0% found this document useful (0 votes)
2K views7 pages

Sheet Pile Wall Design Example PDF

This document summarizes the design of a sheet pile wall retaining soil with an active pressure of 30 kPa and passive pressure calculated using Rankine equations. Key steps include: 1) Calculating earth pressures and drawing a pressure diagram 2) Optimizing the horizontal tieback depth to 2.45m to minimize bending moments 3) Designing a 26mm diameter tieback installed at 20° to provide 217kN tension over 5.5m length 4) Computing maximum bending moments of 335 kNm/m and 152 kNm/m at different stages 5) Further optimizing the tieback depth to 3.75m to equalize maximum moments.

Uploaded by

vasi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views7 pages

Sheet Pile Wall Design Example PDF

This document summarizes the design of a sheet pile wall retaining soil with an active pressure of 30 kPa and passive pressure calculated using Rankine equations. Key steps include: 1) Calculating earth pressures and drawing a pressure diagram 2) Optimizing the horizontal tieback depth to 2.45m to minimize bending moments 3) Designing a 26mm diameter tieback installed at 20° to provide 217kN tension over 5.5m length 4) Computing maximum bending moments of 335 kNm/m and 152 kNm/m at different stages 5) Further optimizing the tieback depth to 3.75m to equalize maximum moments.

Uploaded by

vasi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Lawrence Technological University

Department of Civil Engineering


ECE 5473: Earth Retaining Structures
Summer 2012

Sheet Pile Wall design Example

The following content summarizes the design calculation steps presented in lecture June 28, 2012.

q = 30 kPa

In-place soil (medium sand):


γ= 17.0 kN/m3
10.0 m
φ = 34°

1. Wall design parameters are given in the figure above.

2. Ka = 0.283 and Kp = 3.537, calculated using Rankine earth pressure equations.

3. The pressure diagram is drawn (below) to show the active earth pressure behind the wall and the
factored (FS = 1.5) passive earth pressure in front of the wall. This pressure diagram was drawn
using a spreadsheet with an increment size of 0.05 m.

Page 1 of 7
Pressure Diagram
pressure (kPa)
-150 -100 -50 0 50 100 pore pressure behind
0 8.48 wall

2 active earth pressure


horizontal tieback force behind wall
4 passive earth
pressure behind wall
6
depth (m)

passive earth
pressure in front of
8
wall
pore pressure in
10 56.54 front of wall

sum
12
-98.21

14

4. An initial tieback depth of 3 m from the top of the wall is assumed. This value may need to be
revised depending on the outcome of the subsequent analyses. Moments are summed about the
tieback depth on the wall. The embedment depth is changed until the sum of the moments is nearly
equal to zero. The optimum embedment depth is accordingly found to be 2.45 m.

5. Summing the forces in the horizontal direction, the required horizontal tieback load required to
balance horizontal forces is equal to 203.56 kN/m (note the direction of the horizontal tieback force in
the figure. Assuming a 1 m horizontal spacing between tiebacks installed into the face of the wall,
this force corresponds to a 204 kN force per tieback. Assuming a 20° installation angle to the
horizontal, the design tieback tension is

204 
= = 217 
cos 20°

Referring to the DYWIDAG Soil Anchor tables, a 26 mm diameter bar (70% ultimate strength = 397
kN) is sufficient to provide this tension. Assuming the bar is installed into a grouted hole 0.15 m in
diameter, the circumference a of the grouted anchor is

 =  = 0.15  = 0.471 

Referring to Table 16.4 from Macnab, A. (2002), Earth Retention Systems Handbook, a possible
presumptive ultimate bond stress for this anchor is 100 kPa (2 kips/ft2). Using this presumptive
ultimate bond stress, the minimum bonded anchor length is

Page 2 of 7
217 
 = = 2.2 
100 

The minimum unbonded length is found considering the geometry of the Rankine wedge as shown in
the following figure:

70°

10.0 m 82°
7m

45°- φ/2 = 28°

Using the law of sines, the unbonded length is found

 7
= ⇒  = 3.3 
sin 28° sin 82°

Therefore, the total required length of the tieback behind the wall is 3.3 m + 2.2 m = 5.5 m.

6. A bending moment diagram is generated using a spreadsheet to numerically integrate the pressure
diagram (including unfactored passive earth pressure) and resulting shear diagram. The output
moment diagram is plotted below.

Page 3 of 7
moment (kNm/m)
-400 -350 -300 -250 -200 -150 -100 -50 0 50 100
0

6
depth (m)

-334.63
8

10

12

14

The maximum moment for the final constructed wall is therefore 335 kNm/m.

7. Assuming a 0.6 m excavation below the tieback prior to tieback installation, the maximum bending
moment is calculated using the following pressure diagram:

Page 4 of 7
Pressure Diagram
pressure (kPa)
-600 -400 -200 0 200
0 pore pressure behind
wall
2 active earth pressure
behind wall
4
passive earth
pressure behind wall
6
depth (m)

passive earth
8 pressure in front of
wall
pore pressure in
10 front of wall

12

14

The maximum moment is calculated from the resulting moment diagram:

Page 5 of 7
moment (kNm/m)
-100 -50 0 50 100 150 200
0

3
depth (m)

5 152.12

The maximum pre-tieback bending moment in the wall is therefore 152 kNm/m. Since this value is
significantly less than the maximum moment calculated for the completed wall, the tieback elevation
can be optimized by increasing the depth of the tieback.

8. The tieback depth is adjusted within the spreadsheets to arrive at a maximum moment that is nearly
equal for steps (6) and (7) above. The optimum tieback depth is found to be 3.75 m. The resulting
required horizontal tieback load is 218 kN/m. The resulting maximum moments are 240 kNm/m and
238 kN/m for the final wall and pre-tieback configurations, respectively.

9. Taking the maximum computed moment as 240 kNm/m, the ultimate moment for steel design is
calculated by applying an 80% reduction factor:

! = 0.8240 / = 192 /

Considering a load factor of 1.6 and a resistance factor of 0.9, the required nominal bending moment
resistance of the sheet piling is computed

0.9 $ ≥ 1.6 !
1.6
$ ≥ 192 /
0.9
$ ≥ 341 /

Page 6 of 7
For ASTM A572 Gr. 60 steel, Fy = 415 MPa (415,000 kPa). For nominal moment resistance greater
than or equal to 341 kNm/m, the corresponding elastic section modulus requirement is computed

341 /
'≥
415,000 /)
' ≥ 0.000822 * / = 822+* /

Referring to the Skyline Steel PZ/PS section tables, the PZ 22 section, with an elastic section modulus
of 973 cm 3/m, is sufficient for this design.

Page 7 of 7

You might also like