0% found this document useful (0 votes)
149 views7 pages

The Gauss-Seidel Method-Procedure & Example: δ =0 i = 2,3, ……………. G V =1, δ =0 i = G+1, G+2, ……… n

1) The document describes the Gauss-Seidel method for solving load flows in power systems. It provides the steps of the method and an example application. 2) The example power system has 3 buses: a slack bus, a generator bus, and a load bus. Initial values are assumed and voltages are iteratively calculated until convergence within 0.01 pu. 3) Following the steps, the voltages converge to V1 = 1∠0°, V2 = 1∠3.72°, V3 = 0.923∠-3.88°. Line flows and losses are then calculated.

Uploaded by

Saikat Mahmud
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
149 views7 pages

The Gauss-Seidel Method-Procedure & Example: δ =0 i = 2,3, ……………. G V =1, δ =0 i = G+1, G+2, ……… n

1) The document describes the Gauss-Seidel method for solving load flows in power systems. It provides the steps of the method and an example application. 2) The example power system has 3 buses: a slack bus, a generator bus, and a load bus. Initial values are assumed and voltages are iteratively calculated until convergence within 0.01 pu. 3) Following the steps, the voltages converge to V1 = 1∠0°, V2 = 1∠3.72°, V3 = 0.923∠-3.88°. Line flows and losses are then calculated.

Uploaded by

Saikat Mahmud
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

The Gauss-Seidel Method-Procedure & Example

Consider a power system with a total of n buses, out of which G is


the number of generator buses. Bus number 1 is taken as the slack
(swing) bus. The steps for the Gauss-Seidel algorithm for load
flow studies are summarized in the following.

1. Form the network YBUS (excluding the generator-transformer


circuit) in pu system.

2. Assume the following initial values,

δi=0 i = 2,3, ……………. G


Vi=1, δi=0 i = G+1, G+2, ……… n
3. Calculate Q2 by the equation, use the value of subscript i=2

n
(7)
Q i = − Im[(Yii Vi + ∑ Yij Vj )Vi* ] , j≠i
j=1

4. Calculate V2=V2c∠δ2c by the equation (c stands for calculated


value), use i=2

1 Pi − jQ i n (8)
Vi = [ − ∑ Yij Vj ], j ≠ i
Yii Vi* j=1

Set V2=V2s∠δ2c where, V2s is the specified generator voltage at bus


2.

5. Repeat steps 3 and 4 for k = 3, 4, …G

6. Calculate VG+1 by equation (8). Note this is a load bus and the
sign of Pi and Qi should be reversed.

7. Repeat step 6 for all the load buses k = G+2, G+3…. n

8. Calculate ∆V and ∆δ for all the buses comparing with values


from the previous step by the relationship,
∆Vi = Vi1 − Vi0 , ∆δ i = δ i1 − δ i0 i=2,3, ….n

9. This is the end of the iteration. Check convergence of the


solution for all the bus voltages. If the maximum value is
within the specified tolerance, a solution has been reached.
Otherwise, repeat steps 3 though 8 until the solution is
reached.
10. Calculate P1 and Q1 from

n (9)
S1 = V1[( ∑ Y1 j Vj )]*
j=1

The transmission line flows can be computed from

(10)
Sij = Vi [(Vi − Vj ) y ij ]*

where, yij is the admittance of line i-j.

Convergence can be accelerated by using an acceleration


factor (between 1.3 and 1.6) in steps 4 though 7. The new
value is calculated as,

Vikα+1 = Vik + α (Vik +1 − Vik )

k +1
where, α is the acceleration factor. Viα is the accelerated
value which is used in the next step instead of Vik+1
Example: The Gauss-Seidel Method
The one line diagram of a power system, with the generator reactances
omitted, is given below. The reactances indicated are on 100 MVA base.

1 j0.5 2

j0.2 j0.25

The power output of generator 2 is 60 MW and the voltage is 1 pu. The load
on bus 3 is P=80 MW, Q=60 MVAR. Considering the voltage of slack
generator 1 to be, obtain a power flow solution using a tolerance of 0.01 on
the voltage magnitudes.

Summary of bus information provided

Bus 1 : slack (swing) V 1= 1∠0 0 P1 = Q 1=

Bus 2 : Generator (PV) V2=1 pu, δ2= P2= 60 MW (0.6 pu) Q 2=

Bus 3 : Load (PQ) V 3= δ3= P3=80 MW Q3=60MVAR

6 known quantities, 6 unknown quantities.

Follow the steps as given on the procedure:

 7 − 2 − 5
1.
Y = − j − 2 6 − 4
BUS  
 − 5 − 4 9 
2. Select the unknown quantities as,

δ2 = 0 │V3 │= 1 δ3 = 0
3. Iteration #1

Calculate,

Q2= -Im[(Y22 V2 + Y21 V1 + Y23 V3) V2*]


= -Im[ (-j6 x 1∠0 0 +j2 x 1∠0 0 + j4 x1∠0 0)]
=0

1 P2 − jQ 2
4. V2 = [ − Y21V1 − Y23 V3 ]
Y22 V2*
1 0.6 + j0
= [ − j2 x1∠0 − j4 x (1∠0)]
- j6 V2*
= 1 + j0.1 = 1.00498∠5.710

Set, V2= 1.00∠5.71 = 0.999+j0.0995


0

5. Does not apply

6.
1 P3 − jQ 3
V3 = [ − Y31V1 − Y32 V2 ]
Y33 V3*
1 − 0.8 + j0.6
= [ − j5x1∠0 − j4 x (1∠5.71)]
- j9 V3*
= 0.93112 - j0.0446 = 0.9321∠ - 2.74 0

7. Does not apply

8. Check:

∆V2 = V2(1) − V2( 0 ) = (0.995 + j0.0995) − (1 + j0) = 0.0996


∆V3 = V3(1) − V3( 0 ) = (0.93112 − j0.0446) − (1 + j0) = 0.082
MaximumVariation = 0.0996
9. Iteration #2

Q 2 = − Im{[− j6 x1∠5.710 + j2 x1∠0 0 + j4 x 0.932∠ − 2.74 0 ]x (1∠ − 5.710 )}


= 0.3216 pu
1 0.6 − j0.3216
V2 == [ *
− j2 x1∠0 − j4 x (0.932∠ − 2.74 0 )]
- j6 V2
= 1.0003∠4.3030
Set, V2 = 1∠4.3030

1 − 0.8 + j0.6
V3 = [ *
− j5 x1∠0 − j4(1∠ 4 . 303 0
)]
- j9 V3
= 0.9227 − j0.058 = 0.9245∠ − 3.6250

Check:

∆V2 = 1∠4.3030 − 1∠5.710 = 0.0245


=
∆V3 0.9245∠ − 3.6250 − 0.9321∠ − 2.74
= 0
0.016
Magnitude of maximum change is 0.0245

Iteration #3

V2 = 0.9978 + j0.065 = 1∠3.72 0


V3 = 0.921 − j0.062 = 0.923∠ − 3.880
∆V2 = 0.01004
∆V3 = 0.0043
The desired tolerance is acheived.
The Line flows, Line losses, and Slack Generation

Flow in line 1-2

S12 = V1I12
*

= V1 [(V1 − V2 ) y12 ]* xBaseMVA


= −13.0043MW + j0.4232 MVAR
Similarly, flow in line 2-1

S21 = V2 I*21
= V2 [(V2 − V1 ) y 21 ]* xBaseMVA
= 13.0043MW + j0.4232 MVAR

Loss in line 1-2


Sloss(1-2)= j0.8464 MVAR

or, Ploss(1-2) =0; Qloss(1-2) = 0.8464 MVAR (reactive)

Flow in line 1-3

S13 = V1I13
*

= V1 [(V1 − V3 ) y13 ]* xBaseMVA


= 31.2438MW + j39.489 MVAR

Calculate the other line flows.

Slack Generation

S1= S12 + S13


=18.239 MW + j39.9128 MVAR
The line flows are shown in the figure below.

V1 = 1∠0 0 V2 = 1∠3.72 0

18.24+j39.9 60+j34.4

1 2
-13.0+j.42 13.0+j.42
31.24+j39.48 48.89 +j33.99

-31.24-j34.41 3 -48.89-j25.12

S3=80+j60

You might also like