Example: Calculate Whether Lightning Protection is required or not for following Building. Calculate No of Down
Conductor for Lightning Protection
Area of Building / Structure:
5 0.2
10 0.5
20 1.1
30 1.9
40 2.8
50 3.7
60 4.7
80 6.9
100 9.2
Others 1.2
Calculation:
Collection Area (Ac)=(L x W) + 2 (L x H) + 2(W x H) +(3.14 x H2)
Collection Area (Ac) = (60×28)+2x(60×23)+2x(28×23)+(3.14x23x23)
Collection Area (Ac) =7389 Meter2
Probable No of Strikes to Building / Structure (P)= Ac x Ng x 10-6 No’s / Year
Probable No of Strikes to Building / Structure (P)= 7389x69x10 –6 No’s / Year
Probable No of Strikes to Building / Structure (P)= 05098 No’s / Year
Overall Multiplying Factor (M) =A x B x C x D x E
Application of Structure (A)= Houses & Buildings as per Table Multiplying Factor = 0.3
Type of Constructions (B)= Steel framed encased without Metal Roof as per Table Multiplying Factor =0.2
Contests or Consequential Effects (C)= Domestic / Office Buildings as per Table Multiplying Factor =0.3
Degree of Isolation (D)= Structure in a large area having greater height as per Table Multiplying Factor =0.4
Type of Country (E)= Flat country at any level so as per Table Multiplying Factor =0.3
Overall Multiplying Factor (M) =0.3×0.2×0.3×0.4×0.3
Overall Multiplying Factor (M) =0.00216
Overall Risk Factor Calculated (xc)= M x P
Overall Risk Factor Calculated (xc)= 0.00216 x0.05098
Overall Risk Factor Calculated (xc)= 000110127
Base Area of Structure (Ab) = (LxW)
Base Area of Structure (Ab)=60×28
Base Area of Structure (Ab)=1680 Meter2
Perimeter of Structure (P) =2x (L+W)
Perimeter of Structure (P)=2x(60+28)
Perimeter of Structure (P)=176 Meter
Lightning Protection Required or Not
If Calculated Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor than only
Lighting Protection Required
Here Calculated Overall Risk Factor is 0.000110127 > Max Acceptable Overall Risk Factor is 00000001
Lightning Protection is Required
No of Down Conductor
Down Conductors As per Base Area of Structure (s) =1+(Ab-100)/300
Down Conductors As per Base Area of Structure (s) =1+(1680-100)/300
Down Conductors As per Base Area of Structure (s) =6 No’s
Down Conductors As per Perimeter of Structure (t)= P/30
Down Conductors As per Perimeter of Structure (t)= 176/30
Down Conductors As per Perimeter of Structure (t)= 6 No’s
Minimum No of Down Conductor is 6 No’s
Results:
Lightning Protection is Required
Down Conductors As per Base Area of Structure (s) =6 No’s
Down Conductors As per Perimeter of Structure (t)= 6 No’s
Minimum No of Down Conductor is 6 No’s