Numerical module for automatic synchronising of generator 90f - 90U - 25
Functions Measurement functions
• The device performs frequency • Voltage and frequency busbar side. and voltage regulation of a • Voltage and frequency generator generator, thereafter it executes side. automatic paralleling with a live • Phase-displacement. bus-bar (already supplied bus-bar). • Primary voltage values. Alternatively it permits the regulation at optimal frequency Recording functions and voltage values, then executes • Record of the last events (last automatic paralleling with a dead eight, parallel executed, failed, bus-bar (non supplied bus-bar). reason) with date and time For synchronisation, (YY/MM/DD - hh:mm:ss.mmm) MX3EG1A sends controls that and fault values. operate on the turbine speed and • Record of the logical status change on the generator field. (last 32) representing the parallel When the parallel conditions are sequences, digital inputs included, positively checked, MX3EG1A with date and time (YY/MM/DD controls the circuit breaker. - hh:mm:ss.mmm) • Two inputs, supplied from • Disturbance recording with generator and bus-bar voltages, record of all input signals and permit measurement of respective Communication correlated logical status; voltages, frequencies and • Rear serial port for connection to possibility to choose the cause phase-displacement. Lonwork™ network at 1.25 Mbit/s. determining trigger and define • It is possible to configure the logic • Alternatively: serial port RS485 the recording time before and inputs to receive: synchronisation and Modbus protocol. after trigger (for a total recording and parallel requests (with Live-bus time of 2.5 s). Start_LB or Dead-bus Start_DB), Human Machine Interface • Record on counters and LED's. Stop control, circuit breaker • Local HMI with keyboard, closed (CB52), anomalies, etc. backlit LCD display, 12 LED's, • The device includes two setting Monitoring and control: 8 of which are freely assignable groups, switch in operation of digital inputs and outputs to the functions. groups: from HMI, Digital input • 5 freely assignable inputs (controls, • Local HMI by PC connected or Communication. blocks, setting group switch). to the front serial port. • 6 output relays one of which is for • Remote interface by the Local diagnostic and 5 freely assignable Area Network. to the functions. Characteristics Auxiliary supply Output relay contacts Bus-bar side rated voltage Uaux: 19 to 100 Vd.c. Rated current 5A Ubn 40 to 130 V or: 19 to 72 Va.c. Breaking Generator side rated voltage Uaux: 64 to 300 Vd.c. 0.3 A @ 110 Vd.c., L/R=40 ms Ugn 40 to 130 V or: 64 to 275 Va.c. Make and carr y 30 A for 0.5 s Bus-bar side line VT's rated Burden: 5 W/10 W d.c. Mechanical life 106 operations voltage 0.1 to 1000 kV 10VA/20VA a.c. Generator side line VT's rated Standards voltage 0.1 to 1000 kV EN 60255-6 IEC 255 Rated frequency fn 50/60 Hz
Closing pulse duration
tc 0.10 to 9.99 s Closing delay tr 0.02 to 0.99 s Maximum parallel attempts Ns 1 to 10 Minimum interval twc 0.10 to 9.99 Maximum sequence duration ts 1 to 30 min Stability verification time td 0.10 to 10 s Max busbar frequency deviation Dfb 1 to 5 % Max generator frequency deviation Dfg 1 to 20 % Max busbar voltage deviation DUb 1 to 5 % Max generator voltage deviation DUg 70 to 85 % Live Bus mode Norm/Sub/Super Max difference in frequency Df 0.02 to 0.50 Hz Max difference in voltage DU 1 to 30 % Max phase-displacement Dp 1 to 30°
Dead Bus Mode
OFF/ON/ON_CHECK "Dead bus" voltage threshold Ud 0.10 to 0.30 Ubn Frequency regulation mode CPf CONT/PULSE Pulse duration tfpu 0.10 to 9.99 s Minimum interval tfpa 1.00 to 9.99 s Max. interval tfpm 10.00 to 99.99 s START LB: Live bus synchronisation and paralleling request Load pulse mode LP ON/OFF START DB: Dead bus synchronisation and paralleling request. Pulse duration tlp 0.10 to 9.99 s STOP: Sequence stop control. Voltage regulation mode CB52: Paralleling CB's auxiliary contact. CPU CONT/PULSE tupu 0.10 to 9.99 s tupa 0.10 to 9.99 s
ALSTOM FIR S.p.A. - via Viscardi,5 - 24016 SAN PELLEGRINO T. - BG - ITALIA
Tel. ++39 0345 28111 - Fax ++39 0345 22590 - Telex 301152 FIR I - E-mail: [email protected]