Power System: Reactors
Power System: Reactors
in
power system
Series Shunt
REACTOR REACTOR
PURPOSE PURPOSE
To reduce short To reduce over
circuit current voltage
AREA OF
AREA OF
APPLICATION
APPLICATION
Bus , Lines,
Tie Lines
Tertiary winging of
ICT
Z
Acts as inductance and
opposes the flow of short
circuit current.
Acts as inductive load
and reduce high voltage
by absorbing MVAR.
Classification of shunt reactors
Shunt Reactors
Air Core
Core less Gapped Core
Installed
Capacity
44220 MW
Peak Load
demand 34224
MW
Grid voltage lower
than rated (Max
Availability 0.95PU or 399 KV)
28450
MW
11Hrs 15Hrs 22 03
Hrs Hrs
Effect of high grid voltage
Formula Data
System Voltage Skv 420 KV
Fault Current level FkA 40 KA
Short Ckt MVA Scc= 1.732 X Skv X FkA 29097 MVA
Max Bus voltage V1 = 441 KV or (441/420) PU 1.05 PU
Acceptable Bus V2 = 416 KV or (416/420)PU 0.99 PU
voltage
Total reactive Sr = Scc{ ( V2 – V1)/V1} 1763 MVAR
power
Standard capacity Sst 63 MVAR
Nos of reactor Sr / Sst 27 Nos
required
Technical
1. Limited voltage rise on transmission lines at the time of
light loads or after load shedding
2. Prevention of self excitation on generator on leading PF
load.
3. Reduction of over voltage on sound phases during a line
to ground fault.
4. Reduction of switching over voltage due to initial
charging of lines.
Commercial
1. Being a capital item, investment on this equipment will
be adjusted in the fixed cost portion of tariff so that
entire amount ( capital + interest ) will return within the
operating period of the reactors.
Basic operating
principle
Basic operating principle
1. Initial charging current (i) produces pulsating flux in the coil
2. Induced voltage (e) = L (di / dt) is produced in opposite direction of
the coil due to pulsating flux
3. As a result of two opposite voltages current equal to (V-e) / R
passes through the coil
System Induced
Voltage, (V) Voltage, (e)
Ir Iy Ib
2. Induced voltage (e) depends upon the construction and magnetization characteristic of
the core
3. Shunt reactor is a device with the fixed impedance value. Therefore the individual phase
current is directly proportional to the applied phase voltage (i.e. I=U/Z).
4. For balance three phase current (Ir + Iy + Ib = 0), no current flows through the neutral.
5.Only during fault when phase current becomes un balance (Ir + Iy + Ib ≠ 0), current less
than 1 PU passes through the neutral. It is due to the fact that positive sequence
reactance(X1) is more or less equal to zero sequence reactance (x0) in five limbs core
configuration (Normally X1/Xo = 0.9).
6. During operation heat is produced as a result of copper loss ( due top I2R) and core
Loss ( due to Hysteresis and eddy current)
7. Typical total core & copper loss (KW)= rating of reactor (MVAR) x 0.2%
8. Typical core loss & copper loss = 75% & 25% of total loss respectively
Induced voltage and
Magnetizing
characteristic of the
core
Characteristics of the induced voltage
The magnitude of the inductive voltage (e) developed in the
reactor coil due to pulsating flux depends upon -
1. Flux density in the core ( Concentration of flux in the core )
2. Magnetization characteristic of the core ( Ability of the core
to produce flux)
V–I
linearity
range
•The flux produced by the core remains proportional to the current passes through the coil
till the core gets saturated.
•After saturation of core it can not produce flux further with the increase of current.
•Because of this magnetic saturation of the core, reactor coil can not develop inductive
voltage (e) further.
•In such condition impedance of the coil becomes lower with respect to the applied
voltage and higher current drawn by the winding causing high I2R loss ( heat generation)
or earth fault.
Components of Reactor
WTI
OTI
The core sections between consecutive air gaps are moulded in epoxy
resin to prevent movement between individual laminations. The spacers
forming the air gaps are blocks of ceramics with a high modules of elasticity
and the whole stacking of core modules is cemented together during the
assembly to form a solid column without possibility of rocking , or rubbing
between individual parts.
Loss in Watt / Kg
1.11
0.97
0.89
0.74
0.66
0.57
23 27
ZDKH
M0H M0H
M4 M5 M6
Interleaved disc winding has been used for rated voltages 220 KV
and above. This type of winding configuration provides better impulse
voltage
distribution. For lower voltage classes a continuous disc winding or a multi
layer helical winding are used.
Vibration in reactor
To reduce the vibration within the limit ( 200 micron) following measures are
taken during construction – 1. Air gap are filled with ceramic materials 2.
Earthing of Reactor
Copper loss due to I2R loss is Core loss due to hysteresis & eddy
about 25% of total loss i.e. current is about 75% of total loss i.e.
0.25X120 = 30 KW 0.75X120 = 90 KW
110KW
Operation
Position of Bus reactors in ts ii
Tie Line to
TS II Expn
400KV
Bus
Reactor II
400KV
TS II Expansion Extension
Reactor I
Gen (2 X 250MW) Bus
Power Grid
Feeder
Tie Line
ICT
230KV
Bus Mines Feeder
Stage I Gen
(3 X 210MW)
State Grid Feeder
Tie Line to TS
I
voltage compensation methods in power
system
Over excitation Under excitation
to deliver reactive power to absorb reactive power for
for increasing terminal decreasing terminal voltage
voltage
Switchyard Bus
395 – 415KV
Capacitive loading
105% Grid Voltage (445KV)
Inductive loading
Operation of bus reactor
Switching ON : Whenever bus voltage goes to 4% higher
than rated voltage i.e. 400 x104/100 = 416 KV
Gen
Bus
UCB IV Parameters Time Terminal MVAR PF
Voltage
Voltage
Before 10:15 15.9 KV 50 MVAR 410 KV 0.98
Reactor II charging Hrs
(SL No 6007011
After 10:06 15.9 KV 55 MVAR 405KV 0.98
Location 17th Bay)
charging Hrs
Before 12:10
Reactor I 16 KV 40 MVAR 408 KV 0.99
charging Hrs
(SL No 6007012
Location 16th Bay) After 12:17
16 KV 60 MVAR 405 KV 0.99
charging Hrs
Noise &
Running Ambient
Site Parameters OTI WTI Vibration
Hours Temp
Label
Switched On:
Reactor II 10:13 Hrs
(SL No 6007011 1Hour 30 Deg C 34 Deg C 28 Deg C Normal
Location 17th Bay) Switched Off:
11:15 Hrs
Switched On:
Reactor I 12:15 Hrs
(SL No 6007012 1 Hour 33 Deg C 34 Deg C 33 Deg C Normal
Location 16th Bay) Switched Off:
13:10 Hrs
Behavior of shunt reactor
during operation
Switching on of shunt reactor
Typical inrush current 3 to 5.5 times of rated current.
DC Off set
current
Phase to ground
fault at line side
Phase to ground
fault
Phase to ground
fault at neutral side
Phase to phase
short circuit fault
Un balance in
phase current
N R Y B
Zero seq
current
(<1 PU)
•Shunt reactor is a device with the fixed impedance value. Therefore the
individual phase current is directly proportional to the applied phase voltage
(i.e. I=U/Z). During external fault voltage of the faulty phase becomes lower
than other phases and a result of that unbalance is created in the phase
current. Because of unbalance phase current , zero seq. current less than 1
PU passes through the neutral.
Unbalance in phase
current due to external
earth fault
Un balance in
phase current
N R Y B
Zero seq
current
Rated current
passes through the
line side phase
BACK-UP PROTECTION
A variety of relays are available
a) Over current & earth fault protection. ( 50, 50N, 51, 51N, 67, 67N – any combination of
these)
b. Under impedance / distance ( z<)(21r).
c. Neutral displacement protection (un>)
Bus I
Bus II
Transfer bus
U1 V1 W1
N
Line side CT 1
1s2 1s2 1s2
DP
87
V2 W2
U2
CT Specification
1. Ratio: 200/1A
2. Class: PS
3. Knee point voltage: 200V
4. Magnetizing current: 40 mA
5. Secondary resistance: 1 Ohms
Typical Relay connection for Differential protection
N U1 V1 W1
Instantaneous
Residual over
1s1 1s1 1s1 Current Relay (50N)
Or
1s2 1s2 1s2 AC Time residual
Over Current relay
(51N)
CT Specification
1. Ratio: 200/1A
2. Class: PS
3. Knee point voltage: 200V
4. Magnetizing current: 40 mA
5. Secondary resistance: 1
Ohms
U2 V2 W2
N U1 V1 W1
CT Specification
1. Ratio: 200/1A
2. Class: PS
3. Knee point voltage: 200V
4. Magnetizing current: 40 mA
5. Secondary resistance: 1
Ohms
U2 V2 W2
N U1 V1 W1 Line Side
U2 V2 W2
Neutral Side
Electrical Test on
reactor
Prepared by
M. G. Morshad / Additional Chief Manager ( Elect.)
Transformer Maintenance Division
Thermal Power Station II
Neyveli Lignite Corporation Ltd
Electrical test as per IS 5553
Routine Test ( To confirm the operating criteria)
1. Measurement of WR
2. Measurement of IR & PI
3. Measurement of impedance by bridge methods
4. Measurement of loss and current at rated voltage and ambient temperature
5. Isolation test
N R Y B Voltage lead
Current lead
Resistance
measuring Kit
Measuring methods -
1. Only at the stable value of current (I), corresponding voltage (V) value
is taken for measuring the value of resistance ( R = V/I).
2. Applied current must not be higher than 15% of the rated current
3. % error in measurement increases with increases of applied current
due to increases in I2R loss at higher current.
4. Value to be measured between (R – N) , (Y-N), and (B-N), and all the
measured value must be equal.
N R Y B
_ +
5 KV IR measuring
Kit (Megger)
Minimum IR
Below 6.6 KV 6.6 - 11KV 22 – 33 KV Above 66 KV
value
K = 1.00 30 Deg C 200 MΩ 400 MΩ 500 MΩ 600 MΩ
K = 6.6 70 Deg C 30 MΩ 60 MΩ 75 MΩ 90 MΩ
CC
G
CL Core clamp Core Bolt Core Tank
Procedure :
1.Disconnect the closing link that connects the two terminals CL-G.
Reactor
windings
Temp U= C4 M3 CN X (Ω)
Lx (H) =
(0C) 100/5 (μF) (mH) (pF) (M3/U)X(C4/CN)x1000 =2∏fLx
U 38 20.00 8.98966 1.0032 50.915 8.856355604 2783.43
V 38 20.00 8.96700 1.0032 50.915 8.834031621 2776.41
W 38 20.00 8.96210 1.0032 50.915 8.829204282 2774.89
Where
U = CT Ratio ( 100/5)
Purpose: To measure the loss ( core & copper loss) in reactor at rated
operating condition.
Reactors
windings
0.415 1.1 3 - -
3.3 3.6 10 - 20/40
6.6 7.2 20 - 40/60
11 12 28 - 60/75
15 17.5 38 - 75/95
24 50 - 95/125
33 36 70 - 145/170
52 95 - 250
66 72.6 140 - 325
123 185/230 - 450/550
145 230/275 - 550/650
170 230/275/325 - 550/650/750
230 245 325/370/395 - 750/850/950
300 395/460 750/850 950/1050
362 460/510 850/950 1050/1175
400 420 570/360 950/1050 1300/1425
Separate source voltage withstand test
at 230 KV for one minute
PURPOSE : To verify the operating voltage withstanding capacity of the
minor insulation ( paper ) used in line terminals and windings.
R Y B N KV
50 Hz, AC
Generator
B Y R KV
PDD
50 Hz, AC
Generator
Method Test voltage from a 160Hz ( to avoid saturation of core), sinusoidal source is applied at
line terminals through a step up transformer keeping neutral terminal and tank
grounded. PD is measured by PDD connected with impedance ( z) & capacitors as
shown in the fig
Maximum test voltage ( 1.5 x 420KV /1.732) or 364 KV rms
Confirmation The test is declared to be successful if the test voltage does not collapse during the
test. and the PD level is observed within 500pC
5 Sec
30 Minutes
5 Minutes
420KV 364KV
364KV
Full wave lighting impulse voltage withstand
test at 1300 KVp on line terminal
PURPOSE : To verify the impulse voltage withstanding capacity of the major
insulation ( pressboard) used between the windings, line terminals caused by lighting
strike.
-
N R Y B
Impulse
Generator
0.1 Ώ
Recorder
Method Test voltage from an impulse generator is applied at line terminals keeping neutral
grounded through 0.1 Ώ resister and other terminals directly grounded. The sequence for
applying impulse is - one impulse of a voltage between 50% and 75 % of the full test
voltage, and three subsequent impulses at full voltage
Test voltage 1300 KV peak with Front time
-
N R Y B
Impulse
Generator
+
5
0
0
Ώ
Recorder
Method Test voltage from an impulse generator is applied at line terminals keeping
neutral grounded through 500 Ώ resister and other terminals directly
grounded. The sequence for applying impulse is - one impulse of a voltage
between 50% and 75 % of the full test voltage, and three subsequent
impulses at full voltage
Test voltage 1050 KV peak
Duration of Front time Tp> 100μs , Time above 90% Td> 200μs and Time to the first
test zero passage T0> 500μs ( preferably 1000 μs )
Confirmation The test is successful if the test voltage does not collapse during the test.
Type Test
8 Hours
Calculated winding temp at Time of S/D Tw = {R2/R1 (235+T)R1} – 235 (2.743/2.569) x ( 235+ 38)
– 235 = 56.49 Deg C
Average oil temp at S/D T1 55.30 – ½(55.30 – 4425) =
49.22 Deg c
Winding temp gradient Tg = (Tw – T1 ) 56.49 – 49.22 =
7.27 Deg c
Average oil temp rise Td = (T1 - Ta) 49.22 – 34.23 =
14.99 Deg C
Corrected winding temperature Tc = (Tg + Td) 7.27+ 14.99 =
22.26 Deg C
Winding temperature rise (Tc – Ta)
Full wave lighting impulse voltage withstanding
test at 550 KVp on neutral terminal
PURPOSE : To verify the impulse voltage withstanding capacity of the major and
minor insulation (Pressboard and paper) used in neutral terminals and side of the winding
caused by switching operation.
N
-
R Y B
Impulse
Generator
+
5
0
0
Ώ
Recorder
N R Y B
50 Hz, AC
Generator
1 Meter
A sound spectrum analyses is used for measuring sound level. The sound
spectrum indicates the magnitude of sound components as a function of
frequency. The sound pressure level is the measured at various points
around at a distance (D) of 30 cm for ONAN or 2 m for ONAF cooling
system spaced at an interval (X) of 1 meter.
Limit
Sound level Within 81db
Vibration level Within 200 microns
Magnetizing curve test / knee voltage
measurement
Test procedure
• Each phase of the reactor is charged one by one with direct current.
• When the maximum test current reached, supply is switched off and the reactor
winding is short-circuited simultaneously by DC current breaker.
• The decaying current in the circuit is registered by a computer assisted data
acquisition system.
• The saturation curve Flux (Ø) / Flux (Ø) nom. versus I / Inom is then determined
using the formula.
Ø / Ø nom
2
I / I nom
2
Measurement of capacitance and tan delta
between winding and tank
Purpose : To ascertain the condition of the solid insulation of the windings.
N R Y B 10 KV
+ - Tan
Delta
+ - Kit
+ Ir -
+ -
1. FRA test
2. DGA test before and after electrical test
3. Vacuum test on reactor tank
4. Oil leak test
5. Snap back test on HV bushing
FRA test
Purpose- Frequency Response Analysis (FRA) is carried out to
detect displacement (or movement) of the windings. Usually the
first measurement in the factory is used as a fingerprint. Results of
later measurements are compared with the first one in the factory.
X
FFT