressor is
running. If the compressor is not operating, it is normal while the high pressure
Note 4
If the fault indicators and the protecting relays are normal, but
9 Maintenance