Handbook On Troubleshooting and Maintenance of Sub-Mersible Pump
Handbook On Troubleshooting and Maintenance of Sub-Mersible Pump
TROUBLE SHOOTING
AND
MAINTENANCE
OF
SUBMERSIBLE PUMPS
February, 2019
(DRAFT)
QUALITY POLICY
(DRAFT)
“To develop safe, modern and cost
effective Railway Technology
complying with Statutory and
Regulatory requirements, through
excellence in Research, Designs and
Standards and Continual
improvements in Quality
Management System to cater to
growing demand of passenger and
freight traffic on the railways”.
PREFACE
Preface iii
Contents iv
1. GENERAL DESCRIPTION 01
1.1 PUMP 01
1.2 CLASSIFICATION OF PUMPS 01
1.3 SUBMERSIBLE PUMP 01
1.4 ADVANTAGES OF SUBMERSIBLE PUMP 02
1.5 DISADVANTAGES OF SUBMERSIBLE PUMP 02
1.6 APPLICATION OF SUBMERSIBLE PUMP 02
1.7 BASIC TERMINOLOGY OF PUMP 03
1.7.1 Head 03
1.7.2 Static Head 03
1.7.3 Total Head/ Total Dynamic Head 03
1.7.4 NPSH (Net Positive Suction Head) 03
1.7.5 Specific Gravity (S.G.) 03
1.7.6 Specific Speed 04
1.7.7 Vapour Pressure 04
1.7.8 Viscosity 04
1.7.9 Flow (Q) 04
1.7.10 Friction Loss 04
1.7.11 Friction 04
1.7.12 Shaft 05
1.7.13 Cavitation 05
3. TROUBLE SHOORING 15
4. MISCELLANEOUS 18
4.1 SELECTION OF CABLE SIZE 18
4.1.1 How to Choose Correct Cable Size According Pump? 18
4.1.2 Points to Take into Consideration When Selecting Cables 18
4.2 PUMP SELECTION 19
4.2.1 Application of Pump 19
4.2.2 Head Discharge 19
4.2.3 Power 20
4.2.4 NPSH (Net Positive Suction Head) 21
4.2.5 Efficiency 22
4.2.6 Pump Selection Curve 22
4.2.7 Head Flow Curve 23
4.2.8 Material 23
4.2.9 Fluid 24
4.3 INSULATION CLASS 24
4.3.1 Insulation Class A 24
4.3.2 Insulation Class B 25
4.3.3 Insulation Class F 25
4.3.4 Insulation Class H 25
4.3.5 Important Factors Selecting Insulation Class for Motor 25
5. MINIMUM SUBMERGENCE 26
5.1 INTRODUCTION 26
5.2 MINIMUM SUBMERGENCE 26
5.3 CAVITATION 27
5.4 VORTEXING 27
5.5 ENTRAINED GAS 28
REFERENCE 29
CAMTECH/E/2018-19/EP-09/Submersible Pumps/1.0 1
CHAPTER 1
GENERAL DESCRIPTION
1.1 PUMP
Pump is a mechanical device which raises the energy levels of various fluids by
converting kinetic energy imparted by its prime movers into hydraulic energy.
Pump is a machine to transport the liquid from one place to another place usually
through a pipe.
It imparts energy to a fluid passing through it to enable the fluid to move from one point
to another.
It converts mechanical energy into kinetic energy.
In practice, pumps change both the velocity and the pressure passing through them.
A pump may, therefore, be defined as “a mechanical device which converts the
mechanical energy imparted to it from an external source (electric motor, diesel engine
or even manual energy) into hydraulic energy in the fluid handled by it”.
As a consequence, the energy level of fluid handled by the pump or flowing through the
pump is augmented, making it possible for the fluid to move from a lower level to a
higher level, against gravity and friction.
PUMPS
Gear Pumps
Piston Pumps
Lobe Pumps
Plunger Pumps Screw Pumps
Vane Pumps
This pump initially found most versatile use in naval applications and gained popularity
for deep well applications.
Both pump and motor are installed deep inside the tube-well/ bore well.
It makes, suction head minimum which makes it possible to lift water from depths as
low as 800 meters.
These pumps are coupled with wet type squirrel cage induction motor/ PMSM
(Permanent Magnet Synchronous Motors)/ IPMSM (Integrated Permanent Magnet
Synchronous Motors)/ BLDC (Brush Less D C motors). Both motor and pump operate
totally submerged below the surface of water.
The motor winding is either wet or dry type.
The water has to be perfectly clear, free from sand, as sand has an abrasive action on the
impellers.
The supply voltage has to be perfectly good and fairly constant, since considerable
voltage drop occurs in the cable as the motor is under great depth.
Rewinding and repair of the motor is a specialized job and it has to be absolutely
perfect.
1.7.1 Head
The head of the pump is an expression of how much height the pump can lift the
liquid. This is measured in terms of meter of water column, independent on the liquid density.
The vertical height difference from surface of water source to centreline of impeller is
termed as static suction head or suction lift (‘suction lift’ can also mean total suction
head).
The vertical height difference from centreline of impeller to discharge point is termed as
discharge static head.
The vertical height difference from surface of water source to discharge point is termed
as total static head.
Total height difference (total static head) plus friction losses & ‘demand’ pressure
from nozzles etc. i.e. Total Suction Head + Total Delivery head = Total Dynamic Head.
Net positive suction head – related to how much suction lift a pump can achieve by
creating a partial vacuum. Atmospheric pressure then pushes liquid into pump. A method of
calculating if the pump will work or not.
Net Positive Suction Head or NPSH for pumps can be defined as the difference
between liquid pressure at pump suction and liquid vapor pressure, expressed in terms of
height of liquid column.
A number which is the function of pump flow, head, efficiency etc. Not used in day
to day pump selection, but very useful as pumps with similar specific speed will have
similar shaped curves, similar efficiency/ NPSH/ solids handling characteristics.
If the vapour pressure of a liquid is greater than the surrounding air pressure, the
liquid will boil.
1.7.7 Viscosity
A measure of a liquid’s resistance to flow i.e. how thick it is. The viscosity
determines the type of pump used, the speed it can run at, and with gear pumps, the internal
clearances required.
Flow rate with which liquid is moved by the pump. Measured in m3/hr or GPM, LPD,
LPM or LPS.
Capacity depends on- liquid characteristics, pump size, inlet & outlet sections,
impeller size, impeller rotational speed RPM, size & shape of angles between vanes.
The amount of pressure/ head required to ‘force’ liquid through pipe and fittings.
1.7.10 Friction
1.7.11 Shaft
Shaft is a component that carries all the rotating pump parts and also provides power
to the impeller. The shaft has to withstand the rotating torque, axial and radial thrust.
1.7.12 Cavitation
If the pressure drops below the vapour pressure of the liquid at the operating
temperature, the liquid will vaporize.
CHAPTER 2
2.1 INSTALLATION:
Before installation, read the installation and operating manual of OEM carefully for right
method of installation.
Out of consideration for the rubber parts in pump and motor, the liquid temperature
must not exceed 40 °C (~105 °F).
Before connecting the pump supply, make sure that the electricity supply has been
switched ‘OFF’ so that it cannot be accidentally switched ‘ON’.
The required voltage quality for submersible motors, measured at the motor terminals,
is –10%/+6% of the nominal voltage during the supply voltage and losses in cables.
The pump must be properly earthed.
The pump must be connected to an external mains switch with a minimum contact gap
of 3mm in all poles.
The motors are wound for direct-on-line starting or star-delta starting and the starting
current is between 4 and 6 times the full load current of the motor.
The run-up time of the pump is only about 0.1 second. Direct-on-line starting is
therefore normally approved by the electricity supply authorities.
The installation can be fitted with a special over voltage protective device to protect the
motor from voltage surges in the electricity supply lines when lightning strikes
somewhere in the area.
The overvoltage protective device will not, however, protect the motor against a direct
stroke of lightning.
The overvoltage protective device should be connected to the installation as close as
possible to the motor and always in accordance with local regulations.
When the pump has been connected to the electric supply, determine the correct
direction of rotation as follows:
1. Start the pump and check the quantity of water and head developed.
2. In case of head not developed, stop the pump and interchange two of the phase
connections. In the case of motors wound for star-delta starting, exchange lead wire.
3. Again start the pump and check the quantity of water and head developed.
4. Stop the pump and compare the results taken under points 1 and 3, the connection
which gives the larger quantity of water and the higher head is the correct
connection.
Warning
Before starting any work on the pump/motor, make sure that the electric supply has
been switched ‘OFF’ so that it cannot be accidentally switched ‘ON’.
The bolts and nuts securing the straps to the pump must be tightened diagonally to
the torques stated in the following table:
Table-1
Straps Bolt/Nut Torque [Nm]
M8 18
M10 35
M12 45
M16 120
Caution
Make sure that the coupling between the pump and motor engages properly. When
assembling the motor and pump, the nuts must be tightened diagonally to the torques stated
in the following table:
Make sure that the pump chambers are aligned when assembly has been completed.
Before fitting the submersible drop cable to the motor, make sure that the cable socket
is clean and dry.
To facilitate the fitting of the cable, lubricate the rubber parts of the cable plug with
non-conducting silicone paste.
Tighten the screws holding the cable to the torques stated:
Motor 4”: 1.5 Nm
Motor 6": 4.0-5.0 Nm
Motor 8": 15.0 Nm
NOTE:
• Plastic pipes are recommended for 4” pumps only.
• When plastic pipes are used, an unloaded straining wire to be fastened to the discharge
chamber of the pump, should secure the pump. See figure.
• When connecting plastic pipes, a compression coupling should be used between the
pump and the first pipe section.
• Where flanged pipes are used, the flanges should be slotted to take the submersible drop
cable and a water indicator hose, if fitted.
Cable clips must be fitted every 3 meters to fix the submersible drop cable and the straining
wire, if fitted, to the riser pipe of the pump.
• Cable clip set consists of a 1.5 mm thick rubber band and buttons.
• Cable fitting: Cut off the rubber band so that the piece with no slit becomes as long as
possible.
• Insert a button in the first slit.
• Position the wire alongside the submersible drop cable,
• Wind the band once around the wire and the cable.
• Then wind it tightly at least twice around the pipe, wire and the cable.
• Push the slit over the button and then cut off the band.
• Where large cable cross-sections are used, it will be necessary to wind the band several
times.
• Where plastic pipes are used, some slackness must be left between each cable clip as
plastic pipes expand when loaded.
• When flanged pipes are used, the cable clips should be fitted above and below each
joint.
Note:
Do not lower or lift the pump by means of the motor cable.
NOTE: For pumps fitted with plastic pipes, the expansion of the pipes when loaded
should be taken into consideration, when deciding on the installation depth of
the pump.
• When the pump has been connected correctly and it is submerged in the water to be
pumped, it should be started with the discharge valve closed off to approximate 1/3 of its
maximum volume of water.
• Check the direction of rotation as described
earlier under “Checking of direction of
rotation”.
• If there are impurities in the water, the valve
should be opened gradually as the water
becomes clearer. The pump should not be
stopped until the water is completely clean,
as otherwise, the pump parts and the non-
return valve may choke up.
• As the valve is being opened, the drawdown
of the water level should be checked to
ensure that the pump always remains
submerged.
• The dynamic water level should always be
above the suction interconnector of the
pump.
Where:
L1: Minimum installation depth below
dynamic water level. Minimum 1 meter
is recommended.
L2 : Depth to dynamic water level.
L3 : Depth to static water level.
L4: Drawdown. This is the difference
between the dynamic and the static water
levels.
L5: Installation depth.
• If the pump can pump more than yielded by the well, it is recommended to fit the motor
protector, or some other type of dry-running protection.
• If no water level electrodes or level switches are installed, the water level may be drawn
down to the suction interconnector of the pump and the pump will then draw in air.
Caution
Long time operation without water or containing air may damage the pump and
cause insufficient cooling of the motor.
CHAPTER 3
TROUBLE SHOOTING
3. The pump a) The drawdown is larger Increase the installation depth of the
runs at than anticipated. pump, throttle the pump or replace it by
reduced a smaller model to obtain a smaller
capacity. capacity.
e) The non-return valve of Pull out the pump and check/replace the
the pump is partly valve.
blocked.
f) The pump and the riser Pull out the pump. Check and clean or
pipe are partly choked replace the pump, if necessary. Clean
by impurities (ochre). the pipes.
4. Pump gives a) The differential of the Increase the differential. However, the
less than the pressure switch between stop pressure must not exceed the
rated the start and stop operating pressure of the pressure tank,
discharge pressures is too small. and the start pressure should be high
enough to ensure sufficient water
supply.
c) The non-return valve is Pull out the pump and clean/replace the
leaking or stuck half- non-return valve.
open.
CHAPTER 4
MISCELLANEOUS
4.1 SELECTION OF CABLE SIZE
Selected cable shall be suitable for the field condition where it is to be used in.
It shall be adequate in size to operate within the rated temperature of the cable and to
ensure the voltage drop within 3% from the point of supply to the motor terminals.
If simply someone took the same cable type to cover the distance from splice to
electrical panel, the cable would most likely to burn and so would submersible motor.
This is because the cable will get overheated in open air due to its small cross-section
area &also due to length of cable, it will generate a large voltage drop so the motor will
be under-supplied.
For these reasons, borehole professionals will splice the motor short lead to a larger
cross-size “drop cable” that will safely carry the required current and supply the motor
with the desired voltage.
a. Surface Pumps
Surface pumps are designed to pump water from surface source like spring,
ponds, tanks or wells. Basically if we have water in reservoir then we use surface pump.
One more reason to use surface pump, if we head long suction head another reason for
selecting surface pump is cheap cost. Most of our surface pumps are either diaphragm
pump or rotary vane pump.
b. Submersible pump
Pump which merged in water with their motor are known as submersible pump.
They made up of steel which have high corrosion resistance properties below and that is
why it is costly than surface pump and one more thing this pump majorly used have low
suction head.
𝑇𝑜𝑡𝑎𝑙 𝑠𝑢𝑐𝑡𝑖𝑜𝑛 ℎ𝑒𝑎𝑑 = (𝑠𝑡𝑎𝑡𝑖𝑐 ℎ𝑒𝑎𝑑 + 𝑠𝑡𝑎𝑡𝑖𝑐 𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒 ℎ𝑒𝑎𝑑 + 𝑓𝑟𝑖𝑐𝑡𝑖𝑜𝑛 𝑙𝑜𝑠𝑠)
Head discharge
Head discharge basically a term which shows total fluid discharge from the
pump. It generally measures in meters.
The above curve shows relation between head and volume (discharge).
Start at a point called the closed value head where the pump is the not doing any
work just generating pressure.
It is a point where we don't want pump to work at all because it is simply churning
at the point.
The flow rate then increase and the available head drop off.
The head of centrifugal pump is determined by impeller diameter and rpm.
To select the point for operating point of the pump. It should be selected at duty
point because at duty point pump provide maximum efficiency.
4.2.3 Power
Pump power is nothing but basically it is a power of motor which used by pump to
transfer water from one place to other and it play a very important role in pump selection.
Power curve is provided below for better understanding.
Power curve
The power curve shows the power used by the pump at particular flow rate. The
selection of power for particular pump should at the point of maximum flow rate because if
the operator run the pump at greater than duty point then pump will not gave maximum
overall efficiency. If the power is selected at duty point, pump life and efficiency both will
be good.
NPSH means “Net Positive Suction Head”and it is further dividedin two categories.
i. NPSHR (net positive suction head required):It means the minimum pressure
required at the suction port of the pump to keep the pump away from cavitation.
ii. NPSHA (net positive suction head available): NPSHA is a function of installed
system and must be calculated, whereas NPSHR is function of pump and provided by
pump manufacturer.
NPSH Curve
The curve that is shown on this set is the NPSH (net positive suction head). It shows
the immersion that the pump impeller needs to avoid it get cavity and becoming damaged.
For cavitation free operation of the pump NPSHA should be greater than NPSHR
to calculate NPSHAfollowing formula is used.
Where,
Ha = atmospheric pressure at sea level
Hv = vapor pressure of fluid at operating temperature
+Hs = suction head
-Hf = suction lift
4.2.5 Efficiency
In most of the cases, user neglects the efficiency of pump compared to price. But in
the simple way to understand effectively, “more efficiency more profit”.
Efficiency curve
This curve contains all the curves of related parameter of pump and help to selecting
a good pump.
Now, for selecting a pump, first we see best efficiency point on curve. Compare that
point with the duty point .If the best efficiency point close to our pump duty point which is
on head discharge curve. Then our system is ideal for selection and gives better result to add
better performance.
Duty Point
It is a point on which we select our pump, we compare our pump's duty point with
BEP which present on efficiency curve.
According to that duty point we select the power used to run the pump.
This curve shows, if your duty point lies in between point A1 and point A2 on the
following place then your pump will get maximum performance, shows this type of
characteristic which shows on plotted curve.
4.2.8 Material
Material plays a vital role in pump selection and it clearly affects the application and life of
pump. So following basic properties of material should be considered for material selection
Corrosion resistance
Abrasive-wear resistance
Cavitation resistance
Strength
Casting and machining properties
Cost
Material preference according cost and properties rank wise order from high material
properties to low material properties in both surface & submersible pump.
4.2.9 Fluid
Fluid is another important parameter in pump selection because you might need to
specify a pump that delivers 10 bars of pressure. But if you do not consider the pumped
liquid properties, it is highly unlikely you will make the right choice.
If you don't account differing viscosity and density of liquid,you may end up with
too big a pump, which is overly expensive to buy and run. if the pump is too small you
simply burn out the motor of pump. The denser liquid need more power to transfer liquid
and at different temperature the liquid change it density so keep this in mind while selecting
pump.
CONCLUSION
It is concluded that if we consider given points in above discussion that we can select
a appropriate pump for our application. The most important point of pump selection is duty
point where we measure all the parameters related to pump.
Critical factor in the life of electrical equipment is heat. The type of insulation used
in a motor depends on the operating temperature that the motor will experience. Average
insulation life decreases rapidly with increase in motor internal operating temperatures.
NEMA (National Electrical Manufacturers Association) has established safe maximum
operating temperatures for motors based on an average 20000 hour lifetime.
These maximum temperatures are the sum of the ambient and maximum temperature
rise ratings of the motor. There are four NEMA insulation classes based thermal endurance
of the system for maximum temperature rating purposes. These are listed on the Motor's
name-plate and are either A, B, F, or H. These codes indicate the maximum temperature the
motor insulation can withstand without failure.
In class ‘F’ maximum permissible winding temperature is 155°C. Insulation class ‘F’
consists of insulating materials or combinations of materials such as mica, fiber, asbestos,
etc. bonded together with epoxy, poly-esterimide (polyamide or polyimide), polyurethane or
other resins having superior thermal stability.
CHAPTER 5
MINIMUM SUBMERGENCE
5.1 INTRODUCTION
Minimum submerge is the condition of water level above the inlet of pump to satisfy
pump operating conditions. Submergence is the distance between liquid levels and
submerges setting. In order to insure proper hydraulic performance, the pump manufactures
minimum submerge should be followed. Submergence is necessary to maintain prime,
prevent vortexing and may be provided to the pump NPSH requirement.
Following situations arise due to insufficient submergence of the pump which are:
i. Cavitation
ii. Vortexing
iii. Entrained Gas
5.3 CAVITATION
Cavitation is the condition at which the suction pressure at inlet of pump is below the
vapour pressure of the liquid. Cavitation can be generally avoided by providing the NPSHR
of the pump at the maximum flow requirement and water temperature anticipated. The
following analysis should be performed during the pump selection process.
i. Determine the maximum flow requirement under all possible operating condition
and select the pump which handles the maximum flow requirement within the
published performance curves.
ii. Calculate NPSHA for the application and compare with maximum NPSHR of the
selected pump at maximum flow point established in point 1 above. NPSHA must be
greater than NPSHR to prevent cavitation.
iii. The submersible pump intake must always be submerged for proper operation. In
some cases, the minimum submergence requirement is dictated by the NPSHR needs
of the pump. The minimum submergence should be not less than 3 feet (or as
specified by the manufacture) at the lowest possible pumping level at maximum
flow.
Factors which may create/ contribute to conditions favourable for cavitation, which are
often overlooked at the design stage, are:
i. Entrained (free) gas.
ii. Sudden drop in discharge head that significantly increase pumps flow.
iii. Insufficient submergence (dewatering/improper low level shut-off point).
5.4 VORTEXING
Vortexing is a term
frequently used to describe
flow patterns which result in
formation of vortices, causing
loud rumbling noise. A vortex
is a whirlpool caused by a
combination of factors such as
sump design, inlet velocity,
and direction of flow,
submergence and position of
intake. Air entering the pump
through these vortices is
responsible for noise and
vibration, but not cavitation.
Vortexing is rare in
submersible pump application;
however, when it does occur,
it is generally a result of
improper submergence.
Most liquid carry small amounts of air or other gases completely dissolved in the
liquid. Entrained gas is typically not a problem until it exceeds approximately 1-2% of the
total pumped volume of the fluid.
The two most common entrained gas problems encountered in water well
applications involving submersible pumps are cascading water (falling water) and formation
of gases.
REFERENCE
1. Data and literature collected from M/s Shakti Pumps (I) Limited, Pithampur – 454774
Distt. Dhar, (M. P.).
2. Data and literature collected from M/s Texmo Pumps, Mettupalayam Road, Coimbatore
(TN).
OUR OBJECTIVE