DC Arc Document
DC Arc Document
-
Abstract A test program has been completed to measure as an effective approach to personnel protection when other
incident energy from 6-cycle arcs on 600 V 3-phase electric measures to prevent or limit arc exposure can not be
power distribution systems. Testing was performed using an employed.
arc electrode gap of 1.25 inches that had previously
produced maximum incident energy for a 600 V power These efforts have typically used theoretical models to
system with a 36.25 kA prospective fault current. The effect quantify arc exposure severity. While this approach has
on incident energy of enclosing the arcs in a cubic box was enabled significant progress in protecting people from
determined. Simple algorithms were developed to allow injuries, improved techniques for predicting arc energy and
estimation of incident energy at a specified distance from arc protective clothing performance offer more effective
electrodes as a function of the available bolted fault current solutions. Even greater advancements could be achieved if
on a 600 V electric power distribution system. A comparison hazard analysis tools and aids could be easier to use by the
is made with previously published methods for estimating electricians, operators, and technicians most at risk, as well
incident energy and safe approach distances. The impact of as engineers, supervisors and managers involved in
the estimating algorithm on the management of the electric equipment and protective clothing selection, system design,
arc hazard is discussed. and facilities operation.
Index Terms -- Arc Burn, Arc Energy, Arc Protective The basic research documented in this series of papers and
Clothing, Incident Energy. other publications such as Staged Tests Increase Awareness
Of Arc-Flash Hazards in Electrical Equipment by Jones et al
INTRODUCTION [2] provide the basis for a more refined tool set for managing
arc exposure and reducing injury severity. In addition to
The knowledge and tools for minimizing arc flash non- improved validation of energy prediction, these tools serve to
contact burn injuries associated with the distribution and improve hazard awareness, aid in identifying and quantifying
utilization of electricity are still in early stages of development the hazard, and simplify the task of selecting appropriate
as compared to those related to shock and fire hazards. This protective cIot hing.
paper is the third in a series aimed at enhancing basic
understanding of the phenomena of electric arcs and the TESTING BACKGROUND
performance of protective clothing systems exposed to arcs,.
It documents techniques and results from tests designed to The authors previously completed extensive arc testing at an
help users predict incident energy for 3-phase, 600 volt arcs independent testing laboratory in Canada as repotted in [3]
in open air and in a 20” cubic box. and [4]. As a result of this testing a number of important
factors related to estimating incident energy have been
Prior to the research documented in these papers, the quantified:
understanding and management of electric arcs was largely
based on theoretical modeling first proposed by Lee in 1981 1. Incident energy reaches a maximum as electrode
[I].Efforts to protect workers potentially exposed to the spacing increases, but the maximum incident energy
intense radiant energy of arc flashes have led to typically occurs at an electrode spacing that is larger
advancements in hardware, work practices, and protective than the spacing that produces maximum arc power.
clothing. Switchgear manufacturers have developed more
robust and “arc resistant” designs to divert heat and 2. Incident energy is directly proportional to the time
explosive forces away from workers interacting with the duration of the arc.
switchgear. The utilization of current limiting protective
devices not only limits damage to circuit parts, but also 3. Incident energy is significantly affected by the
significantly reduces duration of personnel exposure . The environment surrounding the arc. Enclosing a 3-
use of flame resistant (FR) clothing has gained acceptance phase arc in a box can increase the incident energy up
When the electrical system impedance changes, the The data acquisition system digitally sampled and recorded
available bolted fault kVA, and consequently, the maximum arc voltage, arc current, time, and temperature rise from
arc power and incident energy also change. As the bolted seven copper calorimeters. An estimate of arc energy was
fault current increases, one would expect the arc gap calculated by multiplying the phase-to-phase voltageld3 by
producing maximum incident energy to decrease in size, and the phase current for each phase, summing the result for
vice-versa. Testing has not been performed to determine the all 3 phases, and then multiplying the result by the arc
actual spacing for maximum arc incident energy as a duration.
function of available bolted fault current. In addition, since
enclosing an arc in a box physically constrains the arc Two different test setups were used for the 3-phase arc
plasma and modifies the arc impedance, it is expected that testing. Test Setup No. 1 was for a 3-phase arc in open air
the electrode spacing that produces maximum incident as shown in Fig. 1. Test Setup No. 2 utilized electrodes
energy in open air may not be the same as the electrode mounted inside and 4 inches from the back of a cubic
spacing that produces mayimum incident energy with the arc metal box (20” wide x 20” high x 20” deep) as shown in Fig.
in a box, and this has not been confirmed by testing either. 2. Tests were conducted with the box ungrounded since
earlier testing [4] indicated that the ungrounded box
The data in Fig. 8 of [4] shows that the change in incident produced the maximum incident energy.
energy with variation of arc gap spacing around the
maximum energy point is relatively small. In that case For each setup, an array of seven copper calorimeters was
(bolted fault of 36.25 kA), the reduction of the arc gap from located a specified distance from the centerline of the
1.25 to 1.00 inches, or the increase in arc gap from 1.25 to 2 electrodes. A set of three calorimeters was located in a
inches produced only a 10% decrease in arc incident energy. horizontal row at the same height as the tip of the
electrodes. A second set of three calorimeters was located
The decision was made to proceed with 3-phase arc tests in a horizontal row 6 inches below the elevation of the
using an arc gap of 1.25 inches since: 1) it was a common electrode tips. The middle calorimeters in each set were
spacing used in electrical equipment, 2) it was verified by test aligned with the center electrode. A single calorimeter was
to be the arc gap which produced maximum incident energy located 6 inches above the center electrode tip.
- 330 -
test to test, a time duration correction factor was applied to
the temperature rise data from the seven copper
calorimeter sensors to insure that each reported incident
energy was based on an arc duration of 6 cycles. The
mean incident energy for the seven sensors and the
maximum incident energy recorded by a single sensor were
calculated for each test.
The first series of tests used the open arc Test Setup No. 1
and measured the incident energy 24 inches from the arc
electrodes while the bolted fault current was adjusted in steps
from 16 to 50 kA. At the conclusion of these tests, the bolted
fault current was set at 40.9 kA and the sensor distance was
changed to 18 and 30 inches to determine the variation of
incident energy with distance.
- 331 -
TABLE I
%PHASEARC TEST RESULTS
600 V SYSTEM - 1.25 INCHARC GAP
Open Arc
-- - lnches
24
volts
768
kA
50.39
Open Arc 24 687 45.36
Open Arc 24 614 40.92
Open Arc 24 616 35.29
Open Arc 24 623 31.16
Open Arc 24 617 27.66
Open Arc 24 614 23.41
Open Arc 24 615 19.08
Open Arc 24 616 16.30
Open Arc 18 614 40.92
Open Arc
Arc In Box
30 - 614 40.92
24 759 51.19
Arc In Box 24 680 46.05
Arc In Box 24 612 41.99
Arc In Box 24 618 36.25
Arc In Box 24 613 312 0
Arc !n Box 24 617 27.66
Arc In Box 24 611 23.65
Arc In Box 24 615 19.08
Arc In Box 24 616 16.30
Arc In Box 18 612 41.99 347.4 31.36 12571 9.35
Arc In Box 30 612 41.99 326.5 32.12 12275 4.13
Arc In Box 36 612 41.99 325.4 32.15 11871 3.15
Arc In Box 48 612 41.99 331.6 31.79 12430 1.81
Arc In Box 60 -- 612 41.99 328.2 32.16 I2245 1.05
-
3Phase 6 Cycle Arc 600 V System 3Phase 6 Cycle Arc - 600 V System
Incident Energy v s Bolted Fault kA Incident Energy vs Bolted Fault kA
2 Feet From Open Arc - 1.25” Gap 2 Feet From Arc In Box - 1 . 2 5 Gap
I I
5.0 14.00
s s 12.00
E 4.0
1 10.00 ,
- 2
3.0
I I fi
-
E
2
8.00
.-
{ 2.0 E
=
5 6.00
400
I
U
-
E 1.0 i -
g 2.00
0.0 0.00
0.00 20.00 40.00 60.00 20.00 40.00 60.00
Bolted Fault kA Bolted Fault kA
0 AVER. INUD. ENERGY 0 AVER. INCID. ENERGY
MAX. INCID.ENERGY
- 332 -
multiplying factor of 3.0 determined for the 22” wide x 20”
high x 21” deep box tested in [4].
Max. Incid. Energy vs Bolted Fault kA
Video observation of the arcs in the box indicated that a Open Arc v s Arc In Box
significant portion of the increased incident energy was due 2 Feet From Arc Electrodes
to increased convective heat energy transfer due to hot gas
14.0 1
expansion and projection out the front of the box toward the
sensors. This effect visibly and dramatically increased at 120
higher current levels. It appeared that as the arc current
s
F 10.0
increased, the arc plasma volume increased and the plasma
projection out of the box increased. Arcs are known to
consist primarily (90%) of radiant energy, but the arc-in-the- 8 6.0
box configuration appears to enhance the convective energy 40
component.
-C 2.0
Incident energy in per unit of incident energy at 2 feet is 0.0
plotted as a function of distance from the arc electrodes in 0 20 40 60
Fig. 7 for the open arc with an available bolted fault current
of 40.9 kA. A power equation which curve fits the maximum
incident energy data is indicated on the figure. Incident
energy is shown to be inversely proportional to the distance
to the 1.96 power, very close to the theoretical distance Fig. 5. Incident Energy Comparison
squared relationship predicted by Ralph Lee [I]. The same
information is plotted in Fig. 8 for the arc-in-the-box with an
available bolted fault current of 42 kA. The power equation Ratio of Arc In Box Incident Energy To
in Fig. 8 has an exponent of -1.47 indicating that the incident Open Arc incident Energy
energy from the arc-in-the-box decreases at a slower rate as
distance increases than for the arc in open air. Both power
equations may not be valid for distances less than 18 inches
since testing was not performed in that range.
- 333 -
TABLE II
3-Phase 6 Cycle Arcs 600 V System - MAXIMUMINCIDENT ENERGY- 6 CYCLE ARC IN BOX
AS A FUNCTION OF BOLTED FAULT CURRENT
Max. Incident Energy vs. Distance
Arc In 20” Cubic Box 1.25” Gap - & DISTANCE FROMARC ELECTRODES
-E 1.60
1.40
Bolted
Fault 1
k x . Incident Energy In caUcm2
Distance FromArc Electrodes In Inches
;. &f
1.20 kA 18 1 21 1 24 1 27 I 30 1 36 1 42 I 48 1 54 1 60
-5 1.00
QI 0.80
1 16 I 4.1 I 3.3 I 2.7 1 2.3 1 2.0 I 1.5 I 1.2 1 1.0 I 0.8 1 0.7 I
18 4.1 3.2 2.7 2.2 1.9 1.5 1.2 1.0 0.8 0.7
5$ 0.60
20 4.1 3.3 2.7 2.2 1.9 1.5 1.2 1.0 0.8 0.7
2 Q) 0.40 22 4.2 3.4 2.8 2.3 2.0 1.5 I 1.2 I 1.0 I 0.8 1 0.7 ,
a! fi 0.20 I
I I I I I I I
24 4.5 3.6 2.9 2.5 2.1 1.6 1.3 1.0 0.9 0.8 I
0.00
10 30 50 70
1 I I I 1 I I
26 4.8 3.8 3.1 2.6 2.3 1.7 1.4 1.1 1.0 0.8 I
Distance From Arc Bectrodes,Inches
I 28 I 5.3 I 4.2 I 3.4 I 2.9 1 2.5 1 1.9 I 1.5 I 1.2 1 1.0 I 0.9 1
I I I I 1 1
30 5.8 ] 4.7 3.8 3.2 2.7 2.1 1.7 1.4 1.2 1.0 1 I 1
32 16.5 I 5.2 J4.3 I 3.6 I 3.1 I 2.3 I 1.9 I 1.5 I 1.3 I 1.1
Fig. 8. Arc-ln-Box Distance Variation
I 34 I 7.3 1 5.8 1 4.8 1 4.0 I 3.4 I 2.6 1 2.1 I 1.7 I 1.4 I 1.2 I
where: DB = Distance From Arc Electrodes, inches ( D ~ 2 1 8 ) I I I 1 I
36 ] 8.2 6.5 5.4 4.5 13.9 3.0 ] 2.4 1.9 1.6 1.4 1 I
EMB= Maximum 20” Cubic Box Incident Energy, 38 I 9.2 I 7.3 I 6.0 I 5.1 I 4.3 1 3.3 I 2.6 I 2.2 1 1.8 I 1.6
cal/cm2
F = Bolted Fault Current, kA (16-50 kA Range)
40 110.31 8.2 16.8 15.7 14.9 13.7 13.0 12.4 12.0 1.8 I
42 111.51 9.2 17.6 16.4 15.4 14.2 13.3 12.7 12.3 12.0
Predicted EMB values using Equation (2) for distances 44 112.9~10.3~
I I I
8.4 17.1
I
16.1
I
14.6
I
13.7
I
13.0
I
12.6
I
12.2
I
Estimated maximum incident energy levels for a 3-phase, 6 Incident energy produced by a 6-cycle arc with a 1.25”
cycle arc with a 1.25 inch electrode gap in a 20” cubic box electrode gap on a 600 V electrical system (available bolted
calculated using Equation (2) are shown in Table II. fault current of 42 kA) was determined at various distances
Estimated incident energy for arc durations other than 6 from the arc electrodes using three different methods: 1) the
cycles can be determined by multiplying EMAor EMBby the 3-phase arc test algorithm, 2) a commercially available
ratio of the arc duration in seconds, fA, divided by 0.1 as computer program, and 3) the Duke Heat Flux Calculator.
shown in Equations 3 & 4 : Results are plotted for comparison in Fig. 9. Both the
commercially available program and the Duke Heat Flux
EMA= 5271 D -‘ 9593 t A [ 0.0016 F2 - 0.0076 F + 0.8938 ] (3)
Calculator use single-phase models of the electrical arc to
predict incident energy. Three-phase test values of
-1 4738 maximum incident energy for the open arcs were from 2.5 to
EMB~ 1 0 3 8 . 7D tA [ 0.0093 F2 - 0.3453 F + 5.9675 J (4) 3 times the values predicted by the single-phase models.
Three phase test values of maximum incident energy for the
Equations (3) & (4) may be solved for the distance required
arcs in the cubic box were 5.2 to 12.2 times the values
to produce a given maximum incident energy level as shown
predicted by the single-phase models. In both
below in Equations (5) & (6):
cases the ratios increased as distance from the arc
electrodes increased as shown in Fig. 10. The dramatic
D A = [(tA/EMA)(8.434F2-40.06F+4711)]05104 (5) increase in ratio with distance shown in Fig. lO(a) for the
arc-in-the-box is primarily a result of the single-phase model
DB= [ (fA/EMB) (9.66 F2 - 358.7 F + 6198) ] 06785 (6) assumption of incident energy variation inversely
proportional to distance squared instead of distance to the
This form of the equations is useful to define incident energy 1.5 power.
boundaries i.e. the distance for a second-degree burn or for
the protection limit of a specific FR clothing system. Note Ralph Lee Curable Burn Comparison
that Equations (3) through (6) may not be valid outside the
indicated variable ranges for Equations (1) and (2). Equations (5) & (6) were used to calculate, for a range of
- 334 -
Comparison Of
Arc Incident Energy
Estimating Methods
600 V System
42 kA Bolted Fault
6 Cycles - 1 . 2 5 Gap
3 ph. Arc Tests-
-c-
MX. Arc Box
-0- 3 ph. Arc Tests-
Mean Arc Box
--t 3 Fh.Arc psts-
bbx. Open Arc
-A- 3 Fh. Arc Tests-
&an Open Arc
-+-Commercial
10 30 50 70 Frogram-l Fhase
Distance From Arc Bectrodes, --t Duke Heat Flux
inches &IC.-I Fhase
Ratio Of Max. 3 Ph. Arc-In-Box Test Ratio Of Max. 3 Ph. Open Arc Test
ResultsWith Calc. 1 Ph. Incid. Energy Results With Calc. 1 Ph. Incid. Energy
--
14 I
12
' - - __ -.-
Commercii?
.-010 Rogram
3 8 -u-- Duke Heat --o- Duke Heat
6 Flux Cab
4
0 20 40 60 80 15 20 25 30 35
Distance From Arc Bectrodes, Inches Distance From Arc Bectrodes, Inches
I
Fig. I O . (a) Arc-In-Box Incident Energy Compared To Fig. I O . (b) Open Arc Incident Energy Compared To
Calculated Results Calculated Results
- 335 -
I I
Human Skin Burn Limit Comparison
- -
3-Phase 6 Cycle Arcs 1.25 Inch Gap 600 V System
1 I
I I
TABLE 111
PROTECTIVE CLOTHING GUIDELINES FOR THE ELECTRIC ARC HAZARD
- 336 -
Clothing System
Protective Equipment Compa rison
Protection Comparison
For Electric Arc Exposure 16
bkta-Aramid Royal Blue
14
Flame Retardant Treated Cotton
A Cotton T-shirt + Veta-Aramid Royal Blue
0 Cotton T Shirt + 2 Layer Meta-Aramid Royal Blue 12
A Cotton T-shirt + 2 Layer ParalMeta-Aramid =E
I
3 IO
50
45
if
40
Z 8
U
1 8 6
- 35
E
0" 30
i 4
U?' 25
0' 20 2
2 15
10 0
5
0
4.8 6.4 7.9 8.2 10.2 8.9 10.4 15 17
Fabric System Weight, ounceslydZ
Fig. 13. FR Clothing System Comparison Fig. 14. Eye, Face, Hand Protection Performance
SELECTING FR CLOTHING EBTis defined as the average of the five highest incident
energy values which did not cause FR fabric break-open
Once the incident energy exposure level for a particular and did not exceed the second degree burn criteria. EBT
situation has been determined, and the exposure level is is reported when ATPV cannot be measured due to FR
sufficient to cause either a second degree burn or ignition of fabric break-open. Break-open is defined as any
clothing, the user should select an appropriate FR clothing
system to provide protection from the arc hazard. ASTM e
opening in the innermost (nearest the rotected surface)
layer of FR fabric of more than 0.5 in area or a slit or
PS57 data in Table I of [4] indicates that an average incident crack in the innermost FR fabric, 1 inch or greater in
energy level of 3.0 cal/cm2 (L95%CL) is required for a 1% length. In the event of FR fabric break-open, a
probability of ignition of a 5.2 oz/yd2 blue cotton Twill shirt flammable fabric under-layer or human skin is directly
material. Minimum incident energy required to produce a exposed to incident energy.
second-degree burn is 1.2 cal/cm2 as discussed above.
Performance data about clothing systems utilizing specific
The authors published a table of Protective Clothing fabrics is tabulated in [4]. A comparison of the performance
Guidelines in [4] that was based on fabric testing utilizing the of a few selected FR fabric systems is illustrated in Fig. 13.
ASTM PS58 test method [6].This information is reproduced Note that a dotted line at 3.0 callcm' indicates incident
in Table Ill and defines proposed clothing classes based energy required for 1% probability of ignition for 5.2 oz/yd2
upon the available incident energy. Clothing Class No. 2 has blue cotton twill shirt material.
been split into two sub-categories, Classes No. 2A and 28, to
reflect the use of either cotton or FR underwear. Table Ill is A comparison of the relative performance of polycarbonate
based upon FR clothing produced by a number of safety glasses, polycarbonate visors used in face shields and
manufacturers and gives general guidance about how many hoods, and common leather work gloves is shown in Fig. 14.
layers of FR fabric should be considered to use for a given ATPV values in Fig. 14 were estimated from energy
incident energy exposure. The terms ATPV and EBT,used in transmission data in [2] based on a limited number of
Table Ill, are defined in ASTM PS58 Standard [5] and are specimen exposures.
explained below:
Using boundary Equation (5)to determine the distance from
ATPV is defined as the incident energy that would just a 3-phase, 6 cycle arc in open air for a specified incident
cause the onset of a second-degree burn. energy level, Figure 15 was constructed showing the
- 337 -
Second Degree Burn Boundary Distance9 As A Function Of Bolted Fault kA
-
600 V, 3-Phase, 6 Cyle Arcs In Open Air 1.25 Electrode Gap
58.0
--e Human Skin 2nd
Degree Burn Limit -
1.2 callcm2
48.0
-+-Untreated Cotton
ATPV - 2 callcm2
38.0
+Class 1 FR Clothing
-
AfPV 5 ca llcm2
28.0
Class 2A FR Clothing
-
ATPV 8 callcm2
18.0
18 24 30 36 42 48 54
Bolted Fault kA
Fig. 15. Second Degree Burn Boundary Distances For 600V, 3-Phase, 6-Cycle Electric Arcs In Open Air
-t-Class 1 FR Clothing
ATPV - 5 callcm2
.- +Class 2A FR Clothing
.-E ATPV - 8 callcm2
E
18.0
18 24 30 36 42 48 54
Bolted Fault kA
Fig. 16. Second Degree Burn Boundary Distances For 600V, 3-Phase, 6-Cycle Electric Arcs In 20” Cubic Box
* Data based on measured incident energy under specified test conditions. Real arc exposures may be more or less than
these simulated exposures.
- 338 -
TABLE IV
EVOLUTION IN KNOWLEDGEOF ARC FLASH PHENOMENAAND DETERMINE THE AVALLABLE BOLTED FAULT
IMPLEMENTATIONOF HAZARD MANAGEMENTMETHODS
CURRENT AT THE LOCATION OF THE POTENTIAL
3-PHASE FAULT
YEAR I DEVELOPMENT
Ir
1981 I Theoretical modeling (Lee)
1981 - Present
Advanced awareness based
on theoretical modeling and
field experience
1 DETERMINE THE ARC FAULT CLEARING TIME BASED
UPON THE ELECTRICAL PROTECTION SYSTEM 1
Regulatory requirements
1990 - 1993 based on theoretical SELECT WHETHER THE INCIDENT ENERGY IS TO BE
modelina (OSHA 1910 DETERMINED FOR A 3-PHASE ARC IN OPEN AIR OR
I Subpai S 8, R)
NFPA 70E consensus
1995 standard on work practices
and PPE application based DETERMINE THE MINTMUM BODY APPROACH
on theoretical modeling DISTANCE TO THE POTENTIAL ARC
R&D in incident energy
1995 - 1998 prediction and FR clothing
protection evaluation USE EQUATION (3) OR (4) TO ESTIMATE THE
MAXIMUM‘INCIDENT ENERGY AT THE MINIMUM
APPROACH DISTANCE FOR A 3-PHASE ARC
WITH A 1.25” ELECTRODE GAP
- 339 -
ACKNOWLEDGEMENT
REFERENCES
- 340 -
APPENDIX
SECOND DEGREE BURN BOUNDARY DISTANCES
18 24 30 36 42 54
Bolted Fault kA
Fig. A I . (a) Second Degree Burn Boundary Distances For 600V, 3-Phase, 3-Cycle Electric Arcs In Open Air
4;
8 48.0
-m- Untreated Cotton
-
ATPV 2 callcm2
C Q
0’0
crro
+-Class 1 FR Clothing
-
ATPV 5 callcm2
Fig. A I . (b) Second Degree Burn Boundary Distances For 600V, 3-Phase, 3-Cycle Electric Arcs In 20” Cubic BOX
* Data based on measured incident energy under specified test conditions. Real arc exposures may be more or less than
these simulated exposures.
- 341 -
Second Degree Burn Boundary Distances? A s A Function Of Bolted Fault kA
600 V, 3-Phase, 9 Cyle Arcs In Open Air - 1.25 Electrode Gap
+Class 1 FR Clothing
-
ATPV 5 callcm2
+Class 2A FR Clothing
ATPV - 8 ca llcm 2
18 24 30 36 42 48 54
Bolted Fault kA
Fig. A2. (a) Second Degree Burn Boundary Distances For 600V,3-Phase, 9-Cycle Electric Arcs In Open Air
Fig. A2. (b) Second Degree Burn Boundary Distances For 600V, 3-Phase, 9-Cycle Electric Arcs In 20" Cubic Box
* Data based on measured incident energy under specified test conditions. Real arc exposures may be more or less than
these simulated exposures.
- 342 -
Second Degree Burn Boundary Distances" A s A Function Of Bolted Fault kA
-
600 V, 3-Phase, 12 Cyle Arcs In Open Air 1.25' Electrode Gap
78.0
-+-Human Skin 2nd
Degree Burn Limit -
1.2 callcm2
-m- Untreated Cotton
-
ATPV 2 callcm2
+Class 1 FR Clothing
5 2 38.0
U -
ATPV 5 callcm2
.E E
5E 2O 28.0 +Class 2A FR Clothing
-
ATPV 8 ca llcm2
18.0
18 24 30 36 42 48 54
Bolted Fault kA
Fig. A3. (a) Second Degree Burn Boundary Distances For 600V, 3-Phase, 12-Cycle Electric Arcs In Open Air
+Class 1 FR Clothing
ATPV - 5 callcm2
+Class 2A FR Clothing
-
ATPV 8 callcm2
18.0
18 24 30 36 42 48 54
Bolted Fault kA
Fig. A3. (b) Second Degree Burn Boundary Distances For 600V, 3-Phase, 12-Cycle Electric Arcs In 20" Cubic Box
Data based on measured incident energy under specified test conditions. Real arc exposures may be more or less than
these simulated exposures.
- 343 -
Second Degree Burn Boundary Distances* As A Function Of Bolted Fault kA
600 V, 3-Phase, 18 Cyle Arcs In Open Air - 1.25" Electrode Gap
88.0
av) &Human Skin 2nd
2 78.0 Degree Burn Limit -
.- 1.2 callcm2
0 UT 68.0
Eo, ---c Untreated Cotton
011
58.0
ATPV - 2 callcm2
Et;
a
2d 48.0 +Class 1 FR Clothing
ATPV - 5 callcm2
5E
.E 38.0
.E 2 +Class 2A FR Clothing
g 28.0
ATPV - 8 callcm2
LL
18.0
18 24 30 36 42 48 54
Bolted Fault kA
Fig. A4. (a) Second Degree Burn Boundary Distances For 600V, 3-Phase, 18-Cycle Electric Arcs In Open Air
+Class 2B FR Clothing
52
E 28.0 -
ATPV 16 ca llcm2
.-E
.-
5 --Class 3 FR Clothing
ATPV - 25 callcm2
18.0
18 24 30 36 42 48 54
+Class 4 FR Clothing
Bolted Fault kA -
ATPV 40 callcm2
Fig A4 (b) Second Degree Burn Boundary Distances For 600V, 3-Phase, 18-Cycle Electric Arcs In 20" Cublc Box
* Data based on measured incident energy under specified test conditions
Real arc exposures may be more or less than
these simulated exposures
- 344 -
Second Degree Burn Boundary Distance9 A s A Function Of Bolted Fault kA
-
600 V, 3-Phase, 24 Cyle Arcs In Open Air 1.25 Electrode Gap
108.0
-Human Skin 2nd
98.0
E2 v,
Degree Burn Limit -
4p 88.0 1.2 callcm2
&Untreated Cotton
0'0
$ 78.0 -
ATPV 2 callcm2
m o
g& 68.0 -+-Class 1 FR Clothing
25
P O
58.0 -
ATPV 5 callcm2
Fig. A5. (a) Second Degree Burn Boundary Distances For 600V, 3-Phase, 24-Cycle Electric Arcs In Open Air
E -+Class 1 FR Clothing
E!
58.0
-
ATPV 5 callcm2
av)
O Q
5:
E 48.0
- - ~Class
t 2A FR Clothing
ATPV - 8 calicm2
C Q
011
m o
0 2
2 38.0 ++Class 2B FR Clothing
2; -
ATPV 16 calicm2
5;
.-Er 28.0
4 C l a s s 3 FR Clothing
.-
I ATPV - 25 callcm2
18.0
18 24 30 36 42 48 54 +Class 4 FR Clothing
Bolted Fault kA -
ATPV 40 callcm2
Fig. A5. (b) Second Degree Burn Boundary Distances For 600V, 3-Phase, 24-Cycle Electric Arcs In 20" Cubic Box
* Data based on measured incident energy under specified test conditions. Real arc exposures may be more or less than
these simulated exposures.
- 345 -
Second Degree Burn Boundary Distance9 As A Function Of Bolted Fault kA
-
600 V, 3-Phase, 30 Cyle Arcs In Open Air 1.26“ Electrode Gap
118.0
-+-Human Skin 2nd
p) v) 108.0
o m
3 98.0 1.2 callcm2
.--2s ---c Untreated Cotton
n cn^
Tat
88.0
-
ATPV 2 callcm2
’
0 78.0
g g +.--Class 1 FR Clothing
a o 68.0
-
ATPV 6 callcm2
2 58.0
53 48.0
+Class 2A FR Clothing
-
ATPV 8 callcm2
.E E
.E 2 38.0
-++Class 28 FR Clothing
LL 28.0
-
ATPV 16 callcm2
18.0
&Class 3 FR Clothing
18 24 30 36
Bolted Fault kA
42 48 54
-
ATPV 26 callcm2
Fig. A6. (a) Second Degree Burn Boundary Distances For 600V, 3-Phase, 30-Cycle Electric Arcs In Open Air
I
Second Degree Burn Boundary Distance9 A s A Function Of Bolted Fault kA
600 V, 3-Phase, 30 Cyle Arcs In 20” Cubic Box - 1.25” Electrode Gap
68.0
52
5 48.0 ATPV - 8 callcm2
r a
o e
Q O
Il.b
Q 38.0
$a -
ATPV 16 callcm2
z:
E
I-
28.0
.-S -8- Class 3 FR Clothin
5 -
ATPV 25 callcm2
18.0
18 24 30 36 42 48 54 +Class 4 FR Clothing
Bolted Fault kA -
ATPV 40 callcm2
Fig A6 (b) Second Degree Burn Boundary Distances For 600V, 3-Phase, 30-Cycle Electric Arcs In 20” Cubic Box
* Data based on measured incident energy under specified test conditions
Real arc exposures may be more or less than
these simulated exposures
- 346 -