Se 402 e PDF
Se 402 e PDF
- 10 -
Elektronik GmbH
- 11 -
Elektronik GmbH
Functions
Analogue and digital inputs and outputs
Analogue inputs (actual values) 4, standard signal 0 ... 10V, 0(4) ... 20mA, THK, PT100
Analogue outputs 2 (option) 0 ... 10V, 0(4) ... 20mA (indicate range when ordering)
Digital inputs 16 (8 option)
Digital outputs 16 (8 option)
- 12 -
Elektronik GmbH
Functions
Programmer
Programs 25
Loops 8 per program
Set values 4
Digital tracks 12
Segments 50 per program maximum (maximum of 400 segments in the device)
Process steps 50 maximum, freely configurable
Controller
Control zones 2 (optional 4)
Controller types PID continuous action, 2-setpoint, 2-setpoint PID,
3-setpoint, 3-setpoint PID, 3-setpoint stepping (PI), configurable
PID parameters 8 sets of parameters (Xp, Tn, Tv) per control zone
Tolerance band 1 per control zone (+tolerance/-tolerance)
Limit values 2 limit values per control zone (high/low limit value)
Formula
Formula 4, Operations: +, -, :, *, +, -, :, *,
Tolerances
Tolerances 8
Tolerance outputs 16 (1 for each plus-tolerance, 1 for each minus-tolerance)
Comparisons Sv-Sv, Av-Av, formula value X-Sv, X-Av, X-X
Limit values
Limit values 8
Possible values Sv, Av, formula value X, variable value, controller actual value and set value
Alarms
Alarms 16
Internal error alarms 20
Alarm priority levels 8
Alarm delays 8 (= priorities), 0.1 ... 99.9 sec, configurable
Alarm processing 1:1, binary or BCD, configurable
System alarm output for visual and acoustic signal, acknowledgement of individual alarms selective
Analogue multiplexers
MUX modules 2
Possible values Sv, Av, formula value X, variable
Analogue inputs per MUX module 4
Internal PLC function
Number of statements 1600 maximum
Programming by statement list statement list (STL)
Possible commands logical commands, timer commands (switch-on-, -off-delay, time impulse)
Number of timers 64
Number of flags 512
Cycle time 100 msec
- 13 -
Elektronik GmbH
Configuration
• Menu-assisted configuration in tables
(no programming knowledge necessary)
• Easy language switching by menu
• 5 operating levels
• Configurable texts and dimensions
• Configuration backup on PC
• Direct modem connection possible
• Hardware configuration (plug-in card)
• Configuration of all software function modules available in the device
(actual-, set value, control zone, tolerances, limit values etc.)
• Configuration changes on the device during operation
Programs (Recipes)
• 25 programs with up to 50 segments
• Configurable process steps
• Plain text descriptions for programs (up to 16 characters)
• Graphic representation of set value curves and control tracks
• Configurable program loops (8 loops per program)
• Test, modify, copy, delete programs
Operation
• Control zone overall display
• Graphic set/actual value comparison
• Numerical and graphic data display of set values and tracks
• Representation of actual values, limit values, tolerance values and
formula values
• Plain text alarm display with history memory
• 4 operator panel display page (freely configurable display pages)
• Jump in the program
• Programming of an automatic program start
• Manual operation for set values and tracks even during program run
• Control parameter auto-optimization (“self-tuning“)
• Manual operation mode for the manipulated variable Y (“Y-Man.“)
- 14 -
Elektronik GmbH
Configuration: RS232
via PC Control System: RS422
Protocol: JBus (Option)
Protocol: JBus
STK-Box
(RS422/RS232-Converter)
Supplementary Equipment
• DAC2-402 2 analogue outputs, with electrical isolation
0 ... 10V, 0 ... 20 mA, 4 ... 20 mA, resolution12 Bit
• E8A8-402 8 digital inputs, 8 digital outputs (200mA maximum)
optocoupler 24 V DC
= total 16 digital inputs and 16 digital outputs in the device
• SI-JBUS-402 Computer interface (RS232, RS422)
for process control system connection (e.g. ECS)
• 4RZ-402 2 further control zones for a total of 4 (software upgrade)
• DIA402 Display/operating dialogue: Italian, Finnish, Swedish (Progr./Operation)
Device standard languages: German, English, French
- 15 -
Elektronik GmbH
144,0
144,0
Side view
mating 136,0
connector
220,0
225,0
60,0
Rear view
Hardware reset
Configuration interface
CPU-board mating connector
mating connector (serial interface)
136,0
ADDA-board DSI-board
mating connector mating connector
(serial interface)
136,0
- 16 -
Elektronik GmbH
LCD Display,
with background lighting,
160 x 128 pixels
Power Pack 6 A
Watch Dog
Alarm Relay Li-battery
Hardware clock
85..264V AC
50..60 Hz
CPU Board
8 opto-inputs,
8 opto-outputs
8 digital inputs
8 digital outputs
Main Memory Internal Memory
128 kB SRAM 512 kB EPROM
ADDA Board
E8A8 (option)
4 act. value inputs for
8 digital inputs 8 opto-inputs, 4 analogue inputs
thermocouples, Pt100
8 digital outputs 8 opto-outputs
and 0 ... 10 V, 0(4) ... 20 mA
DAC 2 (option)
2 analogue outputs 2 analogue outputs
0 ... 10 V, 0(4) ... 20 mA