ALSTOM Library PDF
ALSTOM Library PDF
1 Introduction ..... p2
2 Fundamentals of Protection Practice ......... p4
3 Fundamental Theory ........pi 6
4 Fault Calculations ........ p30
5 Equivalent Circuits and Parameters
of Power System Plant p46
6 Current and Voltage Transformers......... p78
7 Relay Technology ........ p98
8 Protection: Signalling and Intertripping .... p112
9 Overcurrent Protection for Phase
and Earth Faults ...... p122
10 Unit Protection of Feeders ...... p152
11 Distance Protection ...... p170
12 Distance Protection Schemes ...... p192
13 Protection of Complex Transmission Circuits ....... p202
14 Auto-Reciosing ...... p218
15 Busbar Protection ... p232
16 Transformer and Transformer-Feeder Protection ...... p254
17 Generator and
Generator-Transformer Protection ......p28O
18 Industrial and Commercial
Power System Protection p316
19 A.C, Motor Protection p336
20 Protection of A.C. Electrified Railways p352
21 Relay Testing and Commissioning p370
22 Power System Measurements p398
23 Power Quality p410
24 Substation Control and Automation p422
25 Distribution System Automation p442
Appendix 1 Terminology p454
Appendix 2 ANSI/IEC Relay Symbols p466
Appendix 3 Application Tables p468
Index .. p476
1• Introduction
This is the measure of the importance of protection The different types have somewhat different capabilities,
systems as applied in power system practice and of the due to the limitations of the technology used. They are
responsibility vested in the Protection Engineer. described in more detail in Chapter 7.
In many cases, it is not feasible to protect against all
hazards with a relay that responds to a single power
system quantity. An arrangement using several
quantities may be required. In this case, either several
relays, each responding to a single quantity, or, more
commonly, a single relay containing several elements,
each responding independently to a different quantity
may be used.
The terminology used in describing protection systems
and relays is given in Appendix 1. Different symbols for
describing relay functions in diagrams of protection
schemes are used, the two most common methods (IEC
and IEEE/ANSI) are provided in Appendix 2.
2 .3 ZONES OF PROTECTION
To limit the extent of the power system that is
disconnected when a fault occurs, protection is arranged
Figure 2.6: CTLocations
in zones. The principle is shown in Figure 2.5. Ideally, the
zones of protection should overlap, so that no part of the
power system is left unprotected. This is shown in Figure the circuit breaker A that is not completely protected
2.6(a), the circuit breaker being included in both zones. against faults. In Figure 2.6(b) a fault at F would cause
the busbar protection to operate and open the circuit
breaker but the fault may continue to be fed through the
feeder. The feeder protection, if of the unit type (see
section 2.5.2), would not operate, since the fault is
outside its zone. This problem is dealt with by
intertripping or some form of zone extension, to ensure
that the remote end of the feeder is tripped also.
The point of connection of the protection with the power
system usually defines the zone and corresponds to the
location of the current transformers. Unit type
protection will result in the boundary being a clearly
defined closed loop. Figure 2.7 illustrates a typical
arrangement of overlapping zones.
For practical physical and economic reasons, this ideal is Alternatively, the zone may be unrestricted; the start will
not always achieved, accommodation for current be defined but the extent (or 'reach') will depend on
transformers being in some cases available only on one measurement of the system quantities and will therefore
side of the circuit breakers, as in Figure 2.6(b). This be subject to variation, owing to changes in system
leaves a section between the current transformers and conditions and measurement errors.
2.4 RELIABILITY 2.4.4 Testing
The need for a high degree of reliability is discussed in Comprehensive testing is just as important, and this
Section 2.1. Incorrect operation can be attributed to one testing should cover all aspects of the protection
of the following classifications: scheme, as well as reproducing operational and
environmental conditions as closely as possible. Type
a. incorrect design/settings
testing of protection equipment to recognised standards
b. incorrect installation/testing fulfils many of these requirements, but it may still be
necessary to test the complete protection scheme (relays,
c. deterioration in service
current transformers and other ancillary items) and the
tests must simulate fault conditions realistically.
2.4.1 Design
The design of a protection scheme is of paramount 2.4.5 Deterioration in Service
importance. This is to ensure that the system will
Subsequent to installation in perfect condition,
operate under all required conditions, and (equally
deterioration of equipment will take place and may
important) refrain from operating when so required
eventually interfere with correct functioning. For
(including, where appropriate, being restrained from
example, contacts may become rough or burnt owing to
operating for faults external to the zone being
frequent operation, or tarnished owing to atmospheric
protected). Due consideration must be given to the contamination; coils and other circuits may become
nature, frequency and duration of faults likely to be open-circuited, electronic components and auxiliary
experienced, all relevant parameters of the power system devices may fail, and mechanical parts may seize up.
(including the characteristics of the supply source, and
methods of operation) and the type of protection The time between operations of protection relays may be
equipment used. Of course, no amount of effort at this years rather than days. During this period defects may
stage can make up for the use of protection equipment have developed unnoticed until revealed by the failure of
that has not itself been subject to proper design. the protection to respond to a power system fault. For
this reason, relays should be regularly tested in order to
check for correct functioning.
2.4.2 Settings Testing should preferably be carried out without
It is essential to ensure that settings are chosen for disturbing permanent connections. This can be achieved
protection relays and systems which take into account by the provision of test blocks or switches.
the parameters of the primary system, including fault The quality of testing personnel is an essential feature
and load levels, and dynamic performance requirements when assessing reliability and considering means for
etc. The characteristics of power systems change with improvement. Staff must be technically competent and
time, due to changes in loads, location, type and amount adequately trained, as well as self-disciplined to proceed
of generation, etc. Therefore, setting values of relays in a systematic manner to achieve final acceptance.
may need to be checked at suitable intervals to ensure
Important circuits that are especially vulnerable can be
that they are still appropriate. Otherwise, unwanted
provided with continuous electrical supervision; such
operation or failure to operate when required may occur.
arrangements are commonly applied to circuit breaker
trip circuits and to pilot circuits. Modern digital and
numerical relays u s u a l l y incorporate self-
2.4.3 Installation
testing/diagnostic facilities to assist in the detection of
The need for correct installation of protection systems is failures. With these types of relay, it may be possible to
obvious, but the complexity of the interconnections of arrange for such failures to be automatically reported by
many systems and their relationship to the remainder of communications link to a remote operations centre, so
the installation may make checking difficult. Site testing that appropriate action may be taken to ensure
is therefore necessary; since it will be difficult to continued safe operation of that part of the power
reproduce all fault conditions correctly, these tests must system and arrangements put in hand for investigation
be directed to proving the installation. The tests should and correction of the fault.
be limited to such simple and direct tests as will prove
the correctness of the connections, relay settings, and
freedom from damage of the equipment. No attempt 2.4,6 Protection Performance
should be made to 'type test' the equipment or to Protection system performance is frequently assessed
establish complex aspects of its technical performance. statistically. For this purpose each system fault is classed
as an incident and only those that are cleared by the 2.5.1 Time Grading
tripping of the correct circuit breakers are classed as
Protection systems in successive zones are arranged to
'correct'. The percentage of correct clearances can then
operate in times that are graded through the sequence of
be determined.
equipments so that upon the occurrence of a fault,
This principle of assessment gives an accurate evaluation although a number of protection equipments respond,
of the protection of the system as a whole, but it is only those relevant to the faulty zone complete the
severe in its judgement of relay performance. Many tripping function. The others make incomplete
relays are called into operation for each system fault, operations and then reset. The speed of response will
and all must behave correctly for a correct clearance to often depend on the severity of the fault, and will
be recorded. generally be slower than for a unit system.
Complete reliability is unlikely ever to be achieved by
further improvements in construction. If the level of
2.5.2 Unit Systems
reliability achieved by a single device is not acceptable,
improvement can be achieved through redundancy, e.g. It is possible to design protection systems that respond
duplication of equipment. Two complete, independent, only to fault conditions occurring within a clearly
main protection systems are provided, and arranged so defined zone. This type of protection system is known as
that either by itself can carry out the required function. "unit protection1. Certain types of unit protection are
If the probability of each equipment failing is x/unit, the known by specific names, e.g. restricted earth fault and
resultant probability of both equipments failing differential protection. Unit protection can be applied
simultaneously, allowing for redundancy, is x2. Where x throughout a power system and, since it does not involve
is small the resultant risk {x2} may be negligible. time grading, is relatively fast in operation. The speed of
response is substantially independent of fault severity.
Where multiple protection systems are used, the tripping
signal can be provided in a number of different ways. Unit protection usually involves comparison of quantities
The two most common methods are: at the boundaries of the protected zone as defined by the
locations of the current transformers. This comparison
a. all protection systems must operate for a tripping
may be achieved by direct hard-wired connections or
operation to occur (e.g. 'two-out-of-two'
may be achieved via a communications link. However
arrangement)
certain protection systems derive their "restricted"
b. only one protection system need operate to cause property from the configuration of the power system and
a trip (e.g. 'one-out-of two' arrangement) may be classed as unit protection, e.g. earth fault
The former method guards against maloperation while protection applied to the high voltage delta winding of a
the latter guards against failure to operate due to an power transformer. Whichever method is used, it must
unrevealed fault in a protection system. Rarely, three be kept in mind that selectivity is not merely a matter of
main protection systems are provided, configured in a relay design. It also depends on the correct co-
'two-out-of three' tripping arrangement, to provide both ordination of current transformers and relays with a
reliability of tripping, and security against unwanted suitable choice of relay settings, taking into account the
tripping. possible range of such variables as fault currents,
maximum load current, system impedances and other
It has long been the practice to apply duplicate related factors, where appropriate.
protection systems to busbars, both being required to
operate to complete a tripping operation. Loss of a
busbar may cause widespread loss of supply, which is 2.6 STABILITY
clearly undesirable. In other cases, important circuits are The term 'stability' is usually associated with unit
provided with duplicate main protection systems, either protection schemes and refers to the ability of the
being able to trip independently. On critical circuits, use protection system to remain unaffected by conditions
may also be made of a digital fault simulator to model external to the protected zone, for example through load
the relevant section of the power system and check the current and external fault conditions.
performance of the relays used.
2.7 SPEED
2 . 5 SELECTIVITY The function of protection systems is to isolate faults on
When a fault occurs, the protection scheme is required the power system as rapidly as possible. The main
to trip only those circuit breakers whose operation is objective is to safeguard continuity of supply by
required to isolate the fault. This property of selective removing each disturbance before it leads to widespread
tripping is also called 'discrimination' and is achieved by loss of synchronism and consequent collapse of the
two general methods. power system.
As the loading on a power system increases, the phase 2.9 PRIMARY AND BACK-UP PROTECTION
shift between voltages at different busbars on the
The reliability of a power system has been discussed
system also increases, and therefore so does the
earlier, including the use of more than one primary (or
probability that synchronism will be lost when the
'main') protection system operating in parallel. In the
system is disturbed by a fault. The shorter the time a
event of failure or non-availability of the primary
fault is allowed to remain in the system, the greater can protection some other means of ensuring that the fault
be the loading of the system. Figure 2.8 shows typical is isolated must be provided. These secondary systems
relations between system loading and fault clearance are referred to as 'back-up protection'.
times for various types of fault. It will be noted that
phase faults have a more marked effect on the stability Back-up protection may be considered as either being
of the system than a simple earth fault and therefore 'local' or 'remote'. Local back-up protection is achieved
require faster clearance. by protection which detects an un-cleared primary
system fault at its own location and which then trips its
own circuit breakers, e.g. time graded overcurrent relays.
Remote back-up protection is provided by protection
that detects an un-cleared primary system fault at a
remote location and then issues a local trip command,
e.g. the second or third zones of a distance relay. In both
cases the main and back-up protection systems detect a
fault simultaneously, operation of the back-up
protection being delayed to ensure that the primary
protection clears the fault if possible. Normally being
unit protection, operation of the primary protection will
be fast and will result in the minimum amount of the
power system being disconnected. Operation of the
Figure 2.8: Typical power/time relationship
for various fault types back-up protection will be, of necessity, slower and will
result in a greater proportion of the primary system
System stability is not, however, the only consideration. being lost.
Rapid operation of protection ensures that fault damage The extent and type of back-up protection applied will
is minimised, as energy liberated during a fault is naturally be related to the failure risks and relative
proportional to the square of the fault current times the economic importance of the system. For distribution
duration of the fault. Protection must thus operate as systems where fault clearance times are not critical, time
quickly as possible but speed of operation must be delayed remote back-up protection may be adequate.
weighed against economy. Distribution circuits, which For EHV systems, where system stability is at risk unless
do not normally require a fast fault clearance, are usually a fault is cleared quickly, multiple primary protection
protected by time-graded systems. Generating plant and systems, operating in parallel and possibly of different
EHV systems require protection gear of the highest types (e.g. distance and unit protection), will be used to
attainable speed; the only limiting factor will be the ensure fast and reliable tripping. Back-up overcurrent
necessity for correct operation, and therefore unit protection may then optionally be applied to ensure that
systems are normal practice. two separate protection systems are available during
maintenance of one of the primary protection systems.
Back-up protection systems should, ideally, be
2.8 SENSITIVITY
completely separate from the primary systems. For
Sensitivity is a term frequently used when referring to example a circuit protected by a current differential relay
the minimum operating level (current, voltage, power may also have time graded overcurrent and earth fault
etc.) of relays or complete protection schemes. The relay relays added to provide circuit breaker tripping in the
or scheme is said to be sensitive if the primary operating event of failure of the main primary unit protection. To
parameter(s) is low. maintain complete separation and thus integrity, current
transformers, voltage transformers, relays, circuit breaker
With older electromechanical relays, sensitivity was
trip coils and d.c. supplies would be duplicated. This
considered in terms of the sensitivity of the measuring
ideal is rarely attained in practice. The following
movement and was measured in terms of its volt-ampere
compromises are typical:
consumption to cause operation. With modern digital
and numerical relays the achievable sensitivity is seldom a. separate current transformers (cores and secondary
limited by the device design but by its application and windings only) are provided. This involves little extra
CT/VT parameters. cost or accommodation compared with the use of
common current transformers that would have to be The majority of protection relay elements have self-reset
larger because of the combined burden. This practice contact systems, which, if so desired, can be modified to
is becoming less common when digital or numerical provide hand reset output contacts by the use of
relays are used, because of the extremely low input auxiliary elements. Hand or electrically reset relays are
burden of these relay types used when it is necessary to maintain a signal or lockout
b. voltage transformers are not duplicated because of condition. Contacts are shown on diagrams in the
cost and space considerations. Each protection relay position corresponding to the un-operated or de-
supply is separately protected (fuse or MCB) and energised condition, regardless of the continuous service
continuously supervised to ensure security of the VT condition of the equipment. For example, an
output. An alarm is given on failure of the supply and, undervoltage relay, which is continually energised in
where appropriate, prevent an unwanted operation of normal circumstances, would still be shown in the de-
the protection energised condition.
c. trip supplies to the two protections should be A 'make' contact is one that closes when the relay picks
separately protected (fuse or MCB). Duplication of up, whereas a 'break' contact is one that is closed when
tripping batteries and of circuit breaker tripping coils the relay is de-energised and opens when the relay picks
may be provided. Trip circuits should be continuously up. Examples of these conventions and variations are
supervised shown in Figure 2.9.
2.10.1 Contact Systems The relay may therefore energise the tripping coil
directly, or, according to the coil rating and the number
Relays may be fitted with a variety of contact systems of circuits to be energised, may do so through the
for providing electrical outputs for tripping and remote agency of another multi-contact auxiliary relay.
indication purposes. The most common types
encountered are as follows: The basic trip circuit is simple, being made up of a hand-
trip control switch and the contacts of the protection
a. Self-reset relays in parallel to energise the trip coil from a battery,
The contacts remain in the operated condition only through a normally open auxiliary switch operated by
while the controlling quantity is applied, returning the circuit breaker. This auxiliary switch is needed to
to their original condition when it is removed open the trip circuit when the circuit breaker opens
b. Hand or electrical reset since the protection relay contacts will usually be quite
These contacts remain in the operated condition incapable of performing the interrupting duty. The
after the controlling quantity is removed. They can auxiliary switch will be adjusted to close as early as
be reset either by hand or by an auxiliary possible in the closing stroke, to make the protection
electromagnetic element effective in case the breaker is being closed on to a fault.
Where multiple output contacts, or contacts with 2.11 T R I P P I N G CIRCUITS
appreciable current-carrying capacity are required,
There are three main circuits in use for circuit breaker
interposing, contactor type elements will normally be used.
tripping:
In general, static and microprocessor relays have discrete
a. series sealing
measuring and tripping circuits, or modules. The
functioning of the measuring modules is independent of b. shunt reinforcing
operation of the tripping modules. Such a relay is c. shunt reinforcement with sealing
equivalent to a sensitive electromechanical relay with a
tripping contactor, so that the number or rating of These are illustrated in Figure 2.10.
outputs has no more significance than the fact that they
have been provided.
For larger switchgear installations the tripping power
(a) Series sealing
requirement of each circuit breaker is considerable, and
further, two or more breakers may have to be tripped by
one protection system. There may also be remote
signalling requirements, interlocking with other
functions (for example auto-reclosing arrangements),
and other control functions to be performed. These
(b) Shunt reinforcing
various operations may then be carried out by multi-
contact tripping relays, which are energised by the
protection relays and provide the necessary number of
adequately rated output contacts.
Protection systems are invariably provided with Figure 2.10: Typical relay tripping circuits
indicating devices, called 'flags', or "targets', as a guide
for operations personnel. Not every relay will have one, For electromechanical relays, electrically operated
as indicators are arranged to operate only if a trip indicators, actuated after the main contacts have closed,
operation is initiated. Indicators, with very few avoid imposing an additional friction load on the
exceptions, are bi-stable devices, and may be either measuring element, which would be a serious handicap
mechanical or electrical. A mechanical indicator consists for certain types. Care must be taken with directly
of a small shutter that is released by the protection relay operated indicators to line up their operation with the
movement to expose the indicator pattern. closure of the main contacts. The indicator must have
Electrical indicators may be simple attracted armature operated by the time the contacts make, but must not
elements, where operation of the armature releases a have done so more than marginally earlier. This is to stop
shutter to expose an indicator as above, or indicator indication occurring when the tripping operation has not
lights (usually light emitting diodes). For the latter, some been completed.
kind of memory circuit is provided to ensure that the With modern digital and numerical relays, the use of
indicator remains lit after the initiating event has passed. various alternative methods of providing trip circuit
With the advent of digital and numerical relays, the functions is largely obsolete. Auxiliary miniature
operation indicator has almost become redundant. contactors are provided within the relay to provide
Relays will be provided with one or two simple indicators output contact functions and the operation of these
that indicate that the relay is powered up and whether contactors is independent of the measuring system, as
an operation has occurred. The remainder of the mentioned previously. The making current of the relay
information previously presented via indicators is output contacts and the need to avoid these contacts
available by interrogating the relay locally via a 'man- breaking the trip coil current largely dictates circuit
machine interface' (e.g. a keypad and liquid crystal breaker trip coil arrangements. Comments on the
display screen), or remotely via a communication system. various means of providing tripping arrangements are,
however, included below as a historical reference
applicable to earlier electromechanical relay designs.
2.11.1 Series sealing is countered by means of a further contact on the
auxiliary unit connected as a retaining contact.
The coil of the series contactor carries the trip current
initiated by the protection relay, and the contactor closes This means that provision must be made for releasing the
a contact in parallel with the protection relay contact. sealing circuit when tripping is complete; this is a
This closure relieves the protection relay contact of further disadvantage, because it is sometimes inconvenient to
duty and keeps the tripping circuit securely closed, even if find a suitable contact to use for this purpose.
chatter occurs at the main contact. The total tripping time
is not affected, and the indicator does not operate until
current is actually flowing through the trip coil. 2 . 1 2 TRIP CIRCUIT SUPERVISION
The main disadvantage of this method is that such series The trip circuit includes the protection relay and other
elements must have their coils matched with the trip components, such as fuses, links, relay contacts, auxiliary
circuit with which they are associated. switch contacts, etc., and in some cases through a
considerable amount of circuit wiring with intermediate
The coil of these contacts must be of low impedance,
terminal boards. These interconnections, coupled with
with about 5% of the trip supply voltage being dropped
the importance of the circuit, result in a requirement in
across them.
many cases to monitor the integrity of the circuit. This
When used in association with high-speed trip relays, is known as trip circuit supervision. The simplest
which usually interrupt their own coil current, the arrangement contains a healthy trip lamp, as shown in
auxiliary elements must be fast enough to operate and Figure 2.H(a).
release the flag before their coil current is cut off. This
The resistance in series with the lamp prevents the
may pose a problem in design if a variable number of
breaker being tripped by an internal short circuit caused
auxiliary elements (for different phases and so on) may
by failure of the lamp. This provides supervision while
be required to operate in parallel to energise a common
the circuit breaker is closed; a simple extension gives
tripping relay.
pre-closing supervision.
Figure 2.11 (b) shows how, the addition of a normally
2.11.2 Shunt reinforcing closed auxiliary switch and a resistance unit can provide
supervision while the breaker is both open and closed.
Here the sensitive contacts are arranged to trip the
circuit breaker and simultaneously to energise the
auxiliary unit, which then reinforces the contact that is
energising the trip coil.
Two contacts are required on the protection relay, since (a) Supervision while circuit breaker is closed (scheme H4)
it is not permissible to energise the trip coil and the
reinforcing contactor in parallel. If this were done, and
more than one protection relay were connected to trip
the same circuit breaker, all the auxiliary relays would be (b) Supervision while circuit breaker is open or closed (scheme H5)
energised in parallel for each relay operation and the
indication would be confused.
The duplicate main contacts are frequently provided as a
three-point arrangement to reduce the number of
contact fingers.
Alarm
(c) Supervision with circuit breaker open or closed
2.11.3 Shunt reinforcement with sealing with remote alarm (scheme H7)
3 . 2 VECTOR ALGEBRA
A vector represents a quantity in both magnitude and
direction. In Figure 3.1 the vector OP has a magnitude
\Z\ at an angle 6 with the reference axis OX.
...Equation 3.2
...Equation 3.3
where the operator j indicates that the component y is The modulus IZI and the argument 8 are together known
perpendicular to component x. In electrical as 'polar co-ordinates', and x and y are described as;
nomenclature, the axis OC is the 'real' or 'in-phase' axis, 'cartesian co-ordinates'. Conversion between co-
and the vertical axis OY is called the 'imaginary' or ordinate systems is easily achieved. As the operator j
'quadrature' axis. The operator j rotates a vector anti- obeys the ordinary laws of algebra, complex quantities in
clockwise through 90°. If a vector is made to rotate anti- rectangular form can be manipulated algebraically, as
clockwise through 180°, then the operator j has can be seen by the following:
performed its function twice, and since the vector has ...Equation 3.5
reversed its sense, then:
...Equation3.6
(see Figure 3.2)
3.3.2 Complex Numbers
A complex number may be defined as a constant that
represents the real and imaginary components of a
...Equation 3.7 physical quantity. The impedance parameter of an
electric circuit is a complex number having real and
Figure 3.2: Addition of vectors
imaginary components, which are described as resistance
and reactance respectively.
Confusion often arises between vectors and complex
numbers. A vector, as previously defined, may be a
complex number. In this context, it is simply a physical
quantity of constant magnitude acting in a constant
direction. A complex number, which, being a physical
quantity relating stimulus and response in a given
operation, is known as a 'complex operator'. In this
context, it is distinguished from a vector by the fact that
it has no direction of its own.
Because complex numbers assume a passive role in any
calculation, the form taken by the variables in the
problem determines the method of representing them.
where:
Em is the maximum amplitude of the waveform;
the angular velocity,
is the argument defining the amplitude of the
voltage at a time t=O
At t-O, the actual value of the voltage is So if
E m is regarded as the modulus of a vector, whose
argument is then is the imaginary component
of the vector Figure 3.3 illustrates this quantity
as a vector and as a sinusoidal function of time.
...Equation 3.12
Figure 3.4 Methods of representing a circuit
where the terms on the left
hand side of the equation are voltage drops across the
circuit elements. Expressed in
Voltage drops are also positive when acting in the component of current, and is known as 'reactive power'.
direction of current flow. From Figure 3.4(a) it can be
As P and Q are constants which specify the power
seen that [Z1+Z2+Z3)I\s the total voltage drop in the
exchange in a given circuit, and are products of thel
loop in the direction of current flow, and must equate to
current and voltage vectors, then if is the vector
the total voltage rise E,-E2. In Figure 3.4(6^ the voltage
product it follows that with as the reference vector
drop between nodes a and b designated Vab indicates
and 0 as the angle between and
that point b is at a lower potential than a, and is_positive
when current flows from a to b. Conversely Vba is a
...Equation 3.16
negative voltage drop.
Symbolically: Vab= Van - Vbn ; Vba= Vbn - Van Equation 3.14 The quantity S is described as the 'apparent power', and
is the term used in establishing the rating of a circuit,
where n is a common reference point. has units of VA.
3.4.3 Power
3.4.4 Single-Phase and Polyphase Systems
The product of the potential difference across and the
A system is single or polyphase depending upon whether
current through a branch of a circuit is a measure of the
the sources feeding it are single or polyphase. A source
rate at which energy is exchanged between that branch
is single or polyphase according to whether there are one
and the remainder of the circuit. If the potential
or several driving voltages associated with it. For
difference is a positive voltage drop, the branch is
example, a three-phase source is a source containing
passive and absorbs energy. Conversely, if the potential
three alternating driving voltages that are assumed to
difference is a positive voltage rise, the branch is active
reach a maximum in phase order, A, B, C. Each phase
and supplies energy.
driving voltage is associated with a phase branch of the
The rate at which energy system network as shown in Figure 3.5(a).
is exchanged is known as
power, and by convention, If a polyphase system has balanced voltages, that isj
the power is positive when equal in magnitude and reaching a maximum at equally
energy is being absorbed and negative when being displaced time intervals, and the phase branch
supplied. With a.c. circuits the power alternates, so, to impedances are identical, it is called a 'balanced' system,
obtain a rate at which energy is supplied or absorbed, it It will become 'unbalanced' if any of the above
is necessary to take the average power over one whole conditions are not satisfied. Calculations using al
cycle. balanced polyphase system are simplified, as it is only
then the necessary to solve for a single phase, the solution for the
power equation is: remaining phases being obtained by symmetry.
The power system is normally operated as a three-phase,
balanced, system. For this reason the phase voltages are
...Equation 3.15
equal in magnitude and can be represented by three
where:
vectors spaced 120° or radians apart, as shown in
Figure 3.5(b).
...Equation 3.17
Hence:
...Equation 3.19
Right selection
Simple transposition of the above formulae will refer the Figure 3.6: Selection of base voltages
ohmic value of impedance to the per unit or percentage
values and base quantities.
Of the many theorems that exist, the three most The aim of network reduction is to reduce a system to a
important are given. These are: the Superposition simple equivalent while retaining the identity of that
Theorem, Thevenin's Theorem and Kennelly's Star/Delta part of the system to be studied.
Theorem.
For example, consider the system shown in Figure 3.9.
3.6.2.1 Superposition Theorem The network has two sources E' and E", a line AOB
(general network theorem) shunted by an impedance, which may be regarded as the
reduction of a further network connected between A and
The resultant current that flows in any branch of a
B, and a load connected between 0 and N. The object of
network due to the simultaneous action of several
the reduction is to study the effect of opening a breaker
driving voltages is equal to the algebraic sum of the
at A or B during normal system operations, or of a fault
component currents due to each driving voltage acting
at A or B. Thus the identity of nodes A and B must be
alone with the remainder short-circuited.
retained together with the sources, but the branch ON
3.6.2.2 Thevenin's Theorem can be eliminated, simplifying the study. Proceeding, A,
(active network reduction theorem) B, N, forms a star branch and can therefore be converted
Any active network that may be viewed from two to an equivalent delta.
terminals can be replaced by a single driving voltage
acting in series with a single impedance. The driving
voltage is the open-circuit voltage between the two
terminals and the impedance is the impedance of the
network viewed from the terminals with all sources short-
circuited.
and so on.
and so on.
Most reduction problems follow the same pattern as the
example above. The rules to apply in practical network
reduction are:
a. decide on the nature of the disturbance or
disturbances to be studied
b. decide on the information required, for example
the branch currents in the network for a fault at a
particular location
Figure 3.10: Reduction using c. reduce all passive sections of the network not
star/delta transform directly involved with the section under j
The network is now reduced as shown in Figure 3.10. examination
By applying Thevenin's theorem to the active loops, these d. reduce all active meshes to a simple equivalent,
can be replaced by a single driving voltage in series with that is, to a simple source in series with a single]
an impedance as shown in Figure 3.11. impedance
(b) Reduction of right active mesh With the widespread availability of computer-based
power system simulation software, it is now usual to use
such software on a routine basis for network calculations
without significant network reduction taking place.
However, the network reduction techniques given above
are still valid, as there will be occasions where such
software is not immediately available and a hand
calculation must be carried out.
(a) Reduction of left active mesh In certain circuits, for example parallel lines on the same
towers, there is mutual coupling between branches.
Correct circuit reduction must take account of this I
coupling.
...Equation 3.21
where Z12=Z21 and Y12=Y21, if the network is
(Figure 3.13(b)), and, if the branch impedances are assumed to be reciprocal. Further, by solving the
equal, the usual case, then: above equations it can be shown that:
...Equation 3.22
(Figure 3.13(c)).
If the same conditions are applied to the equivalent 3.2 Equivalent Circuits I. Frank M. Starr, Proc. A.I.E.E.
mesh, then: Vol.51. 1932, pp. 287-298.
Hence:
...Equation 3.25
(a) Three - phase fault diagram for a fault at node A 0.68/0.62= 1.1 ohms
and
0.68/0.38= 1.79 ohms
...Equation 4.2
where all quantities are referred to the reference phase ...Equation 4.3
A. A similar set of equations can be written for phase
and sequence currents. Figure 4.5 illustrates the where is the positive sequence impedance of the
resolution of a system of unbalanced vectors. system viewed from the fault. As before the fault no
current was flowing from the fault into the system, it
follows that , the fault current flow ing from th e
system into the fault must equal - . Therefore:
...Equation 4.4
Figure4.6: Fault at F:
Positive sequence diagrams
4.3.1 Positive Sequence Network
4.3.2 Negative Sequence Network
During normal balanced system conditions, only positive
sequence currents and voltages can exist in the system, If only positive sequence quantities appear in a power
and therefore the normal system impedance network is a system under normal conditions, then negative sequence
positive sequence network. quantities can only exist during an unbalanced fault.
When a fault occurs in a power system, the current in the If no negative sequence quantities are present in the
fault branch prior to the fault, then, when a fault occurs, 4.4 EQUATIONS AND NETWORK CONNECTIONS
the change in voltage is , and the resulting current FOR VARIOUS TYPES OF FAULTS
flowing from the network into the fault is:
The most important types of faults are as follows:
a. single-phase to earth
b. phase to phase
...Equation 4.5
c. phase-phase-earth
The impedances in the negative sequence network are
generally the same as those in the positive sequence
d. three-phase (with or without earth)
network. In machines , but the difference is The above faults are described as single shunt faults
generally ignored, particularly in large networks. because they occur at one location and involve a
The negative sequence diagrams, shown in Figure 4.7, are
connection between one phase and another or to
similar to the positive sequence diagrams, with t wo
earth.In addition, the Protection Engineer often studies
important differences; no driving voltages exist before
two other types of fault:
the fault and the negative sequence voltage e. single-phase open circuit
is greatest at the fault point. f. cross-country fault
By determining the currents and voltages at the fault
point, it is possible to define the fault and connect the
sequence networks to represent the fault condition.
From the initial equations and the network diagram, the
nature of the fault currents and voltages in different
branches of the system can be determined.For shunt
faults of zero impedance, and neglecting load current,
the equations defining each fault (using phase-neutral
(a) Negative sequence network
values) can be written down as follows:
a. Single-phase-earth (A-E)
...Equation 4.7
(b) Gradient diagram
Consider a fault defined by Equations 4.7 and by Figure Again, from Equation 4.9 and Equations 4.1 and 4.2:
4.8(a). Converting Equations 4.7 into sequence ...Equation 4.18
quantities by using Equations 4.1 and 4.2, then:
and
...Equation 4.19
...Equation 4.12 ...Equation 4.13
Substituting for and using network Equations 4.5
Substituting for
and 4.6:
, and in Equation
4.13 from Equations 4.4, 4.5 and 4.6:
thus, using Equation 4.18:
...Equation 4.15
...Equation 4.16 or
From network Equations 4.4 and 4.5, Equation 4.16 can
be re-written:
...Equation 4.22
From the above equations it follows that connecting the Hence,from Equations 4.2,
three sequence networks in parallel as shown in Figure
V0=U3Va
4,10(b) may represent a phase-
fb) Equivalent circuit
and therefore:
...Equation 4.28
From Equations
4.28, it can be concluded that the sequence networks
are connected in parallel, as shown in Figure 4.12(b).
phase-earth fault.
(a) Definition of fault Figure 4.10:
Phase-phase-earth fault at F
...Equation 4.23
and
...Equation 4.24
Substituting = 0 in Equation 4.5 gives: (b) Equivalent circuit
...Equation 4.25
Figure 4.12: Open circuit on phase A
and substituting V-, = 0 in Equation
4.4:
4.4.6 Cross-country Faults
A cross-country fault is one where there are two faults
or
affecting the same circuit, but in different locations and
...Equation 4.26
possibly involving different phases. Figure 4.13(a)
Further, since from Equation 4.24 = 0, it follows from illustrates this.
Equation 4.6 that i s z e r o wh e n is finite.
The constraints expressed in terms of sequence
T h e equivalent sequence connections for a three-phase
quantities are as follows:
fault are shown in Figure 4.11.
a) At point F
...Equation 4.29
Therefore:
...Equation 4.30
network (from (b) above) the maximum through c. phase-phase-earth (B-C-E) ...Equation 4.37
In power system calculations, the positive and negative As an example of current distribution technique, consider
sequence impedances are normally equal. Thus, the the system in Figure 4.14(a}. The equivalent sequence
division of sequence currents in the two networks will networks are given in Figures 4.14(b) and (c), together <4st
branch
4.5.2 Voltage Distribution
The voltage distribution in any branch of a network is
determined from the sequence voltage distribution. As
shown by Equations 4.4, 4.5 and 4.6 and the gradient
diagrams, Figures 4.6(b) and 4.7(b), the positive
sequence voltage is a minimum at the fault, whereas the
zero and negative sequence voltages are a maximum.
Thus, the sequence voltages in any part of the system
(a) Single line diagram
may be given generally as:
...Equation 4.3
where
Thus:
...Equation 4.45
b. Phase-phase-earth (B-C-E)
...Equation 4.47
b. Phase-phase-earth (B-C-E)
...Equation 4.48
At source:
At source:
At relaying point X:
4.7 REFERENCES
4.1 Circuit Analysis ofA.C. Power Systems, Volume I.
Edith Clarke. John Wiley & Sons.
4.2 Method of Symmetrical Co-ordinates Applied to
the Solution of Polyphase Networks. C.L
Fortescue. Trans. A.I.E.E.,Vol. 37, Part II, 1918, pp
1027-40.
4.3 Power System Analysis. J.R. Mortlock and M.W.
Humphrey Davies. Chapman and Hall.
4.4 Neutral Groundings. R Willheim and M. Waters,
Elsevier.
4.5 Fault Calculations. F.H.W. Lackey, Oliver ft Boyd.
• 5 • Equivalent Circuits and Parameters
of Power System Plant
5.1 INTRODUCTION
Knowledge of the behaviour of the principal electrical
system plant items under normal and fault conditions is
a prerequisite for the proper application of protection.
This chapter summarises basic synchronous machine,
transformer and transmission line theory and gives
equivalent circuits and parameters so that a fault study
can be successfully completed before the selection and
application of the protection systems described in later
chapters. Only what might be referred to as 'traditional'
synchronous machine theory is covered, as that is all that
calculations for fault level studies generally require.
Readers interested in more advanced models of
synchronous machines are referred to the numerous
papers on the subject, of which reference [5.1] is a good
starting point.
Power system plant may be divided into two broad
groups - static and rotating.
The modelling of static plant for fault level calculations
provides few difficulties, as plant parameters generally
do not change during the period of interest following
fault inception. The problem in modelling rotating plant
is that the parameters change depending on the
response to a change in power system conditions.
where
\SYMMETRY
The exact instant at which the short circuit is applied to
the stator winding is of significance. If resistance is Table 5.1 gives values of machine reactances for salient
negligible compared with reactance, the current in a coil pole and cylindrical rotor machines typical of latest
will lag the voltage by 90°, that is, at the instant when design practice. Also included are parameters for
the voltage wave attains a maximum, any current synchronous compensators - such machines are now
flowing through would be passing through zero. If a rarely built, but significant numbers can still be found in
short circuit were applied at this instant, the resulting operation.
current would rise smoothly and would be a simple a.c.
component. However, at the moment when the induced 5.8.1 Synchronous Reactance Xd = X, + X,ul
voltage is zero, any current flowing must pass through a
maximum (owing to the 90° lag). If a fault occurs at this The order of magnitude of XL is normally 0.1-0.25p.u.,
moment, the resulting current will assume the while that of Xad\s 1.0-2.5p.u. The leakage reactance X£
corresponding relationship; it will be at its peak and in can be reduced by increasing the machine size (derating),
the ensuing 180" will go through zero to maximum in or increased by artificially increasing the slot leakage,
the reverse direction and so on. In fact the current must but it will be noted that XL is only about 10% of the
actually start from zero and so will follow a sine wave total value of Xd and cannot exercise much influence.
that is completely asymmetrical. Intermediate positions The armature reaction reactance can be reduced by
will give varying degrees of asymmetry. decreasing the armature reaction of the machine, which
This asymmetry can be considered to be due to a d.c. in design terms means reducing the ampere conductor or
component of current which dies away because electrical (as distinct from magnetic) loading - this will
resistance is present. often mean a physically larger machine. Alternatively
the excitation needed to generate open-circuit voltage
The d.c. component of stator current sets up a d.c. field may be increased; this is simply achieved by increasing
in the stator which causes a supply frequency ripple on the machine air-gap, but is only possible if the excitation
the field current, and this alternating rotor flux has a system is modified to meet the increased requirements.
further effect on the stator. This is best shown by
considering the supply frequency flux as being In general, control of Xd is obtained almost entirely by
represented by two half magnitude waves each rotating varying Xa(i, and in most cases a reduction in Xd will
mean a larger and more costly machine. It is also worth
/ Salient pole Cylindr ;at rotor turbine generators Salient pole generators
Type of machine synchronous Air Cooled Hydrogen Hydrogen/ 4 Pole Multi-pole
condensers Cooled Water Cooled
Short circuit ratio O.5-U.7 1.0-1.2 0.4-0.6 0.4-0.6 0.4-0.6 0.4-0.6 0.6-0.8
Direct axis synchronous reactance Xd (p.u.) 1.6-2.0 0.8-1.0 2.0-2.8 2.1-2.4 2.1-2.6 1.75-3.0 1.4-1.9
Quadrature axis synchronous reactance Xq (p.u.) 1.0-1.23 0.5-0.65 1.8-2.7 1.9-2.4 2.0-2.5 0.9-1.5 0.8-1.0
Direct axis transient reactance X'd (p.u.) 0.3-0.5 0.2-0.35 0.2-0.3 0.27-0.33 0.3-0.36 0.26-0.35 0.24-0.4
Direct axis sub-transient reactance X"d (p.u.) 0.15-0.23 0.19-0.23 0.21-0.27 0.19-0.25 0.16-0.25
0.2-0.4 0.12-0.25
Quadrature axis sub-transient reactance X"q (p.u.) 0.16-0.25 0.19-0.23 0.21-0.28 0.19-0.35 0.18-0.24
0.25-0.6 0.15-0.25
Negative sequence reactance X2 (p.u.) 0.14-0.35 0.16-0.23 0.19-0.24 0.21-0.27 0.16-0.27 0.16-0.23
0.25-0.5
Zero sequence reactance Xo (p.u.) 0.12-0.16 0.06-0.10 0.06-0.1 0.1-0.15 0.1-0.15 0.01-0.1 0.045-0.23
Direct axis short circuit transient time constant T' d (s) 1.5-2.5 1.0-2.0 0.6-1.3 0.7-1.0 0.75-1.0 0.4-1.1 0.25-1
Direct axis open circuit transient time constant Vfo (s) 5-10 3-7 6-12 6-10 6-9.5 3.0-9.0 1.7-4.0
Direct axis short circuit sub-transient- time constant T" d (s) 0.04-0.9 0.05-0.10 0.013-0.022 0.017-0.025 0.022-0.03 0.02-0.04 0.02-0.06
Direct axis open circuit sub-transient time constant T"d<,(s) 0.07-0.11 0.08-0.25 0.018-0.03 0.023-0.032 0.025-0.035 0.035-0.06 0.03-0.1
Quadrature axis short circuit sub-transient time constant T" q (sj 0.04-0.6 0.05-0.6 0.013-0.022 0.018-0.027 0.02-0.03 0.025-0.04 0.025-0.08
Quadrature axis open circuit sub-transient time constant T" qo (s) 0.1-0.2 0.2-0.9 0.026-0.045 0.03-0.05 0.04-0.065 0.13-0.2 0.1-0.35
Table 5. V. Typical synchronous generator parameters NB all reactance values are unsaturated.
noting that XL normally changes in sympathy with Xad, rise to parasitic currents and heating; most machines arc
but that it is completely overshadowed by it. quite limited in the amount of such current which they I
The value has a special significance as it are able to carry, both in the steady - state and
approximates to the short circuit ratio (S.C.R.), the only transiently.
difference being that the 5.C.R. takes saturation into An accurate calculation of the negative sequence current!
account whereas Xd is derived from the air-gap line. capability of a generator involves consideration of the
current paths in the rotor body. In a turbine generator
5.8.2 Transient Reactance rotor, for instance, they include the solid rotor body, slot
wedges, excitation winding and end-winding retaining
The transient reactance covers the behaviour of a
rings. There is a tendency for local over-heating to occuB
machine in the period 0.1-3.0 seconds after a
and, although possible for the stator, continuous local
disturbance. This generally corresponds to the speed of
temperature measurement is not practical in the rotor.j
changes in a system and therefore X'd has a major
Calculation requires complex mathematical techniques
influence in transient stability studies.
to be applied, and involves specialist software.
Generally, the leakage reactance XL is equal to the
In practice an empirical method is used, based on the
effective field leakage reactance about 0.1-
fact that a given type of machine is capable of carrying, for
0.25p.u. The principal factor determining the value
short periods, an amount of heat determined by its
of is the field leakage. This is largely beyond the
thermal capacity, and for a long period, a rate of heat
control of the designer, in that other considerations are at
input which it can dissipate continuously. Synchronous
present more significant than field leakage and hence
machines are designed to be capable of operating
take precedence in determining the field design.
continuously on an unbalanced system such that, with!
XL can be varied as already outlined, and, in practice, none of the phase currents exceeding the rated current,!
control of transient reactance is usually achieved by the ratio of the negative sequence current I2 to the rated
varying Xi current //v does not exceed the values given in Table 5.2,
Under fault conditions, the machine shall also be capable
5.8.3 Sub-transient Reactance of operation with the product ofand time in
The sub-transient reactance determines the initial
current peaks following a disturbance and in the case of
a sudden fault is of importance for selecting the breaking seconds (t) not exceeding the values given.
capacity of associated circuit breakers. The mechanical
stresses on the machine reach maximum values that
depend on this constant. The effective damper winding
leakage reactance X'kd is largely determined by the
leakage of the damper windings and control of this is
only possible to a limited extent. X'kd normally has a
value between 0.05 and 0.15 p.u. The major factor is XL
which, as indicated previously, is of the order of 0.1 -0.25
p.u., and control of the sub-transient reactance is
normally achieved by varying XL.
It should be noted that good transient stability is
obtained by keeping the value of X' d low, which
therefore also implies a low value of X"d. The fault rating
of switchgear, etc. will therefore be relatively high. It is
not normally possible to improve transient stability
performance in a generator without adverse effects on
fault levels, and vice versa.
...Equation 5.8
(b) Circuit diagram with tertiary winding
where:
Zsc-t= impedance between 'series common1 and tertiary
windings
...Equation 5.10
MVA Primary Primary Taps Secondary Z% HV/LV X/R ratio MVA Primary Primary Taps Secondary Z% HV/LV X/R ratio
kV kV kV
IHfllffl
7.5 33 +5.72 %-17.16 % 11 7.5 15 24 33 ±1O% 6.9 24 25
MVA Primary Primary condary W Tertiary Z% X/R MVA Primary Primary Seconda Z%
kV Taps kV HV/LV ratio kV Taps ry HV/LV ratio
kV
20 220 + 12.5% - 6.9 - 9.9 18 95 132 ±10% 11 13.5 46
7 50/0
20 230 +12.5%- 6.9 - 10-14 13 140 157.5 ±10% 11.5 12.7 41
57 275 7±10%
5% 11.8 7.2 18.2 34 141 400 ±5% 15 14.7 57
74 345 +14.4% -10% 96 12 8.9 25 151 236 ±5% 15 13.6 47
71
79.2 220 +10% -15% 11.6 11 18.9 35 167 145 +7.5%-16.5% 15 25.7
+10% -15%
120 275 34.5 22.5 180 289 ±5% 16 13.4 34
125 230 ±16.8% 66 13.1 52 180 132 ±10% 15 13.8 40
247 432 +3.75%-16.25% 15.5 15.2 61
125 230 not 150 10-14 22
13 250 300 +11.2%-17.6% 15 28.6 70
180 275 known 66 22.2 38
290 420 ±10% 15 15.7 43
255 230 ±15% 16.5 14.8 43
Table 5.6: Impedances of two winding distribution 307 432 +3.75%-16.25% 15.5 15.3 67
transformers - Primary voltage >200kV/ 346 435 +5%-15% 17.5 16.4 81
420 432 +5.55%-14.45% 22 16 87
437.8 144.1 +10.8%-21.6% 21 14.6 50
450 132 +10% 19 14 49
600 420 ±11.25% 21 16.2 74
MVA Primary Primary Secondary Secondary Tertiary Z% X/R
kV Taps kV Taps kV HV/LV ratio 716 525 ±10% 19 15.7 61
100 66 - 33 - - 107 28 721 362 +6.25%- 22 15.2
180 275 132 ±15% 13 15.5 55 736 245 +13
7 %75%
-13% 22 15.5 73
240 400 _ 132 +15% -5% 13 20.2 83 900 525 +7%-13% 23 15.7 67
240 400 132 + 15%-5% 13 20.0 51 (a) Three-phas units
240 400 - 132 + 15%-5% 13 20.0 61
MVA/ kV Primary Seconda Z% X/R
250 400 - 132 + 15%-5% 13 10-13 50 phase Taps ry kV HV/LV ratio
500 400 - 132 +0%-15% 22 14.3 51 266.7 432/V3 +6.67%-13.33% 23.5 15.8 92
750 400 - 275 - 13 12.1 90 266.7 432/V3 +6.6%-13.4% 23.5 15.7 79
1000 400 - 275 - 13 15.8 89 277 515/V3 ±5% 22 16.9 105
1000 400 - 275 - 33 17.0 91 375 525/V3 +6.66%-13.32% 26 15 118
333.3 50OV3 ±10% 23OV'3 22 18.2 101 375 420/V3 +6.66%-13.32% 26 112
Table 5.8: Autotransformer data (b) Single-phase units
Table 5.7: Impedances of generator transformers
5 . 1 8 OVERHEAD L I N E S AND CABLES between conductors becomes Zm. However, for rigorous
calculations a detailed treatment is necessary, with
In this section a description of common overhead lines
account being taken of the spacing of a conductor in
and cable systems is given, together with tables of their
relation to its neighbour and earth.
important characteristics. The formulae for calculating
the characteristics are developed to give a basic idea of
the factors involved, and to enable calculations to be 5 .1 9 CALCULATION OF S E R I E S IMPEDANCE
made for systems other than those tabulated. The self impedance of a conductor with an earth return
A transmission circuit may be represented by an and the mutual impedance between two parallel
equivalent or T network using lumped constants as conductors with a common earth return are given by the
shown in Figure 5.15. Z is the total series impedance Carson equations:
(R +jX}L and Y is the total shunt admittance (G +jB)L,
where L is the circuit length. The terms inside the
brackets in Figure 5.15 are correction factors that allow
for the fact that in the actual circuit the parameters are
distributed over the whole length of the circuit and not
lumped, as in the equivalent circuits.
With short lines it is usually possible to ignore the shunt ..Equation 5.11
admittance, which greatly simplifies calculations, but on
longer lines it must be included. Another simplification where:
that can be made is that of assuming the conductor R = conductor a.c. resistance (ohms/km)
configuration to be symmetrical. The self-impedance of dc = geometric mean radius of a single conductor
each conductor becomes Zp, and the mutual impedance D = spacing between the parallel conductors
f = system frequency
(c) T Equivalent
..Equation 5.12
Note: Z and Tin (b) and (c) are the total series where Zp and Zm are given by Equation 5.11.
impedance and shunt admittance respectively.
Substituting Equation 5.11 in Equation 5.12 gives:
Z=(R+jX)L and Y=(G+jB)L where L is the circuit length.
...Equation 5.14
...Equation 5.18
...Equation 5.16
where D is the spacing between conductors a and b and It should be noted that the logarithmic terms above are
D' is the spacing between conductor b and the image of similar to those in Equation 5.13 except that r is the
conductor a as shown in Figure 5.14. actual radius of the conductors and D' is the spacing
between the conductors and their images.
Since the capacitance C=q/V and the capacitive
reactance it follows that the self and mutual Again, where the conductors are not symmetrically
capacitive reactanc e of the conductor system in Figure spaced but transposed, Equation 5.18 can be re-written
5.16 can be obtained directly from Equations 5.15 and making use of the geometric mean distance between
5.16. Further, as leakage can usually be neglected, the conductors, and giving the distance of each
self and mutual shunt impedances Z' p and Z' m in conductor above ground, that is, h a i h 2 , h c , as follows:
megohm-km at a system frequency of 50Hz are:
...Equation 5.19
...Equation 5.17
Equation 5.20
where:
and so on.
The equation required for the calculation of shunt
voltage drops is identical to Equation 5.20 in form,
except that primes must be included, the impedances
being derived from Equation 5.17.
Table 5. 10; Sequence self and mutual impedances
for various lines
...Equation 5.21
For example:
and so on.
So Equation 5.20 can be simplified while still taking account ...Equation 5.23
of the effect of the earth wire by deleting the fourth row and
fourth column and substituting Jaa for Zaa,Jab for Zab, and so The development of these equations for double circuit
on, calculated using Equation 5.21. The single circuit line lines with two earth wires is similar except that more
with a single earth wire can therefore be replaced by an terms are involved.
equivalent single circuit line having phase self and mutual
The sequence mutual impedances are very small and can
impedances Jaa , Jab and so on.
usually be neglected; this also applies for double circuit
It can be shown from the symmetrical component theory lines except for the mutual impedance between the zero
given in Chapter 4 that the sequence voltage drops of a sequence circuits, namely (Z00' = Z0'0). Table 5.10 gives
general three-phase circuit are: typical values of all sequence self and mutual impedances
some single and double circuit lines with earth wires. All
conductors are 400mm2 ACSR, except for the 132kV
double circuit example where they are 200mm2.
And, from Equation 5.20 modified as indicated above and Consider an earthed, infinite busbar source behind a
Equation 5.22, the sequence impedances are: length of transmission line as shown in Figure 5.19(a).
An earth fault involving phase A is assumed to occur at
F. If the driving voltage is E and the fault current is Ia
distance relay applications because the phase and earth
fault relays are set to measure Z2 and are compensated
for the earth return impedance (Z0-Z1)/3.
It is cu s tomary to quote the imp edances of a
transmission circuit in terms of Z1 and the ratio Zo/Z1,
since in this form they are most directly useful. By
definition, the positive sequence impedance Z1 is a
function of the conductor spacing and radius, whereas
the Zo/Z1 ratio is dependent primarily on the level of
earth resistivity p. Further details may be found in
Chapter 12.
(a) Actual circuit
5.23 CABLE C IRCU IT S
The basic formulae for calculating the series and shunt
impedances of a transmission circuit, Equations 5.11 and
5.17 may be applied for evaluating cable parameters;
si nce the condu ctor configurat ion i s normally
symmetrical GMD and GMR values can be used without
risk of appreciable errors. However, the formulae must
be modified by the inclusion of empirical factors to take
account of sheath and screen effects. A useful general
reference on cable formulae is given in reference [5.4];
(b) Equivalent circuit
more detailed information on particular types of cables
Figure 5.19: Three-phase equivalent should be obtained direct from the manufacturers. The
of a transmission circuit
equivalent circuit for determining the positive and
then the earth negative sequence series impedances of a cable is shown
fault impedance is Ze . From symmetrical component in Figure 5.20. From this circuit it can be shown that:
theory (see Chapter 4):
thus
since, as shown, Z1 = Z2 for a
...Equation 5.24
transmission circuit. From
Equations 5.12, Z1=Zp-Zm and Z0=Zp+2Zm. Thus, where Rc Rs are the core and sheath (screen] resistances
substituting these values in the above equation gives per unit length, Xc and Xs core and sheath (screen)
Ze=Zp. This relation is physically valid because Zp is the reactances per unit length and Xcs the mutual reactance
self-impedance of a single conductor with an earth return. between core and sheath (screen) per unit length. Xcs is
Similarly, for a phase fault between phases B and C at F: in general equal to Xs.
The zero sequence series impedances are obtained
directly using Equation 5.11 and account can be taken of
the sheath in the same way as an earth wire in the case
where is the voltage between phases and 2Z is the
of an overhead line.
impedance of the fault loop.
The shunt capacitances of a sheathed cable can be
Making use of the above relations a transmission circuit
calculated from the simple formula:
may be represented, without any loss in generality, by
the equivalent of Figure 5.19(b), where Z1 is the phase
impedance to the fault and (ZO-Z1 )/3 is the impedance
of the earth path, there being no mutual impedance
between the phases or between phase and earth. The
equivalent is valid for single and double circuit lines ...Equation 5.2S
except that for double circuit lines there is zero sequence where d is the overall diameter for a round conductor, T
mutual impedance, hence Z0=(Z00-Z0'0). core insulation thickness and e permittivity of dielectric.
The equivalent circuit of Figure 5.19(b) is valuable in When the conductors are oval or shaped, an equivalent
diameter d' may be used where d'=(l/pi)x periphery of Number of Strands 6MR
conduc tor. No simple f ormul a exis ts for belted o r 0.726r
7
unscreened cables, but an empirical formula that gives 19 0.758r
reasonable results is: 37 0.768r
61 0.772r
91 0.774r
127 0.776r
...Equation 5.26 169 0.776r
Solid 0 . 7 79r
where G is a geometric factor which is a function of core and
belt insulation thickness and overall conductor diameter. Table 5.11: GMR for stranded copper, aluminium and aluminium
alloy conductors (r = conductor radius)
5 . 2 4 O V E RH E A D L I N E A N D C A BL E D AT A
The follo wing tables contain t ypical data on overhead Numb er of La yers Number of Al Str an ds
lines and cables that can be used in conjunction with the 1 6 0.5r*
various e qua t i ons qu ote d in this text. It i s n ot inten ded 1 12 0.75r*
2 18 0.776r
that this da ta should replace that supplied by
2 24 0.803 r
manufact urers. Wher e th e resu lts of ca lculations are 2 26 0.812r
important reliance should not be plac ed on the d ata in 2 30 0.826r
these Tables and data should be sourced directly from a 2 32 0.833r
3 36 0.778r
manufacturer/supplier. 3 45 0.794r
3 48 0.799r
At the conceptual design stage, initial selection of overhead
3 54 0.81 r
line conductor size will be determined by four factors: 3 66 0.827r
a. m aximum lo ad to be carrie d in MV A 4 72 0.789r
4 76 0.793r
b. length of line
4 84 0.801 r
c. cond uctor mater ial and h ence ma ximum * - Indicative values only, since GMR for single layer conductors is affected by cyclic
temperature magnetic flux, which depends on various factors.
d. cost of losses Table S. 12: GMR for aluminium conductor steel reinforced
(ACSR) (r = conductor radius)
Table 5.2 1 gi ves indicative deta ils o f the c apab ility o f
various sizes of overhead lines using the above factors,
for AAAC and ACSR conductor materials. It is based on
commonly used standards for voltage drop and ambient
temperature. Since these factors may not be appropriate
for any particular proj ect, the Table sh ould o nly be used
as a guid e for init ial siz ing, with a ppropriate ly d etailed
calculatio ns ca rried out to arrive at a final pr opos al.
53.5 7 3.12 9.35 0.342 Raven 6 3.37 1 3.37 53.5 8.9 62.4 10.11 0.536
67.4 7 3.50 10.52 0.271 Quail 3.78 3.78 67.4 11.2 78.6 11.34 0.426
6 1
85.0 7 3.93 11.79 0.215
Pigeon 6 4.25 1 4.25 85.0 14.2 99.2 12.75 0.337
107.2 7 4.42 13.26 0.171
Penguin 6 4.77 1 4.77 107.2 17.9 125.1 14.31 0.268
126.G 19 2.91 14.58 0.144
152.0 19 3.19 15.98 0.120 Partridge 26 2.57 7 2 135.2 22.0 157.2 16,28 0.214
177.3 19 3.45 17.25 0.103 Ostrich 26 2.73 7 2.21 152.0 26.0 178.9 17.28 0.191
202.7 19 3.69 18.44 0.090
Merlin 18 3.47 1 3.47 170.5 9.5 179.9 17.35 0.169
228.0 37 2.80 19.61 0.080
Lark 30 2.92 7 2.92 201.4 46.9 24S.3 20.44 0.144
253.3 37 2.95 20.65 0.072
Hawk 26 3.44 7 2.67 241.7 39.2 280.9 21.79 0.120
278.7 37 3.10 21.67 0.066
304.3 3.23 22.63 0.060 Dove 26 3.72 7 2.89 282.0 45.9 327.9 23.55 0.103
37
329.3 61 2.62 23.60 0.056 Teal 30 3.61 19 2.16 306,6 69.6 376.2 25.24 0.095
354.7 61 2.72 24.49 0.052 Swift 3.38 3.38 322.3 331.2 23.62 0.089
36 1 9.0
380.0 61 2.82 25.35 0.048
Tern 45 3.38 7 2.25 402.8 27.8 430.7 27.03 0,072
405.3 61 2.91 26.19 0.045
Canary 54 3.28 7 3.28 456.1 59.1 515.2 29.52 0.064
456.0 61 3.09 27.79 0.040
506.7 61 . 3.25 29.26 0.036 Curlew 54 3.52 7 3.52 523.7 68.1 591.8 31.68 0.055
(a) ASTM Standards Finch 54 3.65 19 2.29 565.0 78.3 643.3 33.35 0.051
CANNA75.5
12 2 7 2 37.7 22.0 59.7 10 0.765
- (a) ASTM
12 2.25 7 2.25 47.7 27.8 75.5 11.25 0.604
CANNA 93.3 2.5 7 2.5 58.9 34.4 93.3 12.5 0.489
12 o
CANNA 116.2 94.2 22.0 116.2 0.306
Standard Designation No. of A! Wire Sectional Overall RDC at 20 C
30 2 7 2 14 (Ohm/km)
Strands diameter area diameter
CROCUS 116.2 2 7 2 94.2 22.0 116.2 14 0.306
30 (mm) |mm2) (mm)
CANNA 147.1 2.25 7 2.25 119.3 27.8 147.1 15.75 0.243
30
BS 3242 Box 7 1.85 18.8 5.6 1.750
CROCUS 181.6 2.5 7 2.5 147.3 34.4 181.6 17.5 0.197
30 BS 3242 Acacia 7 2.08 23.8 6.2 1.384
CROCUS 228 2.8 7 2.8 184.7 43.1 227.8 19.6 0.157
30
BS 3242 Almond 7 2.34 30.1 7.0 1.094
CROCUS 297 2.8 19 2.25 221.7 75.5 297.2 22.45 0.131
36
BS 3242 Cedar 7 2.54 35.5 7.6 0.928
CANNA 288 3.15 7 3.15 233.8 54.6 288.3 22.05 0.124
30
BS 3242 Fir 7 2.95 47.8 8.9 0.688
CROCUS 288 3.15 7 3.15 233.8 54.6 288.3 22.05 0.124
30 BS 3242 Hazel 7 3.3 59.9 9.9 0.550
CROCUS 412 3.6 19 325.7 86.0 411.7 26.4 0.089
32 2.4
BS 3242 Pine 7 3.61 71.6 10.8 0.460
CROCUS 612 3.13 19 2.65 507.8 104.8 612.6 32.03 0.057
66 BS 3242 Willow 7 4.04 89.7 12.1 0.367
CROCUS 865 3.72 19 3.15 717.3 148.1 865.4 38.01 0.040
66 BS 3242 - 7 4.19 96.5 12.6 0.341
(d) to NF C34-120 BS 3242 1 4.45 108.9 13.4 0.302
Table 5. 14: Overhe ad line conductor data - aluminium BS 3242 Oak 1 4.65 118.9 14.0 0.277
conductors steel reinforced (ACSR). BS 3242 Mullberry 19 3.18 150.9 15.9 0.219
BS 3242 Ash 19 3.48 180.7 17.4 0.183
BS 3242 Elm 19 3.76 211.0 18.8 0.157
BS 3242 Poplar 37 2.87 239.4 20.1 0.139
BS 3242 Sycamore 37 3.23 303.2 22.6 0.109
BS 3242 Upas 37 3.53 362.1 24.7 0.092
BS 3242 Yew 37 4.06 479.0 28.4 0.069
BS 3242 Totara 37 4.14 498.1 29.0 0.067
BS 3242 Rubus 61 3.5 586.9 31.5 0.057
BS 3242 Araucaria 61 4.14 821.1 28.4 0.040
Standard Strands diameter area diameter at 20 o C Strands di ameter area diam eter at 20°C
2
(mm) (mm ) (mm) (Ohm/km) (mm) (mm') (mm) ( Ohm/km)
CSAC49.1-M87 10 7 1.45 11.5 4.3 2.863 NFC34-125 ASTER 22 7 2 22.0 6.0 1.497
CSAC49.1-M87 16 7 1.83 18.4 5.5 1.788 NFC34-125 ASTER 34-4 7 2.5 34.4 7.5 0.9 G8
CSAC49.1-M87 25 7 2.29 28.8 6.9 1.142 NFC34-125 ASTER 54-6 7 3.15 54.6 9.5 0.604
CSAC49.1-M87 40 7 2.89 46.0 8.7 0.716 NFC34-125 ASTER 75-5 19 2.25 75.5 11.3 0.438
CSAC49.1-M87 63 7 3.63 72.5 10.9 0.454 NFC34-125 ASTER 93,3 19 2.5 93.3 12.5 0.355
CSAC49.1-M87 100 19 2.78 115.1 13.9 0.287 NFC34-125 ASTER 117 19 2.8 117.0 14.0 0.283
CSAC49.1-M87 125 19 3.1 143.9 15.5 0.230 NFC34-125 ASTER 148 19 3.15 148.1 15.8 0.223
CSAC49.1-M87 3.51 184.2 17.6 0.180 NFC34-125 ASTER 181- 37 2.5 181.6 17.5 0.183
160 19 6
CSAC49.1-M87 200 19 3.93 230.2 19.6 0.144 NFC34-125 ASTER 228 37 2.8 227.8 19.6 0.146
287.7 NFC34-125 ASTER 288 37 3.15 288.3 22.1 0.115
CSAC49.1-M87 250 19 4.39 22.0 0.115
CSAC49.1-M87 315 37 3.53 362.1 24.7 0.092 NFC34-125 ASTER 366 37 3.55 366.2 24.9 0.091
CSAC49.1-M87 400 37 3.98 460.4 27.9 0.072 NFC34-125 ASTER 570 61 3.45 570.2 31.1 0.058
CSAC49.1-M87 450 37 4.22 517.9 29.6 0.064 NFC34-125 ASTER 851 91 3.45 850.7 38.0 0.039 I
CSAC49.1-M87 500 37 4.45 575.5 31.2 0.058 NFC34-125 ASTER 1144 91 4 1143.5 44.0 0.029
C5AC49.1-M87 560 37 4.71 644.5 33.0 0.051 NFC34-125 ASTER 1600 127 4 1595.9 52.0 0.021 |
DIN 48206 70/12 26 1.85 7 1.44 69.9 11.4 81.3 11.7 0.479
DIN 48206 95/15 26 2.15 7 1.67 94.4 15.3 109.7 13.6 0.355
DIN 48206 125/30 30 2.33 7 2.33 127.9 29.8 157.8 16.3 0.262
DIN 48206 150/25 26 2.7 7 2.1 148.9 24.2 173.1 17.1 0.225
DIN 48206 170/40 30 2.7 7 2.7 171.8 40.1 211.8 18.9 0.195
DIN 48206 185/30 26 3 7 2.33 183.8 29.8 213.6 19 0.182
DIN 48206 210/50 30 3 7 3 212.1 49.5 261.5 21 0.158
DIN 48206 230/30 24 3.5 7 2.33 230.9 29.8 260.8 21 0.145
DIN 48206 265/35 24 3.74 7 2.49 263.7 34.1 297.7 22.4 0.127
DIN 48206 305/40 54 2.68 7 2.68 304.6 39.5 344.1 24.1 0.110
DIN 48206 380/50 54 3 7 3 381.7 49.5 431.2 27 0.088
DIN 48206 450/40 48 3.45 7 2.68 448.7 39.5 488.2 28.7 0.075
DIN 48206 560/50 48 3.86 7 3 561.7 49.5 611.2 32.2 0.060
DIN 48206 680/85 54 4 19 2.4 678.6 86.0 764.5 36 0.049
(b) DIN
Standard Designation Strar dia ding and wire Sectional area Total Approximate RDC at20°C
Alloy meter (mm) (mm2] area overall diameter (ohm/km)
(mm'] (mm)
Steel Alloy Steel
63 kV 132
kV
Sectional RDC RA 3..3kV 6..6kV 11kV 22kV 33kV Flat Double triangle Double Double e Flat
area of (20oC) C 50Hz
circuit vertical vertical triangl
e circui
15.3 1.8771 1.877 0.391 0.405 0.415 0.429 0.441 8.8 0.499 7.7 0.508 7.5 0.515 7.4 0.537 7.1 0.523 7.3 0.552 6.9
21.2 1.3557 1.356 0.381 0.395 0.405 0.419 0.430 9.0 0.488 7.8 0.498 7.7 0.505 7.6 0.527 7.2 0.513 7.4 0.542 7.0
23.9 1.2013 1.201 0.376 0.390 0.401 0.415 0.426 9.1 0.484 7.9 0.494 7.8 0.501 7.6 0.522 7.3 0.509 7.5 0.537 7.1
26.2 1.0930 1.093 0.374 0.388 0.398 0.412 0.424 9.2 0.482 8.0 0.491 7.8 0.498 7.7 0.520 7.3 0.506 7.5 0.535 7.1
28.3 1.0246 1.025 0.352 0.366 0.377 0.391 0.402 9.4 0.460 8.2 0.470 8.0 0.477 7.8 0.498 7.5 0.485 7.7 0.513 7.3
33.6 0.8535 0.854 0.366 0.380 0.390 0.404 0.416 9.4 0.474 8.1 0.484 7.9 0.491 7.8 0.512 7.5 0.499 7.7 0.527 7.2
37.7 0.7647 0.765 0.327 0.341 0.351 0.365 0.376 9.7 0.435 8.4 0.444 8.2 0.451 8.1 0.473 7.7 0.459 7.9 0.488 7.4
42.4 0.6768 0.677 0.359 0.373 0.383 0.397 0.409 9.6 0.467 8.3 0.476 8.1 0.483 7.9 0.505 7.6 0.491 7.8 0.520 7.3
44.0 0.6516 0.652 0.320 0.334 0.344 0.358 0.369 9.9 0.427 8.5 0.437 8.3 0.444 8.2 0.465 7.8 0.452 8.0 0.481 7.5
47.7 0.6042 0.604 0.319 0.333 0.344 0.358 0.369 9.9 0.427 8.5 0.437 8.3 0.444 8.2 0.465 7.8 0.452 8.1 0.480 7.6
51.2 0.5634 0.564 0.317 0.331 0.341 0.355 0.367 10.0 0.425 8.6 0.434 8.4 0.441 8.2 0.463 7.9 0.449 8.1 0.478 7.6
58.9 0.4894 0.490 0.313 0.327 0.337 0.351 0.362 10.1 0.421 8.7 0.430 8.5 0.437 8.3 0.459 7.9 0.445 8.2 0.474 1.1
63.1 0.4545 0.455 0.346 0.360 0.371 0.385 0.396 9.9 0.454 8.5 0.464 8.3 0.471 8.2 0.492 7.8 0.479 8.0 0.507 7.6
67.4 0.4255 0.426 0.344 0.358 0.369 0.383 0.394 10.0 0.452 8.5 0.462 8.3 0.469 8.2 0.490 7.8 0.477 8.1 0.505 7.6
73.4 0.3930 0.393 0.306 0.320 0.330 0.344 0.356 10.3 0.414 8.8 0.423 8.6 0.430 8.5 0.452 8.1 0.438 8.3 0.467 7,8
79.2 0.3622 0.362 0.339 0.353 0.363 0.377 0.389 10.1 0.447 8.7 0.457 8.4 0.464 8.3 0.485 7.9 0.472 8.2 0.500 7.6
85.0 0.3374 0.338 0.337 0.351 0.361 0.375 0.387 10.2 0.445 8.7 0.454 8.5 0.461 8.4 0.483 7.9 0.469 8.2 0.498 7.7
94.4 0.3054 0.306 0.302 0.316 0.327 0.341 0.352 10.3 0.410 8.8 0.420 8.6 0.427 8.4 0.448 8.0 0.435 8.3 0.463 7,8
105.0 0.2733 0.274 0.330 0.344 0.355 0.369 0.380 10.4 0.438 8.8 0.448 8.6 0.455 8.5 0.476 8.1 0.463 8.3 0.491 7,8
121.6 0.2371 0.237 0.294 0.308 0.318 0.332 0.344 10.6 0.402 9.0 0.412 8.8 0.419 8.6 0.440 8.2 0.427 8.4 0.455 7.9
127-9 0.2254 0.226 0.290 0.304 0.314 0.328 0.340 10.7 0.398 9.0 0.407 8.8 0.414 8.7 0.436 8.2 0.422 8.5 0.451 8.0
131.2 0.2197 0.220 0.289 0.303 0.313 0.327 0.339 10.7 0.397 9.1 0.4O7 8.8 0.414 8.7 0.435 8.3 0.421 8.5 0.450 8.0
135.2 0.2133 0.214 0.297 0.311 0.322 0.336 0.347 10.5 0.405 9.0 0.415 8.8 0.422 8.6 0.443 8.2 0.430 8.4 0.458 7.9
148.9 0.1937 0.194 0.288 0.302 0.312 0.326 0.338 10.8 0.396 9.1 0.406 8.9 0.413 8.7 0.434 8.3 0.420 8.6 0.449 8,0
158.7 0.1814 0.182 0.292 0.306 0.316 0.330 0.342 10.7 0.400 9.1 0.410 8.9 0.417 8.7 0.438 8.3 0.425 8.5 0.453 8.0
170.5 0.1691 0.170 0.290 0.304 0.314 0.328 0.340 10.8 0.398 9.1 0.407 8.9 0.414 8.8 0.436 8.3 0.422 8.6 0.451 8.0
184.2 0.1565 0.157 0.287 0.302 0.312 0.326 0.337 10.9 0.395 9.2 0.4O5 9.0 0.412 8.8 0,433 8.4 0.420 8.6 0.449 8.1
201.4 0.1438 0.144 0.280 0.294 0.304 0.318 0.330 11.0 0.388 9.3 0.398 9.1 0.405 8.9 0.426 8.5 0.412 8.8 0.441 8.2
210.6 0.1366 0.137 0.283 0.297 0.308 0.322 0.333 11.0 0.391 9.3 0.401 9.1 0.408 8.9 0.429 8.4 0.416 8.7 0.444 8.1
221.7 0.1307 0.131 0.274 0.288 0.298 0.312 0.323 11.3 0.381 9.5 0.391 9.3 0.398 9.1 0.419 8.6 0.406 8.9 0.435 8.3
230.9 0.1249 0.126 0.276 0.290 0.300 0.314 0.326 11.2 0.384 9.4 0.393 9.2 0.400 9.0 0.422 8.6 0.408 8.9 0.437 8.3
241.7 0.1193 0.120 0.279 0.293 0.303 0.317 0.329 11.2 0.387 9.4 0.396 9.2 0.403 9.0 0.425 8.5 0.411 8.8 0.440 8.2
263.7 0.1093 0.110 0.272 0.286 0.296 0.310 0.321 11.3 0.380 9.5 0.389 9.3 0.396 9.1 0.418 8.6 0.404 8.9 0.433 8.3
282.0 0.1022 0.103 0.274 0.288 0.298 0.312 0.324 11.3 0.382 9.5 0.392 9.3 0.399 9.1 0.420 8.6 0.406 8.9 0.435 8.3
306.6 0.0945 0.095 0.267 0.281 0.291 0.305 0.317 11.5 0.375 9.7 0.384 9.4 0.391 9.2 0.413 8.7 0.399 9.1 0.428 8,4
322.3 0.0895 0.090 0.270 0.284 0.294 0.308 0.320 11.5 0.378 9.6 Q.387 9.4 0.394 9.2 0.416 8.7 0.402 9.0 0.431 8.4
339.3 0.085 0.086 0.265 0.279 0.289 0.303 0.315 11.6 0.373 9.7 0.383 9.5 0.390 9.3 0.411 8.8 0.398 9.1 0.426 8.5
362.6 0.0799 0.081 0.262 0.276 0.286 0.300 0.311 11.7 0.369 9.8 0.379 9.6 0.386 9.4 0.408 8.9 0.394 9.2 0.423 8.5
386.0 0.0747 0.076 0.261 0.275 0.285 0.299 0.311 11.8 0.369 9.8 0.379 9.6 0.386 9.4 0.407 8.9 0.393 9.2 0.422 8.6
402.8 0.0719 0.073 0.261 0.275 0.285 0.299 0.310 11.8 0.368 9.9 0.378 9.6 0.385 9.4 0.4O7 8.9 0.393 9.2 0.422 8.6
428.9 0.0671 0.068 0.267 0.281 0.291 0.305 0.316 11.5 0.374 9.7 0.384 9.4 0.391 9.2 0.413 8.7 0.399 9.0 0.428 8.4
443.7 0.0642 0.066 0.257 0.271 0.281 0.295 0.306 11.9 0.364 10.0 0.374 9.7 0.381 9.5 0.402 9.0 0.389 9.3 0.418 8.7
456.1 0.0635 0.065 0.257 0.271 0.281 0.295 0.307 12.0 0.365 10.0 0.374 9.7 0.381 9.5 0.403 9.0 0.389 9.3 0.418 8.7
483.4 0.0599 0.061 0.255 0.269 0.279 0.293 0.305 12.0 0.363 10.0 0.372 9.8 0.379 9.6 0.401 9.0 0.387 9.4 0.416 8.7
494.4 0.0583 0.060 0.254 0.268 0.279 0.293 0.304 12.1 0.362 10.0 0.372 9.8 0.379 9.6 0.400 9.0 0.387 9.4 0.415 8.7
510.5 0.0565 0.058 0.252 0.266 0.277 0.291 0.302 12.1 0.360 10.1 0.370 9.8 0.377 9.6 0.398 9.1 0.385 9.4 0.413 8.7
523.7 0.0553 0.057 0.252 0.266 0.277 0.291 0.302 12.1 0.360 10.1 0.3/0 9.8 0.377 9.6 0.398 9.1 0.385 9.4 0.413 8.7
Table 5.17: Feeder circuits data - overhead lines
XAC at 50 Hz XAC at 50 Hz and shunt
capacitance
Sectiona RDC RACat 3.3kV 6.6kV 11 kV 22kV 33kV 6 6kV Triangle Double 132kV Flat
(20°C) Flat circuit Double Double
area of 50Hz vertical circuit
vertical triangle
15.3 1.8771 1.877 0.469 0.486 0.498 0.515 0.529 8.8 0.598 7.7 0.610 7.5 0.619 7.4 0.644 7.1 0.628 7.3 0.662 6.9
21.2 1.3557 1.356 0.457 0.474 0.486 0.503 0.516 9.0 0.586 7.8 0.598 7.7 0.606 7.6 0.632 7.2 0.616 7.4 0.650 7.0
23.9 1.2013 1.201 0.452 0.469 0.481 0.498 0.511 9.1 0.581 7.9 0.593 7.8 0.601 7.6 0.627 7.3 0.611 7.5 0.645 7.1
26.2 1.0930 1.093 0.449 0.466 0.478 0.495 0.508 9.2 0.578 8.0 0.590 7.8 0.598 7.7 0.624 7.3 0.608 7.5 0.642 7.1
28.3 1.0246 1.025 0.423 0.440 0.452 0.469 0.483 9.4 0.552 8.2 0.564 8.0 0.572 7.8 0.598 7.5 0.582 7.7 0.616 7.3
33.6 0.8535 0.854 0.439 0.456 0.468 0.4B5 0.499 9.4 0.569 8.1 0.580 7.9 0.589 7.8 0.614 7.5 0.598 7.7 0.633 7.2
37.7 0.7647 0.765 0.392 0.409 0.421 0.438 0.452 9.7 0.521 8.4 0.533 8.2 0.541 8.1 0.567 7.7 0.551 7.9 0.585 7.4
42.4 0.6768 0.677 0.431 0.447 0.460 0.477 0.490 9.6 0.560 8.3 0.572 8.1 0.580 7.9 0.606 7.6 0.589 7.8 0.624 7.3
44.0 0.6516 0.652 0.384 0.400 0.413 0.429 0.443 9.9 0.513 8.5 0.525 8.3 0.533 8.2 0.559 7.8 0.542 8.0 0.577 7.5
47.7 0.6042 0.604 0.383 0.400 0.412 0.429 0.443 9.9 0.513 8.5 0.524 8.3 0.533 8.2 0.558 7.8 0.542 8.1 0.576 7.6
51.2 0.5634 0.564 0.380 0.397 0.409 0.426 0.440 10.0 0.510 8.6 0.521 8.4 0.530 8.2 0.555 7.9 0.539 8.1 0.573 7.6
58.9 0.4894 0.490 0.375 0.392 0.404 0.421 0.435 10.1 0.505 8.7 0.516 8.5 0.525 8.3 0.550 7.9 0.534 8.2 0.568 7.7
63.1 0.4545 0.455 0.416 0.432 0.445 0.462 0.475 9.9 0.545 8.5 0.557 8.3 0.565 8.2 0.591 7.8 0.574 8.0 0.609 7.5
67,4 0.4255 0.426 0.413 0.430 0.442 0.459 0.473 10.0 0.543 8.5 0.554 8.3 0.563 8.2 0.588 7.8 0.572 8.1 0.606 7.6
73.4 0.3930 0.393 0.367 0.384 0.396 0.413 0.427 10.3 0.496 8.8 0.508 8.6 0.516 8.5 0.542 8.1 0.526 8.3 0.560 7.8
79.2 0.3622 0.362 0.407 0.424 0.436 0.453 0.467 10.1 0.536 8.7 0.548 8.4 0.556 8.3 0.582 7.9 0.566 8.2 0.600 7.6
85.0 0.3374 0.338 0.404 0.421 0.433 0.450 0.464 10.2 0.534 8.7 0.545 8.5 0.554 8.4 0.579 7.9 0.563 8.2 0.598 7.7
94.4 0.3054 0.306 0.363 0.380 0.392 0.409 0.423 10.3 0.492 8.8 0.504 8.6 0.512 8.4 0.538 8.0 0.522 8.3 0.556 7.8
105.0 0.2733 0.274 0.396 0.413 0.426 0.442 0.456 10.4 0.526 8.8 0.537 8.6 0.546 8.5 0.572 8.1 0.555 8.3 0.590 7.8
121.6 0.2371 0.238 0.353 0.370 0.382 0.399 0.413 10.6 0.482 9.0 0.494 8.8 0.502 8.6 0.528 8.2 0.512 8.4 0.546 7.9
127.9 0.2254 0.226 0.348 0.365 0.377 0.394 0.408 10.7 0.477 9.0 0.489 8.8 0.497 8.7 0.523 8.2 0.507 8.5 0.541 8.0
131.2 0.2197 0.220 0.347 0.364 0.376 0.393 0.407 10.7 0.476 9.1 0.488 8.8 0.496 8.7 0.522 8.3 0.506 8.5 0.540 8.0
135.2 0.2133 0.214 0.357 0.374 0.386 0.403 0.416 10.5 0.486 9.0 0.498 8.8 0.506 8.6 0.532 8.2 0.516 8.4 0.550 7.9
148.9 0.1937 0.194 0.346 0.362 0.375 0.392 0.405 10.8 0.475 9.1 0.487 8.9 0.495 8.7 0.521 8.3 0.504 8.6 0.539 8.0
158 7 0.1814 0.182 0.351 0.367 0.380 0.397 0.410 10.7 0.480 9.1 0.492 8.9 0.500 8.7 0.526 8.3 0.509 8.5 0.544 8.0
170.5 0.1691 0.170 0.348 0.365 0.377 0.394 0.408 10.8 0.477 9.1 0.489 8.9 0.497 8.8 0.523 8.3 0.507 8.6 0.541 8.0
184.2 0.1565 0.157 0.345 0.362 0.374 0.391 0.405 10.9 0.474 9.2 0.486 9.0 0.494 8.8 0.520 8.4 0.504 8.6 0.538 8.1
201.4 0.1438 0.145 0.336 0.353 0.365 0.382 0.396 11.0 0.466 9.3 0.477 9.1 0.486 8.9 0.511 8.5 0.495 8.8 0.529 8.2
210.6 0.1366 0.137 0.340 0.357 0.369 0.386 0.400 11.0 0.469 9.3 0.481 9.1 0.489 3.9 0.515 8.4 0.499 8.7 0.533 8.1
221.7 0.1307 0.132 0.328 0345 0.357 0.374 0.388 11.3 0.458 9.5 0.469 9.3 0.478 9.1 0.503 8.6 0.487 8.9 0.522 8.3
230.9 0.1249 0.126 0.331 0.348 0.360 0.377 0.391 11.2 0.460 9.4 0.472 9.2 0.480 9.0 0.506 8.6 0.490 8.9 0.524 8.3
241.7 0.1193 0.120 0.335 0.351 0.364 0.381 0.394 11.2 0.464 9.4 0.476 9.2 0.484 9.0 0.510 8.5 0.493 8.8 0.528 8.2
263.7 0.1093 0.110 0.326 0.343 0.355 0.372 0.386 11.3 0.455 9.5 0.467 9.3 0.476 9.1 0.501 8.6 0.485 8.9 0.519 8.3
282.0 0.1022 0.103 0.329 0.346 0.358 0.375 0.389 11.3 0.458 9.5 0.470 9.3 0.478 9.1 0.504 8.6 0.488 8.9 0.522 8.3
306.6 0.0945 0.096 0.320 0.337 0.349 0.366 0.380 11.5 0.450 9.7 0.461 9.4 0.470 9.2 0.495 8.7 0.479 9.1 0.514 8.4
322.3 0.0895 0.091 0.324 0.341 0.353 0.370 0.384 11.5 0.453 9.6 0.465 9.4 0.473 9.2 0.499 8.7 0.483 9.0 0.517 8.4
339.3 0.0850 0.086 0.318 0.335 0.347 0.364 0.378 11.6 0.448 9.7 0.459 9.5 0.468 9.3 0.493 8.8 0.477 9.1 0.511 8.5
362.6 0.0799 0.081 0.314 0.331 0.343 0.360 0.374 11.7 0.443 9.8 0.455 9.6 0.463 9.4 0.439 8.9 0.473 9.2 0.507 8.5
38G.0 0.0747 0.076 0.313 0.330 0.342 0.359 0.373 11.8 0.443 9.8 0.454 9.6 0.463 9.4 0.488 8.9 0.472 9.2 0.506 8.6
402.8 0.0719 0.074 0.313 0.330 0.342 0.359 0.372 11.8 0.442 9.9 0.454 9.6 0.462 9.4 0.488 8.9 0.472 9.2 0.506 8.6
428.9 0.0671 0.069 0.320 0.337 0.349 0.366 0.380 11.5 0.449 9.7 0.461 9.4 0.469 9.2 0.495 8.7 0.479 9.0 0.513 8.4
443.7 0.0642 0.066 0.308 0.325 0.337 0.354 0.367 11.9 0.437 10.0 0.449 9.7 0.457 9.5 0.483 9.0 0.467 9.3 0.501 8.7
456.1 0.0635 0.065 0.305 0.322 0.334 0.351 0.364 12.0 0.434 10.0 0.446 9.7 0.454 9.6 0.480 9.0 0.463 9.4 0.498 8.7
483.4 0.0599 0.062 0.306 0.323 0.335 0.352 0.366 12.0 0.435 10.0 0.447 9.8 0.455 9.6 0.481 9.0 0.465 9.4 0.499 8.7
494.4 0.0583 0.060 0.305 0.322 0.334 0.351 0.365 12.1 0.435 10.0 0.446 9.8 0.455 9.6 0.480 9.0 0.464 9.4 0.498 8.7
510.5 0.05G5 0.059 0.303 0.320 0.332 0.349 0.362 12.1 0.432 10.1 0.444 9.8 0.452 9.6 0.478 9.1 0.462 9.4 0.496 8.7
523.7 0.0553 0.057 0.303 0.320 0.332 0.349 0.363 12.1 0.432 10.1 0.444 9.8 0.452 9.6 0.478 9.1 0.46? 9.4 0.496 8,7
Series resistance R (ohm/km) 0 927 0.669 0.494 0 342 0.247 0.196 0.158 0.127 0.098 0.08 0.064 0.051 0042
Series Reactance X (ohm/km) 0.097 0.092 0.089 0.033 0.08 0.078 0.076 0.075 0.073 0.072 0.071 0.088 0.086
3.3kV
Susceptance omegaC 0.059 0.067 0.079 0.09 0.104 0.111 0.122 0.133 0.146 0.16 0.179 0,19 0.202
6.6kV Series Resistance R ((ohm/km)
S/k ) 0.927 0.669 0.494 0.342 0.247 0.196 0.158 0.127 0.098 0.08 0.064 0.057 0 042
Series Reactance X (ohm/km) 0121 0113 0.108 0102 0096 0.093 0.091 0.088 0.086 0.085 0.083 0,088 0 086
Susceptance omegaC 0.085 0.095 0.104
0.12 0.136
0.149 0.16 0.177 0.189 0.195 0.204 0.205 0.228 1
(mS/km)
11kV Series Resistance R (ohm/km) 0.927 0.669 0.494 0.342 0.247 0.196 0.158 0.127 0.098 0.08 0.064 0.051 0.042
Series Reactance X (ohm/km) 0128 0.119 0.114 0.107 0.101 0.098 0.095 0.092 0.089 0.087 0.084 0.089 0086
Susceptance omegaC 0.068 0.074 0.082 0.094 0.105 0.115 0.123 0.135 0.15 0.165 0.182 0.194 0.216
22kV Series Resistance ( S/k j - 0.669 0.494 0 348 0.247 0.196 0.158 0.127 0098 0.08 0.064 0.051 0042
R (ohm/km)
Series Reactance X (ohm/km) - 0.136 0.129 0.121 0.114 0.11 0.107 0.103 0.1 0.094 0.091 0,096 0.093
Susceptance omegaC 0.053 0.057 0.065 0.072 0.078 0.084 0.091 0.1 0.109 0.12 0.128 0.141
(mS/km)
33kV Series Resistance R (ohm/km) - 0.669 0.494 0.348 0.247 0.196 0.158 0.127 0.098 0,08 0.064 0.051 0.042
Series Reactance X (ohm/km) - 0.15 0.143 0134 0.127 0.122 0.118 0.114 0.109 0.105 0.102 0.103 0,1
Susceptance omegaC 0.042 0.045 0.05 0.055 0.059 0.063 0.068 0.075 0.081 0.089 0.094 0.103
66kV* Series Resistance R ((ohm/km)
S/ 0.0387 0.031 0.025 0.0215
4
Series Reactance X [ohm/km] 0.117 0,113 0.109 0.102
Susceptance omegaC 0.079 0.082 0.088 0.11
(mS/km)
145kV* Series Resistance R (ohm/km) 0.0387 0,031 0.025 0.0215
Series Reactance X (ohm/km) 0.13 0.125 4
0.12 0.115
Susceptance omegaC 0.053 0.06 0.063 0.072
245kV* Series Resistance R((ohm/km)
S/k ) 0.0487 0.0387 0.0310 0.025 0.0215 0.016 0.0126
4 1
Series Reactance X (ohm/km) 0.145 0.137 0.134 0.128 0.123 0.119 0.113
Susceptance omegaC 0.044 0.047 0.00 0.057 0.057 0.063 0.072
(mS/km)
420kV Scries Resistance R (ohm/km) 0.0310 0.025 0.0215 0.0161 0.0126
* Series Reactance X (ohm/km) 4
0.172 0.162 0.156 0.151 0.144
■
Conductor (mm 2 )
Size
10 16 25 35 50 70 95 120 150 165 240 300 400 *500 *630 *800 •1000
3.3kV Series Resistance R (ohm/km) 439.9 304.9 220.4 174.5 142.3 113.9 87.6 70.8 56.7 45.5 37.1 31.2 27.2
Series Reactance X (ohm/km) 87,7 83.6 76.7 74.8 72.5 70.2 67.5 66.6 65.7 64.7 63.8 62.9 62.4 73.5 72.1 71.2 69.8
Susceptance omegaC
6.6kV Series Resistance R ((ohm/km)
S/k ) 514.2 326 206.4 148.8 110 76.2 55.1 43.6 35.6 28.5 21.9 17.6 14.1 11.3 9.3 7.8 6.7
Series Reactance X (ohm/km) 26.2 24.3 22 21.2 20.4 19.6 18.7 18.3 17.9 17.6 17.1 16.9 16.5 18.8 18.4 18 17.8
Susceptance omegaC
(mS/km)
Series Resistance R (ohm/km) 111 0.87 0.63 0.46 0.32 0.23 0.184 0.15 0.12 0,092 0.O74 0.059 0.048 0.039 0.033 0,028
11 kV Series Reactance X (ohm/km) - 9.26 0.107 0.1 0.096 0.091 0.087 0.085 0.083 0.081 0.079 0.077 0,076 0.O85 0.083 0.081 0.08
Susceptanre omegaC ___
(mS/km)
Series Resistance R (ohm/km) - 17.69 12.75 9.42 6.53 4.71 3.74 3.04 2.44 1.87 1.51 1.21 0.96 0.79 0.66 0.57
22kV Series Reactance X (ohm/km) - 2.89 2.71 2.6 2.46 2.36 2.25 2.19 2.11 2.04 1.97 1.92 1.9 1.84 1.8 1.76
Susceptance omegaC
(mS/km)
Series Resistance R (ohm/km) - - 4.19 2.9 2.09 0.181 0.147 0.118 0.09 0.073 0.058 0.046 0.038 0.031 0.027
33kV Series Reactance X (ohm/km) - - - 1.16 1.09 1.03 0.107 0.103 0.101 0.097 0.094 0.09 0.098 0.097 0.092 0.089
Susceptance omegaC 0,104 0.116 0.124 0.194 0.151 0.281 0,179 0.198 0.22 0.245
(mS/km)
Cables are of the solid type, 3 core except for those marked *. Impedances at 50Hz frequency
6.1 INTRODUCTION
Whenever the values of voltage or current in a power
circuit are too high to permit convenient direct
connection of measuring instruments or relays, coupling
is made through transformers. Such 'measuring1
transformers are required to produce a scaled down
replica of the input quantity to the accuracy expected
for the particular measurement; this is made possible by
the high efficiency of the transformer. The performance
of measuring transformers during and following large
instantaneous changes in the input quantity is
important, in that this quantity may depart from the
sinusoidal waveform. The deviation may consist of a
step change in magnitude, or a transient component
that persists for an appreciable period, or both. The
resulting effect on instrument performance is usually
negligible, although for precision metering a persistent
change in the accuracy of the transformer may be
significant.
However, many protection systems are required to
operate during the period of transient disturbance in the
output of the measuring transformers that follows a
system fault. The errors in transformer output may
abnormally delay the operation of the protection, or
cause unnecessary operations. The functioning of such
transformers must, therefore, be examined analytically.
It can be shown that the transformer can be represented
by the equivalent circuit of Figure 6.1, where all
quantities are referred to the secondary side.
6.2.5 Construction
6.2.2 Voltage Factors
The construction of a voltage transformer takes into
The quantity Vf in Table 6.2 is an upper limit of operating account the following factors:
voltage, expressed in per unit of rated voltage. This is
important for correct relay operation and operation a. output - seldom more than 200-300VA. Cooling is
under unbalanced fault conditions on unearthed or rarely a problem
impedance earthed systems, resulting in a rise in the b. insulation - designed for the system impulse
voltage on the healthy phases. voltage level. Insulation volume is often larger
Voltage factors, with the permissible duration of the than the winding volume
maximum voltage, are given in Table 6.3. c. mechanical design - not usually necessary to
withstand short-circuit currents. Must be small to
Voltage factor Time V f Primary winding connection/system fit the space available within switchgear
Earthing conditions
rating
1.2 continuous
Three-phase units are common up to 36kV but for higher
Between lines in any network.
Between transformer star point and voltages single-phase units are usual. Voltage
earth in any network transformers for medium voltage circuits will have dry
1.2 continuous Between line and earth in an type insulation, but for high and extra high voltage
1.5 30 s effectively earthed network
systems, oil immersed units are general. Resin
1.2 continuous Between line and earth in a non-effectively
1.9 30 s earthed neutral system with automatic
encapsulated designs are in use on systems up to 33kV.
earth fault tripping Figure 6.3 shows a typical voltage transformer.
1.2 continuous Between line and earth in an isolated neutral
1.3 8 hours system without automatic earth fault tripping,
or in a resonant earthed system without
automatic earth fault tripping
Table 6.3: Voltage transformers: Permissible duration of
maximum voltage
The primary winding of a current transformer is The general vector diagram (Figure 6.2) can be simplified
connected in series with the power circuit and the by the omission of details that are not of interest in
impedance is negligible compared with that of the power current measurement; see Figure 6.10. Errors arise
circuit. The power system impedance governs the because of the shunting of the burden by the exciting
current passing through the primary winding of the impedance. This uses a small portion of the input current
current transformer. This condition can be represented for exciting the core, reducing the amount passed to the
by inserting the load impedance, referred through the burden. So Is = Ip- Ie, where /P is dependent on Ze, the
turns ratio, in the input connection of Figure 6.1. exciting impedance and the secondary e.m.f. Es, given by
This approach is developed in Figure 6.9, taking the the equation E s = I s (Z s + Z b ), where:
numerical example of a 300/5A CT applied to an 11 kV power Z s = the self-impedance of the secondary winding,
system. The system is considered to be carrying rated which can generally be taken as the resistive
current (300A) and the CT is feeding a burden of 10VA. component R s only
Figur
e 6.10: Vector diagram for current
transformer (referred to secondary)
A study of the final equivalent circuit of Figure 6.9(c),
taking note of the typical component values, will reveal all
6.4.1. 7 Current or Ratio Error
the properties of a current transformer. It will be seen that:
This is the difference in magnitude between fp and Is and is
a. the secondary current will not be affected by
equal to Ir, the component of Ie which is in phase with Is.
change of the burden impedance over a
considerable range 6.4.1.2 Phase Error
b. the secondary circuit must not be interrupted while This is represented by lq, the component of Ic in
the primary winding is energised. The induced quadrature with /s and results in the phase error
secondary e.m.f. under these circumstances will be The values of the current error and phase error depend on
high enough to present a danger to life and insulation the phase displacement between Is and Iei but neither
c. the ratio and phase angle errors can be calculated current nor phase error can exceed the vectorial error fe.
easily if the magnetising characteristics and the It will be seen that with a moderately inductive burden,
burden impedance are known resulting in /s and Ic approximately in phase, there will
be little phase error and the exciting component will
result almost entirely in ratio error.
A reduction of the secondary winding by one or two
turns is often used to compensate for this. For example,
in the CT corresponding to Figure 6.9, the worst error due
to the use of an inductive burden of rated value would
Table 6.5: Protection CT error limits for classes 5P and 1OP
be about 1.2%. If the nominal turns ratio is 2:120,
removal of one secondary turn would raise the output by
0.83% leaving the overall current error as -0.37%. Even though the burden of a protection CT is only a few
For lower value burden or a different burden power VA at rated current, the output required from the CT may
factor, the error would change in the positive direction to be considerable if the accuracy limit factor is high. For
a maximum of +0.7% at zero burden; the leakage example, with an accuracy limit factor of 30 and a
reactance of the secondary winding is assumed to be burden of 10VA, the CT may have to supply 9000VA to
negligible. No corresponding correction can be made for the secondary circuit.
phase error, but it should be noted that the phase error Alternatively, the same CT may be subjected to a high
is small for moderately reactive burdens. burden. For overcurrent and earth fault protection, with
elements of similar VA consumption at setting, the earth
fault element of an electromechanical relay set at 10%
6.4.2 Composite Error would have 100 times the impedance of the overcurrent
This is defined in IEC 60044-1 as the r.m.s. value of the elements set at 100%. Although saturation of the relay
difference between the ideal secondary current and the elements somewhat modifies this aspect of the matter, it
actual secondary current. It includes current and phase will be seen that the earth fault element is a severe
errors and the effects of harmonics in the exciting burden, and the CT is likely to have a considerable ratio
current. The accuracy class of measuring current error in this case. So it is not much use applying turns
transformers is shown in Table 6.4. compensation to such current transformers; it is
generally simpler to wind the CT with turns
corresponding to the nominal ratio.
Current transformers are often used for the dual duty of
measurement and protection. They will then need to be
rated according to a class selected from both Tables 6.4
and 6.5. The applied burden is the total of instrument
and relay burdens. Turns compensation may well be
needed to achieve the measurement performance.
Measurement ratings are expressed in terms of rated
burden and class, for example 15VA Class 0.5. Protection
ratings are expressed in terms of rated burden, class, and
accuracy limit factor, for example 10VA Class 10P10.
The 'linear' current transformer constitutes an even more c. the primary conductor(s) passes through the
radical departure from the normal solid core CT in that it approximate centre of the core aperture or, if
incorporates an appreciable air gap, for example 7.5- wound, is approximately evenly distributed along
the whole length of the magnetic circuit
d. flux equalising windings, where fitted to the
requirements of the design, consist of at least four
parallel-connected coils, evenly distributed along
the whole length of the magnetic circuit, each coil
occupying one quadrant
Alternatively, when a current transformer does not
obviously comply with all of the above requirements, it
may be proved to be of low-reactance where:
e. the composite error, as measured in the accepted
way, does not exceed by a factor of 1.3 that error
obtained directly from the V-l excitation
characteristic of the secondary winding
...Equation 6.4
...Equation 6.5
Hence, the ratio of the transient flux to the steady state Figure 6.13: Response of a CTof
infinite shunt impedance to transient asymmetric
value is: primary current
T1 = CT secondary circuit time constant Le/Re I1 = When the exponential component drives the CT into
saturation, the magnetising inductance decreases,
prospective peak secondary current 6.4.10.2 Practical
causing a large increase in the alternating component ie.
conditions
The total exciting current during the transient period is
Practical conditions differ from theory for the following of the form shown in Figure 6.15 and the corresponding
reasons: resultant distortion in the secondary current output, due
to saturation, is shown in Figure 6.16.
a. no account has been taken of secondary leakage or
burden inductance. This is usually small compared
with Le. so that it has little effect on the maximum
transient flux
b. iron loss has not been considered. This has the
effect of reducing the secondary time constant, but
the value of the equivalent resistance is variable,
depending upon both the sine and exponential
terms. Consequently, it cannot be included in any
linear theory and is too complicated for a
satisfactory treatment to be evolved
c. the theory is based upon a linear excitation
characteristic. This is only approximately true up to Figure 6.15: Typical exciting current of CT
the knee-point of the excitation curve. A precise during transient asymmetric input current
Figure. 6.18: Schematic representation of the concepts behind the optical sensing of varying electric and magnetic fields
from earthed or galvanic links. Thus the only link that analysing circuitry. In sharp contrast with a
remains between the control-room and the switchyard is conventional free-standing instrument transformer, the
a fibre optic cable. optical instrument transformer needs an electronic
interface module in order to function. Therefore its
Another type of hybrid non-conventional instrument
sensing principle (the optical material) is passive but its
transformer is achieved by retrofitting a passive optical
operational integrity relies on the interface that is
sensing medium into a conventional 'hard-wire
powered in the control room (Figure 6.21).
secondary' instrument transformer. This can be termed
as a passive hybrid type since no power supply of any
kind is needed at the secondary level.
6.5.7.3 'All-optical' transducers
These instrument transformers are based entirely on
optical materials and are fully passive. The sensing
function is achieved directly by the sensing material and
a simple fibre optic cable running between the base of
the unit and the sensor location provides the
communication link.
The sensing element is made of an optical material that is
positioned in the electric or magnetic field to be sensed.
In the case of a current measuring device the sensitive
element is either located free in the magnetic field (Figure
6.19(a)) or it can be immersed in a field-shaping magnetic
'gap' (Figure 6.19(b)). In the case of a voltage-sensing
device (Figure 6.20) the same alternatives exist, this time
for elements that are sensitive to electric fields. The
possibility exists of combining both sensors within a
single housing, thus providing both a CT and VT within a
single compact housing that gives rise to space savings
within a substation.
Similar to conventional instrument transformers there are Although 'all-optical' instrument transformers were first
live tank' and 'dead tank' optical transducers. Typically, introduced 10-15 years ago, there are still only a few in
current transducers take the shape of a closed loop of service nowadays. Figure 6.24 shows a field installation
light-transparent material, fitted around a straight of a combined optical CT/VT.
conductor carrying the line current (Figure 6.22). In this
case a bulk-glass sensor unit is depicted (Figure 6.22(a)),
along with an 'all-optical' sensor example, as shown in
Figure 6.22(b). Light detectors are basically very sensitive
devices and the sensing material can thus be selected in
such a way as to scale-up readily for larger currents. 'All-
optical' voltage transducers however do not lend
themselves easily for extremely high line voltages. Two
concepts using a 'full-voltage' sensor are shown in Figure
6.23.
7 . 2 ELECTROMECHANICAL RELAYS
These relays were the earliest forms of relay used for the
protection of power systems, and they date back nearly
100 years. They work on the principle of a mechanical
force causing operation of a relay contact in response to
a stimulus. The mechanical force is generated through
current flow in one or more windings on a magnetic core
or cores, hence the term electromechanical relay. The
principle advantage of such relays is that they provide
galvanic isolation between the inputs and outputs in a
simple, cheap and reliable form - therefore for simple
on/off switching functions where the output contacts
have to carry substantial currents, they are still used.
Electromechanical relays can be classified into several
different types as follows:
a. attracted armature
b. moving coil
c. induction
d. thermal
e. motor operated
f. mechanical
However, only attracted armature types have significant
application at this time, all other types having been
superseded by more modern equivalents.
The energising quantity can be either an a.c. or a d.c. Figure 7.3: Typical attracted armature relay mounted in case
Figure 7.6: Selection of digital relays Table 7.1: Numerical distance relay features
Figure 7.7: Typical numerical relays
where:
/s = sampling frequency
fh = highest frequency of interest
transients. Additionally, the input signals must be If too low a sampling frequency is chosen,
amplitude limited to avoid them exceeding the power aliasing of the input signal can occur (Figure 7.12),
supply voltages, as otherwise the waveform will appear resulting in high frequencies appearing as part of signal in
distorted, as shown in Figure 7.11. the frequency range of interest. Incorrect results will then
be obtained. The solution is to apply an anti-aliasing
Analogue signals are converted to digital form using an
filter, coupled with an appropriate choice of sampling
A/D converter. The cheapest method is to use a single
frequency, to the analogue signal, so those frequency
A/D converter, preceded by a multiplexer to connect
components that could cause aliasing are filtered out.
each of the input signals in turn to the converter. The
Digital sine and cosine filters are used (Figure 7.13), with
signals may be initially input to a number of
a frequency response shown in Figure 7.14, to extract the
simultaneous sample-and-hold circuits prior to
real and imaginary components of the signal. Frequency
multiplexing, or the time relationship between
tracking of the input signals is applied to adjust the
successive samples must be known if the phase
sampling frequency so that the desired number of
relationship between signals is important. The
samples/cycle is always obtained. A modern numerical
alternative is to provide each input with a dedicated A/D
relay may sample each analogue input quantity at
converter, and logic to ensure that all converters
between 16 and 24 samples per cycle.
perform the measurement simultaneously.
The frequency of sampling must be carefully considered,
as the Nyquist criterion applies:
Figure 7.1V. Signal distortion
due to excessive amplitude
All subsequent signal processing is carried out digitally in b. HMI interface software - the high level software
software, final digital outputs use relays to provide for communicating with a user, via the front panel
isolation or are sent via an external communications bus controls or through a data link to another
to other devices. computer running suitable software, storage of
setting data, etc.
7.5.2 Relay Software
c. application software - this is the software that
The software provided is commonly organised into a
defines the protection function of the relay
series of tasks, operating in real time. An essential
component is the Real Time Operating System (RTOS), d. auxiliary functions - software to implement other
whose function is to ensure that the other tasks are features offered in the relay - often structured as
executed as and when required, on a priority basis. a series of modules to reflect the options offered to
a user by the manufacturer
Other task software provided will naturally vary
according to the function of the specific relay, but can be 7.5.3 Application Software
generalised as follows:
The relevant software algorithm is then applied. Firstly,
a. system services software - this is akin to the BIOS the values of the quantities of interest have to be
of an ordinary PC, and controls the low-level I/O determined from the available information contained in
for the relay (i.e. drivers for the relay hardware, the data samples. This is conveniently done by the
boot-up sequence, etc.) application of the Discrete Fourier Transform [DFT], and
Sample points
7.8 REFERENCES
7.1 Protective Relays Application Guide, 3rd edition, ALSTOM T&D Protection and Control, 1987
• 8 • Protection: Signalling
and Intertripping
8.1 INTRODUCTION
Unit protection schemes, formed by a number of relays
located remotely from each other, and some distance
protection schemes, require some form of communication
between each location in order to achieve a unit protection
function. This form of communication is known as
protection signalling. Additionally communications
facilities are also required when remote operation of a
circuit breaker is required as a result of a local event. This
form of communications is known as intertripping.
The communication messages involved may be quite
simple, involving instructions for the receiving device to
take some defined action (trip, block, etc.), or it may be
the passing of measured data in some form from one
device to another (as in a unit protection scheme).
Various types of communication links are available for
protection signalling, for example:
i. private pilot wires installed by the power
authority
ii. pilot wires or channels rented from a
communications company
iii. carrier channels at high frequencies over the
power lines
iv. radio channels at very high or ultra high
frequencies
v. optical fibres
Whether or not a particular link is used depends on
factors such as the availability of an appropriate
communication network, the distance between
protection relaying points, the terrain over which the
power network is constructed, as well as cost.
Protection signalling is used to implement Unit
Protection schemes, provide teleprotection commands,
or implement intertripping between circuit breakers.
magnitude of current respectively - between local and piece of apparatus in sympathy with the tripping of other
remote relaying points. Comparison of local and remote circuit breakers. The main use of such schemes \s to
signals provides the basis for both fault detection and ensure that protection at both ends of a faulted circuit
discrimination of the schemes. will operate to isolate the equipment concerned. Possible
circumstances when it may be used are:
Details of Unit Protection schemes are given in Chapter 10.
Communications methods are covered later in this Chapter. a. a feeder with a weak infeed at one end, insufficient
to operate the protection for all faults
8.3 TELEPROTECTION COMMANDS b. feeder protection applied to transformer -feeder
Some Distance Protection schemes described in Chapter circuits. Faults on the transformer windings may
12 use signalling to convey a command between local operate the transformer protection but not the
and remote relaying points. Receipt of the information feeder protection. Similarly, some earth faults may
is used to aid or speed up clearance of faults within a not be detected due to transformer connections
protected zone or to prevent tripping from faults outside c. faults between the CB and feeder protection CT's,
a protected zone. when these are located on the feeder side of the CB.
Teleprotection systems are often referred to by their Bus-zone protection does not result in fault
mode of operation, or the role of the teleprotection clearance - the fault is still fed from the remote end
command in the system. of the feeder, while feeder unit protection may not
operate as the fault is outside the protected zone
d. some distance protection schemes use
8.4 INTERTRIPPING intertripping to improve fault clearance times for
Intertripping is the controlled tripping of a circuit some kinds of fault - see Chapters 12/13
breaker so as to complete the isolation of a circuit or Intertripping schemes use signalling to convey a trip
command to remote circuit breakers to isolate circuits. 8.5 PERFORMANCE REQUIREMENTS
For high reliability EHV protection schemes, intertripping
Overall fault clearance time is the sum of:
may be used to give back-up to main protections, or
back-tripping in the case of breaker failure. Three types a. signalling time
of intertripping are commonly encountered, and are b. protection relay operating time
described below.
c. trip relay operating time
8.4.1 Direct Tripping
d. circuit breaker operating time
In direct tripping applications, intertrip signals are sent
directly to the master trip relay. Receipt of the command The overall time must be less than the maximum time for
causes circuit breaker operation. The method of which a fault can remain on the system for minimum
communication must be reliable and secure because any plant damage, loss of stability, etc. Fast operation is
signal detected at the receiving end will cause a trip of therefore a pre-requisite of most signalling systems.
the circuit at that end. The communications system Typically the time allowed for the transfer of a command
design must be such that interference on the is of the same order as the operating time of the
communication circuit does not cause spurious trips. associated protection relays. Nominal operating times
Should a spurious trip occur, considerable unnecessary range from 5 to 40ms dependent on the mode of
isolation of the primary system might result, which is at operation of the teleprotection system.
best undesirable and at worst quite unacceptable.
Protection signals are subjected to the noise and
interference associated with each communication
8.4.2 Permissive Tripping medium. If noise reproduces the signal used to convey
Permissive trip commands are always monitored by a the command, unwanted commands may be produced,
protection relay. The circuit breaker is tripped when whilst if noise occurs when a command signal is being
receipt of the command coincides with operation of the transmitted, the command may be retarded or missed
protection relay at the receiving end responding to a completely. Performance is expressed in terms of
system fault. Requirements for the communications security and dependability. Security is assessed by the
channel are less onerous than for direct tripping probability of an unwanted command occurring, and
schemes, since receipt of an incorrect signal must dependability is assessed by the probability of missing a
coincide with operation of the receiving end protection command. The required degree of security and
for a trip operation to take place. The intention of these dependability is related to the mode of operation, the
schemes is to speed up tripping for faults occurring characteristics of the communication medium and the
within the protected zone. operating standards of the particular power authority.
Typical design objectives for teleprotection systems are
not more than one incorrect trip per 500 equipment
8.4.3 Blocking Scheme years and less than one failure to trip in every 1000
Blocking commands are initiated by a protection element attempts, or a delay of more than 50msec should not
that detects faults external to the protected zone. occur more than once per 10 equipment years. To
Detection of an external fault at the local end of a achieve these objectives, special emphasis may be
protected circuit results in a blocking signal being attached to the security and dependability of the
transmitted to the remote end. At the remote end, teleprotection command for each mode of operation in
receipt of the blocking signal prevents the remote end the system, as follows.
protection operating if it had detected the external fault.
Loss of the communications channel is less serious for
this scheme than in others as loss of the channel does 8.5.1 Performance Requirements - Intertripping
not result in a failure to trip when required. However, Since any unwanted command causes incorrect tripping,
the risk of a spurious trip is higher. very high security is required at all noise levels up to the
Figure 8.1 shows the typical applications of protection maximum that might ever be encountered.
signalling and their relationship to other signalling
systems commonly required for control and management 8.5.2 Performance Requirements - Permissive Tripping
of a power system. Of course, not all of the protection
signals shown will be required in any particular scheme. Security somewhat lower than that required for
intertripping is usually satisfactory, since incorrect
tripping can occur only if an unwanted command
happens to coincide with operation of the protection
relay for an out-of-zone fault.
For permissive over-reach schemes, resetting after a physical fibre connection and thus enables more
command should be highly dependable to avoid any comprehensive monitoring of the power system to be
chance of maloperations during current reversals. achieved by the provision of a large number of
communication channels.
8.5.3 Performance Requirements - Blocking Schemes 8.6.1 Private Pilot Wires and Channels
Low security is usually adequate since an unwanted Pilot wires are continuous copper connections between
command can never cause an incorrect trip. High signalling stations, while pilot channels are
dependability is required since absence of the command discontinuous pilot wires with isolation transformers or
could cause incorrect tripping if the protection relay repeaters along the route between signalling stations.
operates for an out-of-zone fault. They may be laid in a trench with high voltage cables,
Typical performance requirements are shown in Figure 8.2. laid by a separate route or strung as an open wire on a
separate wood pole route.
Distances over which signalling is required vary
considerably. At one end of the scale, the distance may be
only a few tens of metres, where the devices concerned are
located in the same substation. For applications on EHV
lines, the distance between devices may be between 10-
100km or more. For short distances, no special measures
are required against interference, but over longer distances,
special send and receive relays may be required to boost
signal levels and provide immunity against induced
voltages from power circuits, lightning strikes to ground
adjacent to the route, etc. Isolation transformers may also
have to be provided to guard against rises in substation
ground potential due to earth faults.
The capacity of a link can be increased if frequency
division multiplexing techniques are used to run paralle
signalling systems, but some Utilities prefer the link to be
used only for protection signalling.
Private pilot wires or channels can be attractive to an
Figure 8.2: Typical performance requirements Utility running a very dense power system with short
for protection signalling when the distances between stations.
communication link is subjected to noise
Optical fibre communications are well established in the Plain high frequency signals can be used successfully for
electrical supply industry. They are the preferred means the signalling of blocking information over a power line.
for the communications link between a substation and a A normally quiescent power line carrier equipment can
telephone exchange when rented circuits are used, as be dedicated entirely to the transfer to teleprotection
trials have shown that this link is particularly susceptible blocking commands. Phase comparison power line
to interference from power system faults if copper carrier unit protection schemes often use such
conductors are used. Whilst such fibres can be laid in equipment and take advantage of the very high speed
cable trenches, there is a strong trend to associate them and dependability of the signalling system. The special
with the conductors themselves by producing composite characteristics of dedicated 'on/off' keyed carrier systems
cables comprising optical fibres embedded within the are discussed later. A relatively insensitive receiver is
conductors, either earth or phase. For overhead lines use used to discriminate against noise on an amplitude basis,
of OPGW (Optical Ground Wire) earth conductors is very and for some applications the security may be
common, while an alternative is to wrap the optical satisfactory for permissive tripping, particularly if the
cable helically around a phase or earth conductor. This normal high-speed operation of about 6ms is sacrificed
latter technique can be used without restringing of the by the addition of delays. The need for regular reflex
line. testing of a normally quiescent channel usually precludes
any use for intertripping.
Plain tone power line carrier signalling systems are
8 . 7 SIGNALLING METHODS particularly suited to providing the blocking commands
Various methods are used in protection signalling; not all often associated with the protection of multi-ended
need be suited to every transmission medium. The feeders, as described in Chapter 13. A blocking
methods to be considered briefly are: command sent from one end can be received
simultaneously at all the other ends using a single power
a. D.C. voltage step or d.c. voltage reversals
line carrier channel. Other signalling systems usually
b. plain tone keyed signals at high and voice require discrete communication channels between each
frequencies of the ends or involve repeaters, leading to decreased
c. frequency shift keyed signals involving two or more dependability of the blocking command.
tones at high and voice frequencies Plain voice frequency signals can be used for blocking,
General purpose telecommunications equipment permissive intertrip and direct intertrip applications for
operating over power line carrier, radio or optical fibre all transmission media but operation is at such a low
media incorporate frequency translating or multiplexing signal level that security from maloperation is not very
techniques to provide the user with standardised good. Operation in the 'tone on' to 'tone off1 mode gives
communication channels. They have a nominal the best channel monitoring, but offers little security; to
bandwidth/channel of 4kHz and are often referred to as obtain a satisfactory performance the output must be
voice frequency (vf) channels. Protection signalling delayed. This results in relatively slow operation: 70
equipments operating at voice frequencies exploit the milliseconds for permissive intertripping, and 180
standardisation of the communication interface. Where milliseconds for direct intertripping.
voice frequency channels are not available or suitable,
protection signalling may make use of a medium or
specialised equipment dedicated entirely to the
signalling requirements.
Figure 8.5: Communication arrangements commonly encountered in protection signalling
8.7.3 Frequency Shift Keyed Signals give the required degree of security in direct intertrip
Frequency shift keyed high frequency signals can be schemes: the short operating times needed may result in
used over a power line carrier link to give short uneconomical use of the available voice frequency
operating times (15 milliseconds for blocking and spectrum, particularly if the channel is not exclusively
permissive intertripping, 20 milliseconds for direct employed for protection signalling. As noise power is
intertripping) for al l applications of protection directly proportional to bandwidth, a large bandwidth
signalling. The required amount of security can be causes an increase in the noise level admitted to the
achieved by using a broadband noise detector to detector, making operation in the presence of noise more
monitor the actual operational signalling equipment. difficult. So, again, it is difficult to obtain both high
dependability and high security.
Frequency shift keyed voice frequency signals can be
used for all protection signalling applications over all The signal frequency shift technique has advantages
transmission media. Frequency modulation techniques where fast signalling is needed for blocked distance and
make possible an improvement in performance, because permissive intertrip applications. It has little inherent
amplitude limiting rejects the amplitude modulation security, but additional circuits responsive to every type
component of noise, leaving only the phase modulation of interference can give acceptable security. This system
components to be detected. does not require a channel capable of high transmission
rates, as the frequency changes once only; the
The operational protection signal may consist of tone bandwidth can therefore be narrower than in coded
sequence codes with, say, three tones, or a multi-bit systems, giving better noise rejection as well as being
code using two discrete tones for successive bits, or of a advantageous if the channel is shared with telemetry
single frequency shift. and control signalling, which will inevitably be the case
Modern high-speed systems use multi-bit code or single if a power line carrier bearer is employed.
frequency shift techniques. Complex codes are used to
9.Overcurrent Protection for
Phase and Earth Faults
9.1 INTRODUCTION
Figure 9.4 (b): IDMTrelay characteristics 9.5 COMBINED I.D.M.T. AND HIGH SET
INSTANTANEOUS OVERCURRENT RELAYS
A high-set instantaneous element can be used where the
The mathematical descriptions of the curves are given in
source impedance is small in comparison with the
Table 9.1 (a), and the curves based on a common setting
current and time multiplier setting of 1 second are protected circuit impedance. This makes a reduction in
shown in Figure 9.4(a). The tripping characteristics for the tripping time at high fault levels possible. It also
different TMS settings using the SI curve are illustrated improves the overall system grading by allowing the
in Figure 9.5. 'discriminating curves' behind the high set instantaneous
elements to be lowered.
Although the curves are only shown for discrete values of
TMS, continuous adjustment may be possible in an As shown in Figure 9.6, one of the advantages of the high
electromechanical relay. For other relay types, the setting set instantaneous elements is to reduce the operating
steps may be so small as to effectively provide continuous time of the circuit protection by the shaded area below
adjustment. In addition, almost all overcurrent relays are the 'discriminating curves'. If the source impedance
also fitted with a high-set instantaneous element. remains constant, it is then possible to achieve high-
speed protection over a large section of the protected
In most cases, use of the standard SI curve proves
circuit. The rapid fault clearance time achieved helps to
satisfactory, but if satisfactory grading cannot be
minimise damage at the fault location. Figure 9.6 also
achieved, use of the VI or El curves may help to resolve
illustrates a further important advantage gained by the
the problem. When digital or numeric relays are used,
use of high set instantaneous elements. Grading with
other characteristics may be provided, including the
the relay immediately behind the relay that has the
possibility of user-definable curves. More details are
instantaneous elements enabled is carried out at the
provided in the following sections.
current setting of the instantaneous elements and not at
the maximum fault level. For example, in Figure 9.6, 9.6 VERY INVERSE (VI) OVERCURRENT RELAYS
relay R2 is graded with relay R3 at 500A and not 1100A,
Very inverse overcurrent relays are particularly suitable if
allowing relay R2 to be set with a TMS of 0.15 instead of
there is a substantial reduction of fault current as the
0.2 while maintaining a grading margin between relays
distance from the power source increases, i.e. there is a
of 0.4s. Similarly, relay R1 is graded with R2 at 1400A
substantial increase in fault impedance. The VI operating
and not at 2300A.
characteristic is such that the operating time is
approximately doubled for reduction in current from 7 to
4 times the relay current setting. This permits the use of
the same time multiplier setting for several relays in series.
Figure 9.7 provides a comparison of the SI and VI curves
for a relay. The VI curve is much steeper and therefore
the operation increases much faster for the same
reduction in current compared to the SI curve. This
enables the requisite grading margin to be obtained with
a lower TMS for the same setting current, and hence the
tripping time at source can be minimised.
...Equation 9.1
where: 9.7 EXTREMELY INVERSE (EI) OVERCURRENT RELAYS'
I 1 = r.m.s steady-state relay pick-up current I 2 =
steady state r.m.s. current which when fully With this characteristic, the operation time is
offset just causes relay pick-up approximately inversely proportional to the square of the
applied current. This makes it suitable for the protection
When applied to power transformers, the high set
of distribution feeder circuits in which the feeder is
instantaneous overcurrent elements must be set above
subjected to peak currents on switching in, as would be
the maximum through fault current than the power
the case on a power circuit supplying refrigerators,
transformer can supply for a fault across its LV terminals,
pumps, water heaters and so on, which remain
in order to maintain discrimination with the relays on
connected even after a prolonged interruption of supply.
the LV side of the transformer.
The long time operating characteristic of the
extremely
inverse relay at normal peak load values of current also is properly documented, along with the reasons for use.
makes this relay particularly suitable for grading with Since the standard curves provided cover most cases with
fuses. Figure 9.8 shows typical curves to illustrate this. adequate tripping times, and most equipment is designed
It can be seen that use of the El characteristic gives a with standard protection curves in mind, the need to utilise
satisfactory grading margin, but use of the VI or SI this form of protection is relatively rare.
characteristics at the same settings does not. Another
Digital and numerical relays may also include pre-
application of this relay is in conjunction with auto-
defined logic schemes utilising digital (relay) I/O
reclosers in low voltage distribution circuits. The
provided in the relay to implement standard schemes
majority of faults are transient in nature and
such as CB failure and trip circuit supervision. This saves
unnecessary blowing and replacing of the fuses present
in final circuits of such a system can be avoided if the the provision of separate relay or PLC (Programmable
auto-reclosers are set to operate before the fuse blows. Logic Controller) hardware to perform these functions.
If the fault persists, the auto-recloser locks itself in the
closed position after one opening and the fuse blows to
9.9 INDEPENDENT (DEFINITE) TIME
isolate the fault.
iv. CT errors
9.11 RELAY TIME GRADING MARGIN
v. final margin on completion of operation
The time interval that must be allowed between the
operation of two adjacent relays in order to achieve Factors (ii) and (iii] above depend to a certain extent on
correct discrimination between them is called the grading the relay technology used - an electromechanical relay,
margin. If a grading margin is not provided, or is for instance, will have a larger overshoot time than a
insufficient, more than one relay will operate for a fault,
numerical relay.
leading to difficulties in determining the location of the
fault and unnecessary loss of supply to some consumers. Grading is initially carried out for the maximum fault
level at the relaying point under consideration, but a
The grading margin depends on a number of factors:
check is also made that the required grading margin
i. the fault current interrupting time of the circuit exists for all current levels between relay pick-up current
breaker and maximum fault level.
9.11.1 Circuit Breaker Interrupting Time
The circuit breaker interrupting the fault must have
completely interrupted the current before the
discriminating relay ceases to be energised. The time
taken is dependent on the type of circuit breaker used
and the fault current to be interrupted. Manufacturers
normally provide the fault interrupting time at rated
interrupting capacity and this value is invariably used in
the calculation of grading margin.
9.11.3 Overshoot
When the relay is de-energised, operation may continue
for a little longer until any stored energy has been
dissipated. For example, an induction disc relay will have
stored kinetic energy in the motion of the disc; static
relay circuits may have energy stored in capacitors. Figure 9.10; Typical limits of accuracy from IEC 60255-4 for
Relay design is directed to minimising and absorbing an inverse definite minimum time overcurrent relay
This connection is recommended for the protection of If non-unit, non-directional relays are applied to parallel
transformer feeders or feeders that have a zero sequence feeders having a single generating source, any faults that
source in front of the relay. It is essential in the case of might occur on any one line will, regardless of the relay
parallel transformers or transformer feeders, in order to settings used, isolate both lines and completely
ensure correct relay operation for faults beyond the disconnect the power supply. With this type of system
star/delta transformer. This connection should also be configuration, it is necessary to apply directional relays
used whenever single-phase directional relays are at the receiving end and to grade them with the non-
applied to a circuit where a current distribution of the directional relays at the sending end, to ensure correct
form 2-1-1 may arise. discriminative operation of the relays during line faults.
This is done by setting the directional relays R'1 and R2'
in Figure 9.13 with their directional elements looking
into the protected line, and giving them lower time and
current settings than relays R1 and R2. The usual practice
is to set relays R1' and R2' to 50% of the normal full load
of the protected circuit and 0.1TMS, but care must be
taken to ensure that the continuous thermal rating of
the relays of twice rated current is not exceeded. An
example calculation is given in Section 9.20.3
Figure 9.21: Earth fault in Petersen Coil earthed system Figure 9.23: Cphase-earth fault in Petersen Coil earthed
network: theoretical case -no resistance present in XL orXc
In Figure 9.23(a), it can be seen that the fault causes the However, in practical cases, resistance is present and
healthy phase voltages to rise by a factor of and the Figure 9.25 shows the resulting phasor diagrams. If the
charging currents lead the voltages by 90°. residual voltage Vres is used as the polarising voltage, the
residual current is phase shifted by an angle less than
Using a CBCT, the unbalance currents seen on the
90° on the faulted feeder and greater than 90° on the
healthy feeders can be seen to be a simple vector
healthy feeders.
addition of Ia1 and Ib1, and this lies at exactly 90° lagging
to the residual voltage (Figure 9.23(b)). The magnitude Hence a directional relay can be used, and with an RCA
of the residual current IR1 is equal to three times the of 0°, the healthy feeder residual current will fall in the
steady-state charging current per phase. On the faulted 'restrain' area of the relay characteristic while the
feeder, the residual current is equal to lL-lH1-lH2, as faulted feeder residual current falls in the 'operate' area.
shown in Figure 9.23(c) and more clearly by the zero
Often, a resistance is deliberately inserted in parallel
sequence network of Figure 9.24.
with the Petersen Coil to ensure a measurable earth fault
current and increase the angular difference between the
residual signals to aid relay application.
Having established that a directional relay can be used,
two possibilities exist for the type of protection element
that can be applied - sensitive earth fault and zero
sequence wattmetric.
decision. If the wattmetric component of zero sequence 9.20,1 Relay Phase Fault Setting Example
power is detected in the forward direction, it indicates a - IDMT Relays/Fuses
fault on that feeder, while a power in the reverse
Consider the system shown in Figure 9.28.
direction indicates a fault elsewhere on the system. This
method of protection is more popular than the sensitive
earth fault method, and can provide greater security
against false operation due to spurious CBCT output
under non-earth fault conditions.
..Equation 9.5
Hence select relay 1 operating time =0.3+0.05=0.35s, to This relay provides overcurrent protection for reactor R,,
ensure grading with relay F2 at a fault current of and backup overcurrent protection for cables C2 and C3.
9.33kA. The overcurrent protection also provides busbar
protection for Busbar B.
With a primary setting of 480A, a fault current of 9.33kA
represents Again, the El characteristic is used to ensure grading
with relays 1 and 2. The maximum load current is
9330/480 = 19.44 times setting 1000A. Relay 3 current setting is therefore
Thus relay 1 operating time at TMS=1.0 is 0.21s. The
required TMS setting is given by the formula:
Substituting values,
Isr3>1052A
Use a setting of 106% or 1060A, nearest available
setting above 1052A.
This value of TMS is outside the settable range of the
Relay 3 has to grade with relays 1/2 under two
relay (maximum setting 1.2). Therefore, changes must be
conditions:
made to the relay current setting in order to bring the
value of TMS required into the range available, provided 1. for a fault just beyond relays 1 and 2 where the
this does not result in the inability of the relay to operate fault current will be the busbar fault current of
at the minimum fault level. 12.2kA
By re-arrangement of the formula for the El 2. for a fault at Bus C where the fault current seen by
either relay 1 or 2 will be half the total Bus C Relay 4 current setting must be at least
fault current of 10.6kA, i.e. 5.3kA
Examining first condition 1. With a current setting of
620A, a TMS of 1.0 and a fault current of 12.2kA, relay 1 For convenience, use a value of 100% (=3000A). Thus
will operate in 0.21s. Using a grading interval of 0.3s, relay 4 must operate in 0.605s at 15860/3000 = 5.29
relay 3 must therefore operate in times setting. Thus select a time multiplier setting of
0.15, giving a relay operating time of 0.62s for a normal
0.3 + 0.21 = 0.51s
inverse type characteristic.
at a fault current of 12.2kA.
At this stage, it is instructive to review the grading curves,
12.2kA represents 12200/1060 = 11.51 times setting for which are shown in Figure 9.29(a). While it can be seen
relay 3 and thus the time multiplier setting of relay 3 that there are no grading problems between the fuses and
should be 0.84 to give an operating time of 0.51s at relays 1/2, and between relays F1/2 and relays 1/2, it is
11.51 times setting. clear that relay 3 and relay 4 do not grade over the whole
Consider now condition 2. With settings of 620A and range of fault current. This is a consequence of the change
TMS of 1.0 and a fault current of 5.3kA, relay 1 will in characteristic for relay 4 to SI from the El characteristic
operate in 1.11s. Using a grading interval of 0.3s, relay 3 of relay 3 to ensure grading of relay 4 with relay 5. The
must therefore operate in solution is to increase the TMS setting of relay 4 until
correct grading is achieved. The alternative is to increase
0.3 + 1.11 = 1.41s the current setting, but this is undesirable unless the limit
at a fault current of 5.3kA. of the TMS setting is reached, because the current setting
should always be as low as possible to help ensure positive
5.3kA represents 5300/1060 = 5 times setting for relay 3,
operation of the relay and provide overload protection.
and thus the time multiplier setting of relay 3 should be 0.33
Trial and error is often used, but suitable software can
to give an operating time of 1.11s at 5 times setting. Thus
speed the task - for instance it is not difficult to construct
condition 1 represents the worst case and the time multiplier
a spreadsheet with the fuse/relay operation times and
setting of relay 3 should be set at 0.84. In practice, a value
grading margins calculated. Satisfactory grading can be
of 0.85 is used as the nearest available setting on the relay.
found for relay 4 setting values of:
Relay 3 also has an instantaneous element. This is set
I5T4 = 1.0 or 3000A
such that it will not operate for the maximum through-
fault current seen by the relay, a setting of 130% of this TMS = 0.275
value being satisfactory. The setting is therefore: At 22.7kA, the operation time of relay 4 is 0.93s. The
1.3xl2.2kA = revised grading curves are shown in Figure 9.29(b).
This is equal to a current setting of 14.96 times the Relay 5 must grade with relay 4 at a fault current of
setting of relay 3. 22.7kA. At this fault current, relay 4 operates in 0.93s
and thus relay 5 must operate in
9.20.1.6 Relay 4
0.3 + 0.93 = 1.23s at 22.7kA.
This must grade with relay 3 and relay 5. The supply
authority requires that relay 5 use an SI characteristic to A current setting of 110% of relay 4 current setting (i.e.
ensure grading with relays further upstream, so the SI 110%or3300A) is chosen to ensure relay 4 picks up prior
characteristic will be used for relay 4 also. Relay 4 must to relay 5. Thus 22.7kA represents 6.88 times the setting
grade with relay 3 at Bus A maximum fault level of of relay 5. Relay 5 must grade with relay 4 at a fault
22.7kA. However with the use of an instantaneous high current of 22.7kA, where the required operation time is
set element for relay 3, the actual grading point becomes 1.23s. At a TMS of 1.0, relay 5 operation time is
the point at which the high set setting of relay 3
operates, i.e. 15.86kA. At this current, the operation time
of relay 3 is
Figure 9.30: Final relay grading curves for overcurrent relay example
elements. Following the guidelines of Section 9.16, If relays 2 and 3 are non-directional, then, using SI relay
relays 1/2 can use a current setting of 30% (150A) and characteristics for all relays, grading of the relays is
a TMS of 0.2, using the El characteristic. Grading of dictated by the following:
relays 3/4/5 follows the same procedure as described for
a) fault at location F1, with 2 feeders in service
the phase-fault elements of these relays.
b) fault at location F4, with one feeder in service
Figure 9.31 (b) shows the impedance diagram, to a. relay 4 is graded with relay / for faults at location
100MVA, 110kV base. The fault currents for faults with Fl with one transformer feeder in service
various system configurations are shown in Table 9.6. b. relay 4 is graded with relay 3 for faults at location
F3 with two transformer feeders in service
c. relay 6 grades with relay 4 for faults at F4
d. relay 6 also has to grade with relay 4 for faults at
Fl with both transformer feeders in service - relay 6
sees the total fault current but relay 4 only 50% of
this current.
Table 9.6: Fault currents for parallel feeder example Normal rules about calculating current setting values
of relays in series apply. The settings and resulting
operation times are given in Figure 9.33(b) and(c}
respectively.
Table 9.7 shows the fault currents at each bus for open
points at CB1 and CB8.
9.20.4.2 Relay R5
0.5
Hence, relay R5 TMS = = 5.14s
4
Use nearest settable value of TMS of 0.125. Figure 9.36: Ring main example - relay grading curves
9.21 REFERENCES
10.3 CONDITIONS
FOR DIRECTION
COMPARISION
The circulating current and balanced voltage systems of
Figures 10.1 and 10.2 perform full vectorial comparisoi
of the zone boundary currents. Such systems can be
treated as analogues of the protected zone of the power
Figure 10.2: Balanced voltage system system, in which CT secondary quantities represent
primary currents and the relay operating current
corresponds to an in-zone fault current.
These systems are simple in concept; they are
Most systems of unit protection function through the
determination of the relative direction of the fault nevertheless applicable to zones having any number
of boundary connections and for any pattern of
current. This direction can only be expressed on a
comparative basis, and such a comparative measurement terminal currents.
is the common factor of many systems, including To define a current requires that both magnitude and
directional comparison protection and distance phase be stated. Comparison in terms of both of these
teleprotection schemes with directional impedance quantities is performed in the Merz-Price systems, but it
measurement. is not always easy to transmit all this information
over some pilot channels. Chapter 8 provides a detailed
A major factor in consideration of unit protection is the
description of modern methods that may be used.
method of communication between the relays. This is
covered in detail in Chapter 8 in respect of the latest
fibre-optic based digital techniques. For older 'pilot wire'
10.4 CIRCULATING CURRENT SYSTEM
systems, only brief mention is made. For more detailed
descriptions of 'pilot wire' techniques, see reference The principle of this system is shown in outline in
[10.2] in Section 10.13. Figure 10.1. If the current transformers are ideal, the
functioning of the system is straightforward. The
transformers will, however, have errors arising from both unacceptable. One solution is to include a stabilising
Wattmetric and magnetising current losses that cause resistance in series with the relay. Details of how to
deviation from the ideal, and the interconnections calculate the value of the stabilising resistor are usually
between them may have unequal impedances. This can included in the instruction manuals of all relays that
give rise to a 'spill' current through the relay even require one.
without a fault being present, thus limiting the
When a stabilising resistor is used, the relay current
sensitivity that can be obtained. Figure 10.4 illustrates
setting can be reduced to any practical value, the relay
the equivalent circuit of the circulating current scheme.
now being a voltage-measuring device. There is
If a high impedance relay is used, then unless the relay is
obviously a lower limit, below which the relay element
located at point J in the circuit, a current will flow
does not have the sensitivity to pick up. Relay
through the relay even with currents IPg and IPh0 , being
calibration can in fact be in terms of voltage. For more
identical. If a low impedance relay is used, voltage FF'
details, see reference [10.2].
will be very small, but the CT exciting currents will be
unequal due to the unequal burdens and relay current IR
will still be non-zero. 10.4.2 Bias
The 'spill' current in the relay arising from these various
sources of error is dependent on the magnitude of the
through current, being negligible at low values of
through-fault current but sometimes reaching a
disproportionately large value for more severe faults.
Setting the operating threshold of the protection above
the maximum level of spill current produces poor
sensitivity. By making the differential setting
approximately proportional to the fault current, the low-
level fault sensitivity is greatly improved. Figure 10.5
illustrates a typical bias characteristic for a modern relay
that overcomes the problem. At low currents, the bias is
small, thus enabling the relay to be made sensitive. At
higher currents, such as would be obtained from inrush or
through fault conditions, the bias used is higher, and thus
the spill current required to cause operation is higher. The
relay is therefore more tolerant of spill current at higher
fault currents and therefore less likely to maloperate,
while still being sensitive at lower current levels.
Figure 10.8: Typical static circulating current feeder unit protection circuit diagram
10.8 DIGITAL/NUMERICAL CURRENT operate as a result. In older protection schemes, the
DIFFERENTIAL PROTECTION SYSTEMS problem was eliminated by delta connection of the CT
secondary windings. For a digital or numerical relay, a
A digital or numerical unit protection relay may typically
selectable software zero sequence filter is typically
provide phase-segregated current differential protection.
employed.
This means that the comparison of the currents at each
relay is done on a per phase basis. For digital data The problem remains of compensating for the time
communication between relays, it is usual that a direct difference between the current measurements made at
optical connection is used (for short distances) or a the ends of the feeder, since small differences can upset
multiplexed link. Link speeds of up to 64kbit/s (56kbit/s the stability of the scheme, even when using fast direct
in N. America) are normal. Through current bias is fibre-optic links. The problem is overcome by either time
typically applied to provide through fault stability in the synchronisation of the measurements taken by the
event of CT saturation. A dual slope bias technique relays, or calculation of the propagation delay of the link
(Figure 10.5) is used to enhance stability for through continuously.
faults. A typical trip criterion is as follows:
Relays A and B sample signals at time TA1,TA2 ...and communication channels under well-defined conditions.
TB1TB2 ...respectively. The times will not be coincident,
The technique can also be used with all types of pilots,
even if they start coincidentally, due to slight differences
subject to provision of appropriate interfacing devices.
in sampling frequencies. At time TA1, relay A transmits
its data to relay B, containing a time tag and other data. Method (d) is also a robust technique. It involves both
Relay B receives it at time TA1 + Tp1 where Tp1 is the relays being capable of receiving a time signal from
propagation time from relay A to relay B. Relay B a GPS satellite. The propagation delay on each
records this time as time TB*. Relay B also sends communication channel is no longer required to be
messages of identical format to relay A. It transmits such known or calculated as both relays are synchronised to a
a message at time TB3 received by relay A at time common time signal. For the protection scheme to meet
TB3+Tp2 (say time TA*), where Tp2 is the propagation time the required performance in respect of availability and
from relay B to relay A. The message from relay B to maloperation, the GPS signal must be capable of reliable
relay A includes the time TB3, the last received time tag receipt under all atmospheric conditions. There is extra
from relay A (TA1) and the delay time between the arrival satellite signal receiving equipment required at both
time of the message from A (TB*) and TB3 - call this the ends of the line, which implies extra cost.
delay time Td. The total elapsed time is therefore: The minimum setting that can be achieved with such
techniques while ensuring good stability is 20% of CT
primary current.
If it is assumed that Tp1 = Tp2, then the value of Tp1 and Tp2
can be calculated, and hence also TB3. The relay B 10.8.2 Application to Mesh Corner
measured data as received at relay A can then be and 1 1/2 Breaker Switched Substations
adjusted to enable data comparison to be performed.
Relay B performs similar computations in respect of the These substation arrangements are quite common, and
data received from relay A (which also contains similar the arrangement for the latter is shown in Figure 10.10.
time information). Therefore, continuous measurement Problems exist in protecting the feeders due to the
of the propagation delay is made, thus reducing the location of the line CT's, as either Bus 1 or Bus 2 or both
possibility of maloperation due to this cause to a can supply the feeder. Two alternatives are used to
minimum. Comparison is carried out on a per-phase basis, overcome the problem, and they are illustrated in the
so signal transmission and the calculations are required Figure. The first is to common the line CT inputs (as
for each phase. A variation of this technique is available shown for Feeder A) and the alternative is to use a second
that can cope with unequal propagation delays in the two set of CT inputs to the relay (as shown for Feeder B).
power system currents since the systems are designed to
operate at much higher frequencies, but each medium
may be subjected to noise at the carrier frequencies that
may interfere with its correct operation. Variations of
signal level, restrictions of the bandwidth available for
relaying and other characteristics unique to each
medium influence the choice of the most appropriate
type of scheme. Methods and media for communication
are discussed in Chapter 8.
where
I1 = Positive phase sequence component I2
= Negative phase sequence component M,N =
Comparing this with Equation 10.4, a scheme using
constants
summation is potentially 1.667 times more sensitive
With the exception of three phase faults all internal than one using phase current for modulation.
faults give rise to negative phase sequence (NPS)
Even though the use of a negative value of M gives a
currents, I2, which are approximately in phase at the
lower value of IE than if it were positive, it is usually
ends of the line and therefore could form an ideal
preferred since the limiting condition of Im = 0 then
modulating quantity. In order to provide a modulating
applies at the load infeed end. Load and fault
signal during three phase faults, which give rise to
components are additive at the outfeed end so that a
positive phase sequence (PPS) currents, I 1 , only, a
correct modulating quantity occurs there, even with the
practical modulating quantity must include some
lowest fault levels. For operation of the scheme it is
response to I 1 , in addition to l2.
sufficient therefore that the fault current contribution
Typical values of the ratio M: N exceed 5:1, so that the from the load infeed end exceeds the effective setting.
modulating quantity is weighted heavily in favour of
For faults on B or C phases, the NPS components are
NPS, and any PPS associated with load current tends to
displaced by 120° or 240° with respect to the PPS
be swamped out on all but the highest resistance faults.
components. No simple cancellation can occur, but
For a high resistance phase-earth fault, the system instead a phase displacement is introduced. For tripping
remains well balanced so that load current IL is entirely to occur, Equation 10.2 must be satisfied, and to achieve
positive sequence. The fault contribution IF provides high dependability under these marginal conditions, a
equal parts of positive, negative and zero sequence small effective stability angle is essential. Figure 10.15
components IF / 3. Assuming the fault is on 'A' phase and illustrates operation near to the limits of earth fault
the load is resistive, all sequence components are in sensitivity.
phase at the infeed end G: Very sensitive schemes may be implemented by using
high values of M/N but the scheme then becomes more
sensitive to differential errors in NPS currents such as
the unbalanced components of capacitive current or spill
" 3 3
from partially saturated CT's.
and
Techniques such as capacitive current compensation and
6(7-0 At the outfeed reduction of M/N high fault levels may be required to
ensure stability of the scheme.
end load current is negative,
...Equation 10.6
ensure that during through faults, a High Set is never
operated when a Low Set has reset and potential race
conditions are often avoided by the transmitting of an
unmodulated (and therefore blocking) carrier for a short
time following the reset of low set; this feature is often
referred to as 'Marginal Guard.'
settings I1S and I2S respectively are as follows: Higher Precentage Bias Setting, k2 0.3-1.5
In - CT rated secondary current
Table 10.1: Relay Setting Ranges
Is2 = 2.0 pu
10.12 EXAMPLES k1 = 30%
k 2 = 150%
This section gives examples of setting calculations for
simple unit protection schemes. It cannot and is not To provide immunity from the effects of line charging
intended to replace a proper setting calculation for a current, the setting of IS1 must be at least 2.5 times the
particular application. It is intended to illustrate the steady-state charging current, i.e. 4.1A or 0.01 p.u., after
principles of the calculations required. The examples use taking into consideration the CT ratio of 400/1. The nearest
the ALSTOM MiCOM P541 Current Differential relay, available setting above this is 0.20 p.u. This gives the points
which has the setting ranges given in Table 10.1 for on the relay characteristic as shown in Figure 10.17. The
differential protection. The relay also has backup minimum operating current ldmin is related to the value
distance, high-set instantaneous, and earth-fault of IS1 by the formula
protection included in the basic model to provide a
complete 'one-box' solution of main and backup
protection.
and
10.12.2 Unit Protection of a Transformer Feeder Transformer turns ratio at nominal tap
10.13 REFERENCES
10.1 Merz-Price Protective Gear. K. Faye-Hansen and
G. Harlow. IEE Proceedings, 1911.
10.2 Protective Relays Application Guide - 3rd
Edition. ALSTOM Transmission and Distribution
Protection and Control, 1987.
11 . Distance Protection
11.1 INTRODUCTION
The problem of combining fast fault clearance with
selective tripping of plant is a key aim for the protection
of power systems. To meet these requirements, high-
speed protection systems for transmission and primary
distribution circuits that are suitable for use with the
automatic reclosure of circuit breakers are under
continuous development and are very widely applied.
Distance protection, in its basic form, is a non-unit
system of protection offering considerable economic and
technical advantages. Unlike phase and neutral
overcurrent protection, the key advantage of distance
protection is that its fault coverage of the protected
circuit is virtually independent of source impedance
variations.
11.3-RELAY PERFORMANCE
Distance relay performance is defined in terms of reach
accuracy and operating time. Reach accuracy is a
comparison of the actual ohmic reach of the relay under
practical conditions with the relay setting value in ohms.
Reach accuracy particularly depends on the level of
voltage presented to the relay under fault conditions.
The impedance measuring techniques employed in
particular relay designs also have an impact.
Operating times can vary with fault current, with fault
position relative to the relay setting, and with the point
on the voltage wave at which the fault occurs.
Depending on the measuring techniques employed in a
particular relay design, measuring signal transient errors, Figure 11.2: Typical impedance reach
such as those produced by Capacitor Voltage accuracy characteristics for Zone 1
11.3.2 Digital/Numerical Distance Relays
Digital/Numerical distance relays tend to have more
consistent operating times. They are usually slightly
slower than some of the older relay designs when
operating under the best conditions, but their maximum
operating times are also less under adverse waveform
conditions or for boundary fault conditions.
where:
Therefore :
or
..Equation 11.1
..Equation 11.4
where:
Ra = arc resistance (ohms) L
= length of arc (metres) I =
arc current (A)
On long overhead lines carried on steel towers with
overhead earth wires the effect of arc resistance can
usually be neglected. The effect is most significant on
short overhead lines and with fault currents below
2000A (i.e. minimum plant condition), or if the protected
line is of wood-pole construction without earth wires. In
the latter case, the earth fault resistance reduces the
effective earth-fault reach of a mho Zone 1 element to
such an extent that the majority of faults are detected in
Zone 2 time. This problem can usually be overcome by
using a relay with a cross-polarised mho or a polygonal
characteristic.
Where a power system is resistance-earthed, it should be
appreciated that this does not need to be considered
11.7.4.1 Third zone and busbar back-up zone To avoid this, a shaped type of characteristic may be
used, where the resistive coverage is restricted. With a
In this application it is used in conjunction with mho
'lenticular' characteristic, the aspect ratio of the lens
measuring units as a fault detector and/or Zone 3
is adjustable, enabling
measuring unit. So, with the reverse reach arranged to
it to be set to provide the maximum fault resistance
extend into the busbar zone, as shown in Figure 1l.10(a),
coverage consistent with non-operation under maximum
it will provide back-up protection for busbar faults. This
load transfer conditions.
facility can also be provided with quadrilateral
characteristics. A further benefit of the Zone 3 Figure 11.11 shows how the lenticular characteristic can
application is for Switch-on-to-Fault (SOTF) protection, tolerate much higher degrees of line loading than offset
where the Zone 3 time delay would be bypassed for a mho and plain impedance characteristics.
short period immediately following line energisation to
Reduction of load impedance from ZD3 to ZD1 will
allow rapid clearance of a fault anywhere along the
correspond to an equivalent increase in load current.
protected line.
Figure 11.12: Fully cross-polarised mho relay 11.7.6 Partially Cross-Polarised Mho Characteristic
characteristic with variations ofZ$/ZL ratio
Where a reliable, independent method of faulted phase
selection is not provided, a modern non-switched
distance relay may only employ a relatively small
percentage of cross polarisation.
.Equation 11.5
...Equation 11.6
.Equation 11.7
Z=KZL1
If there were infeeds at both ends of the line, the 11.10 DISTANCE RELAY APPLICATION PROBLEMS
impedance measured would be a superposition of any Distance relays may suffer from a number of difficulties
two of the above examples, with the relative magnitudes in their application. Many of them have been overcome
of the infeeds taken into account. in the latest numerical relays. Nevertheless, an
awareness of the problems is useful where a protection
This analysis shows that the relay can only measure an engineer has to deal with older relays that are already
impedance which is independent of infeed and earthing installed and not due for replacement.
arrangements if a proportion of the
residual current In=Ia+Ib+Ic is added to the phase 11.10.1 Minimum Voltage at Relay Terminals
current Ia. This technique is known as 'residual To attain their claimed accuracy, distance relays that do
compensation'. not employ voltage memory techniques require a
Most distance relays compensate for the earth fault minimum voltage at the relay terminals under fault
conditions by using an additional replica impedance ZN conditions. This voltage should be declared in the data
within the measuring circuits. Whereas the phase replica sheet for the relay. With knowledge of the sequence
impedances involved in the fault, or alternatively the
impedance Z1 is fed with the phase current at the
fault MVA, the system voltage and the earthing
relaying point, ZN is fed with the full residual current.
arrangements, it is possible to calculate the minimum
The value of ZN is adjusted so that for a fault at the
voltage at the relay terminals for a fault at the reach
reach point, the sum of the voltages developed across Z1
point of the relay. It is then only necessary to check that
and ZN equals the measured phase to neutral voltage in
the minimum voltage for accurate reach measurement
the faulted phase. can be attained for a given application. Care should be
The required setting for ZN can be determined by taken that both phase and earth faults are considered.
considering an earth fault at the reach point of the relay.
This is illustrated with reference to the A-N fault with
single earthing point behind the relay as in Figure 11.10.2 Minimum Length of Line
11.20(a). To determine the minimum length of line that can be
protected by a distance relay, it is necessary to check first
Voltage supplied from the VT's:
that any minimum voltage requirement of the relay for a
= I1 (Z 1+Z2+Z0) = I1 (2Z1+Z0 ) fault at the Zone 1 reach is within the declared
sensitivity for the relay. Secondly, the ohmic impedance
Voltage across the replica impedances:
of the line (referred if necessary to VT/CT secondary side
= IaZ1+INZN quantities) must fall within the ohmic setting range for
Zone 1 reach of the relay. For very short lines and
= Ia(Z1+ZN)
especially for cable circuits, it may be found that the
= 3I1(Z1+Z N ) circuit impedance is less than the minimum setting
Hence, the required setting of ZN for balance at the range of the relay. In such cases, an alternative method
of protection will be required.
reach point is given by equating the above two
expressions: A suitable alternative might be current differential
protection, as the line length will probably be short
enough for the cost-effective provision of a high
bandwidth communication link between the relays fitted ...Equation 11.8
at the ends of the protected circuit. However, the latest So, for relay balance:
numerical distance relays have a very wide range of
impedance setting ranges and good sensitivity with low
levels of relaying voltage, so such problems are now
rarely encountered. Application checks are still essential,
though. When considering earth faults, particular care Therefore the effective reach is
must be taken to ensure that the appropriate earth fault
loop impedance is used in the calculation.
...Equation 11.9
where:
ZR = relay reach setting ZF
= effective reach
An example of the over-reaching effect is when distance
relays are applied on parallel lines and one line is taken
Figure 11.21: Effect on distance relays
of infeed at the remote busbar
out of service and earthed at each end. This is covered
in Section 13.2.3.
In Figure 11.21, the relay at A will not measure the 11.10.5 Forward Reach Limitations
correct impedance for a fault on line section Zc due to
There are limitations on the maximum forward reach
current infeed IB. Consider a relay setting of ZA+Zc
setting that can be applied to a distance relay. For
For a fault at point F, the relay is presented with an example, with reference to Figure 11.6, Zone 2 of one line
impedance: section should not reach beyond the Zone 1 coverage of
the next line section relay. Where there is a link between 11.10.7 Voltage Transformer Supervision
the forward reach setting and the relay resistive
Fuses or sensitive miniature circuit breakers normally
coverage (e.g. a Mho Zone 3 element), a relay must not
protect the secondary wiring between the voltage
operate under maximum load conditions. Also, if the
transformer secondary windings and the relay terminals.
relay reach is excessive, the healthy phase-earth fault
units of some relay designs may be prone to operation Distance relays having:
for heavy reverse faults. This problem only affected older a. self-polarised offset characteristics encompassing
relays applied to three-terminal lines that have
the zero impedance point of the R/X diagram
significant line section length asymmetry. A number of
the features offered with modern relays can eliminate b. sound phase polarisation
this problem. c. voltage memory polarisation
may maloperate if one or more voltage inputs are
11.10.6 Power Swing Blocking removed due to operation of these devices.
Power swings are variations in power flow that occur For these types of distance relay, supervision of the voltage
when the internal voltages of generators at different inputs is recommended. The supervision may be provided by
points of the power system slip relative to each other. The external means, e.g. separate voltage supervision circuits, or
changes in load flows that occur as a result of faults and it may be incorporated into the distance relay itself. On
their subsequent clearance are one cause of power swings. detection of VT failure, tripping of the distance relay can be
inhibited and/or an alarm is given. Modern distance
A power swing may cause the impedance presented to a
protection relays employ voltage supervision that operates
distance relay to move away from the normal load area
from sequence voltages and currents. Zero or negative
and into the relay characteristic. In the case of a stable
sequence voltages and corresponding zero or negative
power swing it is especially important that the distance
sequence currents are derived. Discrimination between
relay should not trip in order to allow the power system
primary power system faults and wiring faults or loss of
to return to a stable conditions. For this reason, most
supply due to individual fuses blowing or MCB's being
distance protection schemes applied to transmission
opened is obtained by blocking the distance protection only
systems have a power swing blocking facility available.
when zero or negative sequence voltage is detected without
Different relays may use different principles for detection
the presence of zero or negative sequence current. This
of a power swing, but all involve recognising that the
arrangement will not detect the simultaneous loss of all
movement of the measured impedance in relation to the
three voltages and additional detection is required that
relay measurement characteristics is at a rate that is
operates for loss of voltage with no change in current, or a
significantly less than the rate of change that occurs
current less than that corresponding to the three phase
during fault conditions. When the relay detects such a
fault current under minimum fault infeed conditions. If
condition, operation of the relay elements can be
fast-acting miniature circuit breakers are used to protect
blocked. Power swing blocking may be applied
the VT secondary circuits, contacts from these may be used
individually to each of the relay zones, or on an all zones
to inhibit operation of the distance protection elements and
applied/inhibited basis, depending on the particular relay
prevent tripping.
used.
Various techniques are used in different relay designs to
inhibit power swing blocking in the event of a fault 11.11 OTHER DISTANCE RELAY FEATURES
occurring while a power swing is in progress. This is
A modern digital or numerical distance relay will often
particularly important, for example, to allow the relay to
incorporate additional features that assist the protection
respond to a fault that develops on a line during the dead
engineer in providing a comprehensive solution to the
time of a single pole autoreclose cycle.
protection requirements of a particular part of a network.
Some Utilities may designate certain points on the
Table 11.1 provides an indication of the additional features
network as split points, where the network should be
that may be provided in such a relay. The combination of
split in the event of an unstable power swing or pole-
features that are actually provided is manufacturer and
slipping occurring. A dedicated power swing tripping
relay model dependent, but it can be seen from the Table
relay may be employed for this purpose (see Section
that steady progression is being made towards a 'one-box'
11.7.8). Alternatively, it may be possible to achieve
solution that incorporates all the protection and control
splitting by strategically limiting the duration for which
requirements for a line or cable. However, at the highest
the operation a specific distance relay is blocked during
transmission voltages, the level of dependability required
power swing conditions.
for rapid clearance of any protected circuit fault will still
demand the use of two independent protection systems.
Fault Location (Distance to fault)
Instantaneous Overcurrent Protection
Tee'd feeder protection
Alternative setting groups
CT supervision
Check synchroniser
Auto-reclose
CB state monitoring
CB condition monitoring
CB control
Measurement of voltages, currents, etc.
Event Recorder
Disturbance Recorder
CB failure detection/logic
Direetional/Non-directional phase fault overcurrent protection
(backup to distance protection)
Directional/Non-directional earth fault overcurrent protection
(backup to distance protection)
Negative sequence protection
Under/Overvoltage protection
Stub-bus protection
Broken conductor detection
User-programmable scheme logic
Table 11.2: Distance relay parameters for example
Table 11,1: Additional features in a distance relay
R3G = 104
Ohm. R2G =
104Ohm R IG
= 104Ohm
This completes the setting of the relay. Table 11.2 also
shows the settings calculated.
12 • Distance Protection
Schemes
12.1 INTRODUCTION
Conventional time-stepped distance protection is
illustrated in Figure 12.1. One of the main disadvantages
of this scheme is that the instantaneous Zone 1
protection at each end of the protected line cannot be
set to cover the whole of the feeder length and is usually
set to about 80%. This leaves two 'end zones', each
being about 20% of the protected feeder length. Faults
in these zones are cleared in Zone 1 time by the
protection at one end of the feeder and in Zone 2 time
(typically 0.25 to 0.4 seconds) by the protection at the
other end of the feeder.
Since the signalling channel is keyed by over-reaching Zone 12.3.5 Weak Infeed Conditions
2 elements, the scheme reqi ires duplex communication
In the standard permissive over-reach scheme, as with
channels - one frequency for each direction of signalling.
the permissive under-reach scheme, instantaneous
If distance relays with mho characteristics are used, the clearance cannot be achieved for end-zone faults under
scheme may be more advantageous than the permissive weak infeed or breaker open conditions. To overcome
under-reaching scheme for protecting short lines, this disadvantage, two possibilities exist.
because the resistive coverage of the Zone 2 unit may be
The Weak Infeed Echo feature available in some
greater than that of Zone 1.
protection relays allows the remote relay to echo the trip
To prevent operation under current reversal conditions in signal back to the sending relay even if the appropriate
a parallel feeder circuit, it is necessary to use a current remote relay element has not operated. This caters for
reversal guard timer to inhibit the tripping of the forward conditions of the remote end having a weak infeed or
Zone 2 elements. Otherwise maloperation of the scheme circuit breaker open condition, so that the relevant
may occur under current reversal conditions, see Section remote relay element does not operate. Fast clearance
11.9.9 for more details. It is necessary only when the for these faults is now obtained at both ends of the line.
Zone 2 reach is set greater than 150% of the protected The logic is shown in Figure 12.10. A time delay (T 1,) is
line impedance. required in the echo circuit to prevent tripping of the
The timer is used to block the permissive trip and signal remote end breaker when the local breaker is tripped by
send circuits as shown in Figure 12.9. The timer is the busbar protection or breaker fail protection
energised if a signal is received and there is no operation associated with other feeders connected to the busbar.
of Zone 2 elements. An adjustable time delay on pick-up The time delay ensures that the remote end Zone 2
(tp) is usually set to allow instantaneous tripping to take element will reset by the time the echoed signal is
place for any internal faults, taking into account a received at that end.
possible slower operation of Zone 2. The timer will have
operated and blocked the 'permissive trip' and 'signal
send' circuits by the time the current reversal takes place.
Security against
maloperation due to:
Current reversal Special features required Special features required
13.1 INTRODUCTION
Chapters 10-12 have covered the basic principles of
protection for two terminal, single circuit lines whose
circuit impedance is due solely to the conductors used.
However parallel transmission circuits are often
installed, either as duplicate circuits on a common
structure, or as separate lines connecting the same two
terminal points via different routes. Also, circuits may
be multi-ended, a three-ended circuit being the most
common.
For economic reasons, transmission and distribution
lines can be much more complicated, maybe having
three or more terminals (multi-ended feeder), or with
more than one circuit carried on a common structure
(parallel feeders), as shown in Figure 13.1. Other
possibilities are the use of series capacitors or direct-
connected shunt reactors. The protection of such lines
is more complicated and requires the basic schemes
described in the above chapters to be modified.
The purpose of this chapter is to explain the special
requirements of some of these situations in respect of
protection and identify which protection schemes are
particularly appropriate for use in these situations.
13.2.2 Distance Protection If a fault occurs on a line that lies beyond the remote
terminal end of a parallel line circuit, the distance relay
There are a number of problems applicable to distance will under-reach for those zones set to reach into the
relays, as described in the following sections. affected line.
13.2.2.1 Current reversal on double circuit lines Analysis shows that under these conditions, because the
When a fault is cleared sequentially on one circuit of a relay sees only 50% (for two parallel circuits) of the
double circuit line with generation sources at both ends total fault current for a fault in the adjacent line section,
of the circuit, the current in the healthy line can reverse the relay sees the impedance of the affected section as
for a short time. Unwanted tripping of CB's on the twice the correct value. This may have to be allowed for
healthy line can then occur if a Permissive Over-reach or in the settings of Zones 2 and 3 of conventionally set
Blocking distance scheme (see Chapter 12) is used. distance relays.
Figure 13.2 shows how the situation can arise. The CB Since the requirement for the minimum reach of Zone 2
at D clears the fault at F faster than the CB at C. Before is to the end of the protected line section and the under-
CB D opens, the Zone 2 elements at A may see the fault reach effect only occurs for faults in the following line
and operate, sending a trip signal to the relay for CB B. section(s), it is not usually necessary to adjust Zone 2
The reverse looking element of the relay at CB B also impedance settings to compensate.
sees the fault and inhibits tripping of CB's A and B.
However, Zone 3 elements are intended to provide
However, once CB D opens, the relay element at A starts
backup protection to adjacent line sections and hence
to reset, while the forward looking elements at B pick up
the under-reaching effect must be allowed for in the
(due to current reversal) and initiate tripping. If the
impedance calculations.
reset times of the forward-looking elements of the relay
at A are longer than the operating time of the forward- 13.2.2.3 Behaviour of distance relays
looking elements at B, the relays will trip the healthy with earth faults on the protected
line. The solution is to incorporate a blocking time delay
When an earth fault occurs in the system, the voltage
that prevents the tripping of the forward-looking
applied to the earth fault element of the relay in one
elements of the relays and is initiated by the reverse-
circuit includes an induced voltage proportional to the
looking element. The time delay must be longer than the
zero sequence current in the other circuit.
reset times of the relay elements at A.
These currents are expressed below in terms of the line
and source parameters:
and
...Equation 13.1
where:
For the relay to measure the line impedance accurately, If only one of the parallel feeders is in service, the
the following condition must be met: protection in the remaining feeder measures the fault
impedance correctly, except when the feeder that is not
in service is earthed at both ends. In this case, the zero
sequence impedance network is as shown in Figure 13,5.
Humpage and Kandil [13.2] have shown that the
For a solid phase to earth fault at the theoretical reach apparent impedance presented to the relay under these
of the relay, the voltage and current in the faulty phase conditions is given by:
at the relaying point are given by:
...Equation 13.'.
The voltage and current fed into the relay are given by: Figure
13.S:
Zero
sequence
...Equation 13.3
where:
KR is the residual compensation factor KM
is the mutual compensation factor
impedance network
during single circuit
operation
■ 206 •
extreme effective per unit reaches for the relay are 0.67 Thus:
and 1. Relay over-reach is not a problem, as the
condition being examined is a fault in the protected
feeder, for which relay operation is desirable. It can also
be seen from Figure 13.4 that relay R is more likely to
under-reach. However the relay located at the opposite
line end will tend to over-reach. As a result, the Zone 1
13.2.3.4 Distance relay behaviour
characteristic of the relays at both ends of the feeder will
with earth faults on the parallel feeder
overlap for an earth fault anywhere in the feeder - see
Section 13.2.3.5 for more details. Although distance relays with mutual compensation
measure the correct distance to the fault, they may not
Satisfactory protection can be obtained with a transfer
operate correctly if the fault occurs in the adjacent
trip, under-reach type distance scheme. Further,
feeder. Davison and Wright [13.1] have shown that,
compensation for the effect of zero sequence mutual
while distance relays without mutual compensation will
impedance is not necessary unless a distance-to-fault
not over-reach for faults outside the protected feeder,
facility is provided. Some manufacturers compensate for
the relays may see faults in the adjacent feeder if mutual
the effect of the mutual impedance in the distance relay
compensation is provided. With reference to Figure 13.3,
elements, while others may restrict the application of
the amount of over-reach is highest when
compensation to the distance-to-fault function only.
Z"S1=Z"S2=Z"so=oo Under these conditions, faults
The latter is easy to implement in software for a
occurring in the first 43% of feeder A will appear to the
digital/numerical relay but is impractical in relays using
distance relay in feeder B to be within its Zone 1 reach.
older technologies. Compensation is achieved by
The solution is to limit the mutual compensation applied
injecting a proportion of the zero sequence current
to 150% of the zero sequence compensation.
flowing in the parallel feeder into the relay. However,
some Utilities will not permit this due to the potential 13.2.3.5 Distance relay behaviour
hazards associated with feeding a relay protecting one with single-circuit operation
circuit from a CT located in a different circuit. If only one of the parallel feeders is in service, the
For the relay to measure the line impedance accurately, protection in the remaining feeder measures the fault
the following condition must be met: impedance correctly, except when the feeder that is not
in service is earthed at both ends. In this case, the zero
sequence impedance network is as shown in Figure 13.5.
Humpage and Kandil [13.2] have shown that the
apparent impedance presented to the relay under these
For a solid phase to earth fault at the theoretical reach conditions is given by:
of the relay, the voltage and current in the faulty phase
at the relaying point are given by:
...Equation 114
where:
...Equation 13.2
IR is the current fed into the relay =
IA + KRIA0
The voltage and current fed into the relay are given by:
...Equation 13.3
where:
KR is the residual compensation factor KM
is the mutual compensation factor
Figure 13.5: Zero sequence impedance network
during single circuit operation
The ratio IAO/IR varies with the system conditions, protection of two-ended feeders can also be used for
reaching a maximum when the system is earthed behind multi-ended feeders. However, the problems involved in
the relay with no generation at that end. In this case, the application of these schemes to multi-ended feeders
the ratio IAO/IR is equal to ZL1/ZL0, and the apparent are much more complex and require special attention.
impedance presented to the relay is:
The protection schemes that can be used with multi-ended
feeders are unit protection and distance schemes. Each uses
some form of signalling channel, such as fibre-optic cable,
power line carrier or pilot wires. The specific problems that
It is apparent from the above formulae that the relay has may be met when applying these protections to multi-ended
a tendency to over-reach. Care should be taken when feeders are discussed in the following sections.
Zone 1 settings are selected for the distance protection of
lines in which this condition may be encountered. In order
to overcome this possible over-reaching effect, some 13.3.1 A.C. Pilot Wire Protection
Utilities reduce the reach of earth fault relays to around
A.C. pilot wire relays provide a low-cost fast protection;
0.65ZL1 when lines are taken out of service. However, the
they are insensitive to power swings and, owing to their
probability of having a fault on the first section of the
relative simplicity, their reliability is excellent.
following line while one line is out of service is very small,
and many Utilities do not reduce the setting under this The limitations of pilot wire relays for plain feeder
condition. It should be noted that the use of mutual protection also apply. The length of feeder that can be
compensation would not overcome the over-reaching protected is limited by the characteristics of the pilot
effect since earthing clamps are normally placed on the wires. The protection sees increasing pilot wire resistance
line side of the current transformers. as tending to an open circuit and shunt capacitance as an
a.c. short circuit across the pilots. The protection will have
Typical values of zero sequence line impedances for HV
limiting values for each of these quantities, and when
lines in the United Kingdom are given in Table 13.1,
these are exceeded, loss of sensitivity for internal faults
where the maximum per unit over-reach error
and maloperation for external faults may occur. For tee'd
(ZM0lZL0)2 is also given. It should be noted that the over-
feeders, the currents for an external earth fault will not
reach values quoted in this table are maxima, and wilt be
usually be the same. The protection must be linear for any
found only in rare cases. In most cases, there will be
current up to the maximum through-fault value. As a
generation at both ends of the feeder and the amount of
result, the voltage in the pilots during fault conditions
over-reach will therefore be reduced. In the
cannot be kept to low values, and pilot wires with 250V
calculations carried out by Humpage and Kandil, with
insulation grade are required.
more realistic conditions, the maximum error found in a
400kV double circuit line was 18.6%.
13.3.2 Balanced Voltage Schemes for Tee'd Circuits
In this section two types of older balanced voltage
schemes still found in many locations are described.
13.3.2.1 'Translay' balanced voltage protection
This is a modification of the balanced voltage scheme
described in Section 10.7.1. Since it is necessary to
maintain linearity in the balancing circuit, though not in
Table 13. 1. Maximum over-reach errors found
during single circuit working the sending element, the voltage reference is derived
from separate quadrature transformers, as shown in
13.3 MULTI-ENDED FEEDERS Figure 13.6. These are auxiliary units with summation
- UNIT PROTECTION SCHEMES windings energized by the main current transformers in
series with the upper electromagnets of the sensing
A multi-ended feeder is defined as one having three or elements. The secondary windings of the quadrature
more terminals, with either load or generation, or both, current transformers at all ends are interconnected by
at any terminal. Those terminals with load only are the pilots in a series circuit that also includes the lower
usually known as 'taps'. electromagnets of the relays. Secondary windings on the
The simplest multi-terminal feeders are three-ended, and relay elements are not used, but these elements are
are generally known as tee'd feeders. This is the type fitted with bias loops in the usual way.
most commonly found in practice. The plain feeder settings are increased in the tee'd
The protection schemes described previously for the scheme by 50% for one tee and 75% for two.
13.3.3 Power Line Carrier Phase Comparison Schemes
The operating principle of these protection schemes has
already been covered in detail in Section 10.9. It
involves comparing the phase angles of signals derived
from a combination of the sequence currents at each
end of the feeder. When the phase angle difference
exceeds a pre-set value, the 'trip angle', a trip signal is
sent to the corresponding circuit breakers. In order to
prevent incorrect operation for external faults, two
different detectors, set at different levels, are used. The
low-set detector starts the transmission of carrier signal,
while the high-set detector is used to control the trip
output. Without this safeguard, the scheme could
operate incorrectly for external faults because of
operating tolerances of the equipment and the
Figure 13.6: Balanced voltage Tee'd feeder scheme capacitive current of the protected feeder. This
condition is worse with multi-terminal feeders, since the
13.3.2.2 High - speed protection type DSB7 currents at the feeder terminals can be very dissimilar
This type is of higher speed and is shown in Figure 13.7. for an external fault. In the case of the three-terminal
Summation quadrature transformers are used to provide feeder in Figure 13.8, if incorrect operation is to be
the analogue quantity, which is balanced in a series loop avoided, it is necessary to make certain that the low-set
through a pilot circuit. Separate secondary windings on detector at end A or end B is energized when the
the quadrature current transformers are connected to current at end C is high enough to operate the high-set
full-wave rectifiers, the outputs of which are connected detector at that end. As only one low-set starter, at end
in series in a second pilot loop, so that the electromotive A or end B, needs to be energized for correct operation,
forces summate arithmetically. the most unfavourable condition will be when currents
The measuring relay is a double-wound moving coil type, IA and IB are equal. To maintain stability under this
one coil being energized from the vectorial summation condition, the high-set to low-set setting ratio of the
loop; the other receives bias from the scalar summation fault detectors needs to be twice as large as that
in the second loop proportional to the sum of the required when the scheme is applied to a plain feeder.
currents in the several line terminals, the value being This results in a loss of sensitivity, which may make the
adjusted by the inclusion of an appropriate value of equipment unsuitable if the minimum fault level of the
resistance. Since the operating and biasing quantities power system is low.
are both derived by summation, the relays at the
different terminals all behave alike, either to operate or
to restrain as appropriate.
Special features are included to ensure stability, both in
the presence of transformer inrush current flowing
through the feeder zone and also with a 2-1-1
distribution of fault current caused by a short circuit on
the secondary side of a star-delta transformer.
13.3.4 Differential Relay using Optical Fibre The bias feature is necessary in this scheme because it is
Signalling Current differential relays can provide unit designed to operate from conventional current
protection for multi-ended circuits without the transformers that are subject to transient transformation
restrictions associated with other forms of protection. In errors.
Section 8.6.5, the characteristics of optical fibre cables The two quantities are:
and their use in protection signalling are outlined.
Their use in a three-ended system is shown in Figure
13.10, where the relays at each line end are
digital/numerical relays interconnected by optical fibre
links so that each can send information to the others. In
practice the optical fibre links can be dedicated to the Figure 13.11 shows the percentage biased differential
protection system or multiplexed, in which case characteristic used, the tripping criteria being:
multiplexing equipment, not shown in Figure 13.10, will
be used to terminate the fibres.
and
where:
K = percentage bias setting
Is = minimum differential current setting
If the magnitudes of the differential currents indicate
that a fault has occurred, the relays trip their local circuit
breaker.
Figure 13.10: Current differential protection
for tee'd feeders using optical fibre signalling
The relays also continuously monitor the communication the relay in this case can be expressed in terms of the
channel performance and carry out self-testing and source impedances as follows:
diagnostic operations. The system measures individual
phase currents and so single phase tripping can be used
when required. Relays are provided with software to re-
configure the protection between two and three terminal
lines, so that modification of the system from two
The magnitude of the third term in this expression is a
terminals to three terminals does not require relay
function of the total impedances of the branches A and
replacement. Further, loss of a single communications
B and can reach a relatively high value when the fault
link only degrades scheme performance slightly. The
current contribution of branch C is much larger than
relays can recognise this and use alternate
that of branch A. Figure 13.13 illustrates how a
communications paths. Only if all communication paths
distance relay with a mho characteristic located at A
from a relay fail does the scheme have to revert to
with a Zone 2 element set to 120% of the protected
backup protection.
feeder AB, fails to see a fault at the remote busbar B.
The 'tee' point T in this example is halfway between
13.4 MULTI-ENDED FEEDERS - DISTANCE RELAYS substations A and B (ZLA= ZLB) and the fault currents
IA and Ic have been assumed to be identical in
Distance protection is widely used at present for tee'd magnitude and phase angle. With these conditions, the
feeder protection. However, its application is not fault appears to the relay to be located at B' instead of
straightforward, requiring careful consideration and
at B - i.e. the relay appears to under-reach.
systematic checking of all the conditions described later
in this section.
Most of the problems found when applying distance
protection to tee'd feeders are common to all schemes.
A preliminary discussion of these problems will assist in
the assessment of the performance of the different types
of distance schemes.
or
...Equation 13.5
or
The main requirement for transfer trip under-reach The setting of the directional unit should be such that no
schemes is that the Zone 1 of the protection, at one end maloperation can occur for faults in the reverse
at least, shall see a fault in the feeder. In order to meet direction; case 5 in Table 13.2.
this requirement, the Zone 1 characteristics of the relays
at different ends must overlap, either the three of them
13.5.4 Signalling Channel Considerations
or in pairs. Cases 1, 2 and 3 in Table 13.2 should be
checked when the settings for the Zone 1 characteristics The minimum number of signalling channels required
are selected. If the conditions mentioned in case 4 are depends on the type of scheme used. With under-reach
found, direct transfer trip may be used to clear the fault; and blocking schemes, only one channel is required,
the alternative is sequentially at end C when the fault whereas a permissive over-reach scheme req-uires as
current Ic reverses after the circuit breaker at terminal B many channels as there are feeder ends. The signalling
has opened; see Figure 13.18. channel equipment at each terminal should include one
transmitter and (N-1) receivers, where N is the total
Transfer trip schemes may be applied to feeders that number of feeder ends. This may not be a problem if
have branches of similar length. If one or two of the fibre-optic cables are used, but could lead to problems
branches are very short, and this is often the case in otherwise.
tee'd feeders, it may be difficult or impossible to make
the Zone 1 characteristics overlap. Alternative schemes If frequency shift channels are used to improve the
are then required. reliability of the protection schemes, mainly with
transfer trip schemes, N additional frequencies are
Another case for which under-reach schemes may be required for the purpose. Problems of signal attenuation
advantageous is the protection of tapped feeders, mainly and impedance matching should also be carefully
when the tap is short and is not near one of the main considered when power line carrier frequency channels
terminals. Overlap of the Zone 1 characteristics is then are used.
easily achieved, and the tap does not require protection
applied to the terminal.
13.5.5 Directional Comparison Blocking Schemes
The principle of operation of these schemes is the same
13.5.2 Transfer Trip Over-Reach Schemes
as that of the distance blocking schemes described in
For correct operation when internal faults occur, the the previous section. The main advantage of directional
relays at the three ends should see a fault at any point comparison schemes over distance schemes is their
in the feeder. This condition is often difficult to meet, greater capability to detect high-resistance earth faults.
since the impedance seen by the relays for faults at one The reliability of these schemes, in terms of stability for
of the remote ends of the feeder may be too large, as in through faults, is lower than that of distance blocking
case 1 in Table 13.2, increasing the possibility of schemes. However, with the increasing reliability of
maloperation for reverse faults, case 5 in Table 13.2. In modern signalling channels, directional comparison
addition, the relay characteristic might encroach on the blocking schemes seem to offer good solutions to the
load impedance. many and difficult problems encountered in the
protection of multi-ended feeders. Modern relays
implement the required features in different ways -
for further information see Chapter 12 and specific
relay manuals.
3Z1
For Lines 1 and 2,
Hence,
R3ph=84.8
Ohm
R2ph=84.8
Ohm
R1ph=84.8
Ohm
Kz1=0.8xKZ0
=0.8x0.532
=0.426
since the two parallel lines are identical, and hence, for
Lines 1 and 2,
and hence
% Under-reach = 14.3%
This amount of under-reach is not significant and no
adjustment need be made. If adjustment is required, this
can be achieved by using the Kz2 relay setting,
increasing it over the KZ0 setting by the percentage
under-reach. When this is done, care must also be taken
that the percentage over-reach during single circuit
operation is not excessive - if it is then use can be made
of the alternative setting groups provided in most
modern distance relays to change the relay settings
according to the number of circuits in operation.
13.7.1 11 Ground fault resistive reach settings
The same settings can be used as for the phase fault
resistive reaches. Hence,
R3G = 84.8
Ohm R2G =
84.8 Ohm
R1G = 84.8
Ohm
This completes the setting of the relay. Table 13.3 also
shows the settings calculated.
13.8 REFERENCES
13.1 Some factors affecting the accuracy of distance
type protective eguipment under earth fault
conditions. Davison, E.B. and Wright, A. Proc.
IEE Vol. 110, No. 9, Sept. 1963, pp. 1678-1688.
13.2 Distance protection performance under
conditions of single-circuit working in double-
circuit transmission lines. Humpage, W.D. and
Kandil, M.S. Proc. IEE. Vol. 117. No. 4, April
1970, pp. 766-770.
13.3 Distance protection of tee'd circuits. Humpage,
W.A. and Lewis, D.W. Proc. IEE, Vol. 114, No. 10,
Oct. 1967, pp. 1483-1498.
14 • Auto-Reclosing
The weighting given to the above factors is different for mainly to radial feeders where problems of system
HV distribution networks and EHV transmission systems stability do not arise, and the main advantages to be
and therefore it is convenient to discuss them under derived from its use can be summarised as follows:
separate headings. Sections 14.3 and 14.4 cover the a. reduction to a minimum of the interruptions of
application of auto-reclosing to HV distribution networks supply to the consumer
while Sections 14.5-14.9 cover EHV schemes. The rapid b. instantaneous fault clearance can be introduced, with
expansion in the use of auto-reclosing has led to the the accompanying benefits of shorter fault duration,
existence of a variety of different control schemes. The less fault damage, and fewer permanent faults
various features in common use are discussed in Section
14.10. The related subject of auto-closing, that is, the As 80% of overhead line faults are transient, elimination
automatic closing of normally open circuit breakers, of loss of supply from this cause by the introduction of
is dealt with in Section 14.11. auto-reclosing gives obvious benefits through:
Figure 14.3: Typical circuit breaker trip-close Where fault levels are low, it may be difficult to select
operation times I.D.M.T. time settings to give satisfactory grading with an
operating time limit of 15 seconds, and the matter
14.4.1.4 De-ionisation of fault path becomes a question of selecting a reclaim time
compatible with I.D.M.T. requirements.
As mentioned above, successful high speed reclosure
requires the interruption of the fault by the circuit It is common to fit sensitive earth-fault protection to
breaker to be followed by a time delay long enough to supplement the normal protection in order to detect high
allow the ionised air to disperse. This time is dependent resistance earth faults. This protection cannot possibly
on the system voltage, cause of fault, weather conditions be stable on through faults, and is therefore set to have
an operating time longer than that of the main
and so on, but at voltages up to 66kV, 0.1s-0.2s should
protection. This longer time may have to be taken into
be adequate. On HV systems, therefore, fault de-
consideration when deciding on a reclaim time. A broken
ionisation time is of less importance than circuit breaker
overhead conductor in contact with dry ground or a
time delays.
wood fence may cause this type of fault. It is rarely if
14.4.1.5 Protection reset time ever transient and may be a danger to the public. It is
If time delayed protection is used, it is essential that the therefore common practice to use a contact on the
timing device shall fully reset during the dead time, so sensitive earth fault relay to block auto-reclosing and
that correct time discrimination will be maintained after lock out the circuit breaker.
reclosure on to a fault. The reset time of the Where high-speed protection is used, reclaim times of 1
electromechanical I.D.M.T. relay is 10 seconds or more second or less would be adequate. However, such shod
times are rarely used in practice, to relieve the duty on conditions, the amount of synchronising power
the circuit breaker. transmitted, P, crosses the power/angle curve OAB at
point X, showing that the phase displacement between
14.4.2.2 Spring winding time
the two systems is Under fault conditions, the
The reclaim time of motor-wound spring-closed breakers curve OCB is applicable, and the operating point changes
must be at least as long as the spring winding time, to to Y. Assuming constant power input to both ends of the
ensure that the breaker is not subjected to a further line, there is now an accelerating power XY. As a result,
reclosing operating with a partly wound spring. the operating point moves to Z, with an increased phase
displacement, between the two systems. At this
point the circuit breakers trip and break the connection.
14.4.3 Number of Shots The phase displacement continues to increase at a rate
There are no definite rules for defining the number of dependent on the inertia of the two power sources. To
shots for any particular auto-reclose application, but a maintain synchronism, the circuit breaker must be
number of factors must be taken into account. reclosed in a time short enough to prevent the phase
angle exceeding This angle is such that the area
14.4.3.1 / Circuit breaker limitations (2) stays greater than the area (1), which is the condition
Important considerations are the ability of the circuit for maintenance of synchronism.
breaker to perform several trip and close operations in
quick succession and the effect of these operations on
the maintenance period. Maintenance periods vary
according to the type of circuit breaker used and the
fault current broken when clearing each fault. Use of
modern numerical relays can assist, as they often have a
CB condition-monitoring feature included that can be
arranged to indicate to a Control Centre when
maintenance is required. Auto-reclose may then be
locked out until maintenance has been carried out.
14.4.3.2 System conditions
If statistical information on a particular system shows a
moderate percentage of semi-permanent faults that
could be burned out during 2 or 3 time-delayed trips, a
multi-shot scheme may be justified. This is often the
case in forest areas. Another situation is where fused
'tees' are used and the fault level is low, since the fusing
time may not discriminate with the main I.D.M.T. relay. Figure 14.4: Effect of high-speed three-
The use of several shots will heat the fuse to such an phase
auto-reclosing on system stability for a weak system
extent that it would eventually blow before the main
protection operated.
This example, for a weak system, shows that the
successful application of auto-reclosing in such a case
needs high-speed protection and circuit breakers, and a
14.5AUTO-RECLOSING ON EHV TRANSMISSION
LINES short dead time. On strong systems, synchronism is
unlikely to be lost by the tripping out of a single line. For
The most important consideration in the application of such systems, an alternative policy of delayed auto-
auto-reclosing to EHV transmission lines is the reclosing may be adopted. This enables the power
maintenance of system stability and synchronism. The swings on the system resulting from the fault to decay
problems involved are dependent on whether the before reclosure is attempted.
transmission system is weak or strong. With a weak
system, loss of a transmission link may lead quickly to an The various factors to be considered when using EHV
excessive phase angle across the CB used for re-closure, auto-reclose schemes are now dealt with. High-speed
thus preventing a successful re-closure. In a relatively and delayed auto-reclose schemes are discussed
strong system, the rate of change of phase angle will be separately.
slow, so that delayed auto-reclose can be successfully
applied.
14.6 HIGH SPEED AUTO-RECLOSING ON EHV SYSTEMS
An illustration is the interconnector between two power
The first requirement for the application of high-speed
systems as shown in Figure 14.4. Under healthy
auto-reclosing is knowledge of the system disturbance
time that can be tolerated without loss of system the dead time required. This is a particular problem on
stability. This will normally require transient stability long distance EHV transmission lines.
studies to be conducted for a defined set of power
system configurations and fault conditions. With
knowledge of protection and circuit breaker operating 14.6.3 Circuit Breaker Characteristics
characteristics and fault arc de-ionisation times, the The high fault levels involved in EHV systems imposes a
feasibility of high-speed auto-reclosing can then be very severe duty on the circuit breakers used in high-
assessed. These factors are now discussed. speed auto-reclose schemes. The accepted breaker cycle
of break-make-break requires the circuit breaker to
interrupt the fault current, reclose the circuit after a
14.6.1 Protection Characteristics
time delay of upwards of 0.2s and then break the fault
The use of high-speed protection equipment, such as current again if the fault persists. The types of circuit
distance or unit protection schemes, giving operating breaker commonly used on EHV systems are oil, air blast
times of less than 50ms, is essential. In conjunction with and SF6 types.
fast operating circuit breakers, high-speed protection
14.6.3.1 Oil circuit breakers
reduces the duration of the fault arc and thus the total
system disturbance time. Oil circuit breakers are used for transmission voltages up
to 300kV, and can be subdivided into the two types: 'bulk
It is important that the circuit breakers at both ends of a
oil' and 'small oil volume'. The latter is a design aimed at
fault line should be tripped as rapidly as possible. The
reducing the fire hazard associated with the large
time that the line is still being fed from one end
volume of oil contained in the bulk oil breaker.
represents an effective reduction in the dead time, and
may well jeopardise the chances of a successful The operating mechanisms of oil circuit breakers are of
reclosure. When distance protection is used, and the two types, 'fixed trip' and 'trip free', of which the latter
fault occurs near one end of the line, special measures is the most common. With trip-free types, the reclosing
have to be adopted to ensure simultaneous tripping at cycle must allow time for the mechanism to reset after
each end. These are described in Section 14.8. tripping before applying the closing impulse.
Special means have to be adopted to obtain the short
dead times required for high-speed auto-reclosing.
14.6.2 De-ionisation of Fault Arc
Various types of tripping mechanism have been
It is important to know the time that must be allowed for developed to meet this requirement.
complete de-ionisation of the arc, to prevent the arc
The three types of closing mechanism fitted to oil circuit
restriking when the voltage is re-applied.
breakers are:
The de-ionisation time of an uncontrolled arc, in free air
depends on the circuit voltage, conductor spacing, fault i. solenoid
currents, fault duration, wind speed and capacitive ii. spring
coupling from adjacent conductors. Of these, the circuit iii. pneumatic
voltage is the most important, and as a general rule, the CB's with solenoid closing are not suitable for high-
higher the voltage the longer the time required for de- speed auto-reclose due to the long time constant
ionisation. Typical values are given in Table 14.1. involved. Spring, hydraulic or pneumatic closing
mechanisms are universal at the upper end of the EHV
f Line voltage (kV) Minimum de-energisation time range and give the fastest closing time. Figure 14.3
[seconds) shows the operation times for various types of EHV
66
circuit breakers, including the dead time that can be
110 0.28
132 0.3
attained.
220 0.35 14.6.3.2 Air blast circuit breakers
275 0.38
400 0.45 Air blast breakers have been developed for voltages up to
525 0.55 the highest at present in use on transmission lines. They
fall into two categories:
Table 14.1: Fault-arc de-ionisation times a. pressurised head circuit breakers
b. non-pressurised head circuit breakers
If single-phase tripping and auto-reclosing is used, In pressurised head circuit breakers, compressed air is
capacitive coupling between the healthy phases and the maintained in the chamber surrounding the main
faulty phase tends to maintain the arc and hence extend contacts. When a tripping signal is received, an auxiliary
air system separates the main contacts and allows the circuit breakers are locked out after one unsuccessful
compressed air to blast through the gap to the attempt. Also, the incidence of semi-permanent faults
atmosphere, extinguishing the arc. With the contacts which can be cleared by repeated reclosures is less likely
fully open, compressed air is maintained in the chamber. than on HV systems.
Loss of air pressure could result in the contacts reclosing,
or, if a mechanical latch is employed, restriking of the arc 14.7 SINGLE-PHASE AUTO-RECLOSING
in the de-pressurised chamber. For this reason,
sequential series isolators, which isolate the main Single phase to earth faults account for the majority of
contacts after tripping, are commonly used with air blast overhead line faults. When three-phase auto-reclosing
breakers. Since these are comparatively slow in opening, is applied to single circuit interconnectors between two
their operation must be inhibited when auto-reclosing is power systems, the tripping of all three phases may
required. A contact on the auto-reclose relay is made cause the two systems to drift apart in phase, as
available for this purpose. described in Section 14.5. No interchange of
synchronising power can take place during the dead
Non-pressurised head circuit breakers are slower in
time. If only the faulty phase is tripped, synchronising
operation than the pressurised head type and are not power can still be interchanged through the healthy
usually applied in high-speed reclosing schemes. phases. Any difference in phase between the two
3.3 SF6 circuit breakers systems will be correspondingly less, leading to a
reduction in the disturbance on the system when the
Most EHV circuit breaker designs now manufactured use
circuit breaker recloses.
5F6 gas as an insulating and arc-quenching medium. The
basic design of such circuit breakers is in many ways For single-phase auto-reclosing each circuit breaker pole
similar to that of pressurised head air blast circuit must be provided with its own closing and tripping
breakers, and normally retain all, or almost all, of their mechanism; this is normal with EHV air blast and SF6
voltage withstand capability, even if the SF6 pressure level breakers. The associated tripping and reclosing circuitry
falls to atmospheric pressure. Sequential series isolators is therefore more complicated, and, except in distance
are therefore not normally used, but they are sometimes schemes, the protection may need the addition of phase
specified to prevent damage to the circuit breaker in the selection logic.
event of a lightning strike on an open ended conductor. On the occurrence of a phase-earth fault, single-phase
Provision should therefore be made to inhibit sequential auto-reclose schemes trip and reclose only the
series isolation during an auto-reclose cycle. corresponding pole of the circuit breaker. The auto-
reclose function in a relay therefore has three separate
elements, one for each phase. Operation of any element
14.6.4 Choice of Dead Time
energises the corresponding dead timer, which in turn
At voltages of 220kV and above, the de-ionisation time initiates a closing pulse for the appropriate pole of the
will probably dictate the minimum dead time, rather circuit breaker. A successful reclosure results in the auto-
than any circuit breaker limitations. This can be deduced reclose logic resetting at the end of the reclaim time,
from Table 14.1. The dead time setting on a high-speed ready to respond to a further fault incident. If the fault
auto-reclose relay should be long enough to ensure Is persistent and reclosure is unsuccessful, it is usual to
complete de-ionisation of the arc. On EHV systems, an trip and lock out all three poles of the circuit breaker.
unsuccessful reclosure is more detrimental to the system The above describes only one of many variants. Other
than no reclosure at all. possibilities are:
a. three-phase trip and lockout for phase-phase or 3-
14.6.5 Choice of Reclaim Time phase faults, or if either of the remaining phases
should develop a fault during the dead time
Where EHV oil circuit breakers are concerned, the
reclaim time should take account of the time needed for b. use of a selector switch to give a choice of single
the closing mechanism to reset ready for the next or three-phase reclosing
reclosing operation. c. combined single and three-phase auto-reclosing;
single phase to earth faults initiate single-phase
tripping and reclosure, and phase-phase faults
14.6.6 Number of Shots initiate three-phase tripping and reclosure
High-speed auto-reclosing on EHV systems is invariably Modern numerical relays often incorporate the logic for
single shot. Repeated reclosure attempts with high fault all of the above schemes, for the user to select as
levels would have serious effects on system stability, so required. Use can be made of any user-definable logic
feature in a numerical relay to implement other schemes reclosing applied to the circuit breakers at each end of
that may be required. the feeder could result either in no dead time or in a
dead time insufficient to allow de-ionisation of the fault
The advantages of single-phase auto-reclosing are:
arc. A transient fault could therefore be seen as a
a. the maintenance of system integrity permanent one, resulting in the locking out of both
b. on multiple earth systems, negligible interference circuit breakers.
with the transmission of load. This is because the Two methods are available for overcoming this difficulty.
current in the faulted phase can flow through Firstly, one of the transfer-trip or blocking schemes that
earth via the various earthing points until the fault involves the use of an intertrip signal between the two
is cleared and the faulty phase restored ends of the line can be used. Alternatively, a Zone 1
The main disadvantage is the longer de-ionisation time extension scheme may be used to give instantaneous
resulting from capacitive coupling between the faulty tripping over the whole line length. Further details of
and healthy lines. This leads to a longer dead time being these schemes are given in Chapter 12, but a brief
description of how they are used in conjunction with an
required. Maloperation of earth fault relays on double
auto-reclose scheme is given below.
circuit lines owing to the flow of zero sequence currents
may also occur. These are induced by mutual induction
between faulty and healthy lines (see Chapter 13 for
14.8.1 Transfer-Trip or Blocking Schemes
details).
This involves use of a signalling channel between the two
ends of the line. Tripping occurs rapidly at both ends of
14.8 HIGH-SPEED AUTO-RECLOSING ON LINES the faulty line, enabling the use of high-speed auto-
EMPLOYING DISTANCE SCHEMES reclose. Some complication occurs if single-phase auto-
reclose is used, as the signalling channel must identify
The importance of rapid tripping of the circuit breakers
which phase should be tripped, but this problem does not
at each end of a faulted line where high-speed auto-
exist if a modern numerical relay is used.
reclosing is employed has already been covered in
Section 14.6. Simple distance protection presents some Irrespective of the scheme used, it is customary to
difficulties in this respect. provide an auto-reclose blocking relay to prevent the
circuit breakers auto-reclosing for faults seen by the
Owing to the errors involved in determining the ohmic
distance relay in Zones 2 and 3.
setting of the distance relays, it is not possible to set Zone
1 of a distance relay to cover 100% of the protected line -
see Chapter 11 for more details. Zone 1 is set to cover 80- 14.8.2 Zone 1 Extension
85% of the line length, with the remainder of the line
covered by time-delayed Zone 2 protection. In this scheme, the reach of Zone 1 is normally extended
to 120% of the line length and is reset to 80% when a
command from the auto-reclose logic is received. This
auto-reclose logic signal should occur before a closing
pulse is applied to the circuit breaker and remain operated
until the end of the reclaim time. The logic signal should
also be present when auto-reclose is out of service.
The solution is to have a standby transformer T4 Figure 14.8: Double busbar substation
permanently energised from the primary side and
arranged to be switched into service if one of the others
Bus section isolators enable sections of busbar to be
trips on fault.
isolated in the event of fault, and bus coupler breaker BC
The starting circuits for breaker CB4 monitor the permits sections of main and reserve bars to be
operation of transformer protection on any of the interconnected.
transformers T1, T2 and T3 together with the tripping
14.12.1.1 Basic scheme - banked transformers omitted
of an associated circuit breaker CB1-CB3. In the event
of a fault, the auto-close circuit is initiated and circuit Each line circuit breaker is provided with an auto-reclose
breaker CB4 closes, after a short time delay, to switch in relay that recloses the appropriate circuit breakers in the
event of a line fault. For a fault on Line 1, this would
require opening of CBl and the corresponding CB at the
remote end of the line. The operation of either the
busbar protection or a VT Buchholz relay is arranged to
lock out the auto-reclosing sequence. In the event of a
persistent fault on Line 1, the line circuit breakers trip
and lock out after one attempt at reclosure.
14.12.1.2 Scheme with banked transformers
Some utilities use a variation of the basic scheme in
which Transformers T1 and T2 are banked off Lines 1
and 2, as shown in Figure 14.8. This provides some Figure 14.9: Single switch substation
15.1 INTRODUCTION
The protection scheme for a power system should cover
the whole system against all probable types of fault.
Unrestricted forms of line protection, such as overcurrent
and distance systems, meet this requirement, although
faults in the busbar zone are cleared only after some
time delay. But if unit protection is applied to feeders
and plant, the busbars are not inherently protected.
Busbars have often been left without specific protection,
for one or more of the following reasons:
a. the busbars and switchgear have a high degree of
reliability, to the point of being regarded as
intrinsically safe
b. it was feared that accidental operation of busbar
protection might cause widespread dislocation of
the power system, which, if not quickly cleared,
would cause more loss than would the very
infrequent actual bus faults
c. it was hoped that system protection or back-up
protection would provide sufficient bus protection
if needed
It is true that the risk of a fault occurring on modern
metal-clad gear is very small, but it cannot be entirely
ignored. However, the damage resulting from one
uncleared fault, because of the concentration of fault
MVA, may be very extensive indeed, up to the complete
loss of the station by fire. Serious damage to or
destruction of the installation would probably result in
widespread and prolonged supply interruption.
Finally, system protection will frequently not provide the
cover required. Such protection may be good enough for
small distribution substations, but not for important
stations. Even if distance protection is applied to all
feeders, the busbar will lie in the second zone of all the
distance protections, so a bus fault will be cleared
relatively slowly, and the resultant duration of the
voltage dip imposed on the restof the system may not be
tolerable.
With outdoor switchgear the case is less clear since,
although the likelihood of a fault is higher, the risk of
widespread damage resulting is much less. In general
then, busbar protection is required when the system
protection does not cover the busbars, or when, in order
to maintain power system stability, high-speed fault incidence, amounting to no more than an average of one
clearance is necessary. Unit busbar protection provides fault per busbar in twenty years, it is clear that unless
this, with the further advantage that if the busbars are the stability of the protection is absolute, the degree of
sectionalised, one section only need be isolated to clear disturbance to which the power system i.s likely to be.
a fault. The case for unit busbar protection is in fact subjected may be increased by the installation of bus
strongest when there is sectionalisation. protection. The possibility of incorrect operation has, in
the past, led to hesitation in applying bus protection and
has also resulted in application of some very complex
1 5 . 2 BUSBAR FAULTS systems. Increased understanding of the response of
differential systems to transient currents enables such
The majority of bus faults involve one phase and earth,
systems to be applied with confidence in their
but faults arise from many causes and a significant
fundamental stability. The theory of differential
number are interphase clear of earth. In fact, a large
protection is given later in Section 15.7.
proportion of busbar faults result from human error
rather than the failure of switchgear components. Notwithstanding the complete stability of a correctly
applied protection system, dangers exist in practice fora
With fully phase-segregated metalclad gear, only earth
number of reasons. These are:
faults are possible, and a protection scheme need have
earth fault sensitivity only. In other cases, an ability to a. interruption of the secondary circuit of a current
respond to phase faults clear of earth is an advantage, transformer will produce an unbalance, which
although the phase fault sensitivity need not be very high. might cause tripping on load depending on the
relative values of circuit load and effective setting.
It would certainly do so during a through fault,
15.3 PROTECTION REQUIREMENTS producing substantial fault current in the circuit in
Although not basically different from other circuit question
protection, the key position of the busbar intensifies the b. a mechanical shock of sufficient severity may
emphasis put on the essential requirements of speed and cause operation, although the likelihood of this
stability. The special features of busbar protection are occurring with modern numerical schemes is
discussed below. reduced
Under external fault conditions, the current I1 flows Figure 15.4: Three zone frame
through the frame-leakage current transformer. If the earth scheme
insulation resistance is too low, sufficient current may
flow to operate the frame-leakage relay, and, as the check If it is inconvenient to insulate the section switch frame
feature is unrestricted, this will also operate to complete on one side, this switch may be included in that zone. It
the trip circuit. The earth resistance between the earthing is then necessary to intertrip the other zone after
electrode and true earth is seldom greater approximately 0.5 seconds if a fault persists after the
than1Ohm,so with 10Ohm insulation resistance the zone including the section switch has been tripped. This
current I1is limited to 10% of the total earth fault current is illustrated in Figure 15.5.
I1 and I2. For this reason, the recommended minimum
setting for the scheme is about 30% of the minimum
earth fault current.
All cable glands must be insulated, to prevent the
circulation of spurious current through the frame and
earthing system by any voltages induced in the cable
sheath. Preferably, the gland insulation should be
provided in two layers or stages, with an interposing
layer of metal, to facilitate the testing of the gland
insulation. A test level of 5kV from each side is suitable.
15.8 H I G H IMPEDANCE
DIFFERENTIAL PROTECTION
This form of protection is still in common use. The
considerations that have to be taken into account are
detailed in the following sections.
The incidence of fault current with an initial unilateral The current transformers are replaced in the diagram by
transient component causes an abnormal built-up of flux ideal current transformers feeding an equivalent circuit
in a current transformer, as described in Section 6.4.10. that represents the magnetising losses and secondary
When through-fault current traverses a zone protected winding resistance, and also the resistance of
by a differential system, the transient flux produced in the connecting leads. These circuits can then be
the current transformers is not detrimental as long as it interconnected as shown, with a relay connected to the
remains within the substantially linear range of the junction points to form the complete equivalent circuit.
magnetising characteristic. With fault current of
appreciable magnitude and long transient time constant, Saturation has the effect of lowering the exciting
the flux density will pass into the saturated region of the impedance, and is assumed to take place severely in
characteristic; this will not in itself produce a spill current transformer H until, at the limit, the shunt
output from a pair of balancing current transformers impedance becomes zero and the CT can produce no
provided that these are identical and equally burdened. output. This condition is represented by a short circuit,
A group of current transformers, though they may be of shown in broken line, across the exciting impedance. It
the same design, will not be completely identical, but a should be noted that this is not the equivalent of a
more important factor is inequality of burden. In the physical short circuit, since it is behind the winding
case of a differential system for a busbar, an external resistance .
fault may be fed through a single circuit, the current Applying the Thevenin method of solution, the voltage
being supplied to the busbar through all other circuits. developed across the relay will be given by:
The faulted circuit is many times more heavily loaded
than the others and the corresponding current
transformers are likely to be heavily saturated, while
those of the other circuits are not. Severe unbalance is ... Equat ion 15.1
therefore probable, which, with a relay of normal burden,
The current through the relay is given by:
could exceed any acceptable current setting. For this
reason such systems were at one time always provided
with a time delay. This practice is, however, no longer
acceptable.
...Equation 15.2
It is not feasible to calculate the spill current that may
occur, but, fortunately, this is not necessary; an alternative If RR is small, IR will approximate to IF, which is
approach provides both the necessary information and the unacceptable. On the other hand, if RR is large IR is
technique required to obtain a high performance. reduced. Equation 15.2 can be written, with little error,
as follows:
...Equation 15.3 RL + RCT= lead + CT winding resistance
or alternatively: ...Equation 15.4
K = factor depending on relay design
(range 0.7 - 2.0)
It is clear that, by increasing RR, the spill current IR can be It remains to be shown that the setting chosen is
reduced below any specified relay setting. RR is frequently suitable.
increased by the addition of a series-connected resistor The current transformers will have an excitation curve
which is known as the stabilising resistor. which has not so far been related to the relay setting
It can also be seen from Equation 15.4 that it is only the voltage, the latter being equal to the maximum nominal
voltage drop in the relay circuit at setting current that is voltage drop across the lead loop and the CT secondary
important. The relay can be designed as a voltage winding resistance, with the maximum secondary fault
measuring device consuming negligible current; and current flowing through them. Under in-zone fault
provided its setting voltage exceeds the value Vf of conditions it is necessary for the current transformers to
Equation 15.4, the system will be stable. In fact, the produce sufficient output to operate the relay. This will
setting voltage need not exceed Vf, since the derivation be achieved provided the CT knee-point voltage exceeds
of Equation 15.4 involves an extreme condition of the relay setting. In order to cater for errors, it is usual
unbalance between the G and H current transformers to specify that the current transformers should have a
that is not completely realised. So a safety margin is knee-point e.m.f. of at least twice the necessary setting
built-in if the voltage setting is made equal to Vf. voltage; a higher multiple is of advantage in ensuring a
high speed of operation.
It is necessary to realise that the value of If to be inserted
in Equation 15.4 is the complete function of the fault
current and the spill current IR through the relay, in the 15.8.2 Effective Setting or Primary Operating
limiting condition, will be of the same form. If the relay Current
requires more time to operate than the effective duration
of the d.c. transient component, or has been designed The minimum primary operating current is a further
with special features to block the d.c. component, then criterion of the design of a differential system. The
this factor can be ignored and only the symmetrical secondary effective setting is the sum of the relay
value of the fault current need be entered in Equation minimum operating current and the excitation losses in
15.4. If the relay setting voltage, Vs, is made equal to Vf, all parallel connected current transformers, whether
that is, If (RL + RCT), an inherent safety factor of the carrying primary current or not. This summation should
order of two will exist. strictly speaking be vectorial, but is usually done
arithmetically. It can be expressed as:
In the case of a faster relay, capable of operating in one
cycle and with no special features to block the d.c.
component, it is the r.m.s. value of the first offset wave
that is significant. This value, for a fully offset waveform ...Equation 15.6
with no d.c. decrement, is If settings are then
chosen in terms of the symmetrical component of the where:
fault current, the factor which has been ignored IR = effective setting Is = relay circuit setting
will take up most of the basic safety factor, leaving
current IeS = CT excitation current at relay setting
only a very small margin.
voltage
Finally, if a truly instantaneous relay were used, the
relevant value of If would be the maximum offset peak. n = number of parallel - connected CT's
In this case, the factor has become less than unity,
Having established the relay setting voltage from
possibly as low as 0.7. It is therefore possible to rewrite
stability considerations, as shown in Section 15.8.1, and
Equation 15.4 as:
knowing the excitation characteristic of the current
transformers, the effective setting can be computed. The
secondary setting is converted to the primary operating
...Equation 1 5 . 5 current by multiplying by the turns ratio of the current
transformers. The operating current so determined
should be considered in terms of the conditions of the
ISL = stability of scheme application.
VS = relay circuit voltage setting For a phase and earth fault scheme the setting can be
based on the fault current to be expected for minimum
plant and maximum system outage conditions. However,
it should be remembered that:
a. phase-phase faults give only 86% of the three- This will not happen to any large degree if the fault
phase fault current current is a larger multiple of setting; for example, if the
fault current is five times the scheme primary operating
b. fault arc resistance and earth path resistance
current and the CT knee-point e.m.f. is three times the
reduce fault currents somewhat
relay setting voltage, the additional delay is unlikely to
c. a reasonable margin should be allowed to ensure exceed one cycle.
that relays operate quickly and decisively The primary operating current is sometimes designed to
It is desirable that the primary effective setting should not exceed the maximum expected circuit load in order to
exceed 30% of the prospective minimum fault current. reduce the possibility of false operation under load
current as a result of a broken CT lead. Desirable as this
In the case of a scheme exclusively for earth fault safeguard may be, it will be seen that it is better not to
protection, the minimum earth fault current should be increase the effective current setting too much, as this
considered, taking into account any earthing impedance will sacrifice some speed; the check feature in any case,
that might be present as well. Furthermore, in the event maintains stability.
of a double phase to earth fault, regardless of the inter-
An overall earth fault scheme for a large distribution
phase currents, only 50% of the system e.m.f. is available
board may be difficult to design because of the large
in the earth path, causing a further reduction in the earth
number of current transformers paralleled together,
fault current. The primary operating current must
which may lead to an excessive setting. It may be
therefore be not greater than 30% of the minimum
advantageous in such a case to provide a three-element
single-phase earth fault current. In order to achieve phase and earth fault scheme, mainly to reduce the
high-speed operation, it is desirable that settings should number of current transformers paralleled into one group.
be still lower, particularly in the case of the solidly
earthed power system. The transient component of the Extra-high-voltage substations usually present no such
problem. Using the voltage-calibrated relay, the current
fault current in conjunction with unfavourable residual
consumption can be very small.
flux in the CT can cause a high degree of saturation and
loss of output, possibly leading to a delay of several cycles A simplification can be achieved by providing one relay
additional to the natural operating time of the element. per circuit, all connected to the CT paralleling buswires.
Figure 15.14: D.C. circuits for high impedance circulating current scheme
This enables the trip circuits to be confined to the least subdivision being necessary. For phase fault schemes,
area and reduces the risk of accidental operation. the check will usually be a similar type of scheme applied
to the switchboard as a single overall zone.
15.8.3 Check Feature
A set of current transformers separate from those used in
Schemes for earth faults only can be checked by a frame- the discriminating zones should be provided. No CT
earth system, applied to the switchboard as a whole, no switching is required and no current transformers are
needed for the check zone in bus-coupler and bus- cubicle. It is possible that special circumstances
section breakers. involving onerous conditions may over-ride this
15.8.4 Supervision of CT Secondary Circuits convenience and make connection to some other part of
the ring desirable.
Any interruption of a CT secondary circuit up to the
paralleling interconnections will cause an unbalance in Connecting leads will usually be not less than 7/0.67mm
the system, equivalent to the load being carried by the (2.5mm3), but for large sites or in other difficult
relevant primary circuit. Even though this degree of circumstances it may be necessary to use cables of, for
spurious output is below the effective setting the example 7/1.04mm (6mm3) for the bus wire ring and the
condition cannot be ignored, since it is likely to lead to CT connections to it. The cable from the ring to the relay
instability under any through fault condition. need not be of the larger section.
Supervision can be carried out to detect such conditions
When the reserve bar is split by bus section isolators and
by connecting a sensitive alarm relay across the bus
the two portions are protected as separate zones, it is
wires of each zone. For a phase and earth fault scheme,
an internal three-phase rectifier can be used to effect a necessary to common the bus wires by means of auxiliary
summation of the bus wire voltages on to a single alarm contacts, thereby making these two zones into one when
element; see Figures 15.13 and 15.14. the section isolators are closed.
The relay for each zone is connected to one point of the where:
ring bus wire. For convenience of cabling, the main zone
Vs = relay circuit voltage setting If =
relays will be connected through a multicore cable
between the relay panel and the bus section-switch steady-state through fault current RL =
marshalling cubicle. The reserve bar zone and the check
CT lead loop resistence RCT = CT
zone relays will be connected together by a cable
running to the bus coupler circuit breaker marshalling secondary winding resistance
15.8.6.4 Knee-point voltage of current transformers secondary condition is:
This is given by the formula
...Equation 1 5 . 8
15.8.6.5 Effective setting (secondary)
where:
The effective setting of the relay is given by IR
If = fault current
= Is+ nIeSIR
Iek = exciting current at knee - point voltage
where:
VK = knee - point voltage
Is = relay circuit current setting IeS = CT
Any burden connected across the secondary will reduce
excitation current at voltage setting n =
the voltage, but the value cannot be deduced from a
number of CT's in parallel simple combination of burden and exciting impedances.
For the primary fault setting multiply IR by the CT turns These formulae are therefore to be regarded only as a
ratio. guide to the possible peak voltage. With large current
15.8.6.6 Current transformer secondary rating transformers, particularly those with a low secondary
current rating, the voltage may be very high, above a
It is clear from Equations 15.4 and 15.6 that it is suitable insulation voltage. The voltage can be limited
advantageous to keep the secondary fault current low; without detriment to the scheme by connecting a
this is done by making the CT turns ratio high. It is ceramic non-linear resistor in parallel with the relay
common practice to use current transformers with a having a characteristic given by:
secondary rating of 1A.
It can be shown that there is an optimum turns ratio for
where C is a constant depending on dimensions and p is
the current transformers; this value depends on all the
a constant in the range 0.2-0.25.
application parameters but is generally about 2000/1.
Although a lower ratio, for instance 400/1, is often The current passed by the non-linear resistor at the relay
employed, the use of the optimum ratio can result in a voltage setting depends on the value of C; in order to
considerable reduction in the physical size of the current keep the shunting effect to a minimum it is
transformers. recommended to use a non-linear resistor with a value of
C of 450 for relay voltages up to 175V and one with a
15.8.6.7 Peak voltage developed by current transformers
value of C of 900 for setting voltages up to 325V.
Under in-zone fault conditions, a high impedance relay
constitutes an excessive burden to the current 15.8.6.8 High impedance relay
transformers, leading to the development of a high Instantaneous attracted an lature relays are used. Simple
voltage; the voltage waveform will be highly distorted fast-operating relays would have a low safety factor
but the peak value may be many times the nominal constant in the stability equation, Equation 15.5, as
saturation voltage. discussed in Section 15.8.1. The performance is improved
When the burden resistance is finite although high, an by series-tuning the relay coil, thereby making the circuit
approximate formula for the peak voltage is: resistive in effect. Inductive reactance would tend to
reduce stability, whereas the action of capacitance is to
block the unidirectional transient component of fault
current and so raise the stability constant.
...Equation 1 5 . 7
An alternative technique used in some relays is to apply
where:
the limited spill voltage principle shown in Equation
VP = peak voltage developed 15.4. A tuned element is connected via a plug bridge to
VK = knee-point voltage a chain of resistors; and the relay is calibrated in terms of
voltage.
VF = prospective voltage in absence of saturation
This formula does not hold for the open circuit condition
and is inaccurate for very high burden resistances that 1 5 . 9 LOW IMPEDANCE BIASED
DIFFERENTIAL PROTECTION
approximate to an open circuit, because simplifying
assumptions used in the derivation of the formula are The principles of low impedance differential protection
not valid for the extreme condition. have been described in Section 10.4, including the
principle advantages to be gained by the use of a
Another approach applicable to the open circuit
bias
technique. Most modern busbar protection schemes use It must be recognised though that the use of any technique
this technique. for inhibiting operation, to improve stability performance
for through faults, must not be allowed to diminish the
The principles of a check zone, zone selection, and
ability of the relay to respond to internal faults.
tripping arrangements can still be applied. Current
transformer secondary circuits are not switched directly
by isolator contacts but instead by isolator repeat relays
15.9.2 Effective Setting or Primary Operating Current
after a secondary stage of current transformation. These
switching relays form a replica of the busbar within the For an internal fault, and with no through fault current
protection and provide the complete selection logic. flowing, the effective setting (IR) is raised above the
basic relay setting (Is) by whatever biasing effect is
produced by the sum of the CT magnetising currents
15.9.1 Stability flowing through the bias circuit. With low impedance
biased differential schemes particularly where the busbar
With some biased relays, the stability is not assured by
installation has relatively few circuits, these magnetising
the through current bias feature alone, but is enhanced
currents may be negligible, depending on the value of Is
by the addition of a stabilising resistor, having a value
which may be calculated as follows. The basic relay setting current was formerly defined as
the minimum current required solely in the differential
The through current will increase the effective relay
circuit to cause operation - Figure 15.15(a). This
minimum operating current for a biased relay as follows:
approach simplified analysis of performance, but was
IR = Is + BIF considered to be unrealistic, as in practice any current
flowing in the differential circuit must flow in at least
where:
one half of the relay bias circuit causing the practical
IR = effective minimum oprating current ls minimum operating current always to be higher than the
nominal basic setting current. As a result, a later
= relay setting current IF= through fault
definition, as shown in Figure 15.15(b) was developed.
current B = percentage restraint
Conversely, it needs to be appreciated that applying the
As IF is generally much greater than ls, the relay later definition of relay setting current, which flows
effective current, IR = BIF approximately. through at least half the bias circuit, the notional mini-
From Equation 15.4, the value of stabilising resistor is mum operation current in the differential circuit alone
given by: is somewhat less, as shown in Figure 15.15(b). Using the
definition presently applicable, the effective minimum
primary operating current
where:
Figure 15.15:
Definitions of relay
setting current
15.9.5 Arrangement of CT connections A separate module is used for each circuit breaker and
also one for each zone of protection. In addition to these
It is a common modern requirement of low impedance
there is a common alarm module and a number of power
schemes that none of the main CT secondary circuits supply units. Ratio correction facilities are provided
should be switched, in the previously conventional manner, within each differential module to accommodate a wide
to match the switching of primary circuit isolators. range of CT mismatch.
Figure 15.17: Type MBCZ busbar protection showing correlation
between circuit breakers and protection modules
Figure 15.17 shows the correlation between the circuit 15.9.6.2 Stability with saturated current transformers
breakers and the protection modules for a typical double The traditional method for stabilising a differential relay
busbar installation. In practice the modules are mounted is to add a resistor to the differential path. Whilst this
in a multi-tier rack or cubicle. improves stability it increases the burden on the current
The modules are interconnected via a multicore cable transformer for internal faults. The technique used in
that is plugged into the back of the modules. There are the MBCZ scheme overcomes this problem.
five main groups of buswires, allocated for: The MBCZ design detects when a CT is saturated and
i. protection for main busbar ii. short-circuits the differential path for the portion of the
cycle for which saturation occurs. The resultant spill
protection for reserve busbar
current does not then flow through the measuring circuit
iii. protection for the transfer busbar. When the and stability is assured.
reserve busbar is also used as a transfer bar then
This principle allows a very low impedance differential
this group of buswires is used
circuit to be developed that will operate successfully
iv. auxiliary connections used by the protection to with relatively small CT's.
combine modules for some of the more complex
15.9.6.3 Operation for internal faults
busbar configurations
If the CT's carrying fault current are not saturated there
v. protection for the check zone
will be ample current in the differential circuit to operate
One extra module, not shown in this diagram, is plugged the differential relay quickly for fault currents exceeding
into the multicore bus. This is the alarm module, which the minimum operating level, which is adjustable
contains the common alarm circuits and the bias resistors. between 20%-200% rated current.
The power supplies are also fed in through this module.
When the only CT(s) carrying internal fault current
15.9.6.1 Bias become saturated, it might be supposed that the CT
All zones of measurement are biased by the total current saturation detectors may completely inhibit operation by
flowing to or from the busbar system via the feeders. short-circuiting the differential circuit. However, the
This ensures that all zones of measurement will have resulting inhibit pulses remove only an insignificant
similar fault sensitivity under all load conditions. The portion of the differential current, so operation of the
bias is derived from the check zone and fixed at 20% relay is therefore virtually unaffected.
with a characteristic generally as shown in Figure
15.15(b). Thus some ratio mismatch is tolerable.
Figure 15.18: Block diagram of measuring unit
15.9.6.4 Discrepancy alarm feature to operate the two busbar sections as a single bar. The
As shown in Figure 15.18, each measuring module fault current will then divide between the two measuring
contains duplicated biased differential elements and also elements in the ratio of their impedances. If both of the
a pair of supervision elements, which are a part of a two measuring elements are of low and equal impedance
comprehensive supervision facility. the effective minimum operating current of the scheme
will be doubled.
This arrangement provides supervision of CT secondary
circuits for both open circuit conditions and any This is avoided by using a 'master/follower' arrangement.
impairment of the element to operate for an internal By making the impedance of one of the measuring
fault, without waiting for an actual system fault elements very much higher than the other it is possible to
condition to show this up. For a zone to operate it is ensure that one of the relays retains its original minimum
necessary for both the differential supervision element operation current. Then to ensure that both the parallel-
and the biased differential element to operate. For a connected zones are tripped the trip circuits of the two
circuit breaker to be tripped it requires the associated zones are connected in parallel. Any measuring unit can
main zone to be operated and also the overall check have the role of 'master1 or 'follower' as it is selectable by
zone, as shown in Figure 15.19. means of a switch on the front of the module.
15.9.6.6 Transfer tripping for breaker failure
Serious damage may result, and even danger to life, if a
circuit breaker fails to open when called upon to do so.
To reduce this risk breaker fail protection schemes were
developed some years ago.
These schemes are generally based on the assumption
Figure 15.19: Busbar protection trip logic
that if current is still flowing through the circuit breaker
a set time after the trip command has been issued, then
75.9.6.5 Master/follower measuring units it has failed to function. The circuit breakers in the next
stage back in the system are then automatically tripped.
When two sections of a busbar are connected together
For a bus coupler or section breaker this would involve
by isolators it will result in two measuring elements
being connected in parallel when the isolators are closed tripping all the infeeds to the adjacent zone, a facility
that is included in the busbar protection scheme.
Figure 15.20: Architecture for numerical protection scheme
15.11 REFERENCES
15.1 The Behaviour of Current Transformers subjected to
Transient Asymmetric Currents and the Effects on
Associated Protective Relays. J.W. Hodgkiss.
CIGRE Paper Number 329, Session 15-25 June
1960.
Figure 15.21: Busbar protection relay using the
latest numerical technology (MiCOM P740 range)
16 • Transformer and
Transformer-Feeder Protection
16.1 INTRODUCTION
The development of modern power systems has been
reflected in the advances in transformer design. This has
resulted in a wide range of transformers with sizes
ranging from a few kVA to several hundred MVA being
available for use in a wide variety of applications.
The considerations for a transformer protection package
vary with the application and importance of the
transformer. To reduce the effects of thermal stress and
electrodynamic forces, it is advisable to ensure that the
protection package used minimises the time for
disconnection in the event of a fault occurring within the
transformer. Small distribution transformers can be
protected satisfactorily, from both technical and
economic considerations, by the use of fuses or
overcurrent relays. This results in time-delayed
protection due to downstream co-ordination
requirements. However, time-delayed fault clearance is
unacceptable on larger power transformers used in
distribution, transmission and generator applications,
due to system operation/stability and cost of
repair/length of outage considerations.
Transformer faults are generally classified into five
categories:
a. winding and terminal faults
b. core faults
c. tank and transformer accessory faults
d. on-load tap changer faults
e. abnormal operating conditions
f. sustained or uncleared external faults
For faults originating in the transformer itself, the
approximate proportion of faults due to each of the
causes listed above is shown in Figure 16.1.
1 6 .3 MAGNETISING INRUSH
The phenomenon of magnetising inrush is a transient
condition that occurs primarily when a transformer is
energised. It is not a fault condition, and therefore
transformer protection must remain stable during the
Table 16.1: Fault withstand levels inrush transient.
Table 16.4: Current transformer connections for power transformers of various vector groups
calculated automatically by the relay from knowledge of When the power transformer has only one of its three
the line CT ratios and the transformer MVA rating. windings connected to a source of supply, with the other
However, if interposing CT's are used, ratio correction two windings feeding loads, a relay with only two sets of
may not be such an easy task and may need to take into CT inputs can be used, connected as shown in Figure
account a factor of if delta-connected CT's or ICT's 16.10(a). The separate load currents are summated in
are involved. If the transformer is fitted with a tap the CT secondary circuits, and will balance with the
changer, line CT ratios and correction factors are infeed current on the supply side.
normally chosen to achieve current balance at the
When more than one source of fault current infeed
mid tap of the transformer. It is necessary to ensure
exists, there is a danger in the scheme of Figure 16.10(a)
that current mismatch due to off-nominal tap
of current circulating between the two paralleled sets of
operation will not cause spurious operation.
current transformers without producing any bias. It is
The example in Section 16.19.2 provides an illustration of therefore important a relay is used with separate CT
how ratio correction factors are used, and that of Section inputs for the two secondaries - Figure 16.10(b).
16.9.3 shows how to set the ratio correction factors for a When the third winding consists of a delta-connected
transformer with an unsymmetrical tap range. tertiary with no connections brought out, the
transformer may be regarded as a two winding
transformer for protection purposes and protected as
16.8.6 Bias Setting
shown in Figure 16.10(c).
Bias is applied to transformer differential protection for
the same reasons as any unit protection scheme - to
ensure stability for external faults while allowing
sensitive settings to pick up internal faults. The situation
is slightly complicated if a tap changer is present. With
line CT/ICT ratios and correction factors set to achieve
current balance at nominal tap, an off-nominal tap may
be seen by the differential protection as an internal fault.
By selecting the minimum bias to be greater than sum of
the maximum tap of the transformer and possible CT
errors, maloperation due to this cause is avoided. Some
relays use a bias characteristic with three sections, as
shown in Figure 16.9. The first section is set higher than
the transformer magnetising current. The second section
is set to allow for off-nominal tap settings, while the
third has a larger bias slope beginning well above rated
current to cater for heavy through-fault conditions.
Figure 16.13 Combined differentia! and earth fault protection using summation current transformer
Figure 16. 14; Combined differential and restricted earth fault protection using auxiliary CT's
Figure 16.15: Differential protection with in-zone earthing transformer, with restricted earth fault relay
Fiqure 1 6.] 6: Differentia! protection with in-zone earthing transformer; no ^arth fault relay
Figure 16.17: Differential protection with in-zone earthing transformer,
with alternative arrangement of restricted earth fault relay
In addition, this scheme does not respond to any fault in This is also known as Howard protection. If the
a tertiary winding. Unloaded delta-connected tertiary transformer tank is nominally insulated from earth (an
windings are often not protected; alternatively, the delta insulation resistance of 10 ohms being sufficient) earth
winding can be earthed at one point through a current fault protection can be provided by connecting a relay to
transformer that energises an instantaneous relay. This the secondary of a current transformer the primary of
system should be separate from the main winding which is connected between the tank and earth. This
protection. If the tertiary winding earthing lead is scheme is similar to the frame-earth fault busbar
connected to the main winding neutral above the neutral protection described in Chapter 15.
current transformer in an attempt to make a combined
system, there may be 'blind spots' which the protection
cannot cover. 16.15 OIL AND GAS DEVICES
16.9.2.3 Restricted earth fault protection Figure T6.30: REF operating characteristic
for KBCH relay
The KBCH relay implements high-impedance Restricted
Earth Fault (REF) protection. Operation is required for a
Starting with the desired operating time, the VK/Vs ratio and substituting values, VF= 544V. Thus a Metrosil is
and K factor can be found. not required.
An operating of 40ms (2 cycles at 50Hz) is usually
acceptable, and hence, from Figure 16.30, 16.9.3 Unit Protection for On-Load Tap
Changing Transformer
The previous example deals with a transformer having no
taps. In practice, most transformers have a range of taps
The maximum earth fault current is limited by the to cater for different loading conditions. While most
earthing resistor to 1000A (primary). The maximum transformers have an off-load tap-changer, transformers
phase fault current can be estimated by assuming the used for voltage control in a network are fitted with an
source impedance to be zero, so it is limited only by on-load tap-changer. The protection settings must then
transformer impedance to 5250A, or 10A secondary after take the variation of tap-change position into account to
taking account of the ratio compensation. Hence the avoid the possibility of spurious trips at extreme tap
stability voltage can be calculated as positions. For this example, the same transformer as in
Section 16.19.2 will be used, but with an on-load
tapping range of +5% to -15%. The tap-changer is
Hence,
located on the primary winding, while the tap-step
usually does not matter.
The stages involved in the calculation are as follows:
However, a. determine ratio correction at mid-tap and resulting
Actual secondary currents
b. determine HV currents at tap extremities with ratio
correction
Thus from Figure 16.30, with K = 0.5, the protection is c. determine the differential current at the tap
unstable. extremities
By adopting an iterative procedure for values of VKIVS d. determine bias current at tap extremities
and K, a final acceptable result of VK/Vs = 4.55, K= 0.6, e. check for sufficient margin between differential
is obtained. This results in an operating time of 40ms. and operating currents
The required earth fault setting current Iap is 250A. The 16.19.3.1 Ratio correction
chosen E/F CT has an exciting current Ic of 1%, and
In accordance with Section 16.8.4, the mid-tap position :
hence using the equation:
is used to calculate the ratio correction factors. The mid
tap position is -5%, and at this tap position:
where: Primary voltage to give rated secondary voltage: =
33 x 0.95 = 31.35W
and
The stabilising resistance Rstab can be calculated Rated Primary Current = 184A
60.21 Q. as 60.2112.
Transformer HV full load current on secondary of main
The relay can only withstand a maximum of 3kV peak CT's is:
under fault conditions. A check is required to see if this
voltage is exceeded - if it is, a non-linear resistor, known
as a Metrosil, must be connected across the relay and
stabilising resistor. The peak voltage is estimated using
the formula:
where;
and
If = fault current in secondary of CT circuit
, 76.19.3,2 HVcurrents at tap extremities 76.19.3.5 Margin between differential
and operating currents
At the +5% tap, the HV full-load current wi l l be:
The operating current of the relay is given by the formula
At the-150/0 tap,
where:
I RHV = relay HV current
IRLV = relay LV current
Hence,
and
17 • Generator and
Generator-Transformer Protection
17.1 INTRODUCTION
The core of an electric power system is the generation.
With the exception of emerging fuel cell and solar-cell
technology for power systems, the conversion of the
fundamental energy into its electrical equivalent
normally requires a 'prime mover' to develop mechanical
power as an intermediate stage.
The nature of this machine depends upon the source of
energy and in turn this has some bearing on the design
of the generator. Generators based on steam, gas, water
or wind turbines, and reciprocating combustion engines
are all in use. Electrical ratings extend from a few
hundred kVA (or even less) for reciprocating engine and
renewable energy sets, up to steam turbine sets
exceeding 1200MVA.
Small and medium sized sets may be directly connected
to a power distribution system. A larger set may be
associated with an individual transformer, through
which it is coupled to the EHV primary transmission
system.
Switchgear may or may not be provided between the
generator and transformer. In some cases, operational
and economic advantages can be attained by providing
a generator circuit breaker in addition to a high voltage
circuit breaker, but special demands will be placed on
the generator circuit breaker for interruption of
generator fault current waveforms that do not have an
early zero crossing.
A unit transformer may be tapped off the
interconnection between generator and transformer for
the supply of power to auxiliary plant, as shown in
Figure 17.1. The unit transformer could be of the order
of 10% of the unit rating for a large fossil-fuelled steam
set with additional flue-gas desulphurisation plant, but
it may only be of the order of 1% of unit rating for a
hydro set.
required. The amount of protection applied will be
governed by economic considerations, taking into
account the value of the machine, and the value of its
output to the plant owner.
The following problems require consideration from the
point of view of applying protection:
a. stator electrical faults
b. overload
c. overvoltage
Figure 17.1: Generator-transformer unit d. unbalanced loading
e. overfluxing
Industrial or commercial plants with a requirement for
steam/hot water now often include generating plant f. inadvertent energisation
utilising or producing steam to improve overall
e. rotor electrical faults
economics, as a Combined Heat and Power (CHP)
scheme. The plant will typically have a connection to the f. loss of excitation
public Utility distribution system, and such generation is g. loss of synchronism
referred to as 'embedded' generation. The generating
plant may be capable of export of surplus power, or h. failure of prime mover
simply reduce the import of power from the Utility. This j. lubrication oil failure I.
is shown in Figure 17.2.
overspeeding m. rotor
distortion
n. difference in expansion between rotating and
stationary parts
o. excessive vibration
p. core lamination faults
In this arrangement, shown in Figure 17.14(a), the Earth fault protection can also be provided using a voltage-
generator is earthed via the primary winding of a measuring element in the secondary circuit instead. The
distribution transformer. The secondary winding is fitted setting considerations would be similar to those for the
current operated protection, but transposed to voltage.
with a loading resistor to limit the earth fault current.
The circuit diagram is shown in Figure 17.14(b).
An overcurrent relay element energised from a current
transformer connected in the resistor circuit is used to Application of both voltage and current operated
measure secondary earth fault current. The relay should elements to a generator with distribution transformer
have an effective setting equivalent to 5°/o of the earthing provides some advantages. The current
maximum earth fault current at rated generator voltage, operated function will continue to operate in the event
in order to protect 95% of the stator winding. The relay of a short-circuited loading resistor and the voltage
element response to third harmonic current should be protection still functions in the event of an open-
limited to prevent incorrect operation when a sensitive circuited resistor. However, neither scheme will operate
setting is applied. in the event of a flashover on the primary terminals of
the transformer or of the neutral cable between the
As discussed in Section 17.8.2.1 for neutral overcurrent generator and the transformer during an earth fault. A
protection, the protection should be time delayed when CT could be added in the neutral connection close to the
a sensitive setting is applied, in order to prevent generator, to energise a high-set overcurrent element to
maloperation under transient conditions. It also must detect such a fault, but the fault current would probably
grade with generator VT primary protection (for a VT be high enough to operate the phase differential
primary earth fault). An operation time in the range protection.
0.5s-3s is usual. Less sensitive instantaneous protection
17.8.2.4 Neutral voltage displacement protection
can also be applied to provide fast tripping for a heavier
earth fault condition. This can be applied in the same manner as for direct-
connected generators (Section 17.8.1.3). The only
difference is that the are no grading problems as the protection of a generator, using three residuaIly
protection is inherently restricted. A sensitive setting connected phase CT's balanced against a similar single
can therefore be used, enabling cover of up to 95% of CTin the neutral connection. Settings of the order of 5%
the stator winding to be achieved. of maximum earth fault current at the generator
terminals are typical. The usual requirements in respect
of stabilising resistor and non-linear resistor to guard
17.8.3 Restricted Earth Fault Protection against excessive voltage across the relay must be taken,
This technique can be used on small generators not fitted where necessary.
with differential protection to provide fast acting earth
fault protection within a defined zone that encompasses
17.8.4 Earth Fault Protection for
the generator. It is cheaper than full differential
the Entire Stator Winding
protection but only provides protection against earth
faults. The principle is that used for transformer REF All of the methods for earth fault protection detailed so
protection, as detailed in Section 16.7. However, in far leave part of the winding unprotected. In most cases,
contrast to transformer REF protection, both biased low- this is of no consequence as the probability of a fault
impedance and high-impedance techniques can be used. occurring in the 5% of the winding nearest the neutral
connection is very low, due to the reduced phase to earth
17.8.3.1 Low-impedance biased REF protection
voltage. However, a fault can occur anywhere along the
This is shown in Figure 17.15. The main advantage is stator windings in the event of insulation failure due to
that the neutral CT can also be used in a modern relay to localised heating from a core fault. In cases where
provide conventional earth-fault protection and no protection for the entire winding is required, perhaps for
external resistors are used. Relay bias is required, as alarm only, there are various methods available.
described in Section 10.4.2, but the formula for
17.8.4.1 Measurement of third harmonic voltage
calculating the bias is slightly different and also shown
in Figure 17.15. One method is to measure the internally generated third
harmonic voltage that appears across the earthing
impedance due to the flow of third harmonic currents
through the shunt capacitance of the stator windings
etc. When a fault occurs in the part of the stator
winding nearest the neutral end, the third harmonic
voltage drops to near zero, and hence a relay element
that responds to third harmonic voltage can be used to
detect the condition. As the fault location moves
progressively away from the neutral end, the drop in
third harmonic voltage from healthy conditions becomes
less, so that at around 20-30% of the winding distance,
it no longer becomes possible to discriminate between a
healthy and a faulty winding. Hence, a conventional
earth-fault scheme should be used in conjunction with a
third harmonic scheme, to provide overlapping cover
of the entire stator winding. The measurement of third
harmonic voltage can be taken either from a star-point
Figure 17.15: Low impedance biased REF VT or the generator line VT. In the latter case, the VT
protection of a generator
must be capable of carrying residual flux, and this
The initial bias slope is commonly set to 0% to provide prevents the use of 3-limb types. If the third harmonic
maximum sensitivity, and applied up to the rated current voltage is measured at the generator star point, an
of the generator. It may be increased to counter the undervoltage characteristic is used. An overvoltage
effects of CT mismatch. The bias slope above generator characteristic is used if the measurement is taken from
rated current is typically set to 150% of rated value. The the generator line VT. For effective application of this
initial current setting is typically 5% of the minimum form of protection, there should be at least 1% third
earth fault current for a fault at the machine terminals. harmonic voltage across the generator neutral earthing
impedance under all operating conditions.
17.8.3.2 High Impedance REF protection
A problem encountered is that the level of third
The principle of high impedance differential protection is
harmonic voltage generated is related to the output of
given in Chapter 10 and also described further in Section
the generator. The voltage is low when generator output
17.5.2. The same technique can be used for earth-fault
is low. In order to avoid maloperation when operating at isolated networks, or ones with weak interconnections,
low power output, the relay element can be inhibited due to the fault conditions listed earlier.
using an overcurrent or power element (kW, kvar or kVA)
For these reasons, it is prudent to provide power
and internal programmable logic.
frequency overvoitage protection, in the form of a time-
17.8.4.2 Use of low-frequency voltage injection delayed element, either IDMT or definite time. The time
Another method for protecting the entire stator winding delay should be long enough to prevent operation during
of a generator is to deploy signal injection equipment to normal regulator action, and therefore should take
inject a low frequency voltage between the stator star account of the type of AVR fitted and its transient
point and earth. An earth fault at any winding location response. Sometimes a high-set element is provided as
will result in the flow of a measurable injection current well, with a very short definite-time delay or
to cause protection operation. This form of protection instantaneous setting to provide a rapid trip in extreme
can provide earth fault protection when the generator is circumstances. The usefulness of this is questionable for
at standstill, prior to run-up. It is also an appropriate generators fitted with an excitation system other than a
method to apply to variable speed synchronous static type, because the excitation will decay in
machines. Such machines may be employed for variable accordance with the open-circuit time constant of the
speed motoring in pumped-storage generation schemes field winding. This decay can last several seconds. The
or for starting a large gas turbine prime mover. relay element is arranged to trip both the main circuit
breaker (if not already open) and the excitation; tripping
the main circuit breaker alone is not sufficient.
17.9 OVERVOLTAGE PROTECTION
Overvoltages on a generator may occur due to transient
surges on the network, or prolonged power frequency 17.10 UNDERVOLTAGE PROTECTION
overvoltages may arise from a variety of conditions. Undervoltage protection is rarely fitted to generators. It
Surge arrestors may be required to protect against is sometimes used as an interlock element for another
transient overvoltages, but relay protection may be used protection function or scheme, such as field failure
to protect against power frequency overvoltages. protection or inadvertent energisation protection, where
A sustained overvoitage condition should not occur for a the abnormality to be detected leads directly or
machine with a healthy voltage regulator, but it may be indirectly to an undervoltage condition.
caused by the following contingencies: A transmission system undervoltage condition may arise
a. defective operation of the automatic voltage when there is insufficient reactive power generation to
regulator when the machine is in isolated operation maintain the system voltage profile and the condition
must be addressed to avoid the possible phenomenon of
b. operation under manual control with the voltage
system voltage collapse.
regulator out of service. A sudden variation of the
load, in particular the reactive power component, However, it should be addressed by the deployment of
will give rise to a substantial change in voltage 'system protection' schemes. The generation should not
because of the large voltage regulation inherent in be tripped. The greatest case for undervoltage protection
a typical alternator being required would be for a generator supplying an
c. sudden loss of load (due to tripping of outgoing isolated power system or to meet Utility demands for
feeders, leaving the set isolated or feeding a very small connection of embedded generation (see Section 17.21).
load) may cause a sudden rise in terminal voltage due In the case of generators feeding an isolated system,
to the trapped field flux and/or overspeed undervoltage may occur for several reasons, typically
Sudden loss of load should only cause a transient overloading or failure of the AVR. In some cases, the
overvoitage while the voltage regulator and governor act performance of generator auxiliary plant fed via a unit
to correct the situation. A maladjusted voltage regulator transformer from the generator terminals could be
may trip to manual, maintaining excitation at the value adversely affected by prolonged undervoltage.
prior to load loss while the generator supplies little or no Where undervoltage protection is required, it should
load. The terminal voltage will increase substantially, comprise an undervoltage element and an associated
and in severe cases it would be limited only by the
time delay. Settings must be chosen to avoid
saturation characteristic of the generator. A rise in speed
maloperation during the inevitable voltage dips during
simply compounds the problem. If load that is sensitive
power system fault clearance or associated with motor
to overvoltages remains connected, the consequences in
starting. Transient reductions in voltage down to 80% or
terms of equipment damage and lost revenue can be
less may be encountered during motor starting.
severe. Prolonged overvoltages may also occur on
17.11 LOW FORWARD POWER/REVERSE where a protection sensitivity of better than 3% is
POWER PROTECTION required, a metering class CT should be employed to
avoid incorrect protection behaviour due to CT phase
Low forward power or reverse power protection may be
angle errors when the generator supplies a significant
required for some generators to protect the prime mover.
level of reactive power at close to zero power factor.
Parts of the prime mover may not be designed to
experience reverse torque or they may become damaged The reverse power protection should be provided with a
through continued rotation after the prime mover has definite time delay on operation to prevent spurious
suffered some form of failure. operation with transient power swings that may arise
following synchronisation or in the event of a power
transmission system disturbance.
17.11.1 Low Forward Power Protection
Low forward power protection is often used as an
17.12 UNBALANCED LOADING
interlocking function to enable opening of the main
circuit breaker for non-urgent trips - e.g. for a stator A three-phase balanced load produces a reaction field
earth fault on a high-impedance earthed generator, or that, to a first approximation, is constant and rotates
when a normal shutdown of a set is taking place. This is synchronously with the rotor field system. Any
to minimise the risk of plant overspeeding when the unbalanced condition can be resolved into positive,
electrical load is removed from a high-speed cylindrical negative and zero sequence components. The positive
rotor generator. The rotor of this type of generator is sequence component is similar to the normal balanced
highly stressed mechanically and cannot tolerate much load. The zero sequence component produces no main
overspeed. While the governor should control overspeed armature reaction.
conditions, it is not good practice to open the main
circuit breaker simultaneously with tripping of the prime
mover for non-urgent trips. For a steam turbine, for 17.12.1 Effect of Negative Sequence Current
example, there is a risk of overspeeding due to energy The negative sequence component is similar to the
storage in the trapped steam, after steam valve tripping, positive sequence system, except that the resulting
or in the event that the steam valve(s) do not fully close reaction field rotates in the opposite direction to the d.c.
for some reason. For urgent trip conditions, such as field system. Hence, a flux is produced which cuts the
stator differential protection operation, the risk involved rotor at twice the rotational velocity, thereby inducing
in simultaneous prime mover and generator breaker double frequency currents in the field system and in the
tripping must be accepted. rotor body. The resulting eddy-currents are very large
and cause severe heating of the rotor.
17.11.2 Reverse Power Protection So severe is this effect that a single-phase load equal to
the normal three-phase rated current can quickly heat
Prime Mover Motoring Power Possible Damage Protection Setting
(% of rated) the rotor slot wedges to the softening point. They may
Diesel Engine 5-25
then be extruded under centrifugal force until they stand
Fire/explosion due to 50% of
unburnt fuel above the rotor surface, when it is possible that they may
motoring
Mechanical damage strike the stator core.
to gearbox/shafts power
Gas Turbine 10-15 (split gearbox damage A generator is assigned a continuous negative sequence
shaft)
rating. For turbo-generators this rating is low; standard
>50% (single
shaft) values of 10% and 15% of the generator continuous
Hydro 0.2-2 (blades out of blade and runner rating have been adopted. The lower rating applies when
water)
cavitation the more intensive cooling techniques are applied, for
>2
(blades in water) example hydrogen-cooling with gas ducts in the rotor to
Steam Turbine 0.5-6 turbine blade damage facilitate direct cooling of the winding.
gearbox damage
on geared sets Short time heating is of interest during system fault
Table 17.1: Generator reverse power problems conditions and it is usual in determining the generator
negative sequence withstand capability to assume that
the heat dissipation during such periods is negligible.
Reverse power protection is applied to prevent damage
Using this approximation it is possible to express the
to mechanical plant items in the event of failure of the
heating by the law:
prime mover. Table 17.1 gives details of the potential
problems for various prime mover types and the typical
settings for reverse power protection. For applications
where: sequence capacity and may not require protection.
Modern numerical relays derive the negative sequence
I2R = negative sequence component
current level by calculation, with no need for special
(per unit of
circuits to extract the negative sequence component. A
MCR) t = time
true thermal replica approach is often followed, to allow
(seconds)
for:
K = constant proportional to the thermal capacity
a. standing levels of negative sequence current below
of the generator rotor
the continuous withstand capability. This has the
For heating over a period of more than a few seconds, it effect of shortening the time to reach the critical
is necessary to allow for the heat dissipated. From a temperature after an increase in negative sequence
combination of the continuous and short time ratings, current above the continuous withstand capability
the overall heating characteristic can be deduced to be:
b. cooling effects when negative sequence current
levels are below the continuous withstand
capability
The advantage of this approach is that cooling effects are
modelled more accurately, but the disadvantage is that
where: the tripping characteristic may not follow the withstand
characteristic specified by the manufacturer accurately.
I2R = negative phase sequence continuous rating in
per unit ofMCR The typical relay element characteristic takes the form of
The heating characteristics of various designs of
generator are shown in Figure 17.16.
...Equation U.I
where:
t= time to trip
A relay to detect loss of synchronism can be located at The special cases of E G =E S and E U =0 result in a
point A. It can be shown that the impedance presented straight-line locus that is the right-angled bisector of
to the relay under loss of synchronism conditions (phase CD, and in a circular locus that is shrunk to point C,
swinging or pole slipping) is given by: respectively.
The width of the lens is set by the angle a and the line
PP\ perpendicular to the axis of the lens, is used to
determine if the centre of the impedance swing during a
transient is located in the generator or power system.
Operation in the case of a generator is as follows. The
Figure 17.24: Pole slipping detection
by ohm relays
characteristic is divided into 4 zones and 2 regions, as
shown in Figure 17.26.
Tripping only occurs if all zones are traversed Normal operation is with the measured impedance in
sequentially. Power system faults should result in the zone R1. If a pole slip develops, the impedance locus will
zones not being fully traversed so that tripping will not traverse though zones R2, R3, and R4. When entering
be initiated. The security of this type of protection zone R4, a trip signal is issued, provided the impedance
scheme is normally enhanced by the addition of a plain lies below reactance line PP' and hence the locus of
under impedance control element (circle about the origin swing lies within or close to the generator - i.e. the
of the impedance diagram) that is set to prevent tripping generator is pole slipping with respect to the rest of the
for impedance trajectories for remote power system system.
faults. Setting of the ohm elements is such that they lie
parallel to the total system impedance vector, and
enclose it, as shown in Figure 17.24.
windings and to issue an alarm or trip to prevent
damage.
Although current-operated thermal replica protection
cannot take into account the effects of ambient
temperature or uneven heat distribution, it is often
applied as a back-up to direct stator temperature
measuring devices to prevent overheating due to high
stator current. With some relays, the thermal replica
temperature estimate can be made more accurate
through the integration of direct measuring resistance
temperature devices.
Irrespective of whether current-operated thermal replica
protection is applied or not, it is a requirement to
monitor the stator temperature of a large generator in
order to detect overheating from whatever cause.
Temperature sensitive elements, usually of the resistance
type, are embedded in the stator winding at hot-spot
locations envisaged by the manufacturer, the number
Figure 17.26: Definition of zones for lenticular
used being sufficient to cover all variations. The
characteristic
elements are connected to a temperature sensing relay
If the impedance locus lies above line PP' the swing lies element arranged to provide alarm and trip outputs. The
far out in the power system - i.e. one part of the power settings will depend on the type of stator winding
system, including the protected generator, is swinging insulation and on its permitted temperature rise.
against the rest of the network. Tripping may still occur,
but only if swinging is prolonged - meaning that the
17.19 MECHANICAL FAULTS
power system is in danger of complete break-up. Further
confidence checks are introduced by requiring that the Various faults may occur on the mechanical side of a
impedance locus spends a minimum time within each generating set. The following sections detail the more
zone for the pole-slipping condition to be valid. The trip important ones from an electrical point of view.
signal may also be delayed for a number of slip cycles
even if a generator pole-slip occurs - this is to both
provide confirmation of a pole-slipping condition and 17.19.1 Failure of the Prime Mover
allow time for other relays to operate if the cause of the
When a generator operating in parallel with others loses
pole slip lies somewhere in the power system. Should
its power input, it remains in synchronism with the
the impedance locus traverse the zones in any other
system and continues to run as a synchronous motor,
sequence, tripping is blocked.
drawing sufficient power to drive the prime mover. This
condition may not appear to be dangerous and in some
circumstances will not be so. However, there is a danger
17.18 STATOR OVERHEATING Overheating of
of further damage being caused. Table 17.1 lists some
the stator may result from: typical problems that may occur.
i. overload Protection is provided by a low forward power/reverse
ii. failure of the cooling system power relay, as detailed in Section 17.11
iii. overfluxing
iv. core faults 17.19.2 Overspeed
Accidental overloading might occur through the The speed of a turbo-generator set rises when the steam
combination of full active load current component, input is in excess of that required to drive the load at
governed by the prime mover output and an abnormally nominal frequency. The speed governor can normally
high reactive current component, governed by the level control the speed, and, in any case, a set running in
of rotor excitation and/or step-up transformer tap. With parallel with others in an interconnected system cannot
a modern protection relay, it is relatively simple to accelerate much independently even if synchronism is
provide a current-operated thermal replica protection lost. However, if load is suddenly lost when the HV
element to estimate the thermal state of the stator circuit breaker is tripped, the set will begin to accelerate
rapidly. The speed governor is designed to prevent a event of loss of vacuum, as this would cause rapid
dangerous speed rise even with a 100% load rejection, overheating of the low-pressure turbine blades.
but nevertheless an additional centrifugal overspeed trip
device is provided to initiate an emergency mechanical
shutdown if the overspeed exceeds 10%. 17.20 COMPLETE GENERATOR PROTECTION
SCHEMES
To minimise overspeed on load rejection and hence the
mechanical stresses on the rotor, the following sequence From the preceding sections, it is obvious that the
is used whenever electrical tripping is not urgently protection scheme for a generator has to take account of
required: many possible faults and plant design variations.
i. trip prime mover or gradually reduce power input to Determination of the types of protection used for a
zero particular generator will depend on the nature of the
plant and upon economic considerations, which in turn
ii. allow generated power to decay towards zero is affected by set size. Fortunately, modern, multi-
iii. trip generator circuit breaker only when generated function, numerical relays are sufficiently versatile to
power is close to zero or when the power flow include all of the commonly required protection
starts to reverse, to drive the idle turbine functions in a single package, thus simplifying the
decisions to be made. The following sections provide
illustrations of typical protection schemes for generators
17.19.3 Loss of Vacuum connected to a grid network, but not all possibilities are
A failure of the condenser vacuum in a steam turbine illustrated, due to the wide variation in generator sizes
driven generator results in heating of the tubes. This and types.
then produces strain in the tubes, and a rise in
temperature of the low-pressure end of the turbine.
17.20.1 Direct-Connected Generator
Vacuum pressure devices initiate progressive unloading
of the set and, if eventually necessary, tripping of the A typical protection scheme for a direct-connected
turbine valves followed by the high voltage circuit generator is shown in Figure 17.27. It comprises the
breaker. The set must not be allowed to motor in the following protection functions:
The data for this unit are given in Table 17.4. It is fitted
with two main protection systems to ensure security of
tripping in the event of a fault. To economise on space,
the setting calculations for only one system, that using a where:
MiCOM P343 relay are given. Settings are given in
If = minimum generator primary current for a
primary quantities throughout.
multi-phase feeder-end fault
17.22.2.1 Biased differential protection
VN = no-load phase-neutral generator voltage
The settings follow the guidelines previously stated. As
Xd = generator d-axis synchronous reactance
100% stator winding earth-fault protection is provided,
high sensitivity is not required and hence Isl can be set XT = generator transformer reactance
to 10% of generator rated current. This equates to 602A,
Rf = feeder resistance
and the nearest settable value on the relay is 640A (=
0.08 of rated CT current). The settings for K,, Is2 and K2 Xf = feeder reactance
follow the guidelines in the relay manual. n = number of parallel generators
hence, A TMS value of 10 is selected, to match the withstand
curve supplied by the manufacturer.
17.22.2.6 100% Stator earth fault protection
This is provided by a combination of neutral voltage
and
displacement and third harmonic undervoltage
protection. For the neutral voltage displacement
protection to cover 90% of the stator winding, the
minimum voltage allowing for generator operation at a
minimum of 92% of rated voltage is:
The trip setting is 18000x1,2/60=360V/Hz . The nearest settable value for X b2 is 1.725 ,. A time
delay of 0.5s is used.
17.22.2.8 Reverse power protection
The manufacturer-supplied value for motoring power is
2% of rated power. The recommended setting is
therefore 1.6MW. An instrumentation class CT is used in
conjunction with the relay for this protection, to ensure
accuracy of measurement. A time delay of 0.5s is used.
The settings should be checked at the commissioning
stage.
is:
Forward reach, Z A = Z n + Z t
= 0.02 + 0.22
=
0.24Ohm Reverse reach, ZB
= ZGen
= 2 x X'd
= 0.652Ohm,
Reactance line, Z c = 0.9 x Z
= 0.9 x 0.22
= 0.198 Ohm.
where:
Z1 = generator transformer leakage impedance Zn
= network impedance
Table 17.5: Relay settings for large generator protection example
The nearest settable values are 0.243 , 0.656 , and
0.206 respectively.
The lens angle setting, a, is found from the equation:
17.23 REFERENCES
18.1 INTRODUCTION
As industrial and commercial operations processes and
plants have become more complex and extensive (Figure
18.1), the requirement for improved reliability of
electrical power supplies has also increased. The
potential costs of outage time following a failure of the
power supply to a plant have risen dramatically as well.
The introduction of automation techniques into industry
and commerce has naturally led to a demand for the
deployment of more power system automation, to
improve reliability and efficiency.
Figure T8.6: Typical tripping characteristics In some countries, circuit breakers using SF6 gas as the
ofanACB arc-quenching medium are preferred to VCB's as the
Figure 18.7; Overcurrent and earth fault
relay connections
replacement for air- and oil-insulated CB's. Some connection to drive an earth fault relay provides earth
modern types of switchgear cubicles enable the use of fault protection at the source of supply for a 4-wire
either VCB's or SF6-insulated CB's according to customer system. If the neutral CT is omitted, neutral current is
requirements. Ratings of up to 31.5kA r.m.s. fault break seen by the relay as earth fault current and the relay
at 36kV and 40kA at 24kV are typical. SF6-insulated CB's setting would have to be increased to prevent tripping
also have advantages of reliability and maintenance under normal load conditions.
intervals compared to air- or oil-insulated CB's and are
When an earth fault relay is driven from residually
of similar size to VCB's for the same rating.
connected CT's, the relay current and time settings must
be such that that the protection will be stable during the
passage of transient CT spill current through the relay.
18.6 PROTECTION RELAYS
Such spill current can flow in the event of transient,
When the circuit breaker itself does not have integral asymmetric CT saturation during the passage of offset
protection, then a suitable external relay will have to be fault current, inrush current or motor starting current.
provided. For an industrial system, the most common The risk of such nuisance tripping is greater with the
protection relays are time-delayed overcurrent and earth deployment of low impedance electronic relays rather
fault relays. Chapter 9 provides details of the application than electromechanical earth fault relays which
of overcurrent relays. presented significant relay circuit impedance. Energising
Traditionally, for three wire systems, overcurrent relays a relay from a core balance type CT generally enables
have often been applied to two phases only for relay more sensitive settings to be obtained without the risk of
element economy. Even with modern multi-element nuisance tripping with residually connected phase CT's.
relay designs, economy is still a consideration in terms of When this method is applied to a four-wire system, it is
the number of analogue current inputs that have to be essential that both the phase and neutral conductors are
provided. Two overcurrent elements will detect any passed through the core balance CT aperture. For a 3-
interphase fault, so it is conventional to apply two wire system, care must be taken with the arrangement of
elements on the same phases at all relay locations. The the cable sheath, otherwise cable faults involving the
phase CT residual current connections for an earth fault sheath may not result in relay operation (Figure 18.8).
relay element are unaffected by this convention. Figure
18.7 illustrates the possible relay connections and
limitations on settings.
* Element fuses
Fiqure 18.13: Protection of capacitor banks
economical method. Some industrial consumers apply
capacitors to selected motor substations rather than
applying all of the correction at the main incoming
substation busbars. Sometimes, power factor correction
may even be applied to individual motors, resulting in
optimum power factor being obtained under a ll
conditions of aggregate motor load. In some instances,
better motor starting may also result, from the
improvement in the voltage regulation due to the
capacitor. Motor capacitors are often six-terminal units,
and a capacitor may be conveniently connected directly
across each motor phase winding.
Capacitor sizing is important, such that a leading power
factor does not occur under any load condition. If excess
capacitance is applied to a motor, it may be possible for
self-excitation to occur when the motor is switched off or
suffers a supply failure. This can result in the production
of a high voltage or in mechanical damage if there Is a
sudden restoration of supply. Since most star/delta or
auto-transformer starters other than the 'Korndorffer'
types involve a transitional break in supply, it is generally
recommended that the capacitor rating should not
exceed 85% of the motor magnetising reactive power.
Figure 18.14: Protection of double star
capacitor banks
18.13 REFERENCES
draw a current similar to the starting current for a period 19.4.3 Number of Starts Limitation
that may be several seconds. It is thus above the motor
Any motor has a restriction on the number of starts that
stall relay element current threshold. The stall
are allowed in a defined period without the permitted
protection would be expected to operate and defeat the
winding, etc. temperatures being exceeded. Starting
object of the re-acceleration scheme.
should be blocked if the permitted number of starts is
A motor protection relay will therefore recognise the exceeded. The situation is complicated by the fact the
presence of a voltage dip and recovery, and inhibit stall number of permitted 'hot' starts in a given period is less
protection for a defined period. The undervoltage than the number of 'cold' starts, due to the differing
protection element (Section 19.11) can be used to detect initial temperatures of the motor. The relay must
the presence of the voltage dip and inhibit stall maintain a separate count of 'cold' and 'hot' starts. By
protection for a set period after voltage recovery. making use of the data held in the motor thermal replica,
Protection against stalled motors in case of an 'hot' and 'cold' starts can be distinguished.
unsuccessful re-acceleration is therefore maintained.
To allow the motor to cool down between starts, a time
The time delay setting is dependent on the re- delay may be specified between consecutive starts (again
acceleration scheme adopted and the characteristics of distinguishing between 'hot' and 'cold' starts). The start
individual motors. It should be established after inhibit is released after a time determined by the motor
performing a transient stability study for the re- specification. The overall protection function is illustrated
acceleration scheme proposed. in Figure 19.4.
19.5 SHORT-CIRCUIT PROTECTION It is common, however, to provide both instantaneous
and time-delayed relay elements to cater for major and
Motor short-circuit protection is often provided to cater
slowly developing faults.
for major stator winding faults and terminal flashovers.
Because of the relatively greater amount of insulation
between phase windings, faults between phases seldom
19.6.1 Solidly-Earthed System
occur. As the stator windings are completely enclosed in
grounded metal, the fault would very quickly involve Most LV systems fall into this category, for reasons of
earth, which would then operate the instantaneous earth personnel safety. Two types of earth fault protection are
fault protection. A single definite time overcurrent relay commonly found - depending on the sensitivity required.
element is all that is required for this purpose, set to For applications where a sensitivity of > 20% of motor
about 125% of motor starting current. The time delay is continuous rated current is acceptable, conventional
required to prevent spurious operation due to CT spill earth fault protection using the residual CT connection
currents, and is typically set at 100ms. If the motor is fed of Figure 19.5 can be used. A lower limit is imposed on
from a fused contactor, co-ordination is required with the setting by possible load unbalance and/or (for HV
the fuse, and this will probably involve use of a long time systems) system capacitive currents.
delay for the relay element. Since the object of the
protection is to provide rapid fault clearance to minimise
damage caused by the fault, the protection is effectively
worthless in these circumstances. It is therefore only
provided on motors fed via circuit breakers.
Differential (unit) protection may be provided on larger HV
motors fed via circuit breakers to protect against phase-
phase and phase-earth faults, particularly where the
power system is resistance-earthed. Damage to the motor
in case of a fault occurring is minimised, as the differential
protection can be made quite sensitive and hence detects
faults in their early stages. The normal definite time
overcurrent protection would not be sufficiently sensitive,
and sensitive earth fault protection may not be provided.
The user may wish to avoid the detailed calculations
required of capacitance current in order to set sensitive
non-directional earth fault overcurrent protection
correctly on HV systems (Chapter 9) or there may be no
provision for a VT to allow application of directional
sensitive earth fault protection. There is still a lower limit
to the setting that can be applied, due to spill currents Figure 19.5: Residual CTconnection Figure 19.5: Residua! CT
forearth fault protection connection
from CT saturation during starting, while on some motors, forearth fault protection
neutral current has been found to flow during starting,
even with balanced supply voltages, that would cause the Care must be taken to ensure that the relay does not
differential protection to operate. For details on the operate from the spill current resulting from unequal CT
application of differential protection, refer to Chapter 10. saturation during motor starting, where the high
However, non-directional earth fault overcurrent currents involved will almost certainly saturate the
protection will normally be cheaper in cases where motor CT's. It is common to use a stabilising resistor in
adequate sensitivity can be provided. series with the relay, with the value being calculated
using the formula:
Figure 19.10: Residua! voltage earth fault protection for resistance-earthed system.
Motor positive sequence impedance at slip s leading to excessive heating. For the same motor,
negative sequence voltages in excess of 17% will result
in a negative sequence current larger than rated full load
current.
Hence, at standstill (s=1.0), impedance Negative sequence current is at twice supply frequency.
Skin effect in the rotor means that the heating effect in
the rotor of a given negative sequence current is larger
than the same positive sequence current. Thus, negative
sequence current may result in rapid heating of the
The motor negative sequence impedance at slip s motor. Larger motors are more susceptible in this
respect, as the rotor resistance of such machines tends to
be higher. Protection against negative sequence currents
is therefore essential.
and, at normal running speed, the impedance Modern motor protection relays have a negative
sequence current measurement capability, in order to
provide such protection. The level of negative sequence
unbalance depends largely upon the type of fault. For
loss of a single phase at start, the negative sequence
where: current will be 50% of the normal starting current. It is
suffix p indicates positive sequence quantities more difficult to provide an estimate of the negative
sequence current if loss of a phase occurs while running.
and This is because the impact on the motor may vary widely,
suffix n indicates negative sequence quantities from increased heating to stalling due to the reduced
torque available.
A typical setting for negative sequence current
protection must take into account the fact that the
motor circuit protected by the relay may not be the
source of the negative sequence current. Time should be
allowed for the appropriate protection to clear the
source of the negative sequence current without
introducing risk of overheating to the motor being
considered. This indicates a two stage tripping
characteristic, similar in principle to overcurrent
protection. A low-set definite time-delay element can
be used to provide an alarm, with an IDMT element used
to trip the motor in the case of higher levels of negative
sequence current, such as loss-of-phase conditions at
start, occurring. Typical settings might be 20% of CT
rated primary current for the definite time element and
Figure 19.11: Induction motor equivalent circuit
50% for the IDMT element. The IDMT time delay has to
be chosen to protect the motor while, if possible, grading
Now, if resistance is neglected (justifiable as the with other negative sequence relays on the system.
resistance is small compared to the reactance), it can be Some relays may not incorporate two elements, in which
seen that the negative sequence reactance at running case the single element should be set to protect the
speed is approximately equal to the positive sequence motor, with grading being a secondary consideration.
reactance at standstill. An alternative more meaningful
way of expressing this is:
19.8 FAULTS IN ROTOR WINDINGS
On wound rotor machines, some degree of protection
against faults in the rotor winding can be given by an
and it is noted that a typical LV motor starting current is instantaneous stator current overcurrent relay element.
6xFLC. Therefore, a 5% negative sequence voltage (due As the starting current is normally limited by resistance
to, say, unbalanced loads on the system) would produce to a maximum of twice full load, the instantaneous unit
a 30% negative sequence current in the machine, can safely be set to about three times full load if a slight
time delay of approximately 30 milliseconds is Motors fed by contactors have inherent undervoltage
incorporated. It should be noted that faults occurring in protection, unless a latched contactor is used. Where a
the rotor winding would not be detected by any specific undervoltage trip is required, a definite time
differential protection applied to the stator. undervoltage element is used. If two elements are
provided, alarm and trip settings can be used. An
interlock with the motor starter is required to block relay
1 9 .9 RTD TEMPERATURE DETECTION operation when the starting device is open, otherwise a
start will never be permitted. The voltage and time delay
RTD's are used to measure temperatures of motor
settings will be system and motor dependent. They must
windings or shaft bearings. A rise in temperature may allow for all voltage dips likely to occur on the system
denote overloading of the machine, or the beginning of during transient faults, starting of motors, etc. to avoid
a fault in the affected part. A motor protection relay will spurious trips. As motor starting can result in a voltage
therefore usually have the capability of accepting a depression to 80% of nominal, the voltage setting is
number of RTD inputs and internal logic to initiate an likely to be below this value. Re-acceleration is normally
alarm and/or trip when the temperature exceeds the possible for voltage dips lasting between 0.5-2 seconds,
appropriate setpoint(s). Occasionally, HV motors are fed depending on system, motor and drive characteristics,
via a unit transformer, and in these circumstances, some and therefore the time delay will be set bearing these
of the motor protection relay RTD inputs may be factors in mind.
assigned to the transformer winding temperature RTD's,
thus providing overtemperature protection for the
transformer without the use of a separate relay. 1 9 . 1 2 LOSS-OF-LOAD PROTECTION
Loss-of-load protection has a number of possible
functions. It can be used to protect a pump against
1 9 . 1 0 BEARING FAILURES becoming unprimed, or to stop a motor in case of a
There are two types of bearings to be considered: the failure in a mechanical transmission (e.g. conveyor belt),
or it can be used with synchronous motors to protect
anti-friction bearing (ball or roller), used mainly on small
against loss-of-supply conditions. Implementation of
motors (up to around 350kW), and the sleeve bearing,
the function is by a low forward power relay element,
used mainly on large motors.
interlocked with the motor starting device to prevent
The failure of ball or roller bearings usually occurs very operation when the motor is tripped and thus preventing
quickly, causing the motor to come to a standstill as a motor start. Where starting is against a very low load
pieces of the damaged roller get entangled with the (e.g. a compressor), the function may also need to be
others. There is therefore very little chance that any inhibited for the duration of the start, to prevent
relay operating from the input current can detect maloperation.
bearing failures of this type before the bearing is The setting will be influenced by the function to be
completely destroyed. Therefore, protection is limited to performed by the relay. A time delay may be required
disconnecting the stalled motor rapidly to avoid after pickup of the element to prevent operation during
consequential damage. Refer to Section 19.2 on stall system transients. This is especially important for
protection for details of suitable protection. synchronous motor loss-of supply protection.
Failure of a sleeve bearing can be detected by means of
a rise in bearing temperature. The normal thermal
1 9 . 1 3 ADDITIONAL PROTECTION
overload relays cannot give protection to the bearing FOR SYNCHRONOUS MOTORS
itself but will operate to protect the motor from The differences in construction and operational
excessive damage. Use of RTD temperature detection, as characteristics of synchronous motors mean that
noted in Section 19.9, can provide suitable protection, additional protection is required for these types of motor.
allowing investigation into the cause of the bearing This additional protection is discussed in the following
running hot prior to complete failure. sections.
power factor of the motor. It would typically be 0.1 less Rated output 1000kW CMR
than the motor rated power factor i.e. for a motor rated Rated Voltage 3.3 kV
at 0.85 power factor, the setting would be 0.75. Rated frequency 50Hz
Rated power factor/efficiency 0.9/0.92
Stall withstand time cold/hot 20/7s
9.13.2 Protection against Starting current 550% DOL
the hot stall time of 7s but greater than the start time by
a sufficient margin to avoid a spurious trip if the start 19.14.1.7 Other protection considerations
time happens to be a little longer than anticipated. Use
If the relay can be supplied with a suitable voltage signal,
a value of 6.5s.
stall protection can be inhibited during re-acceleration
The protection characteristics for Sections 19.14.1.1-5 after a voltage dip using the undervoltage element (set to
are shown in Figure 19.12. 80-85% of rated voltage). Undervoltage protection (set
to approximately 80% voltage with a time delay of up to
19.14.1.6 Negative phase sequence protection
several seconds, dependent on system characteristics)
Two protection elements are provided, the first is definite and reverse phase protection can also be implemented to
time-delayed to provide an alarm. The second is an IDMT provide extra protection. Unless the drive is critical to the
element used to trip the motor on high levels of negative process, it is not justifiable to provide a VT specially to
sequence current, such as would occur on a loss of phase enable these features to be implemented.
condition at starting.
19.14.2 Protection of an LV Motor
In accordance with Section 19.7, use a setting of 20%
LV motors are commonly fed via fused contactors and
with a time delay of 30s for the definite time element
therefore the tripping times of a protection relay for
and 50% with a TMS of 1.0 for the IDMT element The
overcurrent must be carefully co-ordinated with the fuse where
to ensure that the contactor does not attempt to break a In = motor rated primary current
current in excess of its rating. Table 19.3(a) gives details Ip = CT primary current
of an LV motor and associated fused contactor. A
MiCOM P211 motor protection relay is used to provide Hence, Ib = 5 x 132/150 = 4AA
the protection. With a motor starting current of 670% of nominal, a
setting of the relay thermal time constant with motor
Parameter Value Unit initial thermal state of 50% of 15s is found satisfactory,
Standard IEC 60034 as shown in Figure 19.14.
Motor Voitage 400 V
Motor kW 75 kW
Motor kVA 91.45 kVA
Motor FLC 132 A
Starting Current 670 %
Starting Time 4.5 s
Contactor rating 300 A
Contactor breaking capacity 650 A
Fuse rating 250 A
(a) LV motor example data
Overcurrent Disabled
Overload setting Ib 4.4 A
Overload time delay l>t 15
Unbalance 12 20 %
i
/
i
19.14.2.1 CT ratio
20.1 INTRODUCTION
Many regional, urban and high-speed inter-urban rail
networks worldwide are electrified, to provide the
motive power for trains (Figure 20.1).
..Equation 20.2
where:
D = impedance of shortest hairpin fed
...Equation 20.1 section
where: A = impedance of protected section R =
H = impedance of shortest following section impedance of sections B and C
A = impedance of protected section R = in parallel Z = impedance of
impedance of sections B, C, D in parallel sections A, B, C, D
in parallel
To avoid overreaching for both normal feeding and further, to offset the effects of trains with
hairpin fed faults, the lower of the two calculated regenerative braking, which would provide an additional
impedances is used as the Zone 2 reach setting. current infeed to the fault. An additional 5% reach
increase would generally be sufficient to allow for
20.3.3.3 Zone 3
regenerative underreach
The Zone 3 element would usually be used to provide
overall back-up protection for downstream catenary
sections. The Zone 3 reach (Z3) should typically be set to
at least 115% of the combined apparent impedance of
the protected catenary plus the longest downstream
catenary. Figure 20.9 shows the feeding considered:
Figure 20.9: Fault scenario far Zone 3 An impedance measurement zone with reverse reach is
minimum reach (Normal Feeding) typically applied to provide back-up protection for the
local busbar at a paralleling/sectionalising substation. A
The equation for the minimum Zone 3 reach (normal typical reverse reach is 25% of the Zone 1 reach of the
feeding) for Relay A becomes: relay. Typically Zone 3 is set with a reverse offset to
provide this protection and also so that the Zone 3
element will satisfy the requirement for Switch-on-to
Fault (SOTF) protection.
backward
The phase angle of point B with respect to the resistive 20.3.6 Impact of Trains with Regenerative Braking
axis is determined as: It is common for the Zone 1 characteristic to apply to the
-1
Theta = Cos (max lagging power factor) forward direction only. However, other zones may be set to
have a reverse reach - see Section 20.3.3.4 for details.
The diagram shows how resistive reach E-F for Zone 1 Another case where reverse-reaching zones may be required
has been chosen to avoid the worst-case loading by a is where trains having regenerative braking are used.
suitable margin of 10%-20%. Zones 2 and 3 reach
further, thus the effect of any angular errors introduced Such trains usually regenerate at a leading power factor
to avoid the creation of overvoltages on the catenary. the contact wire. To provide protection against such
Where a regenerating train contributes to fault current, conditions, catenary thermal protection is provided.
the fault impedance measured by distance relays may
shift up to 10° greater than . Some railway
administrations require that the fault impedance 20.4.1 Catenary Thermal Protection Method
remains within the trip characteristic, and does not stray Catenary thermal protection typically uses a current
outside the top left hand resistive boundary of the based thermal replica, using load current to model
polygon. This can be obtained by setting the reverse heating and cooling of the protected catenary. The
resistive reach (Rbw)to be greater than the forward element can be set with both alarm (warning) and trip
resistive reach (Rfw). stages.
final auto-reclose attempt to allow for the higher Maximum Load Current 900A
CB Type Vacuum
catenary to rail fault loop impedance up to the
CB trip time 0.065 s
MPSS rather than the lower catenary-feeder loop
Max Zone 1 protection trip time 0.045 s
impedance. This may be achieved by switching to
Catenary Thermal Protection
an alternative setting group with Z2 set higher Catenary design temperature range for correct tension -18°Cto38°C
than previously
Typical assumed max. winter temperature (610A rating)
Typical assumed max. spring/autumn temp (540A rating) 20°C
Typical assumed summer temperature (515A rating} 23"C
20.6.6 Backup Protection Worst-case assumed hottest ambient 28°C
Backup protection considerations for autotransformer Temperature for Balance Weights to touch ground 38°C
Temperature at which 20% loss of tension, 48°C
fed systems are similar, in principle, to those for classical
train speeds must be restricted
systems, as described in Section 20.5.
Temperature at which possible damage due to 56"C
clashing of supports at overlaps occurs
Heating time constant - daytime 5 mins
20.7 FEEDER SUBSTATION PROTECTION Cooling time constant - nightime 7 mins
Each feeder substation comprises transformers, busbars, Table 20.1: Electrified railway system data
cables, switchgear, etc. All of these items require
protection. Due to the much higher frequency of faults 20.8.1 Section Impedance Data
on the catenary system, special attention must be given
to ensuring that the substation protection remains stable The first step is to calculate the primary impedance for
for catenary faults, whilst offering dependable the catenary sections to be protected. Zone 1 for the
protection for substation faults. relay associated with feeder TF-1 protects section 1,
however the backup protection offered by Zones 2 and 3
Other than this, there are no special requirements for the must discriminate with downstream relays and so the
protection of feeder substation equipment and the forms impedance of sections 2, 3 and 4 needs to be calculated
of protection detailed in Chapters 9-16 are directly too. In this example each pair of catenaries runs
applicable, on a single phase basis. between the common substations, and so the impedance
of adjacent sections will be identical. There are
situations where this is not the case, of which
20.8 EXAMPLE OF CLASSICAL SYSTEM PROTECTION
a. the sections to be protected consist of four tracks
b. the two tracks follow different routes due to the
geography of the route and hence may not be of
the same length
c. if there is a junction within a section
are three examples.
The equivalent section impedance per kilometre is given
by the formula:
ZsecT/km = line impedance/km
+ (BT impcdancc/BT spacing)
Figure 20.17: Network Diagram -
example calculation
t2 = CB max trip time + Relay max trip time b. current for a fault at the end of section 1, with
+ 50ms margin section 2 isolated for maintenance
Hence, For the first configuration, the fault current per track can
be calculated as
t2 = 65 + 45 + 50
160ms
As all of the protection and circuit breakers are
identical, this value can be used for t2. If the downstream where:
relays were electromechanical (typically 40-70ms slower
than numerical), or the circuit breakers were oil
insulated (OCB's, typically 40 to 60ms slower than VCB's),
then the t2 delay would need to be extended
accordingly. The 50ms margin allows for the reset time of
the Z2 element.
Note that the fault current splits into two parallel paths,
fed via TF-1 and TF-2. Hence, the division by 2 in the
equation for calculating the per-track current measured
by the protection.
Hence,
21.1 INTRODUCTION
The testing of protection equipment schemes presents a
number of problems. This is because the main function
of protection equipment is solely concerned with
operation under system fault conditions, and cannot
readily be tested under normal system operating
conditions. This situation is aggravated by the
increasing complexity of protection schemes and use of
relays containing software.
The testing of protection equipment may be divided into
four stages:
i. type tests
ii. routine factory production tests
iii. commissioning tests
iv. periodic maintenance tests
Test 2 Three phase directional pick up and drop off accuracy over
21.2.1 Functional Tests complete RCA setting range in the forward direction, current
angle sweep
The functional tests consist of applying the appropriate Test 3 Three phase directional pick up and drop off accuracy over
inputs to the relay under test and measuring the complete RCA setting range in the reverse direction, current
angle sweep
performance to determine if it meets the specification.
Test 4 Three phase directional pick up and drop off accuracy over
They are usually carried out under controlled complete RCA setting range in the forward direction, voltage
environmental conditions. The testing may be extensive, angle sweep
even where only a simple relay function is being tested., Te5t5 Three phase directional pick up and drop off accuracy over
complete RCA setting range in the reverse direction, voltage
as can be realised by considering the simple overcurrent angle sweep
relay element of Table 21.1. Test6 Three phase polarising voltage threshold test
To determine compliance with the specification, the tests Test 7 Accuracy of DT timer over complete setting range
listed in Table 21.2 are required to be carried out. This is Test 8 Accuracy of IDMT curves over claimed accuracy range
a time consuming task, involving many engineers and Test 9 Accuracy of IDMTTMS/TD
technicians. Hence it is expensive. Test 10 Effect of changing fault current on IDMT operating times
Test 11 Minimum Pick-Up of Starts and Trips for IDMT curves
When a modern numerical relay with many functions is
Test 12 Accuracy of reset timers
considered, each of which has to be type-tested, the
Test 13 Effect of any blocking signals, opto inputs, VTS, Autoreclose
functional type-testing involved is a major issue. In the
Test 14 Voltage polarisation memory
case of a recent relay development project, it was Table 21.2: Overcurrent relay element functional type tests
calculated that if one person had to do all the work, it
21.2.2 Rating Tests seconds. This is carried out between all circuits and case
earth, between all independent circuits and across
Rating type tests are conducted to ensure that
normally open contacts. The acceptance criterion for a
components are used within their specified ratings and
product in new condition is a minimum of 100MOhm.
that there are no fire or electric shock hazards under a
After a damp heat test the pass criterion is a minimum
normal load or fault condition of the power system. This
is in addition to checking that the product complies with of 10MOhma.
its technical specification. The following are amongst
the rating type tests conducted on protection relays, the
21.2.7 Auxiliary Supplies
specified parameters are normally to IEC 60255-6.
Digital and numerical protection relays normally require
an auxiliary supply to provide power to the on-board
21.2.3 Thermal Withstand microprocessor circuitry and the interfacing opto-
isolated input circuits and output relays. The auxiliary
The thermal withstand of VT's, CT's and output contact
supply can be either a.c. or d.c, supplied from a number
circuits is determined to ensure compliance with the
of sources or safe supplies - i.e. batteries, UPS',
specified continuous and short-term overload conditions.
generators, etc., all of which may be subject to voltage
In addition to functional verification, the pass criterion is
dips, short interruptions and voltage variations. Relays
that there is no detrimental effect on the relay assembly,
are designed to ensure that operation is maintained and
or circuit components, when the product is subjected to
no damage occurs during a disturbance of the auxiliary
overload conditions that may be expected in service.
supply.
Thermal withstand is assessed over a time period of 1s
for CT's and 10s for VT's. Tests are carried out for both a.c. and d.c. auxiliary
supplies and include mains variation both above and
below the nominal rating, supply interruptions derived by
21.2.4 Relay Burden open circuit and short circuit, supply dips as a
The burdens of the auxiliary supply, optically isolated percentage of the nominal supply, repetitive starts. The
inputs, VT's and CT's are measured to check that the duration of the interruptions and supply dips range from
product complies with its specification. The burden of 2ms to 60s intervals. A short supply interruption or dip
products with a high number of input/output circuits is up to 20ms, possibly longer, should not cause any
application specific i.e. it increases according to the malfunction of the relay. Malfunctions include the
number of optically isolated input and output contact operation of output relays and watchdog contacts, the
ports which are energised under normal power system reset of microprocessors, alarm or trip indication,
load conditions. It is usually envisaged that not more acceptance of corrupted data over the communication
than 50% of such ports will be energised in any link and the corruption of stored data or settings. For a
application. longer supply interruption, or dip in excess of 20ms, the
relay self recovers without the loss of any function, data,
settings or corruption of data. No operator intervention
21.2.5 Relay Inputs is required to restore operation after an interruption or
dip in the supply. Many relays have a specification that
Relay inputs are tested over the specified ranges. Inputs exceeds this requirement, tolerating dips of up to 50ms
include those for auxiliary voltage, VT, CT, frequency, without operation being affected.
optically isolated digital inputs and communication
circuits. In addition to the above, the relay is subjected to a number
of repetitive starts or a sequence of supply interruptions.
Again the relay is tested to ensure that no damage or data
21.2.6 Relay Output Contacts corruption has occurred during the repetitive tests.
Protection relay output contacts are type tested to Specific tests carried out on d.c. auxiliary supplies
ensure that they comply with the product specification. include reverse polarity, a.c. waveform superimposed on
Particular withstand and endurance type tests have to be the d.c. supply and the effect of a rising and decaying
carried out using d.c, since the normal supply is via a auxiliary voltage. All tests are carried out at various
station battery. levels of loading of the relay auxiliary supply.
Enclosure protection tests prove that the casing system Figure 21.10: Relay undergoing seismic test
and connectors on the product protect against the ingress
of dust, moisture, water droplets (striking the case at pre-
defined angles) and other pollutants. An 'acceptable' level
of dust or water may penetrate the case during testing,
but must not impair normal product operation, safety or
cause tracking across insulated parts of connectors.
Tests in the first category are concerned with the Figure 21.11: Shock/Bump Impulse waveform
response to vibration, shock and seismic disturbance.
The test levels for shock and bump tests are:
The tests are designed to simulate normal in-service
conditions for the product, for example earthquakes. Shock response (energised):
These tests are performed in all three axes, with the
3 pulses, each 10g, 11ms duration
product energised in its normal (quiescent) state. During
the test, all output contacts are continually monitored Shock withstand (de-energised):
for change using contact follower circuits. Vibration 3 pulses, 15g, 11ms duration
levels of Ign, over a 10Hz-150Hz frequency sweep are
used. Seismic tests use excitation in a single axis, using Bump (de-energised):
a test frequency of 35Hz and peak displacements of 1000 pulses, 10g, 16ms duration
7.5mm and 3.5mm in the x and y axes respectively below
the crossover frequency and peak accelerations of 2.0gn
and 1.0gn in these axes above the crossover frequency. 21.6 SOFTWARE TYPE TESTS
The second category consists of vibration endurance, Digital and numerical relays contain software to
shock withstand and bump tests. They are designed to implement the protection and measurement functions of
simulate the longer-term affects of shock and vibration a relay. This software must be thoroughly tested, to
that could occur during transportation. These tests are ensure that the relay complies with all specifications and
performed with the product de-energised. After these that disturbances of various kinds do not result in
tests, the product must still operate within its unexpected results. Software is tested in various stages:
specification and show no signs of permanent
a. unit testing
mechanical damage. Equipment undergoing a seismic
type test is shown in Figure 21.10, while the waveform b. integration testing
for the shock/bump test is shown in Figure 21.11
c. functional qualification testing
The purpose of unit testing is to determine if an 21.6.3 Unit Testing Environment
individual function or procedure implemented using
Both Dynamic and Static Unit Testing are performed in
software, or small group of closely related functions, is the host environment rather than the target
free of data, logic, or standards errors. It is much easier environment. Dynamic Unit Testing uses a test harness
to detect these types of errors in individual units or small to execute the unit(s) concerned. The test harness is
groups of units than it is in an integrated software designed such that it simulates the interfaces of the
architecture and/or system. Unit testing is typically unit(s) being tested - both software-software interfaces
performed against the software detailed design and by and software-hardware interfaces - using what are
the developer of the unit(s). known as stubs. The test harness provides the test data
Integration testing typically focuses on these interfaces to those units being tested and outputs the test results
and also issues such as performance, timings and in a form understandable to a developer. There are many
synchronisation that are not applicable in unit testing. commercially available testing tools to automate test
Integration testing also focuses on 'stressing' the harness production and the execution of tests.
software and related interfaces.
Integration testing is 'black box' in nature, i.e. it does not 21.6.4 Software/Software Integration Testing
take into account the structure of individual units. It is
Software/Software Integration Testing is performed in
typically performed against the software architectural
the host environment. It uses a test harness to simulate
and detailed design. The specified software requirements inputs and outputs, hardware calls and system calls (e.g.
would typically also be used as a source for some of the the target environment operating system).
test cases.
system. The software is also capable of modelling the test results being available on completion
dynamic response of CT's and VT's accurately.
A block schematic of the equipment is shown in Figure
Where it is desired to check the response of a relay or 21.13, is based around a computer which calculates and
protection scheme to an actual power system transient, stores the digital data representing the system voltages
the transient can be simulated using sophisticated power and currents. The computer controls conversion of the
systems analysis software and the results transferred digital data into analogue signals, and it monitors and
digitally to the simulator, or the event recorder recording controls the relays being tested.
of the transient can be used, in either digital or analogue
21.7.2.2 Simulation software
form as inputs to the simulator model. Output signal
conversion involves circuits to eliminate the quantisation Unlike most traditional software used for power systems
steps normally found in conventional D/A conversion. analysis, the software used is suitable for the modelling
Analogue models of the system transducer the fast transients that occur in the first few
characteristics can be interposed between the signal milliseconds after fault inception. Two very accurate
processors and the output amplifiers when required. simulation programs are used, one based on time domain
This equipment shows many advantages over traditional and the other on frequency domain techniques. In both
test equipment: programs, single and double circuit transmission lines are
represented by fully distributed parameter models. The
a. the power system model is capable of reproducing line parameters are calculated from the physical
high frequency transients such as travelling waves
construction of the line (symmetrical, asymmetrical,
b. tests involving very long time constants can be transposed or non-transposed), taking into account the
carried out effect of conductor geometry, conductor internal
c. it is not affected by the harmonic content, noise impedance and the earth return path. It also includes,
and frequency variations in the a.c. supply where appropriate, the frequency dependence of the line
parameters in the frequency domain program. The
d. it is capable of representing the variation in the frequency dependent variable effects are calculated
current associated with generator faults and power using Fast Fourier Transforms and the results are
swings converted to the time domain. Conventional current
e. saturation effects in CT's and VT's can be modelled transformers and capacitor voltage transformers can be
simulated.
f. a set of test routines can be specified in software and
then left to run unattended (or with only occasional The fault can be applied at any one point in the system and
monitoring) to completion, with a detailed record of can be any combination of phase to phase or phase
Figure 21.13: Block diagram of microprocessor-based automated relay testsyi
In addition to these two programs, a simulation program k. transducer models can be included
based on lumped resistance and inductance parameters I. automatic testing removes the likelihood of
is used. This simulation is used to represent systems with measurement and setting errors
long time constants and slow system changes due, for
example, to power swings.
m. two such equipments can be linked together to
simulate a system model with two relaying points
21.7.2.3 Simulator applications
The simulator is also used for the production testing of
The simulator is used for checking the accuracy of relays, in which most of the advantages listed above
calibration and performing type tests on a wide range of apply. As the tests and measurements are made
protection relays during their development. It has the automatically, the quality of testing is also greatly
following advantages over existing test methods: enhanced. Further, in cases of suspected malfunction of
a. 'state of the art' power system modelling data can a relay in the field under known fault conditions, the
be used to test relays simulator can be used to replicate the power system and
fault conditions, and conduct a detailed investigation
b. freedom from frequency variations and noise or
into the performance of the relay. Finally, complex
harmonic content of the a.c. supply
protection schemes can be modelled, using both the
c. the relay under test does not burden the power relays intended for use and software models of them as
system simulation appropriate, to check the suitability of the proposed
scheme under a wide variety of conditions. To illustrate
d. all tests are accurately repeatable
this, Figure 21.14(a) shows a section of a particular power
e. wide bandwidth signals can be produced system modelled. The waveforms of Figure 21.14(b) show
f. a wide range of frequencies can be reproduced the three phase voltages and currents at the primaries of
VT1 and CT1 for the fault condition indicated in Figure
g. selected harmonics may be superimposed on the 21.14(a).
Figure 21.14: Example of application study
21
source - the distorted relay coil current waveform gives 3-phase output set. Much greater precision in the
rise to an extended operation time compared to the setting of the magnitudes and phase angles is possible,
expected value. compared to traditional test sets. Digital signals to
exercise the internal logic elements of the relays may
Modern test sets are computer based. They comprise a
also be provided. The alarm and trip outputs of the relay
PC (usually a standard laptop PC with suitable software)
are connected to digital inputs on the PC so that correct
and a power amplifier that takes the low-level outputs
operation of the relay, including accuracy of the relay
from the PC and amplifies them into voltage and current
tripping characteristic can be monitored and displayed
signals suitable for application to the VT and CT inputs of on-screen, saved for inclusion in reports generated later,
the relay. The phase angle between voltage and current or printed for an immediate record to present to the
outputs will be adjustable, as also will the phase angles client. Optional features may include GPS time
between the individual voltages or currents making up a synchronising equipment and remote-located amplifiers
to facilitate testing of unit protection schemes, and
digital I/O for exercising the programmable scheme logic
of modern relays.
The software for modern test sets is capable of testing
the functionality of a wide variety of relays, and
conducting a set of tests automatically. Such sets ease
the task of the commissioning engineer. The software
will normally offer options for testing, ranging from a
test carried out at a particular point on the characteristic
to complete determination of the tripping characteristic
automatically. This feature can be helpful if there is any
reason to doubt that the relay is operating correctly with
the tripping characteristic specified. Figure 21.21
illustrates a modern PC-based test set.
Traditional test sets use an arrangement of adjustable
transformers and reactors to provide control of current
and voltage without incurring high power dissipation.
Some relays require adjustment of the phase between
the injected voltages and currents, and so phase shifting
transformers may be used. Figure 21.22 shows the
circuit diagram of a traditional test set suitable for
overcurrent relay resting, while Figure 21.23 shows the
circuit diagram for a test set for directional/distance Figure 21.21: Modern PC-based secondary
relays. Timers are included so that the response time of injection test set
Figure 21.22: Circuit diagram of traditional test set for overcurrent relays
Figure 21.23: Circuit diagram for traditional test
set for directional/distance relays
a. checking of the scheme logic specification and The clearance of a fault on the system is correct only if
diagrams to ensure that the objectives of the logic the number of circuit breakers opened is the minimum
are achieved necessary to remove the fault. A small proportion of
faults are incorrectly cleared, the main reasons being:
b. testing of the logic to ensure that the functionality
of the scheme is proven a. limitations in protection scheme design
3. the correct flag indications are given The remaining three causes are not controllable, while
two of these three are unavoidable - engineering is not
4. there is no maloperation of other apparatus that science and there will always be situations that a
may be connected to the same master trip relay or protection relay cannot reasonably be expected to cover
circuit breaker at an affordable cost
commissioning of the equipment.
21.17 REFERENCES
21.1 Protective Relays Application Guide, 3rd edition.
ALSTOM Transmission and Distribution,
Protection and Control, 1987.
22 • Power System Measurements
22.1 INTRODUCTION
The accurate measurement of the voltage, current or
other parameter of a power system is a prerequisite to
any form of control, ranging from automatic closed-loop
control to the recording of data for statistical purposes.
Measurement of these parameters can be accomplished
in a variety of ways, including the use of direct-reading
instruments as well as electrical measuring transducers.
Transducers produce an accurate d.c. analogue output,
usually a current, which corresponds to the parameter
being measured (the measurand). They provide electrical
isolation by transformers, sometimes referred to as
'Galvanic Isolation1, between the input and the output.
This is primarily a safety feature, but also means that the
cabling from the output terminals to any receiving
equipment can be lightweight and have a lower
insulation specification. The advantages over discrete
measuring instruments are as follows:
a. mounted close to the source of the measurement,
reducing instrument transformer burdens and
increasing safety through elimination of long
wiring runs
b. ability to mount display equipment remote from
transducer
c. ability to use multiple display elements per transducer
d. the burden on CT's/VT's is considerably less
Outputs from transducers may be used in many ways -
from simple presentation of measured values for an
operator, to being utilised by a network automation
scheme to determine the control strategy.
The input impedance of any current input circuit will be Table 22.1: Transducer influence quantities
Confusion also arises in specifying the performance adjusted to respond to the r.m.s. value of a pure sine
under real operating conditions. The output signal is wave. If the input waveform becomes distorted, errors
often a d.c. analogue of the measurand, but is obtained will result. For example, the error due to third harmonic
from alternating input quantities and will, inevitably, distortion can amount to 1% for every 3% of harmonic.
contain a certain amount of alternating component, or
Once installed, the user expects the accuracy of a
ripple. Ripple is defined as the peak-to-peak value of the
transducer to remain stable over time. The use of high
alternating component of the output signal although
quality components and conservative power ratings will
some manufacturers quote 'mean-to-peak' or 'r.m.s.'
help to ensure long-term stability, but adverse site
values. To be meaningful, the conditions under which
conditions can cause performance changes which may
the value of the ripple has been measured must be
need to be compensated for during the lifetime of the
stated, e.g. 0.35% r.m.s. = 1.0% peak-to-peak ripple.
equipment.
Under changing conditions of the measurand, the output
signal does not follow the changes instantaneously but
is time-delayed. This is due to the filtering required to 22.3 DIGITAL TRANSDUCER TECHNOLOGY
reduce ripple or, in transducers using numerical
Digital power system transducers make use of the same
technology, prevent aliasing. The amount of the delay is
technology as that described for digital and numerical
called the response time. To a certain extent, ripple and
relays in Chapter 7. The analogue signals acquired from
response time are interrelated. The response time can
VT's and CT's are filtered to avoid aliasing, converted to
usually be shortened at the expense of increased ripple,
digital form using A/D conversion, and then signal
and vice-versa. Transducers having shorter response
processing is carried out to extract the information
times than normal can be supplied for those instances
required. Basic details are given in Chapter 7. Sample
where the power system suffers swings, dips, and low
frequency oscillations that must be monitored. rates of 64 samples/cycle or greater may be used, and the
accuracy class is normally 0.5.
Transducers having a current output have a maximum
Outputs may be both digital and analogue. The analogue
output voltage, known as the compliance voltage. If the
outputs will be affected by the factors influencing
load resistance is too high and hence the compliance
accuracy as described above. Digital outputs are
voltage is exceeded, the output of the transducer is no
typically in the form of a communications link with
longer accurate.
RS232 and/or RS485 types available. The response time
Certain transducers are characterised by the may suffer compared to analogue transducers,
manufacturer for use on systems where the waveform is depending on the rate at which values are transferred to
not a pure sinusoid. They are commonly referred to as the communications link and the delay in processing
'true r.m.s. sensing' types. For these types, the distortion data at the receiving end. In fact, all of the influence
factor of the waveform is an influence quantity. Other quantities that affect a traditional analogue transducer
transducers are referred to as 'mean-sensing' and are also are present in a digital transducer in some form, but
the errors resulting may be much less than in an These features are shown diagrammatically in Figure 22.1.
analogue transducer and it may be more stable over a
long period of time.
The advantages of a transducer using numerical
technology are:
1. improved long-term stability
2. more accurate r.m.s measurements
3. improved communications facilities
4. programmability of scaling
5. wider range of functions
6. reduced size
The improved long term stability reduces costs by
extending the intervals between re-calibration. More
accurate r.m.s measurements provide the user with data Figure 22.1: Schematic of on analogue
transducer
of improved accuracy, especially on supplies with
significant harmonic content. The improved Output ranges of 0-1 OmA, 0-20mA, and 4-20mA are
communications facilities permit many transducers to common. Live zero (e.g. 4-20mA), suppressed zero (e.g.
share the same communications link, and each 0-10mA for 300-500kV) and linear inverse range (e.g.
transducer to provide several measurements. This leads 10-0mA for 0-15kV) transducers normally require an
to economy in interconnecting wiring and number of auxiliary supply. The dual-slope type has two linear
transducers used. Remote or local programmable scaling sections to its output characteristic, for example, an
of the transducer permits scaling of the transducer in the output of 0-2mA for the first part of the input range, 0-
field. The scaling can be changed to reflect changes in 8kV, and 2-10mA for the second part, 8-15kV.
the network, or to be re-used elsewhere. Changes can be
downloaded via the communications link, thus removing
the need for a site visit. It also minimises the risk of the 22.5 TRANSDUCER SELECTION
user specifying an incorrect scaling factor and having to The selection of the correct transducer to perform a
return the transducer to the manufacturer for measurement function depends on many factors. These
adjustment. Suppliers can keep a wider range of are detailed below.
transducers suitable for a wide range of applications and
inputs in stock, thus reducing delivery times.
Transducers are available with a much wider range of 22.5.1 Current Transducers
functions in one package, thus reducing space
Current transducers are usually connected to the
requirements in a switchboard. Functions available
secondary of an instrument current transformer with a
include harmonics up to the 31st, energy, and maximum rated output of 1 or 5 amps. Mean-sensing and true
demand information. The latter are useful for tariff r.m.s. types are available. If the waveform contains
negotiations. significant amounts of harmonics, a true r.m.s sensing
type must be used for accurate measurement of the
input. They can be self-powered, except for the true
22.4 ANALOGUE TRANSDUCER TECHNOLOGY
r.m.s. types, or when a live zero output (for example 4-
All analogue transducers have the following essential 20mA) is required. They are not directional and,
features: therefore, are unable to distinguish between 'export' and
'import' current. To obtain a directional signal, a voltage
a. an input circuit having impedance Zin
input is also required.
b. isolation (no electrical connection) between input
and output
22.5.2 Voltage Transducers
c. an ideal current source generating an output
current, I1 which is an accurate and linear Connection is usually to the secondary of an instrument
function of Qin, the input quantity voltage transformer but may be direct if the measured
quantity is of sufficiently low voltage. The suppressed
d. a parallel output impedance, Zo. This represents
zero type is commonly used to provide an output for a
the actual output impedance of the current source specific range of input voltage where measurement of
and shunts a small fraction, I2, of the ideal output zero on the input quantity is not required. The linear
e. an output current, Io, equal to (I1 -I2) inverse type is often used as an aid to synchronising.
22.5.3 Frequency phase angle transducer use the zero crossing point of the
input waveform to obtain the phase information and are
Accurate measurement of frequency is of vital
importance to transmission system operators but not thus prone to error if the input contains significant
quite so important, perhaps, for the operator of a diesel amounts of harmonics.
generator set Accuracy specifications of 0.1% and Calculating the power factor from the values of the
0.01% are available, based on percent of centre scale outputs of a watt and a var transducer will give a true
frequency. This means, for example that a device quoted measurement in the presence of harmonics.
as 0.1% and having a centre scale value of 50Hz will
have a maximum error of ±50mHz under reference
conditions. 22.5.5 Power Quantities
The measurement of active power (watts) and reactive
22.5.4 Phase Angle power (vars) is generally not quite as simple as for the
other quantities. More care needs to be taken with the
Transducers for the measurement of phase angle are
selection of these types because of the variety of
frequently used for the display of power factor. This is
configurations. It is essential to select the appropriate
achieved by scaling the indicating instrument in a non-
type for the system to be measured by taking into
linear fashion, following the cosine law. For digital
indicators and SCADA equipment, it is necessary for the account factors such as system operating conditions
receiving equipment to provide appropriate conversions (balanced or unbalanced load), the number of current
to achieve the correct display of power factor. Phase and voltage connections available and whether the
angle transducers are available with various input power flow is likely to be 'import1, 'export', or both. The
ranges. When the scaling is -180°...0o...180o( there is an range of the measurand will need to encompass all
ambiguous region, of about ±2° at the extremes of the required possibilities of over-range under normal
range. In this region, where the output is expected to be, conditions so that the transducer and its indicating
for example, -10mA or + 10mA, the output may jump instrument, or other receiving equipment, is not used
sporadically from one of the full-scale values to the above the upper limit of its effective range. Figure 22.2
other. Transducers are also available for measurement of illustrates the connections to be used for the various
the angle between two input voltages. Some types of types of measurement.
Table 22.3: Typical function set provided Tariff metering is a specialised form of measurement,
by a Measurement Centre being concerned with the measurement of electrical
power, reactive power or energy for the purposes of
charging the consumer. As such, it must conform to the
The advantages of a Measurement Centre are that a appropriate national standards for such matters. Primary
comprehensive set of functions are provided in a single tariff metering is used for customer billing purposes, and
item of equipment, taking up very little extra space may involve a measurement accuracy of 0.2% of reading,
compared to a discrete transducer for a much smaller even for readings that are 5% or less of the nominal
number of parameters. Therefore, when the requisite I rated value. Secondary tariff metering is applied where
the user wishes to include his own metering as a check
CT's and VT's are available, it may well make sense to use
on the primary tariff metering installed by the supplier,
a Measurement Centre even if not all of the functionality
or within a large plant or building to gain an accurate
is immediately required. History shows that more and
picture of the consumption of energy in different areas,
more data is required as time passes, and incorporation
perhaps for the purpose of energy audits or internal cost
of full functionality at the outset may make sense.
allocation. The accuracy of such metering is rather less,
Figure 22.3 illustrates the wide variety of transducers an overall accuracy of 0.5% over a wide measurement
and Measurement Centres available.
range being typically required. As this is the overall be tolerated without leading to excessive current/voltage
accuracy required, each element in the metering chain transients on CB closure. The check synchroniser has
(starting with the CT's/VT's) must have an accuracy rather programmable error limits to define the limits of
better than this. Careful attention to wiring and mounting acceptability when making the comparison.
of the transducer is required to avoid errors due to
interference, and the accuracy may need to be maintained
over a fairly wide frequency range. Thus a tariff metering
scheme requires careful design of all of the equipment
included in the scheme. Facilities are normally included to
provide measurements over a large number of defined
time periods (e.g. 24 half-hour periods for generator
energy tariff metering) so that the exporter of the energy
can produce an overall invoice for the user according to
the correct rates for each tariff period. The time intervals
that these periods cover may change according to the time
of year (winter, spring, etc.) and therefore flexibility of
programming of the energy metering is required. Remote
communications are invariably required, so that the data
is transferred to the relevant department on a regular
basis for invoicing purposes.
22.8 SYNCHRONISERS
Synchronisers are required at points on a power system
where two supplies (either generator and grid, or two
grid supplies) may need to be paralleled. They are more
than just a measuring device, as they will provide
contact closures to permit circuit breaker closing when
conditions for paralleling (synchronising) are within Figure 22.4: Check synchroniser applications
when the differences are within pre-set limits. While CB Incoming supply voltage setpoint Incoming supply frequency setpoint
Voltage raise/lower pulse time Frequency raise/lower pulse time
closure at the instant of perfect synchronism is the ideal,
this is very difficult to obtain in practice and some (b) Additional functions for auto-synchroniser
mismatch in one or more of the monitored quantities can Table 22.4: Synchroniser function set
When the close signal is permitted, it may be given only emergency conditions, it could block the synchronising
for a limited period of time, to minimise the chances of of a generator that was urgently required in service to
a CB close signal remaining after the conditions have help assist in overcoming the condition.
moved outside of limits. Similarly, circuits may also be
If (a) above is not within limits, signals are sent
provided to block closure if the CB close signal from the
automatically to the governor of the generating set to
CB close controls is present prior to satisfactory
adjust the speed setpoint appropriately. In the case of (c)
conditions being present - this ensures that an operator
not in limits, similar signals are sent to the Automatic
must be monitoring the synchronising displays and only
Voltage Regulator to raise or lower the setpoint. The
initiating closure when synchronising conditions are
signals are commonly in the form of pulses to raise or
correct, and also detects synchronising switch contacts
lower the setpoint, but could be continuous signals if
that have become welded together.
that is what the particular equipment requires. It is
A check synchroniser does not initiate any adjustments if normal for the speed and voltage of the generator to be
synchronising conditions are not correct, and therefore slightly higher than that of the network, and this can be
acts only as a permissive control in the overall CB closing accommodated either by initial settings on the
circuit to provide a check that conditions are satisfactory. Governor/AVR or by providing setpoint values in the
In a substation, check-synchronisers may be applied synchroniser. This ensures stable synchronising and
individually to all required CB's. Alternatively, a reduced export of power at lagging power factor to the network
number may be installed, together with suitable switching by the generator after CB closure. The possibility of
arrangements in the signal input/output circuits so that a tripping due to reverse/low forward power conditions
single device may be selected to cover several CB's. and/or field failure/under-excitation is avoided. Use of
an auto-synchroniser also helps avoid human error if
manual synchronising were employed - there is potential
22.8.2 Auto-synchroniser for damage to equipment, primarily the generator, if
An auto-synchroniser contains additional functionality synchronising outside of permitted limits occurs.
compared to a check synchroniser. When an auto- To ensure that the CB is closed at the correct instant, the
synchroniser is placed in service, it measures the CB close time is normally a required data item. The auto-
frequency and magnitude of the voltages on both sides synchroniser calculates from a knowledge of this and the
of the circuit breaker, and automatically adjusts one of slip frequency the correct time in advance of phase co-
the voltages if conditions are not correct. Application of incidence to issue the CB close command. This ensures
auto-synchronisers is normally restricted to generators - that the CB closes as close to the instant of phase co-
i.e. the situation shown in Figure 22.4(a), replacing the incidence as possible. Upon receipt of the signal
check synchroniser with an auto-synchroniser. This is indicating 'CB closed' a further signal to raise frequency
because it is generally not possible to adjust either of the may be sent to the governor to ensure stable export of
network voltages by changing the settings of one or a power is achieved. Conversely, failure of the CB to close
very few equipments in a network. When applied to a within a set time period will reset the auto-synchroniser,
generator, it is relatively easy to adjust the frequency and ready for another attempt, and if further attempts are
magnitude of the generated voltage by transmitting still unsuccessful, the auto-synchroniser will lock out
signals to the Governor and AVR respectively. and raise an alarm.
The auto-synchroniser will check the voltage of the Practice in respect of fitting of auto-synchronisers varies
incoming generator against the network voltage for widely between Utilities. Where policy is flexible, it is
compliance with the following (Table 22.4(a), (b)): most common when the time to synchronise is important
a. slip frequency within limits (i.e. difference in - i.e. emergency standby and peak lopping sets. Many
frequency between the generator and network) Utilities still relay on manual synchronising procedures. It
is also possible for both an auto-synchroniser and check-
b. phase difference between the voltages within synchroniser to be fitted in series. This provides protection
limits against internal failure of the auto-synchroniser leading
c. voltage magnitude difference within limits to a CB close command being given incorrectly.
23.1 INTRODUCTION
Over the lastthirty years orso, the amount of equipment
containing electronics has increased dramatically. Such
equipment can both cause and be affected by
electromagnetic disturbances. A disturbance that
affects a process control computer in a large industrial
complex could easily result in shutdown of the process.
The lost production and product loss/recycling during
start-up represents a large cost to the business.
Similarly, a protection relay affected by a disturbance
through conduction or radiation from nearby conductors
could trip a feeder or substation, causing loss of supply
to a large number of consumers. At the other end of the
scale, a domestic user of a PC has to re-boot the PC due
to a transient voltage dip, causing annoyance to that
and other similarly affected users. Therefore,
transporters and users of electrical energy have become
much more interested in the nature and frequency of
disturbances in the power supply. The topic has become
known by the title of Power Quality.
Transients Lightning Capacitive Control system resetting Figure 23.1: ITI curve for equipment
switching Non -linear Damage to sensitive susceptibility
switching loads System electronic components
voltage regulation Damage to insulation
Equipment Application
24.1 INTRODUCTION
The sometimes complex interlocking and sequence
control requirements that are to be found in a
substation of any significant size lend themselves
naturally to the application of automation. These
requirements can be readily expressed in mathematical
logic (truth tables, boolean algebra, etc.) and this branch
of mathematics is well-suited to the application of
computers and associated software. Hence, computers
have been applied to the control of electrical networks
for many years, and examples of them being applied to
substation control/automation were in use in the early
1970's. The first applications were naturally in the bulk
power transmission field, as a natural extension of a
trend to centralised control rooms for such systems. The
large capital investment in such systems and the
consequences of major system disruption made the cost
of such schemes justifiable. In the last ten years or so,
continuing cost pressures on Utilities and advances in
computing power and software have led to the
application of computers to substation control/
automation on a much wider basis.
This Chapter outlines the current technology and
provides examples of modern practice in the field.
and others for engineering use. Optionally, a remote HMI Figure 24.5: Methods of hardware
computer may be made available via a separate link. It interconnection
is always desirable in such schemes to separate the real-
time operations function from engineering tasks, which
do not have the same time-critical importance. Of course, it is possible to overcome the first problem by
duplicating links and running the links in physically
separate routes. However, this makes the I/O port
problem worse, while additional design effort is required
in ensuring cable route diversity.
An alternative is to connect the Bay Modules, HMI
computer and SCADA gateway in a ring, as shown in
Figure 24.5(b). By using a communication architecture
such as found in a LAN network, each device is able to
talk to any other device on the ring without any message
conflicts. A single break in the ring does not result in
loss of any facilities. The detection of ring breakage and
re-configuration required can be made automatically.
Thus, the availability and fault tolerance of the network
is improved. Multiple rings emanating from the HMI
computer can be used if the number of devices exceeds
Figure 24.4: Decentralised topology
the limit for a single ring. It can be easier to install on a
step-by-step basis for retrofit applications, but of course,
The connection between the various Bay Modules and all these advantages have a downside. The cost of such
the HMI computer is of some interest. Simplest is the a topology is higher than that of the other solutions, so
star arrangement of Figure 24.5(a). This is the least-cost this topology is reserved for situations where the highest
solution but suffers from two disadvantages. Firstly, a reliability and availability is required - i.e. HV and EHV
break in the link will result in loss of remote control of transmission substations.
the bay affected; only local control via a local HMI Redundancy can also be provided at the individual device
computer connected to the bay is then possible. level. Relays and other lED's may be duplicated, though
Secondly, the number of communication ports available this would not be usual unless required for other reasons
on the HMI computer will limit the number of Bay (e.g. EHV transmission lines may be required to have
Modules. duplicate main protections - this is not strictly speaking
duplication of individual devices - which would require A significant problem to be overcome in the
each individual main protection to have two identical implementation of communication links is the possibility
relays voting on a '1 out of 2' basis). It is usual to have of electromagnetic interference. The low voltage levels
more than one operators' HMI, either for operational that are used on most types of communication link may
reasons or for fault-tolerance. The system computer may be prone to interference as a result. Careful design of
be duplicated on a 'hot-standby' or 'dual-redundant' the interfaces between the devices used and the
basis, or tasks may be normally shared between two or communication bus, involving the use of opto-couplers
more system computers with each of them having the and protocol converters, is required to minimise the risk.
capability of taking over the functions of one of the Care over the arrangement of the communication cables
others in the event of a failure. is also required. It may also help to use a communication
protocol that incorporates a means of error
The total I/O count in a major substation will become
detection/correction. While it may not be possible to
large and it must be ensured that the computer hardware
correct all errors, detection offers the opportunity to
and communication links have sufficient performance to
request re-transmission of the message, and also for
ensure prompt processing of incoming data. Overload in
statistics to be gathered on error rates on various parts
this area can lead to one or more of the following:
of the system. An unusually high error rate on a part of
a. undue delay in updating the system status the communication system can be flagged to
diagrams/events log/alarm log in response to an maintenance crews for investigation.
incident
b. corruption of system database, so that the
24.4 COMMUNICATION METHODS
information presented to the operator is not an
accurate representation of the state of the actual Digital communication between items of hardware is
electrical system divided into three elements:
a. the protocol, consisting of the hardware, such as
c. system lockup
connectors, connector pin functions, and signal
As I/O at the bay level, both digital and analogue will levels
typically be handled by intelligent relays or specialised b. the format, consisting of the control of the flow of
lED's, it is therefore important to ensure that these data
devices have sufficient I/O capacity. If additional lED's c. the language, or how the information in the data
have to be provided solely for ensuring adequate I/O flow is organised
capacity, cost and space requirements will increase. Each of these areas is covered so that an appreciation of
There will also be an increase in the number of the complexities of d ig i ta l communications is
communication links required. understood.
A practical specification for system response times is
given in Table 24.1. Table 24.2 gives a typical
specification for the maximum I/O capacities of a 24.4.1 Communication Protocols and Formats
substation automation system. Anyone trying to connect up the various elements of a
Hi-Fi system if they have purchased them from different
manufacturers will be aware of the number of different
protocols in use. The situation is the same in the
Signal Type Response Time to/from HMI
industrial field. Manufacturers of devices are often
Digital Input Is
tempted to utilise a proprietary protocol, for no better
Analogue Input is
Digital Output 0.75s
reason sometimes than to encourage the sole use of their
Disturbance Record File 3s devices. Users, of course, have the opposite interest;
\hble 24. /: Practical system response times for
they would like every manufacturer to use the same
a substation automation scheme protocol so that they have the widest choice. In practice,
protocols have evolved over time, and some protocols are
more appropriate to some communication requirements
I/O Type Capacity Digital than others. The protocol used is also linked to the
Input 8196 Digital format used, since the number of conductors required
Output 2048 Analogue may depend on the format used.
Input 2048 Analogue
Output 512 There are two basic formats in use for data
Table 24.2: Typical I/O capacities for a substation
communications:
automation system a. serial
b. parallel
Serial format involves sending the data one bit at a time Thus devices can be located throughout a substation
along the communication channel. Parallel format without causing communications problems and significant
involves sending several bits simultaneously. Clearly, amounts of data can be transmitted rapidly. The main
parallel communication requires more wires than serial drawback is that it is a half-duplex system, so that
communication (a disadvantage) but can transmit a communications use a kind of question and answer
given amount of data faster. In practice, parallel technique known as 'polling'. The equipment that needs
communication is limited to communication over a few the data (e.g. a substation computer or bay controller) must
metres, and hence the majority of communications use ask each device in turn for the data requested and then
serial format. There are a number of popular serial wait for the response prior to moving on to the next device.
communication protocols in common use in the
substation automation field.
24.4.1.1 RS232C Protocol
The RS232C protocol allows for full duplex
communications between two devices. The basic
specification is given in Table 24.3. The hardware
specification can vary - nine conductors are the minimum
required for a full implementation, while a 25 pin
connector is commonly encountered. If flow control of
data is not required, only three signals are required (data
transmit/receive and ground). Being limited to
Figure 24.6: 'Daisy-chain' connection
communication between two devices, this protocol is not of RS485 devices
useful in substation automation schemes. However, it is
described, because it is regularly encountered in remote
communication applications, such as those between a Where devices connected to the communications
small substation and a control centre using modems to channel may need to flag alarm conditions, this dictates
transfer the data over a telephone line. continual polling of all devices connected to the
communications channel. If more than 31 devices need
Max. number of transmitters 1 to be connected, more than one RS485 communications
Max. number of receivers 1 link can be provided.
Connection type 25 core shielded 24.4.1.3 IEC 60870-5 Protocols
Mode of operation Decoupling
Maximum distance of transmission 15m The two commonly used protocols are IEC 60870-5-101
Maximum data rate 20kbit/s and IEC 60870-5-103.
Transmitter voltage 5Vmin,15Vmax
Receiver sensitivity 3V
IEC 60870-5-101 is used for communications between
devices over long distances. A typical application would
Driver slew rate 30V/microsec
Table 24.3: RS232C specification be communications between a substation and a Central
Control Room (CCR). A bit serial communication
technique is used, and transmission speeds of up to
24.4.1.2 RS485 Protocol 64kbit/s are possible, depending on the transmission
This protocol is detailed in Table 24.4, and is much more protocol selected from those specified in the standard,
useful for substation automation schemes. This is Modems can be used, and hence there is no practical
because, many devices can be attached to one data limitation of the distance between devices.
channel, the maximum distance over which IEC60870-5-103 specifies a communication protocol
communications can take place is quite large, and the between a master station and protection devices (e.g.
maximum bit rate is quite high. It only requires a simple protection relays). The standard is based on, and is a
twisted pair connection, with all devices 'daisy-chained' superset of, the German VDEW communication protocol.
on the link, as shown in Figure 24.6. Either fibre optic transmission or an RS485 link can be
Max. number of transmitters 32 used, and transmission speeds are either 9600kbit/s or
19200kbit/s. Maximum transmission distance is 1000m
Max. number of receivers 32
using fibre-optic transmission . Communication is on a
Connection type Shielded Twisted Pair
Mode of operation Differential
'master/slave' basis, in which the master station
Maximum distance of transmission 1200m
continually polls the slaves (relays) to determine if any
Maximum data rate 10Mbit/s information is ready to be sent by the slaves. While some
Transmitter voltage 1.5V min messages are defined by the standard, these are of
Receiver sensitivity Table 300mV
24 4: RS48S SDerificntinn
limited functionality. In addition, the standard allows the 0SI Layer ; Telephone Call Analogy
use of manufacturer-specific 'private' messages. These Conversion of voice into electrical signals. Defines type
permit much greater functionality, but at the same time Physical of connector, no. of pins, signal levels, etc. Optical fibres
and wires that make up the physical telephone network
hinder interoperability of equipment from different
Message transmission, error control and conferencing facilities.
manufacturers because there is no need for the format of . Words not clearly received are requested to be re-transmitted,
Data Link ■ , ',
such messages to be made public. This is arguably the using agreed procedures. For conferencing, defines now control
passes from one person to the next.
greatest drawback of the standard, since extensive use of Call routing, by specifying the method of allocating telephone
'private' messages by manufacturers of devices essentially numbers and provision of dialling facilities. Includes operator
Network facilities for routing to extensions. If the message is from several
turns the standard into several proprietary ones.
sheets of paper, ensures that all sheets have been received and are
in the correct order.
implementing communications over a relatively Provides facilities for automatically making calls at pre-defined times,
and ensures that the correct persons are present when the call
restricted geographical area. A substation automation Session is made. A session may be interrupted and re-established later,
scheme may extend over a very wide area, and hence using the same or a different network/transport connection .
As calls are half-duplex, provides flow control procedures -
suitable protocols are needed for this situation. The e.g one person says 'over' to invite the other to speak.
most common protocols in use conform to the ISO 7- Removes language difficulties by ensuring that the same language
layer model of a network. This model is internationally Presentation is spoken by both parties, or provides translation facilities.
Also provides encryption facilities for confidential calls.
recognised as the standard for the requirements for
Specifies the format in which a message will be sent when used
communications between data processing systems. Application in a specific application- e.g. if the application is to convey
information about meetings attended by a person, will define the
24.4.2.1 ISO 7- layer model format used for the place, time, and purpose of the meeting.
The ISO 7-layer model is shown in Figure 24.7. It Table 24.5: OSI 7-layer model - Telephone call analogy
represents a communications system as a number of
layers, each layer having a specific function. This
approach ensures modularity, and hence assists in The same data item may be stored at different addresses
ensuring that products from different vendors that within different devices, and hence re-programming of
comply with the standard will work together. The the client that receives the information is necessary
functions of each layer are best described by making an when one device is replaced by a different one, even if
analogy with a telephone call, as given in Table 24.5. the functionality is unchanged. It can easily be seen how
a substation equipped with a variety of devices from
different manufacturers and maybe using different
Selects appropriate service for application Application protocols for communication makes the problem of
applying an automation system very difficult and
Provides code conversion, data reformatting Presentation expensive. The major cost in such cases is developing the
software translation routines for protocol conversion and
Co-ordinates interaction between end Session building of the required database specifying where each
application processes item of data to be acquired is held.
Provides for end-to-end data integrity and Transport
quality of service 24,4.2.2 Utility Communications Architecture protocol
Switches and routes information Network A recent protocol, the Utility Communications
Architecture v2.0 (UCA v2.0), seeks to overcome these
Transfers unit of information to other end of Data Link handicaps by adopting an object-oriented approach to
physical link
the data held in a measurement/control device, plus an
Transmits bit stream to medium Physical
internationally recognised protocol (ISO 9506) in the
application layer. Data objects and services available
within a device follow a specified naming system. The
Figure 24,7; ISO 7-layer interconnection
mode!
client can extract a description of the data objects that
a device can supply, and services that it can perform, so
that it is easier to program the client. Scaling factors
There are a number of network protocols that are and units for data items are built into the se l f-
compliant with the OSI model, such as TCP/IP, Modbus, d es c r ip t ion, s o t ha t th e e f for t r e qu ire d during
DNP. This does not mean that the devices using different commissioning is reduced. Devices are not
protocols are interchangeable, or even that devices using interchangeable, in the sense that a device from one
the same protocol are interchangeable.
manufacturer cannot be removed and replaced by a protocol, Is to define the language very precisely at a
device of similar functionality from another vendor. high level, and require such details to be included as a
Rather, this protocol ensures interoperability; that is the part of each message so that the recipient can interpret
ability for devices from different suppliers and of the message without the need for any translator
different functionality to communicate successfully with software.
each other. The transport protocol has been separated
from the application protocol, so problems with register
addresses, etc. no longer exist. All that has to be 24.5 SUBSTATION AUTOMATION FUNCTIONALITY
addressed is the transport protocols used, and clients will The hardware implementation provides the physical
normally be able to communicate with devices using one means to implement the functionality of the substation
of a number of common transport protocols. This automation scheme. The software provided in the
standard has an IEC equivalent, IEC 61850. To begin various devices is used to implement the functionality
with, IEC 61850 covers only the field of substation required. The software may be quite simple or extremely
automation, but will gradually be extended to cover the complex - Table 24.6 illustrates the functionality that
same fields as UCA v2.0. Manufacturers are increasingly may be provided in a large scheme.
moving away from protocols with a proprietary element
in them to UCA v2.0/IEC 61850. It is likely that within a The description of the electrical network and the
short time, most protection and control devices will use characteristics of the various devices associated with the
one or other of these standards for communications. network are held within the computer as a database or
One important reason guiding this change is that these set of databases. Within each database, data is
standards permit the use of the XML language for organised into tables, usually on a 'per device' basis that
exchange of data between databases. As the reflects the important characteristics of the device and
information stored in an automation system or control its interrelationship with other devices on the network.
centre comprises a series of databases, information Electrical system configuration changes require
exchange is therefore facilitated. modification of the database using an appropriate
software tool supplied by the automation system vendor.
The tool is normally a high level, user-friendly interface,
24.4.3 Languages so that modifications to the one-line can be drawn
directly on-screen, with 'pick-and-place' facilities for
A communications language is the interpretation of the
relays, lED's, etc. This work would normally be done
data contained in a message. The communications
offline on the Engineers' workstation, if available, or as a
language normally forms part of the overall
background task on the control computer if not. Careful
communications protocol. Obviously, it is necessary for
and extensive checking of the data is required, both
both transmitter and recipient of the message to use the
before and after entry into the database, to ensure that
same language. While a number of communications
no errors have been made. Full testing on the new
standards attempt to specify the language used, there is
configuration using a simulator is recommended prior to
often flexibility provided, leading to manufacturer-
use of the new database on the main control computer
specific implementations. A popular work-around is for
to ensure that there is minimal possibility of errors.
a number of organisations to agree common standards
and set up a certifying body to check for compliance The software is written as a set of well-proven, standard
against these standards. Thus, equipment that complies modules, so there is little or no need for new modules to
becomes to large degree, interoperable. However, the be written and tested for a particular substation. The
latest trend, as exemplified by the UCA v2.0/IEC 61850 required data for the calculations performed by the
25.1 INTRODUCTION
Distribution systems are generally considered to be
supply networks operating at 132kV and below, and to
which consumers are normally connected. Within a
distribution system, a division into primary and secondary
distribution systems is often made, with primary
distribution systems having voltages above 22kV and
secondary distribution systems voltage below this value.
Automation of distribution systems has existed for many
years. The extent to which automation has been applied
has been determined by a combination of technology
and cost. For many years the available technology
limited the application of automation to those parts of
the distribution system where loss of supply had an
impact on large numbers of consumers. Technology was
not available to handle the large amount of
geographically dispersed data required for automation of
distribution systems in rural areas. Even when
developments in technology began to overcome these
problems, the cost of applying the technology was large
in relation to the benefits gained. Often, there was no
financial incentive to apply automation in rural
distribution systems, and consumers were not entitled to
compensation for loss of supply. As relatively few
consumers would be affected by a fault on a rural
distribution system, compared to a similar fault in an
urban distribution system, the number of customer
complaints received was not a sufficiently important
factor to justify investment in network reliability.
Interruptions to consumers in rural areas were treated as
being inevitable.
Recent developments such as privatisation started to
focus attention on the cost to the consumer of a loss in
supply. Interruptions in supply began to be reflected in
cost penalties (directly or indirectly) to the Utility, thus
providing a financial incentive to improve matters. Rural
consumers gradually became more aware of the disparity
in the number of supply interruptions between rural and
urban distribution networks. This led, in conjunction
with an increasing emphasis on Power Quality issues (see
Chapter 23), to pressure on Utilities to improve the actuator, and simple on/off remote control facilities.
situation. In addition, the population in rural areas Technology has been applied to reduce the cost of such
became more dependent on electrical equipment, and devices, thus improving the economics of their
thus the consequences of a supply outage were more application. Therefore, the field of distribution system
significant. automation is a very broad one, and the solution applied
to any particular problem will reflect the particular
The term automation conjures up the use of
circumstances of problem and regulatory regime of the
microprocessors, maybe linked together over a
Utility concerned.
communications network and running special purpose
software to execute a sequence of actions automatically. Figure 25.1 shows typical distribution systems that form
While such technology is employed and forms part of the subject of this chapter, complete with the elements
distribution system automation, the term automation of the distribution system to which automation
may imply nothing more than the ability to close or open techniques are applied. The remaining sections of this
a switch remotely in addition to local (hand) control. It chapter describe the various automation techniques
may involve nothing more than the addition of an available, together with typical applications.
Less tangible benefits can also be identified, such as Therefore, developments in distribution system
deferral of system enhancement (i.e. deferral of capital automation have concentrated largely on applications to
expenditure) through better knowledge of network the secondary distribution system.
performance. The financial advantage to the Utility of
such benefits may be more difficult to calculate, but
should be incorporated in any financial comparison for a 25.3 PRIMARY DISTRIBUTION SYSTEM AUTOMATION
proposed scheme. The primary distribution system is generally accepted as
There are inevitably costs incurred through use of an comprising those elements of the distribution system
automation scheme: operating at voltages above 22kV. Distribution uses both
cable and overhead lines, and the power levels involved
a. cost of implementation (capital cost) will enable either a large group of domestic consumers,
b. cost of operation or several industrial plants to be served. Very large
industrial plants may justify their own dedicated feeders
c. cost of maintenance
from the primary distribution substation (Figure 25.2).
and clearly the total costs saved must be in excess of the
total costs of implementation and use to make a scheme
viable.
For many years, automation has been implemented at
voltages above 22kV, simply due to the number of
consumers inconvenienced by a supply outage and the
resulting costs (in whatever form). However, in recent
years, the traditional balance of cost/benefit has been
changed, due to:
1. increasing dependence by communities/industry
on electricity
2. privatisation (in some countries)
3. the spread of electricity supply to ever more
remote areas
4. the cost of training and retaining skilled staff
5. increasing emphasis on Power Quality issues
This change has been in favour of increased automation
of the distribution system, including system voltages
down to LV. Regulatory pressure to improve the
reliability and quality of electricity supply to end-users
produces an outcome that the associated costs are only
acceptable if technology is applied to automate the
secondary distribution system. Therefore, automation of
the secondary distribution system has become more
Figure 25.2: Primary distribution system
Automation of the primary distribution system is well voltage variations can also be stored and downloaded at
established, due to the impact of supply loss on the many regular intervals and provides two main benefits. Firstly,
and diverse consumers that it serves. In addition, the monitoring of Power Quality can be undertaken and
distribution system is usually interconnected, so that loss hence customer complaints readily investigated.
of supply to consumers in the event of a circuit outage is Sufficient information may well be available to establish
minimised. The circuit breakers and protection systems the short-term actions required to correct or minimise
used in the system will already be capable of remote the problem, resulting in fewer customer complaints, and
control/monitoring. However, status information a possible reduction in financial penalties. Secondly, a
on a circuit may be confined to simple review of the loading profile of circuits against time can
on/off/open/closed/tripped indications, and determination be undertaken. Using appropriate plant thermal ageing
of the cause of a trip will still require despatch of a models, the rating of circuits can be reviewed and
maintenance crew to the equipment concerned. Only adjusted. This may result in an enhanced rating being
after the cause of a trip has been determined can fault given to circuits, and hence the postponement of capital
location and rectification take place. expenditure.
Hence modern network automation techniques can be
usefully applied. Application of such techniques brings
25.3.3 Space Requirements
the following advantages:
Many countries have significant pressure on land-use for
a. ability to control a much larger area
infrastructure requirements. A modern microprocessor
b. provision of detailed network performance relay can now undertake the functions previously
information requiring several discrete relays, and of measurement
devices, thus eliminating numerous VT's and CT's,
c. reduction in space requirements
measurement transducers/indicators, auxiliary contacts
d. reduction in staffing on circuit breakers, etc. Wiring between plant items is
much reduced. Use of modern communications
techniques such as data transmission by mobile radio
25.3.1 Control Area Size networks can similarly reduce wiring requirements
The modern electric power network has tight coupling to/from the Control Centre. The space requirements in a
between the various elements - a problem in one area substation for housing the relays associated with the
may have knock-on effects over a wide area. Hence, circuits of a distribution network can be reduced, giving
traditional distribution control rooms serving a limited a significant reduction in expenditure on the buildings
geographical area are being replaced by fewer (perhaps associated with the substation. Benefits can also be
only one for a Utility serving up to 10,000km2 area) and obtained from eliminating separate metering devices,
in these cases older automation systems may not be able reducing space provision and hence cost.
to handle the total I/O count. Either the upper limit on
I/O points will have been reached, or response times to
an event become too slow to be of practical use. Use of 25.3.4 Staffing Levels
a modern automation system permits a reduction in the The reduction in the number of Control Centres leads
number of control centres used, with each centre able to naturally to a reduction in the staffing requirement for
oversee a much wider geographical area. Thus, incidents such places. More importantly, the ability of intelligent
that have an impact outside of the immediate area can relays to report their settings and measured values to a
be dealt with more effectively and hence result in a Control Centre, and to accept revised settings
better response to the incident and fewer customer downloaded from the control centre can lead to
complaints. significant improvements in the quality of supply, while at
the same time reducing the staffing required compared to
a manual system. Distribution systems are subject to
25.3.2 Detailed Network Performance Information regular changes in configuration and loading, and these
Modern microprocessor-based relays can store a wealth may require changes to protection relay settings.
of information relating to the cause of a trip and Manual means of determining protection relay settings
transmit such data, when requested, to a Control Centre. involve site surveys at the substations concerned to
Hence, the nature and possibly the location of a fault can record existing settings, followed by further visits to
be identified. The maintenance/repair crew can be carry out changes as required. Pressures on staffing may
provided with better information, thus shortening circuit mean that such exercises are carried out at extended
downtime and enhancing distribution network intervals. A modern automated distribution system
availability. Data relating to network loading and eliminates much of the manual effort by automation of
the reporting and downloading of relay settings. While A typical urban secondary distribution system is shown
scope still exists for introducing errors into relay setting in Figure 25.3. There is a large proportion of
values, the incidence of these is reduced. Regular underground cable, and final feeders to LV distribution
comparison of settings against desired values increases substations take the form of feeders from Ring Main
the possibility of incorrect settings being identified and Units (RMU's). Several RMU's are connected in a loop fed
corrected, thus minimising the resulting disruption. from one or more substations, the loop normally being
open at some point. The open point is normally chosen
to equalise loading at both ends of the ring as far as
25.4 SECONDARY DISTRIBUTION NETWORKS - possible. The cables forming the ring and all associated
URBAN AREAS switchgear, etc., are sized for single-end feeding of the
A high level of interconnection, either ring or mesh, to whole ring, to allow for an outage affecting the ring
ensure a high degree of availability of supply to the between a substation and the first RMU, or at the
consumer, characterises secondary distribution networks in substation itself.
urban areas. Domestic, industrial and commercial The arrangement of an individual RMU is shown in Figure
consumers will suffer great inconvenience through only a 25.4(a). For many years, only local operation and
relatively short loss in supply of only a few hours, with indications (trip/healthy) were provided, so that
business likely to suffer considerable financial loss if an switching operations required a visit from field staff.
interruption is longer than 2-4 hours. For domestic Trips at an RMU resulting in loss of supply to consumers
consumers, loss of supply for between 4-8 hours is largely were annunciated through customer complaints, no
an inconvenience, though loss may result from spoilage of direct indication to the control room was provided.
freezer contents, etc. and in cold weather may place
vulnerable sections of the community at risk. Such hazards
for a privatised Utility give rise to the potential for
significant financial loss, through claims for compensation.
AVR C
Automatic Voltage Regulator Capacitance
Fiducial v a l u e
High Rupturing Capacity (applicable to fuses)
A clearly specified value to which reference is made in
order to specify the accuracy of a transducer. (For HSR
transducers, the fiducial value is the span, except for High Speed Reclosing
transducers having a reversible and symmetrical output HV
when the fiducial value may be either the span or half High Voltage
the span as specified by the manufacturer. It is still
common practice, however, for statements of accuracy HVDC
for frequency transducers to refer to 'percent of centre- High Voltage Direct Current
scale frequency' and, for phase angle transducers, to an I
error in electrical degrees.)
FPI Current
Fault Passage Indicator ICCP
Frequency transducer Term used for IEC 60870-6-603 protocol
A transducer used for the measurement of the frequency ICT
of an a.c. electrical quantity Interposing Current Transformer (software implemented)
F u l l d u p l e x communications A communications I.D.M.T.
system in which data can travel simultaneously in Inverse Definite Minimum Time
both directions IGBT
Gateway
The Gateway is a computer which provides interfaces Insulated Gate Bipolar Transistor
between the local computer system and one or several
I/O
5CADA (or RCC) systems
Input/Output
GIS Gas Insulated Switchgear (usually
IED
SF6)
Intelligent Electronic Device. Equipment containing a
microprocessor and software used to implement one or
more functions in relation to an item of electrical
equipment (e.g. a bay controller, remote SCADA Knee-poi nt e . m . f .
interface/protocol converter). A microprocessor-based That sinusoidal e.m.f. applied to the secondary terminals
numerical relay is also an IED. IED is a generic term used of a current transformer, which, when increased by 10%,
to describe any microprocessor-based equipment, apart causes the exciting current to increase by 50%
from a computer
L
IGBT Inductance
Insulated Gate Bipolar Transistor
LAN
Independent time measuring relay Local Area Network
LCD
A measuring relay, the specified time for which can be
considered as being independent, within specified limits,
Liquid Crystal Display
of the value of the characteristic quantity
LED
Influence quantity
A quantity which is not the subject of the measurement Light Emitting Diode
but which influences the value of the output signal fora
constant value of the measurand LD
Ladder Diagram. One of the IEC 61131-3 programming
Input quantity languages
The quantity, or one of the quantities, which constitute LDC
the signals received by the transducer from the measured
system
Line drop compensator
Instantaneous relay
A relay that operates and resets with no intentional time L i m i t i n g v a l u e of t h e output c u r r e n t
delay. The upper limit of output current which cannot, by
design, be exceeded under any conditions
NOTE: All relays require some time to operate; it is
possible, within the above definition, to discuss the Local Control Mode
operating time characteristics of an instantaneous relay When set for a given control point it means that the
commands can be issued from this point
I n s u l a te d Gate B i p o l a r T r a n s i s t o r A special
design of transistor that is suitable for handling high Lock-out ( a u t o - r e c l o s e ) Prevention of
voltages and currents (relative to an ordinary a CB reclosing after tripping
transistor). Frequently used in static power control Long-term s t a b i l i t y
equipment (inverters, controlled rectifiers, etc) due to the The stability over a period of one year
flexibility of control of the output
L ow-sp eed a u to-r eclose
Intrinsic error See Delayed Auto-Reclose
An error determined when the transducer is under
reference conditions LV
Low Voltage
I n ve r s e t i m e d e l a y r e l a y
A dependent time delay relay having an operating time M a i n protection
which is an inverse function of the electrical The protection system which is normally expected to
characteristic quantity operate in response to a fault in the protected zone
I n v e r s e t i m e r e l a y with d e f i n i t e m i n i m u m Maximum p e r m i s s i b l e v a l u e s of t h e i n p u t
t i m e (I.D.M.T.) c u r r e n t a n d voltage
An inverse time relay having an operating time that Values of current and voltage assigned by the
tends towards a minimum value with increasing values manufacturer which the transducer will withstand
of the electrical characteristic quantity indefinitely without damage
IRIG-B MCB
Miniature Circuit Breaker
An international standard for time synchronisation MCCB
ISO Moulded Case Circuit Breaker
International Standards Organisation M e a n - s e n s i n g t r a n s d u c e r A transducer which
K-bus (K-bus C o u r i e r ) actually measures the mean (average) value of the
Term used for the Courier protocol on K-Bus interface for input waveform but which is adjusted to give an
K-Relay range manufactured by Alstom output corresponding to the r.m.s. value of the input
when that input is sinusoidal
Measurand Nominal r a n g e of u s e
A quantity subjected to measurement A specified range of values which it is intended that an
influence quantity can assume without the output signal
Measuring element
of the transducer changing by amounts in excess of
A unit or module of a transducer which converts the
those specified
measurand, or part of the measurand, into a
corresponding signal Notching r e l a y
A relay which switches in response to a specific number
M e a s u r i n g range
of applied impulses
That part of the span where the performance complies
with the accuracy requirements NPS
M e a s u r i n g relay Negative Phase Sequence
NS
An electrical relay intended to switch when its
characteristic quantity, under specified conditions and Neutral Section (electrified railways)
with a specified accuracy attains its operating value
Numerical relay
Metering (non-tariff) A protection relay which utilises a Digital Signal
Values computed depending on the values of digital or Processor to execute the protection algorithms in
analogue inputs during variable periods software
Metering (tariff) OCB
Energy values computed from digital and/or analogue Oil Circuit Breaker
inputs during variable periods and dedicated to energy
Off Load Tap Changer -
measurement for billing (tariff) purposes
A tap changer that is not designed for operation while
M i d P o i n t S e c t i o n i n g S u b s t a t i o n A substation the transformer is supplying load
located at the electrical interface of two sections of
OHL
electrified railway. It contains provision for the
coupling of the sections electrically in the event of Overhead line
loss of supply to one section OLTC
Mod Bus On Load Tap Changer.
Proprietary communication protocol used on secondary On Load Tap Changer
networks between HMI, substation computers or Bay A tap changer that can be operated while the
Computers and protective devices transformer is supplying load.
MPSS Opening t i m e
Mid Point Sectioning Substation (electrified railways) The time between energisation of a CB trip coil and the
Multi-element transducer instant of contact parting
A transducer having two or more measuring elements. O p e r a t i n g c u r r e n t (of a relay)
The signals from the individual elements are combined to The current at which a relay will pick up
produce an output signal corresponding to the
measurand O p e r a t i n g t i m e (CB)
The time between energisation of a CB trip coil and arc
Multi-section transducer extinction
A transducer having two or more independent measuring
Operating time (relay)
circuits for one or more functions
With a relay de-energised and in its initial condition, the
time which elapses between the application of a
Multi - shot reclosing
characteristic quantity and the instant when the relay
operates
A reclosing scheme that permits more than one reclosing
O p e r a t i n g t i m e c h a r a c t e r i s t i c The curve
operation of a CB after a fault occurs before lock-out
depicting the relationship between different values of
occurs
the characteristic quantity applied to a relay and the
MV corresponding values of operating time
Operating value
Medium Voltage The limiting value of the characteristic quantity at which
N/C the relay actually operates
Normally Closed
N/O
Normally Open
OPGW Phase a n g l e transducer
Optical Ground Wire - a ground wire that includes A transducer used for the measurement of the phase
optical fibres to provide a communications link angle between two a.c. electrical quantities having the
same frequency
OSI 7 - l a y e r model
The Open Systems Interconnection 7-layer model is a Pick-up
model developed by ISO for modelling of a A relay is said to 'pick-up' when it changes from the de-
communications network. energised position to the energised position
Output common mode interference v o l t a g e Pilot c h a n n e l
An unwanted alternating voltage which exists between A means of interconnection between relaying points for
each of the output terminals and a reference point the purpose of protection
Output current (of a t r a n s d u c e r ) PLC
The current produced by the transducer which is an Programmable Logic Controller. A specialised computer
analogue function of the measurand for implementing control sequences using software
Output l o a d PLCC
The total effective resistance of the circuits and Power Line Carrier Communication
apparatus connected externally across the output
P o i n t of Common C o u p l i n g The interface
terminals
between an in-plant network containing embedded
Output power (of a transducer) generation and the utility distribution network to
The power available at the transducer output terminals which the in-plant network is connected
Output s e r i e s mode i n t e r f e r e n c e voltage An POW
unwanted alternating voltage appearing in series Point-on- Wave. Point-on-wave switching is the process
between the output terminals and the load to control moment of switching to minimise the effects
(inrush currents, overvoltages)
Output s i g n a l
An analogue or digital representation of the measurand Power E l e c t r o n i c Device
Output s p a n (span) An electronic device (e.g. thyristor or IGBT) or assembly
of such devices (e.g. inverter). Typically used in a power
The algebraic difference between the lower and upper
transmission system to provide smooth control of output
nominal values of the output signal
of an item of plant
Overcurrent r e l a y
A protection relay whose tripping decision is related to Power factor
the degree by which the measured current exceeds a set The factor by which it is necessary to multiply the
product of the voltage and current to obtain the active
value.
power
Overshoot t i m e
Power L i n e C a r r i e r Communication A mean
The overshoot time is the difference between the
of transmitting information over a power
operating time of the relay at a specified value of the
transmission line by using a cariier fraquency
input energising quantity and the maximum duration of
superimpozed on the normal power frequency.
the value of input energising quantity which, when
suddenly reduced to a specific value below the operating PPS
level, is insufficient to cause operation Positive Phase Sequence
P a r a m e t r i c c o n j u n c t i v e t e s t A conjunctive test Protected zone
that ascertains the range of values of each parameter The portion of a power system protected by a given
for which the test meets specific performance protection system or a part of that protection system
requirements
Protection equipment
PCB The apparatus, including protection relays, transformers
Printed Circuit Board and ancillary equipment, for use in a protection system
PCC Protection r e l a y
Point of Common Coupling A relay designed to initiate disconnection of a part of an
electrical installation or to operate a warning signal, in
PED
the case of a fault or other abnormal condition in the
Power Electronic Device
installation. A protection relay may include more than
one electrical element and accessories
Protection scheme R e c l a i m time (auto-reclose) The time between
a successful closing operation, measured from the
The co-ordinated arrangements for the protection of one
time the auto-reclose relay closing contact makes
or more elements of a power system. A protection
until a further reclosing sequence is permitted in the
scheme may comprise several protection systems
event of a further fault occurring
Protection system
REF
A combination of protection equipment designed to
Restricted Earth Fault
secure, under predetermined conditions, usually
abnormal, the disconnection of an element of a power Reference c o n d i t i o n s
system, or to give an alarm signal, or both Conditions of use for a transducer prescribed for
performance testing, or to ensure valid comparison of
Protocol
results of measurement
A set of rules that define the method in which a function
is carried out - commonly used in respect of Reference r a n g e
communications links, where it defines the hardware and A specified range of values of an influence quantity
software features necessary for successful within which the transducer complies with the
communication between devices. requirements concerning intrinsic errors
PSM Reference v a l u e
Plug Setting Multiple - a term used in conjunction with A specified single value of an influence quantity at which
electromechanical relays, denoting the ratio of the fault the transducer complies with the requirements
current to the current setting of the relay concerning intrinsic errors
PSTN Relay
Public Switched Telephone Network See Protection relay
PT1OO Resetting value
Platinum resistance temperature probe The limiting value of the characteristic quantity at which
the relay returns to its initial position
Resistance Residual current
The algebraic sum, in a multi-phase system, of all the
I R.M.S.- s e n s i n g t r a n s d u c e r A transducer
line currents
specifically designed to respond to the true r.m.s. value
of the input and which is characterised by the R es id ua l vo l ta ge
manufacturer for use on a specified range of The algebraic sum, in a multi-phase system, of all the
waveforms line-to-earth voltages
(Ratio c o r r e c t i o n Response t i m e
A feature of digital/numerical relays that enables The time from the instant of application of a specified
compensation to be carried out for a CT or VT ratio that change of the measurand until the output signal reaches
is not ideal and remains at its final steady value or within a specified
band centred on this value
Rating
The nominal value of an energising quantity that appears R e v e r s i b l e output c u r r e n t
in the designation of a relay. The nominal value usually An output current which reverses polarity in response to
corresponds to the CT and VT secondary ratings a change of sign or direction of the measurand
RCD R i p p l e content of t h e output
Residual Current Device. A protection device which is With steady-state input conditions, the peak-to-peak
actuated by the residual current value of the fluctuating component of the output
RCP r.m.s.
Remote Control Point. The Remote Control Point is a Root Mean Square
SCADA interface. Several RCP's may be managed with
RMU
different communication protocols. Physical
Ring Main Unit
connections are done at a Gateway or at substation
computers or at a substation HMI ROCOF
Rate Of Change Of Frequency (protection relay)
[Reactive power (var) t r a n s d u c e r A transducer
used for the measurement of reactive electrical RSVC
power Relocatable Static Var Compensator
RTD S p e c i f i c conjunctive test
Resistance Temperature Detector A conjunctive test using specific values of each of the
parameters
RTOS
Real Time Operating System Spring winding time
For spring-closed CB's, the time for the spring to be fully
RTU
charged after a closing operation
Remote Terminal Unit. An IED used specifically for
interfacing between a computer and other devices. ST
Sometimes may include control/monitoring/storage Structured Text: One of the IEC 61131-3 programming
functions languages
SAT S t a b i l i t y (of a transducer) The ability of a
Site Acceptance Test. Validation procedures for transducer to keep its performance characteristics
equipment executed with the customer on site unchanged during a specified time, all conditions
remaining constant
SCADA
Supervisory Control and Data Acquisition S t a b i l i t y (of a protection system) The
quantity whereby a protection system remains
SCL
inoperative under all conditions other than those for
Substation Configuration Language. Normalised
which it is specifically designed to operate
configuration language for substation modelling (as
expected by I EC 61850-6) S t a b i l i t y l i m i t s (of a protection system) The
r.m.s. value of the symmetrical component of the
SCP
through fault current up to which the protection system
Substation Control Point. HMI computers at substation
remains stable
level allowing the operators to control the substation
S t ar t in g r e l a y
scs A unit relay which responds to abnormal conditions and
Substation Control System
initiates the operation of other elements of the
Setting protection system
The limiting value of a 'characteristic' or 'energising'
STATCOM
quantity at which the relay is designed to operate under
A particular type of Static Var Compensator, in which
specified conditions. Such values are usually marked on
Power Electronic Devices such as GTO's are used to
the relay and may be expressed as direct values,
generate the reactive power required, rather than
percentages of rated values, or multiples
capacitors and inductors
SFC
Static r e l a y
Sequential Function Chart: One of the IEC 61131-3
An electrical relay in which the designed response is
programming languages
developed by electronic, magnetic, optical or other
Short-term s t a b i l i t y components without mechanical motion. Excludes
The stability over a period of 24 hours relays using digital/numeric technology
S i m p l e x communications system S t a t i c Var Compensator A device that supplies
A communications system in which data can only travel or consumes reactive power, comprised solely of
in one direction static equipment. It is shunt-connected on
Single-shot reclosing transmission lines to provide reactive power
An auto-reclose sequence that provides only one compensation
reclosing operation, lock-out of the CB occurring if it STC
subsequently trips Short Time Current (rating of a CT)
S.I.R. Storage c o n d i t i o n s
System Impedance Ratio The conditions, defined by means of ranges of the
Single element transducer influence quantities, such as temperature, or any special
A transducer having one measuring element conditions, within which the transducer may be stored
(non-operating) without damage
SOE
Sequence Of Events SVC
Static Var Compensator
SOTF
Switch on to Fault (protection)
System d i s t u r b a n c e time (auto-reclose) U n i t protection
The time between fault inception and CB contacts A protection system that is designed to operate only for
making on successful re-closure abnormal conditions within a clearly defined zone of the
power system
System impedance r a t i o The ratio of the power
system source impedance to the impedance of the Unrestricted protection
protected zone A protection system which has no clearly defined zone of
operation and which achieves selective operation only by
T 101
time grading
Term used for I EC 60870-5-101 protocol
UCA
Tap changer
Utility Communications Architecture
A mechanism, usually fitted to the primary winding of a
transformer, to alter the turns ratio of the transformer by UPS
small discrete amounts over a defined range Uninterruptible Power Supply
TCP/IP UTC
Transmission Control Protocol/Internet Protocol. A Universal Time Coordinates
common protocol for the transmission of messages over
the Internet V
TCS
Trip Circuit Supervision Voltage
TC57 VCB
Technical Committee 57 working for the IEC and Vacuum Circuit Breaker
responsible for producing standards in the field of VDEW
Protection (e.g. IEC 61850) Term used for IEC 60870-5-103 protocol. The VDEW
TF protocol is a subset of the IEC 60870-5-103 protocol
a] Transfer Function of a device (usually an element of a Vector group compensation
control system A feature of digital and numerical relays that
b) Transient Factor (of a CT) compensates for the phase angle shift that occurs in
transformers (including VT's) due to use of dissimilar
T hrough f a u l t c u r r e n t
winding connections - e.g. transformers connected
The current flowing through a protected zone to a fault
delta/star
beyond that zone
Time d e l a y
Voltage transducer
A delay intentionally introduced into the operation of a A transducer used for the measurement of a.c. voltage
relay system VT
Time d e l a y r e l a y A relay having an Voltage Transformer
intentional delaying device X
TPI Reactance
Tap Position Indicator {for transformers)
Z
Transducer (electrical measuring
transducer)
Impedance
A device that provides a d.c. output quantity having a
definite relationship to the a.c. measurand
transducer w i t h offset zero ( l i v e zero) A
transducer which gives a predetermined output other
than zero when the measurand is zero
Transducer w i t h suppressed zero
A transducer whose output is zero when the measurand
is less than a certain value
Unit electrical relay
A single relay that can be used alone or in combinations
with others
Appendix 2
Figure A2.1 - ANSI number/!EC symbol comparison
ANSI/IEC Relay Symbols
There are two methods for indicating protection relay functions in common use. One is
given in ANSI Standard C37-2, and uses a numbering system for various functions.
The functions are supplemented by letters where amplification of the function is
required. The other is given in IEC 60617, and uses graphical symbols. To assist the
Protection Engineer in converting from one system to the other, a select list of ANSI
device numbers and their IEC equivalents is given in Figure A2.1.