BAS Point Schedule
BAS Point Schedule
QTY
DI DO
AIR CONDITIONING AND VENTILATION SYSTEM
Interface with Chillers System ( BAC Net/ MOD Bus)
Chillers 3
Water Leaving Temp 3
Water Return/Entering Temp 3
Condenser Water Leaving Temp 3
Condenser Water Return/Entering Temp 3
%RLA 3
Evaporator Refrigerant Pressure 3
Condenser Refrigerant Pressure 3
Compressor Discharge Temperature 3
Evaporator Temp 3
Condensers Temp 3
Oil Tank Temp 3
Oil Differentials Pressure 3
Chilled Water Setpnt 3
Demand Limit Setpnt 3
Manual Reset Alarm 3
Auto Reset Alarm 3
Communication Status 3
Voltage 3
Current 3
kWh 3
Power Factor 3
Other standard parameters 3
Chilers 3
Manual/Auto Status 3
Chiller On/Off Control 3
Chiller On/Off Status 3
Emergency Stop Status 3
Trip Alarm 3
Power Supply Failure 3
CHW Leaving Flow Status 3
CW Leaving Flow Status 3
Chilled Water Leaving and Entering Temperature
Chilled Water Flow Rate 3
Condenser Water Entering/ Leaving Temperature
Cooling Towers 3
Manual/Auto Status (Fan) 3
CT On/Off Control (Fan) 3
CT On/Off Status (Fan) 3
Trip Alarm 3
Power Supply Failure (VSD) 3
VSD Fault
VSD Speed Control
VSD Speed Feed back
On/Off Control 5
Open/Close Status 5
Filter Status 10
Expansion Tank 2
High Level
Low Level
High Level
Low Level
FCUs 130
Fan Coil Unit Status 130
Space Temperature
AHU 33
Auto/Manual Status 33
On / Off Control 33
Fan On / Off Status 33
VSD Speed Control
VSD Speed Feed back
VSD Fault Alarm
Trip Alarm
Return Duct Temperature Sensor
Duct Static Pressure
Supply Air Temperature from the AHU
Valve Control - Modulating
Valve Position
Filter Status 33
Return Air CO2
Supply Air RH
Return Air RH
Duct Smoke Detector 33
Auto/Manual Status 1
On / Off Control 1
Fan On / Off Status 1
Trip Alarm 1
Supply Air RH 1
Return Air Temperature 1
Auto/Manual Status 2
On / Off Control 2
Fan On / Off Status 2
VSD Speed Control
VSD Speed Feed back
VSD Fault Alarm
Trip Alarm
Duct Static Pressure (Supply)
Supply Air Temperature from the AHU
Valve Control - Modulating
Valve Position
Filter Status 2
Power Failure 2
Out door RH ( % )
Out Air CO2 Level
Trip Alarm
Power Failure 4
PLUMBING SYSTEMS
Water Pumps
2
Auto /Manual Status 2
On/Off Control 2
On/Off Flow Status 2
Power Failure Alarm 2
Trip Alarm 2
Low Level, High Level, Very High Level, Very Low Level 4
Rain Water Collection Tank 1
Low Level, High Level, Very High Level, Very Low Level 4
On/Off Control 2
Open/Close Status 2
Rain Water Detection 2
FIRE DETECTION AND PROTECTION SYSTE
M
ELECTRICAL SYSTEM
HV substation 1
Generator 3
Manual Reset Alarm 3
Auto Reset Alarm 3
Communication Status 3
Voltage 3
Current 3
kWh 3
Power Factor 3
Other standard parameters 3
Manual/Auto Status 3
On/Off Control 3
On/Off Status 3
Emergency Stop Status 3
Trip Alarm 3
Auto/Manual Status 75
On / Off Control 75
On / Off Status 75
Gondolars 1
Gondolar Status on/off 1
Control panel 1
Main Switch 1
Control panel 1
BMS Contractor
BMS Contractor
BMS Contractor
BMS Contractor