Line Protection SIPROTEC 7SA8, 7SD8, 7SL8, 7VK87, 7SJ86: SIPROTEC 5 For Every Application and Requirement
Line Protection SIPROTEC 7SA8, 7SD8, 7SL8, 7VK87, 7SJ86: SIPROTEC 5 For Every Application and Requirement
Line Protection
SIPROTEC 7SA8, 7SD8, 7SL8, 7VK87, 7SJ86
www.siemens.com/siprotec
Line Protection Devices
Distinguishing features
2.5 7 XX YY
7 XX YY
Main protection:
2.6 7 SA Distance protection
7 SD Differential protection
2.7
7 SL Distance and differential protection
2.8 7 SJ Overcurrent protection
3.5
3.6
3.7
2.5 / 2 SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 3
Line Protection Devices
Overview
Type designation 7SA82 7SA86 7SA87 7SD82 7SD86 7SD87 7SL82 7SL86 7SL87 7VK87 7SJ86 1
Distance protection
Table 2.5 / 2 Overview of the various distinguishing features of the main protection types 1.5
1.6
1.7
*HQHUDWLRQ 7UDQVPLVVLRQ 'LVWULEXWLRQ
1.8
6- .( 1.9
0' 6/ 6$ 6/ 6-
87 6$
6$ 66 0' 6$ 6' 6- 6-
2
6. 6$
.( 6' .( 6- 66 6- 6' 6- 6' 6. 2.1
0' 6- 9. 87 .( 6- 6/ 87 6' 6. 2.2
2.3
0
2.4
*
Visio-Anw_SIP5-LS-us.pdf
0
2.5
Fig. 2.5 / 2 Areas of application of the SIPROTEC 5 devices in the power transmission system
2.6
2.7
2.8
2.9
2.10
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 3 2.5 / 3
Distance Protection SIPROTEC 7SA87
Properties
Application templates are available in DIGSI for standard The following application templates are available:
1 applications. They comprise all basic configurations and default • Basic distance protection
settings.
1.1 • Distance protection reactance method (RMD) for overhead line
for grounded systems, with AR
1.2 • Distance protection reactance method (RMD) for overhead line
1.3 in grounded systems, with AR for applications with breaker-
and-a-half schemes.
1.4
1.5
1.6 Busbar with line feeder
1.7
1.8 QA 52
7SA87
1.9
MP
V4
VT-1ph 1
2
I1 FG Line FG Circuit breaker
2.1 I2 MP
I-3ph V-1ph 25
I3 CT-3ph 1
2.2 I4
21 67N 50HS V-3ph
85 68 FL 50/51
2.3
V1 27 59 81
MP I-3ph 50BF
2.4 V2
VT-3ph 1
V-3ph
V3
79
CI PI Ctrl
Fig_8_Visio-Appl-Bsp_.pdf
BI
CB
BO
2.5 Teleprotection (85) can use
conventional signalling or serial
Com.
protection interface
Power line
FG Function group 21 Distance protection
MP Measuring point 25 Synchrocheck, synchronizing function
PI Protection interface 27 Undervoltage protection
CI Communication interface 50/51 Overcurrent protection, phases, ground
2.6 CB
BI
Circuit breaker
Binary input
50HS
50BF
High speed instantaneous overcurrent protection
Circuit-breaker failure protection
BO Binary output 59 Overvoltage protection
2.7 67N Directional overcurrent protection for ground-faults
68 Power-swing blocking
2.8 79 Automatic reclosing
81 Frequency protection
85 Teleprotection schemes
2.9 Ctrl Control
FL Fault locator
2.10
3
3.1 Fig. 2.5 / 9 Application example: Distance protection for overhead line
3.2
3.3
3.4
3.5
3.6
3.7
2.5 / 14 SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 3
Distance Protection SIPROTEC 7SA87
Applications
1
Busbar 1
1.1
1.2
7SA87
Power line 1
V1
1.3
V2
Com. 1.4
MP
V3
VT-1ph 1 1.5
I1 FG Line FG Circuit breaker A-QA
I2 MP
1.6
I-3ph Ȉ V-1ph 25
I3 CT-3ph 1
A-QA I4
87
STUB
21 67N 50HS V-3ph 1.7
52
85 68 FL 50/51 I-3ph 50BF 1.8
V1
27 59 81 79
V2 MP 1.9
V-3ph
V3 VT-3ph 1
V4 Ctrl
B-QA 2
52 BI
CI PI CB
BO 2.1
I1
I2 MP 2.2
I3 CT-3ph 2
I4 FG Circuit breaker B-QA
2.3
MP
V4
VT-1ph 2
V-1ph 25 2.4
V-3ph
C-QA I-3ph 50BF
52
79
Teleprotection (85) can use
conventional signalling or serial Ctrl
Fig_9_Visio-Appl-Bsp_.pdf
protection interface 2.5
BI
CB
Power line 2 BO
Fig. 2.5 / 10 Application example: Distance protection for overhead line with breaker-and-a-half scheme
3.1
3.2
3.3
3.4
3.5
3.6
3.7
SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 3 2.5 / 15
Distance Protection SIPROTEC 7SA87
Functions, application templates
1 Application templates
Available in 7SA87
1.2
point, 1.5 CB
1.3
DIS Basic
point
1.4
ANSI Functions Abbr.
1.5 Protection functions for 3-pole tripping 3-pole
Protection functions for 1-pole tripping 1-pole
1.6 Hardware quantity structure expandable I/O
21/21N Distance protection Z<, V< /
1.7 I>/ (V,I)
21T Impedance protection for transformers Z<
1.8
25 Synchrocheck, synchronizing function Sync 2
2.8 67Ns Dir. sensitive ground-fault detection for systems with resonant or isolated neutral
incl. a) V0>, b) Cos-/SinPhi, c) Transient fct., d) Phi(V,I), e) Admittanz
2.9 68 Power-swing blocking ∆Z/∆t
74TC Trip circuit supervision TCS
2.10 78 Out-of-step protection ∆Z/∆t
79 Automatic reclosing, 1-/3-pole AR 2
3 81O Overfrequency protection f>
81U Underfrequency protection f<
3.1 81R Rate-of-frequency-change protection df/dt
85/21 Teleprotection for distance protection
3.2
85/27 Weak or no infeed: Echo and Tripping WI
2.5 / 16 SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 3
Distance Protection SIPROTEC 7SA87
Functions, application templates
Application templates 1
Available in 7SA87
1.2
point, 1.5 CB
1.3
DIS Basic
point
1.4
ANSI Functions Abbr.
90V Automatic voltage control for 2 winding transformer 1.5
90V Automatic voltage control for 3 winding transformer
90V Automatic voltage control for grid coupling transformer 1.6
FL Fault locator, single-ended measurement FL-one
1.7
PMU Synchrophasor measurement (1 PMU can be used for max. 8 voltages and 8 currents) PMU
Arc-protection (only with plug-in module ARC-CD-3FO) 1.8
Measured values, standard
Measured values, extended: Min, Max, Avg 1.9
Switching statistic counters
Circuit breaker wear monitoring Ix, I²t, 2P 2
CFC (Standard, Control)
2.1
CFC arithmetic
Switching sequences function 2.2
Inrush current detection
Disconnector
Region France: Overload protection for lines and cables 'PSL-PSC'
SIPROTEC
[[[
[[[
[[[
[[[
[[[
[[[
[[[
[[[
1.8 Contains the modules: Base module with PS101, IO101 and IO110
1.9
2 Standard variants for SIPROTEC 7SA86, 7SD86, 7SL86, 7SA87, 7SD87, 7SL87, 7VK87
SIPROTEC
[[[
2.2
[[[
[[[
SIPROTEC
[[[
[[[
[[[
[[[
SIPROTEC
s
SIPROTEC
[[[
[[[
[[[
2.6
Run Error SIPROTEC SIPROTEC
[[[
[[[
[[[
[[[
SIPROTEC
s
SIPROTEC
2.10
[[[
[[[
[[[
[[[
3.2
Run Error SIPROTEC SIPROTEC
[[[
[[[
[[[
3.4 Contains the modules: Base module with PS201 and IO208,
expansion module IO209.
3.5
3.6
3.7
2.5 / 54 SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 3
Line Protection
Standard variants
Standard variants for SIPROTEC 7SA86, 7SD86, 7SL86, 7SA87, 7SD87, 7SL87, 7VK87
1
Type 7 1/2, 15 BI, 20 BO, 16 LED, 8 I, 8 V s s
1.1
Run Error SIPROTEC SIPROTEC
[[[
[[[
[[[
[[[
[[[
[[[
[[[
1.6
[[[
1.9
Run Error SIPROTEC SIPROTEC SIPROTEC
[[[
[[[
[[[
SIPROTEC
s
SIPROTEC
s
SIPROTEC
2.2
Housing width 2/3 × 19", /LQH
2.3
[[[
[[[
[[[
SIPROTEC
s
SIPROTEC
s
SIPROTEC
[[[
[[[
[[[
SIPROTEC
s
SIPROTEC
s
SIPROTEC
s
SIPROTEC
[[[
[[[
[[[
Contains the modules: Base module with PS201 and IO208, 2.6
expansion modules IO208, IO209, IO209.
SIPROTEC
2.8
Housing width 1/3 × 19", /LQH
[[[
[[[
2.9
[[[
[[[
[[[
[[[
SIPROTEC
s
SIPROTEC 3.3
Housing width 1/3 × 19", /LQH
3.4
[[[
[[[
[[[