VFD Panel Maintenance Instructions During Lockdown Period: DATE:30.03.2020
VFD Panel Maintenance Instructions During Lockdown Period: DATE:30.03.2020
Due to an unfortunate epidemic, COVID 19, the entire global industry is facing great financial loss as most of the countries
declared a lock-down period to stop the virus from spreading, India is no different. During this lock-down period most of
the manufacturing plants and service industry remain shut down but some have to work to fulfill daily needs of the human
being.
ENVIORNMENTAL CONDITION:
Maximum Ambient
+60⁰C +60⁰C +60⁰C +60⁰C +70⁰C +60⁰C
Temperature
Please make sure during the shut-down period, VFD should not come in direct contact with dust, Moisture, Gas, Chemical
or salt. Panel doors should be properly closed and fan and filter opening should be covered properly.
To avoid any type of unexpected failure of the VFD/ AC Drive, please follow the procedure given underneath:
2. Use industrial blower and pass pressurized air from upside or side opening in the VFD body
3. Check the control and power wire condition physically also check the continuity of the Power terminal
from input supply , Switch gear ,VFD and Motor terminal before Power ON
4. Check the earthing of each and every component physically and do the meggering as it is more
vulnerable to moisture
5. Switch-on the VFD incoming supply and leave it for at least 2 hours. Don’t give any run command to
VFD during this capacitor charging period. In the absence of a three-phase supply, single-phase supply
would also suffice.
6. Check the motor winding conditions and moisture before giving the start command
7. Check mechanical brakes or interlocks properly before giving the start command
8. Check the VFD output voltage and current before and after giving the start command
In case of any assistance required, please feel free to contact Yaskawa or our ABP anytime.