Mtl7000 Series: Ultra-Slim Safety Barriers That Can Be Used Like Terminals
Mtl7000 Series: Ultra-Slim Safety Barriers That Can Be Used Like Terminals
MTL7000 SERIES
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
MTL7000 SERIES – SPECIFICATIONS Key barriers shown in blue
Model Safety Application Basic circuit Max. end- Vwkg at Vmax Internal safety
No. description to-end 10µA fuse/fuse-
MTL resistance disconnect(FD)†
(V) Ω)
(Ω (mA) Ω)
(Ω (V) (V) (mA)
7128+
7128P+
28
28
300
234
93
120
} Controller outputs,
solenoids
4
5
1
1
2
342
275
26.0
26.0
27.2
27.1
50 (FD)
50 (FD)
6 3
7196–
20
26
20
390
300
390
52
87
52
}
Vibration probes
4
6
1
2
2
3
424
342
434
18.5
23.5
18.5
19.2
24.6
19.3
50
50 (FD)
50 (FD)
RETURN-DIODE TYPE
7087+
7187+
28
28
300
28 diode
300
28 diode
93
–
93
–
} Transmitters,
controller outputs,
switches
4
1
1
2
332
33 + 0.9V
342
43 + 0.9V
26.0
26.0
26.0
26.0
26.8
26.8
26.9
26.9
50
50
50 (FD)
50 (FD)
7087P+
7187P+
28
28
234 120
28 diode –
234 120
28 diode –
} Transmitters,
controller outputs,
switches
5
6
2
3
261
30 + 0.9V
274
43 + 0.9V
26.0
26.0
26.0
26.0
26.8
26.8
26.9
26.9
80
80
50 (FD)
50 (FD)
5 2
7055ac 3 10 300 2- or 3-wire (floating) 241 0.6 at 1µA 3.0 100
6 3
3 10 300 RTDs 241 0.6 at 1µA 3.0 100
4 1
}
7061Pac 9 350 26 4 1
384 7.2 8.5 50
9 350 26 Strain-gauge 384 7.2 8.5 50
7161Pac 9 350 26 bridge, sense, output 2 393 7.2 8.8 50 (FD)
9 350 26 2 393 7.2 8.8 50 (FD)
7264ac 12 1k 12 Strain-gauge 5 2 1048 10.0 11.1 50
12 1k 12 bridge sense 1048 10.0 11.1 50
6 3
7066Pac 12 75 160 97.2 9.8 10.9 80
7166Pac
12
12
12
75
75
75
160
160
160
} Strain-gauge
bridge supply
97.2
110.1
110.1
9.8
9.8
9.8
10.9
11.2
11.2
80
50 (FD)
50 (FD)
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
SPECIFICATIONS (continued)
Model Safety Application Basic circuit Max. end- Vwkg at Vmax Internal safety
No. description to-end 10µA fuse†/fuse-
MTL resistance disconnect (FD)
(V) Ω)
(Ω (mA) Ω)
(Ω (V) (V) (mA)
STAR-CONNECTED AC2
}
7060ac 9 75 120 Active dc and 1 101 7.2 8.5 50
9 75 120 ac sensors, 4 1 101 7.2 8.5 50
7160ac 9 75 120 thermocouples 2 110.1 7.2 8.8 50 (FD)
9 75 120 5 2 110.1 7.2 8.8 50 (FD)
}
7265ac 15 100 150 6 3 131 12.0 13.0 50
15 100 150 2-wire dc/ac 131 12.0 13.0 50
7278ac3 28 600 47 systems 640 +24.0 +25.9 50
–22.3 –23.8
28 600 47 640 +24.0 +25.9 50
–22.3 –23.8
ACTIVE BARRIERS
71064 28 300 93 Transmitters – – 35 50
72064 28 300 93 Transmitters – – 35 50
7207+ 28 300 93 Switches 348 + 1.2V – 35 50
28 diode 31 + 0.9V – – 50
7208+ 28 300 93 Solenoids, alarms, 348 + 1.2V – 35 50
LEDs
DUMMY BARRIERS
7099 – – – Securing and earthing – – – –
1
unused cables and screens. 4 1
7299 – – – Feed-through connections – – – –
for power comb. 5 2
6 3
†All barriers have internal, inaccessible, safety fuses. MTL7100 barriers have additional Note 4: Limited availability. Use MTL7706+ as an alternative.
replaceable fuses, lower in value than the internal fuses. It is the value of the replaceable fuse ‘P’ suffix – Barriers with a ‘P’ suffix are higher-power versions of the standard devices
that is quoted for MTL7100 barriers. with lower end-to-end resistance, except the MTL7061Pac/7161Pac. They are suitable for
Note 1: 24Ω ±0.15Ω at 20°C, channels track within 0.15Ω from –20 to +60°C.
type IIC gas groups, except MTL7129P+ which is designed for IIB.
Note 2: In star-connected barriers (eg, MTL7060/7160), the two channels are interlocked
WARNING – Check compatibility of the electrical safety
such that the voltage between them cannot exceed the working voltage, Vwkg.
parameters of the field equipment with those of the barriers to
Note 3: MTL7278ac: the working voltage between the two interlocked channels is 24.0V;
make sure that the combination is safe.
Vmax is 25.3V.
CERTIFICATION
MTL7000 Series barriers protect devices located in all normally
occurring explosive atmospheres, including air/flammable gas-
mixtures, dusts and fibres. MTL7000 Series barriers are certified [EEx MTL7000 standard
ia] IIC (except MTL7129P+, certified IIB) BY BASEEFA to CENELEC
standards, by FM in the USA, CSA in Canada and also by other
authorities, providing worldwide certification. MTL7000 Series
MTL7100 fuse-disconnect
barriers are designed to the same safety descriptions as MTL700
Series equivalents (in some cases slightly stricter) and can therefore be
used for the same applications.
MTL7200 link-disconnect
HOW THEY WORK
All MTL7000 Series barriers are based on the same simple principle. Note: the circuit shown is as an example only.
Each channel contains three stages of Zener or forward-connected Standard, fuse- or link-disconnect options are shown shaded in the
diodes and an ‘infallible’ terminating resistor. In the event of an 'basic circuits' in the specifications tables.
electrical fault in the safe area, the diodes limit the voltage that can
reach the hazardous area and the resistor limits the current: active
output-current limiting circuits are not used. An internal fuse protects
KEY BARRIERS SUMMARISED
the diodes, and the three stages of voltage limitation ensure continued
safety if the first or second stage should fail. MTL7100 barriers have TYPE APPLICATION KEY BARRIER
Analogue Resistance temperature detectors 7055ac 7060ac
an additional replaceable fuse which protects the internal fuse.
input (low level) Thermocouples, ac sensors 7160ac
The MTL7000 Series includes seven key barrier types which cover the Analogue Controller outputs, one line earthed 7028+ 7128+
majority of applications, simplifying barrier selection and the output Controller outputs, neither line earthed 7087+ 7187+
maintenance of spares stocks. dc power supply
26.0V 20-35V
Analogue Transmitters, 2-wire, 4/20mA 7087+ 7206
SUB-SERIES input (high level) 7187+
MTL7000 Series barrier circuits are based on the well-proven designs
Digital (on/off) Switches 7087+ 7207+
originally developed for the MTL700 Series. To simplify identification
input 7187+
for those familiar with the latter, part numbers are the same for
Digital (on/off) Solenoids, alarms, LEDs 7028+ 7208+
equivalent barriers, but with a ‘0’, ‘1’ or ‘2’ inserted after the initial
output 7128+
‘7’ to identify the relevant sub-series:
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
ACTIVE BARRIERS
MTL7206
Loop disconnect link
The MTL7106/MTL7206 is a single-channel barrier designed
primarily for energising a conventional or 'smart' 2-wire 4/20mA
hazardous-area transmitter. They can be thought of as an MTL7128– – 4 1
+20 to 35V
or an MTL7028– barrier with a built-in floating power supply and + 4/20mA 5 4/20mA
250mA 2
electronic over-volt protection. It provides a high voltage output (which Load
is negative with respect to earth) to power the transmitter and delivers 3 resistor
6
0V
a 4/20mA signal into an earthed load in the safe-area. The novel
design is noted for its extreme accuracy.
SPECIFICATION
Supply voltage
20 to 35V dc
Supply current
40mA typical at 20mA with 28V dc supply ‘Smart’ compatibility
45mA typical at 20mA with 24V dc supply HART Communication Foundation HART®
60mA maximum at 20mA with 20V dc supply Honeywell DE
Voltage for transmitter and lines Yokogawa BRAIN
16.0V minimum at 20mA with 250Ω load Foxboro ‘smart’
11.25V minimum at 20mA with 500Ω load Fuji ‘smart’
Note that the output voltage is negative with respect to earth. Chessel 3500 Series
Safe-area load resistance Patent Nos
0 to 500Ω UK: 2205699
Output current European (Germany, France, Italy): EP 0 294 139 BI
0 to 23.6mA USA: 4967302
Accuracy
±2µA (4 to 20mA)
Out of range capability
Over-range; >20mA to 23.6mA
Under-range; <4mA to 0mA
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
Hazardous Safe area
area
MTL7207+
for digital (switch) inputs Loop disconnect link
Current limit
4 50mA 1
+
Iout 10 to 35V dc max
5 1.5mA max 2
50mA
SPECIFICATION 6 3
0V
Current limit
4 50mA 1
LED, +
alarm, Iout
10 to 35V dc max
5 1.5mA max 2
solenoid, 0V
etc
SPECIFICATION 6 3
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
Safe area
MTL7991
power feed module To barriers via
1 800mA max power comb
4
Solid-state
switch Current 2 External power
5 sense
Voltage Trip supply
Green sense circuit Red 3 20 to 26.8V dc
6 power at 1.8A min
LED fault
LED
Note: All specifications quoted at 20°C ambient unless otherwise stated. Channel 1 Channel 2
(terminal 1 to 4) (terminal 2 to 5)
Colour-coded top label
+0.3
7 –0.0
MTL7XXX
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
MTL7000 Series barriers protect devices located in all normally
MTL7000 SERIES BARRIER occurring explosive atmospheres, including air/flammable gas
mixtures, dusts and fibres. Applications covered include the protection
of installations incorporating uncertified devices (‘simple apparatus’)
APPLICATIONS such as thermocouples, switches and resistive sensors, or separately
certified ‘energy storing’ (or ‘voltage producing’) apparatus including
ac sensors, transmitters and current-to-pneumatic (I/P) converters.
Recommended choices for specific applications are discussed briefly
in the following pages.
Vibration probes
The 3-wire transmitters used with vibration monitoring equipment are Probe
driver Monitor
invariably supplied by a –24V dc power supply – hence the Transducer 4 1 –24V
recommended barrier choice is the negatively-polarised MTL7096–
5 2
/7196–. The ‘third terminal’ makes this choice ideal for these 3-wire V out
applications. 6 3
0V
MTL7096–
MTL7196–
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
RTDs Hazardous Safe area
For 3-wire RTDs, a single MTL7055ac barrier is the most economical area
choice. This is suitable for use with a floating bridge – the two leads
from the bridge arms are protected by the barrier with the third 4 1
(supply) lead being earthed through the barrier. The barrier has a low
5 2
end-to-end resistance of only 24Ω/channel to minimise span changes
and its channels track within 0.15Ω (between –20 to +60°C) to 6 3
Receiver
4 1
4-wire constant-current circuits do not need matched barrier
5 2
resistances and can be protected by two MTL7261ac barriers. If the
increase in loop resistance is too great, use two MTL7055ac barriers 6 3
instead. MTL7261ac
MTL7055ac
Receiver
4 1
5 2
6 3
MTL7261ac
MTL7055ac
STRAIN-GAUGE BRIDGES
Single strain-gauge bridges
This shows an arrangement using two or three barriers, which is safe
in IIC gases. With the MTL7261ac, the circuit is powered from a 14V,
4 1
230Ω source; if the bridge resistance is 230Ω, then the bridge +7V
5 2
voltage is 7V. If the bridge resistance is 350Ω, then the bridge voltage –7V
is 8.4V. 6 3
0V
MTL7261ac
An MTL7264ac can be used to sense the bridge supply voltage.
MTL7264ac
4 1
5 2 Output (mV)
6 3
MTL7261ac
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
Double strain-gauge bridges Hazardous Safe area
Quite frequently there is a demand to monitor two load cells, and a area
possible circuit, safe in IIC, is shown. 4 1
+10V
5 2
Here, the lower voltage drop of the MTL7066Pac is an advantage. –10V
6 3
0V
The MTL7066Pac supplies power to the bridge(s) whilst two MTL7066Pac
MTL7061Pac/7161Pac barriers interface with the sense and pick-off
circuits.
Using 350Ω bridge systems, the following voltages are available from
an MTL7066Pac with a ±10V supply: 4 1
+
1 bridge: 12.8V 5 2 Sense
–
2 bridges: 9.4V
6 3
MTL7061Pac
MTL7161Pac
4 1
5 2 Output (mV)
6 3
MTL7061Pac
MTL7161Pac
ANALOGUE OUTPUTS
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
DIGITAL (ON/OFF) INPUTS Hazardous Safe area
area
Switches
The normal choice is the MTL7087+/7187+ with a regulated supply.
4 1
The MTL7207+ is recommended for applications where an +26V
5 2
unregulated supply of up to 35V is used. Logic signal
6 3
MTL7087+ 0V
For optimum power transfer, with relays the resistance of the load MTL7187+
should be approximately equal to the combined resistance of the two MTL7207+
channels and the relay coil should then be rated at about half the
supply voltage.
+VE DC SYSTEMS
Low-level to 12V dc systems
4 1
The two channels of the MTL7162+, MTL7164+ and MTL7167+ can +6V/9V/12V
be combined safely in IIC. dc 5 2
systems +6V/9V/12V
6 3
0V
The MTL7164+ can be used for low-level logic return signals. The MTL7162+
MTL7164+
MTL7162+ and MTL7167+ are used for 6V dc and 12V dc systems MTL7167+
respectively.
4 1
18V dc systems dc +18V
systems 5 2
The single-channel MTL7122+ is recommended for 18V dc systems. 0V
6 3
MTL7122+
AC AND DC SYSTEMS
High-level ac and dc systems
4 1
The versatile star-connected MTL7265ac and MTL7278ac allow
dc and ac 5 2 12V/24V
Vwkg to be developed from each channel to ground but only allow
systems
Vwkg to be developed between channels. This provides some 6 3
0V
common-mode voltage capability and can allow higher cable
MTL7265ac
parameters to be used. MTL7278ac
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
POWER COMB APPLICATIONS Hazardous Safe area
The PWC7000 power comb is invaluable for saving installation time area
and wiring when connecting a 24V dc power source to a number of 1
barriers.
2 External 24V dc
MTL7991 supply
Typical applications include hazardous-area switches, 4/20mA 3
OR 0V
transmitters and solenoids. The diagram illustrates the configuration MTL7099
for 3 barriers but up to 40 barriers can be served by this method. MTL7299
4 1
5 2 Logic
signal
6 MTL7087+ 3
MTL7187+ 0V
MTL7087P+
MTL7187P+
Power comb
PWC7000
MTL7099
MTL7299
WIRED IN APPLICATIONS 4 1
MTL7299s can be 'looped-in' to provide link-disconnects for MTL70xx 5 2
barriers, eg. as shown here with an MTL7055ac and an RTD.
6 3
For high accuracy or sensitive low level applications check that the
MTL7055ac
additional connections do not degrade the signals.
4 1
5 2
6 3
MTL7299
Receiver
4 1
5 2
6 3
MTL7299
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
MAXIMUM CABLE PARAMETERS
Notes
Key barriers in bold
1If values are not quoted for when on earth return is not used, then those for an earth return ('Yes' in the tables) are applicable
2For most practical purposes, the values of the parameters for groups IIB and IIA are respectively 3 and 8 times the values for group IIC
3The maximum power that can be drawn from the barrier or barrier combination under fault conditions; used for assessing the temperature classification of
‘simple' hazardous-area apparatus
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com
HOW TO ORDER
MTL7000/7100/7200 barriers
Replaceable fuses/removable links
Select by barrier number and polarity,
RFA7050 Replaceable fuse assemblies, 50mA,
e.g. MTL7028+
pack of 5
RFA7100 Replaceable fuse assemblies, 100mA,
Mounting accessories
pack of 5
THR2 Standard DIN-rail, 35 x 7.5mm
RLA7000 Removable link, pack of 5
THR7000 T-section DIN-rail, specially-plated,
35 x 7.5mm, 1m length
Enclosures
ISP7000 Insulating spacer
DX070 Enclosure, for MTL7000 x 9
DX170 Enclosure, for MTL7000 x 22
Standard earthing/earth-rail accessories
DX430 Enclosure, for MTL7000 x 58
ETL7000 Earth terminal, DIN-rail mounted
IMB57 Insulating mounting block Literature
ERB57S Earth-rail bracket, straight INM7000 Instruction manual, MTL7000 Series
ERB57O Earth-rail bracket, offset INM57ENC Instruction manual, MTL5000/7000
ERL7 Earth rail, 1m length Series Enclosures
ETM7 Earth terminal, pack of 50 CD700... Customer drawings
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: [email protected] Web site: www.mtl-inst.com