100% found this document useful (3 votes)
392 views33 pages

Turbine Operating Procedure

This document provides procedures for starting up and shutting down a steam turbine system. It includes safety precautions and prerequisites that must be completed before startup. The procedures describe cold startup, hot startup, normal operation, abnormal conditions, normal shutdown, and emergency shutdown. It also provides specifications for the turbine, auxiliaries, governing system, and safety protections. The goal is to ensure the equipment can be safely started up and operated in an orderly manner.

Uploaded by

Yudi Permana
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
392 views33 pages

Turbine Operating Procedure

This document provides procedures for starting up and shutting down a steam turbine system. It includes safety precautions and prerequisites that must be completed before startup. The procedures describe cold startup, hot startup, normal operation, abnormal conditions, normal shutdown, and emergency shutdown. It also provides specifications for the turbine, auxiliaries, governing system, and safety protections. The goal is to ensure the equipment can be safely started up and operated in an orderly manner.

Uploaded by

Yudi Permana
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 33

REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

TURBINE OPERATING PROCEDURE

Rev. Description Date Prepared by Check by : Reviewed by : Approved by :

Client Project No.


Drawing No.

ELECTRONIC FILE NAME NO. Date of issue : Revision No.: 0

2 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

TABLE OF CONTENT

No. Description Page

COVER 1
TABLE OF CONTENT 2
1 Purpose 3
2 Reference document 3
3 Test equipment 3
4 Safety Precautions 3
5 Pre-requisite 4
Description of the System and Equipment
6 4
Specification
7 Turbine and Auxiliaries Equipment Stipulation 5
8 Commisioning and Sequence Start-up 7
9 Main steam heating/warming up 8
10 Start up steam turbine 8

A. Cold start up of steam turbine 8

B. Hot start up of steam turbine 15

C. Control operation 19

D. Abnormal operation condition 20

E. Normal shut down 22

F. Emergency shut down 23


11 Performance curve 24
12 Preparation check list 26
13 Alarm Protection system – information 29
14 Interlock shut down 32

1. Purpose
3 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

The purpose of this document is to present the Steam Turbine start up,
shutdown, and trouble shooting to ensure the equipment and system can
be put into operation in an orderly way.

2. Reference Document
 Design Drawing
 Steam Turbine Operating Manual

3. Test Equipment
 DCS and Local meters

4. Safety Precautions
 Ensuring for all of authorized personal has been provided for “Personal
protective equipment” (Safety shoes, safety helmet, safety glass, ear
plug and / or other safety requirements).
 Ensuring labeling / Marking for all inspected electrical equipment, tools
or appliances that era safe for use before issuing them workers.
 All construction machinery, mechanical equipment and electrical
appliances shall by inspection and tested safe for use by competent
person for non-statutory equipment. And by an approved person for
statutory equipment. In addition all construction equipment must be
checked by competent / authorized personal before commencement of
work at site.
 Provide “Warning line” erected around all sides of work area for the
purpose of preventing disturbing form unauthorized personal during
commissioning.
 When work is performed on electrically powered equipment and
associated circuit, the electrical lock-out / Tag-out shall be applied
prior to work commencement.
 No one shall change, alter or modify any electrical equipment, tools or
instrument except authorized electrician / technician.

5. Pre-requisite
 Check name plate, cleanliness, labeling, and grounding point of the
equipment, such as motor, pump (if any) and etc.
 Check all equipment has been installed completely.
 All instruments have been calibrated.

4 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

 All the lubricating oil pumps as part equipment of the Turbine have
completely installed and have been commissioning.
 Generator have installed completely.
 Generator system have installed completely.
 All I&C for Steam Turbine have installed completely and operable.
 All I&C for Generator have installed completely and operable.
 DCS have installed completely and operable.
 Boiler main steam ready to supply turbine
 Cooling system ready to supply water cooling for condenser and
equipment auxiliary.
 Taking Over Package (TOP) has been issued by construction team that
system is ready for commissioning.

6. Pre-requisite
SPECIFICATION OF TURBINE

Model : N3.5-3.83
Type : Single cylinder, medium tempe-
ratute, intermediate pressure,
impulse condensing turbine
Governing Mode : Nozzle governing
Rated power : 3500 kW
Speed : 5600 rpm
Working grid frequency : 50 Hz
Rated Inlet pressure : 3.83 MPa
Rated Inlet temperature : 435 C
Inlet steam flow : 36.8 t/h
Exhaust pressure at rated condition : 0.0103 MPa
Stage number for Feed Water : Deaerator
Temperature of Feed water : 150 C
Critical Speed : 1750 rpm and 2500 rpm
Trip Speed : 3300 rpm dan 3330 rpm
Vibration bearing at rated speed : ≤ 0.03mm
Vibration bearing at critical speed : ≤ 0.15mm
Speed variation : ≤ 15%
Speed regulation : 4.5%, adjustable
Insensitivity of speed governing : ≤ 0.5%
Cooling water temperature : 32 C
Rotation direction : Clockwise when viewed toward
steam flow direction

7. Turbine and Auxiliaries Equipment Stipulation


5 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

7.1. The normal variable range of the parameters of the steam ahead of
Main Steam Valve (MSV) are as followings:
1) The pressure of steam before MSV : 4,9MPa; max. 5,1MPa, min.
4.6MPa.
2) The temperature of steam before MSV : 470C; max. 480C,
min. 455C.

7.2. The steam turbine is still allowed to operation in long term with
rated electric power under the following circumstances:
1) The steam pressure drops to no less than 4.6MPa, the steam
temperature falling to no less than 455C, and the cooling water
inlet temperature not exceeding 25C.
2) The temperature of cooling water inlet rises to 33C, but the
following conditions must be meet:
a. The steam parameters shall be not less than the rated
values
b. The condenser shall keep the calculated water consumption
c. The quantity of feeding water that enters the HP heater is
not more than 105% of the total steam flow into turbine
under the condition.

7.3. When the pressure of the steam ahead of the MSV is 5.1 MPa
(absolute) or the steam temperature is 485 C, the turbine unit
running shall not exceed 30 minutes. Annual accumulative total
must not exceed 20 hours.

7.4. When the pressure of the steam ahead of the MSV is less than 4.6MPa
(absolute) or the steam temperature is less than 455C, it should be
reduced load operation according to regulations.

7.5. Governing System


1) Turbine speed instant variation is within ±0.5% at stable load
and continuous running.
2) Speed variation is within 5% (unequal rate) when total adding/
reducing load is 100% of rated load.
3) The maximum increase in the short time speed shall not actuated
emergency governor when turbine running from full load to no-
load in suddenly.
4) Steam turbine governor system should be able to maintain full
load operation under the condition of design back pressure and
MSV full open.

7.6. Safety Protection Stipulation:


6 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

1) Emergency governor will trip when turbine running at 111% of


rated speed. In 3 continuous tests, previously 2 tripping speed
difference shall not be over 0.6% and third tripping speed
difference with 2 previous speed average value shall not be over
1%.
2) MSV will close automatically (adjusting the valve, 1 st stage steam
extraction valve and 2nd stage steam extraction valve will close
at the same time) within 1 second following emergency governor
tripped and turbine speed also increase but maximum shall not
run over 14% of rated speed.
3) A signal should be given out from the axial displacement
monitoring device when rotor axial displacement over 0.4mm
toward lower side, and the axial displacement breaker will act
(meanwhile, the magnetic shutoff valve will act with the
electromagnetic device) to make MSV, adjusting valve, 1 st stage
steam extraction valve and 2nd stage steam extraction valve shut
off immediately for safety when displacement over 0.7mm.
4) Protective action when lubrication oil pressure drop:
Start the lubricating oil pump when lubricating oil pressure down to
0.04MPa, through the relevant electromagnetic device makes
magnetic breakers throttle actuate and stop the turbine when
lubricating oil pressure down to 0.03 MPa.
5) When the oil return temperature of the bearing is above 65C,
the dual upper limit remote thermometer can signal through the
relevant device.
6) It shall send a signal when the level of the oil tank below the
lower limit of the normal level, the oil tank is also equipped with
level indicator.
7) In emergency situation, operator in charge of electric can shut
down turbine through the magnetic shutoff oil valve.
8) When the vacuum inside the condenser fails, and the pressure
rises from 0.104MPa to 0.107MPa, the back cylinder air
discharge valve will act to discharge the steam to the
atmosphere.
9) Stage I and II non-regulated extraction steam pipes have
equipped steam extraction quick closing valves which will close
automatically by discharging its pressure oil after the closing of
the MS. Stage III extraction steam uses common check valve
because of its low pressure.

7.7. Oil Line System


The oil pressure of the system shall be kept within the following range when
the unit operates normally:
- Bearing lubricating oil pressure 0.08-0.12 MPa
7 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

- Main oil pump outlet oil pressure 0.834 MPa


The temperature of the bearings shall be below 65C under the normal
operation condition, when the inlet water temperature of the oil
cooler water coolant is below 33C.

7.8. Condensing system


The condensing system is supplied with starting ejector and steam jet air
ejector to maintain the vacuum of the condenser during the start-up
and the normal condition.
The exhaust capacity of the steam jet air jector is 15 kg/h, inlet pressure is
1,2 MPa and its flow is 375 m3/h.

8. Commissioning and Sequence Start Up


8.1 Pre-condition Checking
1) Communication facilities should be ready, boiler operator, turbine
operator, electrical section and instrument section should be easy to
commonication
2) Prepare tools and meters from instrument, electric, mechanical
that ready to application
3) All equipments shall be inspected in detail and it is ensured that the
installation is completed. The turbine generator set’s accessory
equipments and the floor around are clean.
4) All instrumentation sensors/meters had been installed, callibrated
and tested, shuch as temperatur sensor, pressure sensor, vibration
sensor, speed sensor and displacement.
5) Oil system
a. Oil tank level > 100 mm
b. Exhaust oil fan shall be normal condition/ready to operation
c. Lubricating oil filter is clean
d. Control oil filter is clean
e. HP oil pump and valves is ready to operation
f. AC electric pump and valves ready to operation
g. DC oil pump and valves ready to operation
h. Oil shall be equivalent to ISO-VG-46 a and cleanness is
maximal NAS 7
6) Cooling system
a. Cooling tower basin level is +10 cm from NWL
b. Circulating water pumps and valves are ready to operation
c. Cooling tower fans are ready to operation
7) Cooler systeam
A. Oil cooler system
a. Oil cooler and valves are ready to operation
b. No oil leaking
B. Air cooler system
8 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

a. Oil cooler and valves are ready to operation


b. No oil leaking
8) Condenser system
a. Hot well box water level is > 400 mm
b. Inlet and outlet valve water cooling is ready to operation
c. Condensate pump and valves ready to operation
9) HP and LP heater
a. Confirm that HP and LP heater ready to operation
b. All valves are ready to operation
10) Gland heater
a. Gland heater and valves ready to operation
b. Gand heater fan ready to operation
11) Steam jet air injector
a. Steam jet air injector ready to operation
b. Drain valve close position
c. Inlet and outlet water valve close position
d. Inlet valve from condenser close position
e. Inlet steam valve close position
12) Surge tank
a. Surge tank ready to operation
b. Inlet and outlet valve close position
c. Surge tank fan ready to operation
13) Expantion tank
a. Expantion tank ready to operation
b. All inlet valve close position
14) Steam pipe line turbine section
a. Isolation motor valve try to operation with close and open
b. Isolation valve close position
c. By pass valve close position
15) Control section
a. Panel control ( TSI and ETS) are ready to operation
b. Woodward system is ready to operation
16) Generator section
a. Over all generator is ready operation
b. Synchronize System panel and DCS is ready to operation
17) Turbine steam section
a. MSV ready to opration, with open and close
b. MSV close position
c. Extraction valve #1, extraction valve #2 and extraction valve
#3 are ready to operation, with close and open
d. Extraction valve #1, extraction valve #2 and extraction valve
#3 are close position

18) Turning gear


9 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

a. Turning gear motor is ready to opration


b. Manual turning gear is ready to operation

9. Main steam pipe heating/warming.

1. Boiler has been starting and minimal condition of main steam header
pressure > 3,0 Mpa and temperatur > 350 °C. Main steam pipe line
warming up can start with boiler pressure increasing process to 5,3 Mpa.
2. Main steam supply valve from Boiler close position
3. All drain valves of main steam pipe open position.
4. Main steam isolation valve of turbine close position.
5. Start heating the main steam pipe with open by pass valve of main steam
supply valve from boiler, step by step.
6. Monitor pressure and temperatur of pipe line, incraesing pressure rate 0,1
– 0,15 MPa /minute.
7. Heating is completed around 45 minuts and the pipe tempratur > 400 °C

10. Start up Steam Turbine

The turbine start-up method is decided by the metal temperature at the lower part of
casing at the control stage, divided:

a. Cold start up : < 250C


b. Hot start up : ≥ 250C or within 12hours turbine restart

A. Cold start up Steam turbine

1. Ensure condenser ready to operation, inlet and outlet of water cooling


are open.
2. Oil cooler is ready to operation, air release valve close position, intlet
and outlet for water and oil are open position
3. Air cooler is ready to operation, air release valve close position, intlet
and outlet for water are open position.
4. Start cooling tower system, basin water level is + 10 cm from NWL,
start cooling tower fan and cooling water pump.
5. Oil filter shall be clean and ready to operation, open inlet and outlet
valve .
6. Start high pressure oil pump and ensure discharge pressure ± 0,834
Mpa.
7. Start oil tank exhaust fan.
8. Start turning gear,

10 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

9. Open valve step by step for steam extraction #1, steam extraction #2,
steam extraction #3 and turbine drain valve.
10. LP heater drain valve open and condensate recirculation valve to
condenser is close.
11. HP heater drain valve open and condensate recirculation valve to
deaerator is close.
12. Expansion tank, open drain valve step by step from inlet steam pipe,
extraction #1, drain from turbine, extraction #2, xtraction #3.
13. Start gland heater fan.
14. Start condensate pump and recirculation the water from condenser to
LP heater by adjusting control valve. Analisysed the water, if the water
quality is out of specification than some water drained and keep
condenser level is NWL by make up from demin water.
15. Open manual steam valve to surge tank step by step and start surge
tank fan. Keep surge tank pressure 0,1010 – 0,1275 Mpa.
16. Adjusted steam temperatur sealing to rear of turbine by open
condensate spreay valve.
17. Open condenser vacuum valve and start steam air ejector start up by
open the steam valve for starting steam ejector. Main steam pressure ±
1,2 Mpa and condenser vacuum ≤ -0,04 Mpa.
18. Open MSV for turbine and governor valve shlud be close position.
19. Open by pass valve of isolation motor valve step by step and start
heating of MSV and inlet steam pipe. Heating is finished after
temperatur >400 C.
20. Local site – reset trip buthon valve
21. TSI panel on normal operation the interlock swicth shall ‘on’ position for
below items :
a. Shutdown at generator breaker protection action or trip position
b. Shutdown at turbine over speed  3300 rpm and  3330 rpm
c. Shutdown at lubricating oil pressure  0,04 Mpa
d. Shutdown at vacuum prssur  -0,04 Mpa
e. Shutdown of rotor axial displacement  0,7 mm
f. Shutdown at bearing lubrication return oil temperatur > 70 °C
g. Shutdown at bearing temperatur > 100 °C
h. Shutdown at bearing vibration > 70m
i. Shutdown at 505 governor control trip
j. Shutdown from boiler trip
k. Manual shutdown from control room
l. Main interlock swicth
22. Confirm that turbine trip lamp is off.
23. Confirm that main alarm is off
24. Confirm that AC and DC lube oil pump swicth position is auto.
25. Start turbine to 600 rpm from woodward 505 panel by push (increasing
speed rate 100 rpm/minuts) :
11 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

- Reset
- Run
- Speed
- Select
- Input speed 600
- Enter

26. Turning gear motor auto stop/manual stop after rotor speed > 200 rpm.
27. Monitor the temperatur of and lower casing :
 increasing rate less than 3-4C/minute.
 Temperatur difference between upper and lower of casing wall at
control stage shall be less than 50C.
28. Close all drain valve of main steam pipe.
29. Close drain valve of turbine inlet steam pipe.
30. Keep for 5=10 minuts and monitor the speed, temperatur, vibration and
displacement.
31. Obsevation if any mall function stop the start up and investigation,
normal condition go to next step.
32. Incrase the speed to 900 rpm from woodward 505 by push (increasing
speed rate 100 rpm/minuts) :
 Speed
 Select
 Input speed 900
 Enter
33. Keep for 10 minuts and monitor the speed, temperatur, vibration and
displacement.
34. Adjust the steam sealing by increase opening steam valve
35. Keep condensor vacum  -0,04 MPa, by adjusting opening steam to
ejector (maximal 1,2 Mpa).
36. Check opening valves of extraction #1, extraction #2, extraction #3
and turbine drain valve, if valves opening is so large than reduce
opening valves.
37. Obsevation if any mall function stop start up and investigation, normal
condition go to next step.
38. Incrase the speed to 1200 rpm from woodward 505 by push
(increasing speed rate 100 rpm/minuts) :
 Speed
 Select
 Input speed 1200
 Enter
39. Keep for 45-60 minuts and monitor the speed, temperatur, vibration
and displacement.
40. Adjust the steam sealing by increase opening steam valve

12 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

41. Keep condensor vacum  -0,04 MPa, by adjusting opening steam to


ejector (maximal 1,2 Mpa).
42. Check opening valves of extraction #1, extraction #2, extraction #3
and turbine drain valve, if valves opening is so large than reduce
opening valves.
43. Obsevation if any mall function stop start up and investigation, normal
condition go to next step.
44. Incrase the speed to 2600 rpm from woodward 505 by push
(increasing speed rate 100 rpm/minuts) :
 Speed
 Select
 Input speed 2600
 Enter
45. Keep for 5 minuts and monitor the speed, temperatur, vibration and
displacement.
46. Adjust the steam sealing by increase opening steam valve
47. Keep the condensor vacuum is- 0,04 MPa, by adjusting openeng steam
to ejector. (maximal inlet pressure 1,2 Mpa).
48. Obsevation if any mall function stop start up and investigation, normal
condition go to next step.
49. Incrase the speed to 3000 rpm from woodward 505 by push (increasing
speed rate 100 rpm/minuts) :
 Speed
 Select
 Input speed 3000
 Enter
50. Start two stage steam ejector, by open steam valve and condenser inlet
valve. Adjust condenser vacuum is -0,08 Mpa and maximum steam inlet
pressure is 1,2 Mpa.
51. High pressure oil pump auto stop/manual stop
52. Keep for 5 minuts and monitor the speed, temperatur, vibration and
displacement.
53. Adjust the steam sealing by increase opening steam valve, and steam
sealing temperatur for rear turbine controlled by condensate spray.
54. Obsevation if any mall function stop start up and investigation, normal
condition go to next step.
55. Steam turbine ready to syncronize.
56. The 0,6 MW electric load should be loaded immediately after
connections with power grid, increasing load speed 0,3 MW/minuts :
- To 2 MW and kee for 10 minuts
- To 4 MW and keep for 8 minuts
57. After water quality from condenser is suitable with boiler water
standard requirement than condenser drain valve is closed.

13 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

58. LP Heater - Open condensate valve to condenser, open steam valve to


condensor and close drain valve.
59. HP Hater - Open condensate valve to deaerator, open steam valve to
condensor and close drain valve.
60. Close drain valve from extraction #1, exraction #2, extraction #3 and
drain valve from turbine is closed after turbine normal operation.

Cold start up
3500
3000
2500
Speed (RPM)

2000 1.1. Critical speed


1750 rpm
1500 1.2. and 2500 rpm
1000
500
0
5 15 25 35 45 55 65 75 85 95 5 5 5 5 5
10 11 12 13 14

Time (minut)

B. Hot start up steam turbine

1. Ensure condenser ready to operation, inlet and outlet of water cooling are
open.
2. Oil cooler is ready to operation, air release valve close position, intlet and
outlet for water and oil are open position
3. Air cooler is ready to operation, air release valve close position, intlet and
outlet for water are open position.
4. Start cooling tower system, basin water level is + 10 cm from NWL, start
cooling tower fan and cooling water pump.
5. Oil filter shall be clean and ready to operation, open inlet and outlet valve
.
6. Start high pressure oil pump and ensure discharge pressure ± 0,834 Mpa.
7. Start oil tank exhaust fan.
8. Start turning gear,
9. Open valve step by step for steam extraction #1, steam extraction #2,
steam extraction #3 and turbine drain valve.
10. LP heater drain valve open and condensate recirculation valve to
condenser is close.
14 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

11. HP heater drain valve open and condensate recirculation valve to


deaerator is close.
12. Expansion tank, open drain valve step by step from inlet steam pipe,
extraction #1, drain from turbine, extraction #2, extraction #3.
13. Start gland heater fan.
14. Start condensate pump and recirculation the water from condenser to LP
heater by adjusting control valve. Analisysed the water, if the water
quality is out of specification than some water drained and keep
condenser level is NWL by make up from demin water.
15. Open manual steam valve to surge tank step by step and start surge
tank fan. Keep surge tank pressure 0,1010 – 0,1275 Mpa.
16. Adjusted steam temperatur sealing to rear of turbine by open
condensate spreay valve.
17. Open condenser vacuum valve and start steam air ejector start up by
open the steam valve for starting steam ejector. Main steam pressure ±
1,2 Mpa and condenser vacuum ≤ -0,04 Mpa.
18. Open MSV for turbine and governor valve shlud be close position.
19. Open by pass valve of isolation motor valve step by step and start
heating of MSV and inlet steam pipe. Heating is finished after temperatur
>400 C.
20. Local site – reset trip buthon valve
21. TSI panel on normal operation the interlock swicth shall ‘on’ position for
below items :
a. Shutdown at generator breaker protection action or trip position
b. Shutdown at turbine over speed  3300 rpm and  3330 rpm
c. Shutdown at lubricating oil pressure  0,04 Mpa
d. Shutdown at vacuum prssur  -0,04 Mpa
e. Shutdown of rotor axial displacement  0,7 mm
f. Shutdown at bearing lubrication return oil temperatur > 70 °C
g. Shutdown at bearing temperatur > 100 °C
h. Shutdown at bearing vibration > 70 m
i. Shutdown at 505 governor control trip
j. Shutdown from boiler trip
k. Manual shutdown from control room
l. Main interlock swicth
22. Confirm that turbine trip lamp is off.
23. Confirm that main alarm is off
24. Confirm that AC and DC lube oil pump swicth position is auto.
25. Start turbine to 600 rpm from woodward 505 panel by push (increasing
speed rate 100 rpm/minuts) :
a. Reset
b. Run
c. Speed
d. Select
15 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

e. Input speed 600


f. Enter
26. Turning gear motor auto stop/manual stop after rorot speed > 10 rpm.
27. Monitor the temperatur of and lower casing :
28. increasing rate less than 3-4C/minute.
29. Temperatur difference between upper and lower of casing wall at control
stage shall be less than 50C.
30. Close all drain valve of main steam pipe.
31. Close drain valve of turbine inlet steam pipe.
32. Keep for 5-10 minuts and monitor the speed, temperatur, vibration and
displacement.
33. Obsevation if any mall function stop the start up and investigation,
normal condition go to next step.
34. Incrase the speed to 1200 rpm from woodward 505 by push (increasing
speed rate 100 rpm/minuts) :
a. Speed
b. Select
c. Input speed 1200
d. Enter
35. Keep for 10-20 minuts and monitor the speed, temperatur, vibration and
displacement.
36. Adjust the steam sealing by increase opening steam valve
37. Keep condensor vacum  -0,04 MPa, by adjusting opening steam to
ejector (maximal 1,2 Mpa).
38. Check opening valves of extraction #1, extraction #2, extraction #3 and
turbine drain valve, if valves opening is so large than reduce opening
valves.
39. Obsevation if any mall function stop start up and investigation, normal
condition go to next step.
40. Incrase the speed to 2600 rpm from woodward 505 by push (increasing
speed rate 100 rpm/minuts) :
a. Speed
b. Select
c. Input speed 2600
d. Enter
41. Keep for 5-10 minuts and monitor the speed, temperatur, vibration and
displacement.
42. Adjust the steam sealing by increase opening steam valve
43. Keep the condensor vacuum is- 0,04 MPa, by adjusting openeng steam
to ejector. (maximal inlet pressure 1,2 Mpa).
44. Obsevation if any mall function stop start up and investigation, normal
condition go to next step.
45. Incrase the speed to 3000 rpm from woodward 505 by push (increasing
speed rate 100 rpm/minuts) :
16 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

a. Speed
b. Select
c. Input speed 3000
d. Enter
46. Start two stage steam ejector, by open steam valve and condenser inlet
valve. Adjust condenser vacuum is -0,08 Mpa and maximum steam inlet
pressure is 1,2 Mpa.
47. High pressure oil pump auto stop/manual stop
48. Keep for 5 minuts and monitor the speed, temperatur, vibration and
displacement.
49. Adjust the steam sealing by increase opening steam valve, and steam
sealing temperatur for rear turbine controlled by condensate spray.
50. Obsevation if any mall function stop start up and investigation, normal
condition go to next step.
51. Steam turbine ready to syncronize.
52. The 0,6 MW electric load should be loaded immediately after connections
with power grid, increasing load speed 0,3 MW/minuts :
53. To 2 MW and kee for 10 minuts
54. To 4 MW and keep for 8 minuts
55. After water quality from condenser is suitable with requirement standard
boiler water than condenser drain valve is closed.
56. LP Heater - Open condensate valve to condenser, open steam valve to
condensor and close drain valve.
57. HP Hater - Open condensate valve to deaerator, open steam valve to
condensor and close drain valve.
58. Close drain valve from extraction #1, exraction #2, extraction #3 and
drain valve from turbine is closed after turbine normal operation

Hot start up
4000
3000
Speed (RPM)

2000 1.3. Critical speed


1000 1750 rpm
1.4. and 2500 rpm
0
5 15 25 35 45 55 65 75 85 95 10
5
11
5
13
0
14
0
15
0

Time (minut)

C. Control Opration
Parameter should be controled :
17 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

1. Steam inlet turbine :


a. Temperatur : 455 – 485 °C
b. Pressure : 4,6 – 5,1 Mpa

- If steam pressure 5,1 MPa or temperatur 485 °C, inform to boiler


operator to reduce the steam tmperator or pressure.
- If steam pressure 4,6 MPa or tmperatur 455 °C, inform to turbine
operator to reduce load generator, and boiler operator should be
improve boiler operation to increase the steam pressure and
temperatur.

2. The frequency of grid : 50 ±0,5 Hz


- If connect with grid/ PLN distribution line, follow PLN grid and shall
be maintained for 50±0,5 Hz.
- If island mode, frequency controlled by speed governor generator.

3. Main oil pump outlet pressure is 0,9 Mpa


Main oil pump inlet pressure is 0,07 Mpa
Control/Pulse oil pressure is 0,353 Mpa
Lubicration oil pressure is 0,08 – 0,12 Mpa

4. Oil inlet flow temperatur of bearing is 35 – 45 °C


Maximum return oil bearing temperatur is 65 °C
Maximum temperatur of bearing pad is 85 °C

5. Lubricating Oil filter pressure drop is in range 0,0196–0,0392 Mpa


Control Oil filter pressure drop maximal 0,25 Mpa

6. Gland seal steam :


Pressure in surge tank is 101 - 127,5 kPa

7. Exhaust tempratur of rear cylinder :


When on load < 65 °C
When no load < 100 °C

8. Condenser vacuum :
a. Unit load is more than 40% of the rated load, vacuum should be
less than -0,065 Mpa
b. Unit load is 20-40% of the rated load, vacuum should be less than
-0,06 Mpa.
c. Unit load is less than 20% of rated load, vacuum should be less
than -0,04 Mpa

Two kinds of control operation :


18 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

A. Boiler follow
Generating of power is depend on boiler steam out put, if steam pressure
and temperatur change so the steam flow will be change also than
the pressure and temperatur table.
Steam flow change will given effect to generator out put.

B. Turbine follow
Generating of power is depend on turbine setting input by operator, boiler
shall be supplied the steam that turbine required for generating the
power.

D.Abnormal operation condition

One or several items of parameter have alarm, but don’t reach to the stopping and
the unit does not want to stop, the unit is running in abnormal condition. Try
to find the cause of abnormal parameter. Stop the unit if the abnormal
parameter going to reach of the limit and can’t slove.

Item Inspection
1. Axial displacement 1. Check axial bearing pad temperatur and
return oil temperatur to ensure is no wearing
with the bearing pad
2. Check the inlet steam parameters and
vacuum to avoid sharp change
2.Differential 1. Check the expantion direction
Expansion 2. Maintain the load to minimum the change of
inlet steam temperatur and the exhaust
temperatur.
3. Reduce or increase the load gradually,
according the diffrential expantion recording
and shall be normal range.

Big vibration 1. Monitor vibration of each bearing and


analysis the vibration range.
2. Check the following and ensure them in
normal condition
a.The bearing of oil in /out flow form glass
view.
b.The each bearing oil prssure.
c. The temperatur difference between inlet
steam and casing metal.
d.The temperatur and pressure of steam

19 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

exhaust.
e.The casing expantion and difference
expantion.
f. Measure the vibration spectrum.
3. Don’t let the unit near the critical speed if
the vibration is violent during start up. Stop
rising load if the vibration is violent during
rising load, and operate the unit with the
former load. The unit can’t raise load until
the violent vibration has been eliminated.
Stop the unit to check if the vibration is
violent during eccelerating, operating the
unit with reducing speed is forbidden in this
condition.
Lube oil pressure low 1. Check the level in main oil tank
2. Check whether the main oil pump or oil
injectors are working well
Higher temperatur of 1. Check inlet oil pressure of turbine bearing
radial bearing 2. Check lube oil quality/cleanness to ensure
pad and return there is no impurities in lube oil.
oil 3. Check turbine inlet lube oil temperatur, shall
be normal range.
4. Check any steam leaking from gland seal
system that mean so much steam or so high
steam temperatur.
5. Check bearing pads temperatur, shall be
normal range.
Higher temperatur of 1. Check the axial displacement, shall be
axial bearing normal range.
pads and 2. Check the lube oil quality/cleanness to
return lube ensure that is no impurities in oil.
3. Check turbine inlet lube oil temperatur, shall
be normal range.
4. Check bearing pads temperatur, shall be
normal range.
Higher/lower level in 1. Check any leakage at oil tank and lube oil
mail oil tank pipe line when the oil level is lower.
2. Check any water leakage in oil coolers.
Lowering vacuum of 1. Check the exhaust temperatur, should be in
exhaust normal range.
2. Check the vacuum braker and accident blow
valve are working well.
3. Check inlet steam pressure to gland sealing

20 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

should be in normal range.


4. Check water spray system at inlet
condenser.

E. Normal Shut down of steam turbine

1. Inform to Boiler operator and electrical that steam turbine will be stoped.
2. Reduce generator load to minimal load (± 2 MW), reducing rate 0,3 – 0,5
MW/minuts.
3. Monitor some parameters, vibration, displacement
4. Maintance the water balance, so daerator not over flow
5. Keep condenser vacuum is  -0,06 Mpa by adjusting steam ejector.
6. Maintaince Steam temperatur gland sealing is high enough to avoid
negative expansion difference.
7. Open syncrone the generator
8. Shut down turbine by push ‘stop button’ at woodward 505.
9. Ensure AC electric oil pump runing, auto if the lube oil pressure is 0,04
Mpa. ( if auto not runing, put swich on manual and start)
10. All valve extraction will automaticaly closed
11. Close steam valve to surge tank
12. Close steam to ejector system
13. Close main steam isolation valve
14. Close main steam header valve
15. Open all drain valve of main steam inlet pipe of turbine
16. Open all drain valve of main steam line.
17. Stop condensate pump
18. Cooling tower fan stop
19. Make sure that turning gear is runing after turbine rotor rotation
completely stop. Turning gear will operation for 8-10 hours until the rotor
is cold.
20. Open drain valve of surge tank
21. Open drain valves of extraction #1, extraction #2, extraction #3 and
turbine drain valve.
22. LP Heater – open darin valve, close steam valve to condenser and close
condensate valve to condensor
23. HP Heater – open darin valve, close steam valve to condenser and close
condensate valve to deaerator
24. After turning gear stoped than electric oil pump shall stoped.
25. Oil tank fan still runing and stop after 24 hours
26. Stop cooling tower pump

F. Emergancy shut down of steam turbine


21 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

A. Totally shut down steam turbine


Totally shut down should be taken action couse :
1. There are clear friction noise out of the inner of the unit
2. There is water hammring with the turbine
3. There is a serious friction of gland sealing ring or oil sealing ring
4. The level of oil tank lower than limitd volume, and feeding oil fails.
5. There is fire in oil system, and can’t be extinguished quickly.
6. The cooling water stop , and can’t be re supplied quickly.
7. The emergency trip governor doesn’t act when the speed is more than
3330 rpm
8. The vacuum condenser pressure reaches -0,04 Mpa, and it can’t be
lowered.
9. A babbit temperatur of radial bearing pad is more than 100 °C, or a babbit
temperatur of axial bearing pad is more than 100 °C
10. Vibration turbine and generator bearing more than 0,07 mm
11. The lube oil pressure lower than 0,03 mm, and the auxiliary oil pump
doe’st work
12. The protection device of axial displacement doesn’t act when the axial
displacement is more than 0,7 mm.

B. Generator open syncrone and steam turbine idle.


Generator open syncrone and steam turbine idle should be taken action
couse :
1. The steam temperatur is more than 485 °C or steam pressure is higher
than 5,4 Mpa and they will not drop down quickly.
2. The idle running time is more than 15 mnt after load rejection
3. Any problem with AVR panel

11. Performance Curve

The relationship between the feeding steam quantity of the steam turbine and
the electricity generation power shall be offered as the attached drawings,
it drew when the generator efficiency is 96.5% at rated steam inlet
pressure, rated steam temperature and rated backpressure of turbine.
And various correction curves with the change of inlet steam pressure,
inlet steam temperature and extraction pressure shall be offered the also.

In the practical application, not only revise the steam feeding quantity and power
according to the variation of the steam feeding pressure, temperature,
back pressure of the different operating mode of variation, but also revise
the power to the efficiency variation of different load in relationship
between the power and the efficiency of the generator. The relationship
22 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

between the inlet flow and pressure after Curtis stage offered is only for
reference in operation.

23 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

24 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

12. Pre-condition Checking check list

Status
No Parameter
Not OK
Communication facilities should be ready, boiler operator,
1 turbine operator, electrical section and instrument
section should be easy to commonication
Prepare tools and meters from instrument, electric,
2
mechanical that ready to application
All equipments shall be inspected in detail and it is ensured
that the installation is completed. The turbine
3
generator set’s accessory equipments and the floor
around are clean.
All instrumentation sensors/meters had been installed,
callibrated and tested, shuch as temperatur sensor,
4
pressure sensor, vibration sensor, speed sensor
and displacement
Oil system
a. Oil tank level > 100 mm
b. Exhaust oil fan shall be normal
c. condition/ready to operation
d. Lubricating oil filter is clean
e. Control oil filter is clean
5 f. HP oil pump and valves is ready to
operation
g. AC electric pump and valves ready to
operation
h. DC oil pump and valves ready to
operation
i. Oil shall be equivalent to ISO-VG-46 a
and cleanness is maximal NAS 9
Cooling system
a. Cooling tower basin level is +10 cm
from NWL
6 b. Circulating water pumps and valves are
ready to operation
c. Cooling tower fans are ready to
operation

25 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

Cooler systeam
A. Oil cooler system
a.Oil cooler and valves are ready to operation
1.4.
b.No oil leaking
7
B.Air cooler system
a.Oil cooler and valves are ready to operation

b.No oil leaking


Condenser system
a.Hot well box water level is > 400 mm
b.Inlet and outlet valve water cooling is
8
ready to operation
c.Condensate pump and valves ready to
operation
1.8. HP and LP heater
a.Confirm that HP and LP heater ready to
9
operation
b.All valves are ready to operation
Gland heater
a.Gland heater and valves ready to operation
10
b.Gand heater fan ready to operation
Steam jet air injector
a. Steam jet air injector ready to operation
b. Drain valve close position
11
c. Inlet and outlet water valve close position

d. Inlet valve from condenser close position

e. Inlet steam valve close position


Surge tank
a. Surge tank ready to operation
1.12.
12
b. Inlet and outlet valve close position
c. Surge tank fan ready to operation

Expantion tank
1.15. 13 a. Expantion tank ready to operation
b. All inlet valve close position
Steam pipe line turbine section
1.16. 14
a. Isolation motor valve try to operation
26 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

with close and open


b. Isolation valve close position
c. By pass valve close position
Control section
a. Panel control ( TSI and ETS) are ready to
1.19. 15 operation
b. Woodward system is ready to operation
Generator section
a. Over all generator is ready operation
1.21. 16
b. Synchronize System panel and DCS is
ready to operation
Turbine steam section
a. MSV ready to opration, with open and
close
b. MSV close position
1.23. c. Extraction valve #1, extraction valve #2
17 and extraction valve #3 are ready to
operation, with close and open
d. Extraction valve #1, extraction valve #2
and extraction valve #3 are close
position
Turning gear
a. Turning gear motor is ready to opration
1.27. 18
b. Manual turning gear is ready to operation

Tested by Withnessed by Approved by

Name : Name : Name :


Date : Date : Date :

27 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

13. Alarm Protection System - information

POINT SETTING
NO
DESCRIPTIONS TAG NO. ALARM
.
H L

         
A Main Steam      
1 Alarm of inlet main steam low pressure 21PI22_L   <= 46 bar
2 Alarm of inlet main steam high pressure 21PI22_H >= 51 bar  
3 Alarm of inlet main steam low temperature 21TI20_L   <= 455 ⁰C
4 Alarm of inlet main steam high temperature 21TI20_H >= 480 ⁰C  
5 Main stop valve close position 28ZS201    
<= -
6
Alarm of Turbine Exhaust low pressure 28PS204A   0.07MPa
7 Shut down of Turbine Exhaust lower pressure 28PS204B    
8 Alarm - 1 of Turbine Exhaust high temperaure 23TI02_H1 >= 100 ⁰C  
9 Alarm - 2 of Turbine Exhaust high temperaure 23TI02_H2 >= 65 ⁰C  
10 Alarm of turbine casing high differential temperature ∆23TI01_H ∆ 50 ⁰C  
         
B Hot Well Condensor Water      
<=
1
Alarm low - 1 of hotwell water level low alarm 22LI01_L   +200mm
2 Alarm low - 2 of hot well water level lower alarm 22LI01_LL    
3 Alarm high - 1 of hotwell water level high alarm 22LI01_H >=+550 mm  
4 Alarm high - 2 of hot well water level higher alarm 22LI01_HH    
5 hot well water level 22LI01 <= 400 mm  
<= 0.2
6
Alarm of outlet condensor pump low pressure 22PI03_L   MPa
         
C Extraction Valve      

1 Deaerator Extraction valve closed position 28ZS202    


2 HP Extraction valve closed position 28ZS203    
         
D Surge Tank      

28 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

<= 101
1
Alarm of Surge tank low pressure 23PI10_L   kPa
>= 127.5
2
Alarm of Surge tank high pressure 23PI10_H kPa  
3 Alarm of Surge tank low temperature 23TI10_L   <= 190 ⁰C

4 Alarm of Surge tank high temperature 23TI10_H >= 200 ⁰C  


         
E HP & LP Heater      
<= 0.19
1
Alarm of LP heater tank high pressure 25PI01_H MPa  
>= 0.60
2
Alarm of HP heater tank high pressure 26PI01_H MPa  
3 Alarm of LP heater tank high Level 25LI01_H >= 400 mm  
4 Alarm of HP heater tank high Level 26LI01_H >= 400 mm  
5 HP heater tank Level 26LI01 <= 200 mm  
         
F Lubrication Oil      
<= -160
1
Alarm of oil tank low level 26LI02_L   mm
>= +160
2
Alarm of oil tank high level 26LI02_H mm  
3 Alarm of outlet oil from cooler low temperature 24TI03A/B_L   <= 35 ⁰C

4 Alarm of outlet oil from cooler high temperature 24TI03A/B_H >= 45 ⁰C  


<=0.785M
5
Alarm - 1 of Lubricating oil low pressure 28PS201A   Pa
6 Lubricating oil pressure 31PI02 >=0.834MPa  
<=0.055M
7
Alarm - 2 of Lubricating oil lower pressure 28PS201B   Pa
8 Alarm - 3 of Lubricating oil lower pressure 31PI02_L    
9 Shut down - 1 of Lubricating oil lower pressure 28PS201C    
10 Shut down - 2 of Lubricating oil lower pressure
28PS201D    
     
   
G Control Oil - DEH      
13 Alarm of CPC oil filter blocked 24PDS01 >= 0.25 Mpa  
<=0.70MP
14
Alarm of CPC inlet oil low pressure 24PI08_L   a
     
   
H Bearing Oil Temperature      

11 Alarm of front bearing Lub. oil high temp._Turbine 29TI10_H >= 65°C  
29 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

12 Alarm of back bearing Lub. oil high temp._Turbine 29TI11_H >= 65°C  
13 Alarm of front bearing Lub. oil high temp._Generator 29TI12_H >= 65°C  
14 Alarm of back bearing Lub. oil high temp._Generator 29TI13_H >= 65°C  
15 Shutdown of front bearing Lub. oil high temp._Turbine 29TI10_HH    
16 Shutdown of back bearing Lub. oil high temp._Turbine 29TI11_HH    
Shutdown of front bearing Lub. oil high
17
temp._Generator 29TI12_HH    
Shutdown of back bearing Lub. oil high
18
temp._Generator 29TI13_HH    
         
I Bearing Bush Temperature      
1 Alarm of front bearing high temperature _ turbine 29TI03_H >= 85°C  
2 Alarm of back bearing high temperature _ turbine 29TI04A/B_H >= 85°C  
3 Alarm of front bearing high temperature _ generator 29TI05A/B_H >= 85°C  
4 Alarm of back bearing high temperature _ generator 29TI06_H >= 85°C  
5 Shutdown of front bearing high temperature _ turbine 29TI03_HH    

6 Shutdown of back bearing high temperature _ turbine 29TI04A/B_HH    


Shutdown of front bearing high temperature _
7 29TI05A/B_HH    
generator
Shutdown of back bearing high temperature _
8 29TI06_HH    
generator
         

J Bearing Thrust Pad Temperature      

1 Alarm of thrust pad high temperature _ turbine 29TI14A ~ J_H >= 85°C  
2 Shutdown of thrust pad high temperature _ turbine 29TI14A ~ J_HH    

         
K TSI      
>= 3240
1 Alarm of turbine over speed 27SI251H
(8%) rpm  

2 Shut down at turbine overspeed 27SI251HH


   
3 Alarm of rotor axial displacement 27ZI252H >= 0.4mm  
4 Shut down of rotor axial displacement 27ZI252HH    
5 Alarm of bearing vibration 27XI253H >= 50 um  
6 Shut down of bearing vibration 27XI253HH    
         

30 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

L 505 DEH      
1 Alarm at 505E governor control 505 ALARM    
2 Shut down at 505E governor control 505 TRIP    
505_SHUTDOW
3
Manual Emergency Push Button 505 N    
         
M Generator & Cooling      
Alarm of inlet air cooler for generator high
1
temperature 24TI05 >= 40°C  
2 Alarm of Generator winding high temperature 29TI01A ~ F_H >= 80°C  
3 Alarm of Generator core high temperature 29TI02A ~ F_H >= 80°C  
4 Generator breaker protection action or trip position 28ZS203-DCS-C    
         
N Cooling Water      
1 Alarm of Inlet cooling water high temperature 03TI04_H >= 33°C  
<= 0.17
2
Alarm of Inlet cooling water low pressure 03PI07_L   MPa
         
O ETS For Turbine Shutdown      
1 ETS Active for Turbine ETS_ACTIVED    
2 Manual Emergency Push Button - Turbine PB_ETS    
         
P Interlock From Boiler      
1 Boiler Trip / MFT MFT_ACTIVED    
2 Manual Emergency Push Button - Boiler PB_MFT    

14. Interlock shut down


31 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

COMMISIONING PROCEDURE FOR


TURBINE SUPERVISORY AND EMERGENCY TRIP SYSTEM
(TSI & ETS)
INTERLOCK
SWITCH POINT SETTING RESULT
ON/OFF
NO. DESCRIPTIONS TAG NO. TIMER
ON/OFF TRIP
NOT
OK
OK
  HH LL

                 

A Turbine Exhaust Pressure              


Shut down of Turbine Exhaust lower >=
1 3.0 s
pressure 28PS204B     -0.04MPa    
                 
B Oil Lubrication Pressure              
Shut down of Lubricating oil lower
1 2.0 s
pressure 28PS201C     <=0.03MPa    
           
     
C Bearing Oil Temperature              
Shutdown of front bearing Lub. oil >=
1   5.0 s
high temp._Turbine 29TI10_HH 70°C      
Shutdown of back bearing Lub. oil >=
2   5.0 s
high temp._Turbine 29TI11_HH 70°C      
Shutdown of front bearing Lub. oil >=
3   5.0 s
high temp._Generator 29TI12_HH 70°C      
Shutdown of back bearing Lub. oil >=
4   5.0 s
high temp._Generator 29TI13_HH 70°C      
                 
D Bearing Bush Temperature              
Shutdown of front bearing high >=
1 29TI03_HH     5.0 s    
temperature _ turbine 100°C
Shutdown of back bearing high >=
2 29TI04A/B_HH     5.0 s    
temperature _ turbine 100°C
Shutdown of front bearing high >=
3 29TI05A/B_HH     5.0 s    
temperature _ generator 100°C
Shutdown of back bearing high >=
4 29TI06_HH     5.0 s    
temperature _ generator 100°C
                 

E Bearing Thrust Pad Temperature              


Shutdown of thrust pad high >=
1 29TI14A ~ J_HH     5’.0 s    
temperature _ turbine 100°C
                 

32 of 32
REV

STEAM TURBINE START UP 0

AND SHUT DOWN PROCEDURE

K
TSI              
>=
Shut down at turbine overspeed 3330
27SI251HH    
(mechanical) (111%
1 ) rpm      
3300
Shut down at turbine overspeed
(110%
(electrical)
)
Shut down of rotor axial >= 0.7
2 1.0 s
displacement 27ZI252HH   mm      
>= 70
3 1.0 s
Shut down of bearing vibration 27XI253HH   um      
                 
L 505 DEH              
2 Shut down at 505 DEH 505 TRIP     OPENED      
Manual Emergency Push Button 505 505_SHUTDOW
3
DEH N     OPENED      
                 
O Manual Turbine Shutdown              
Manual Emergency Push Button -
1
Turbine PB_ETS     OPENED      
                 
                 

Tested by Withnessed by Approved by

Name : Name : Name :


Date : Date : Date :

33 of 32
JOB NO. : 97-8207

.
DOC. NO. :

CHD
DATE
APPD
BY

You might also like