09 - Chapter 2 PDF
09 - Chapter 2 PDF
CHAPTER 2
2.1 INTRODUCTION
The fault currents produce radial and axial component fluxes which
interact with winding currents to produce axial and radial forces respectively.
19
√
(A) (2.1)
√
(a) Magnetic flux plot (b) Radial force (c) Axial force
Figure 2.1 Magnetic flux and the associated forces (Giorgio Bertagnolli
2006)
The axial component of the flux density (Ba) at the center of the
insulation in between the windings (at point A) is given by,
( )
(T) (2.2)
( )
(N) (2.3)
The radial flux interacts with the winding current and results in
axial force (Fa). As all discs of a winding carry current in the same direction,
the axial force results in compression of the winding. For an uniform ampere-
turn distribution in windings with equal heights, the axial forces at the
winding ends are directed towards the winding center leading to compressive
forces as shown in Figure 2.1(c). Even a small axial displacement of windings
or misalignment of magnetic centers of windings can eventually cause
enormous axial forces leading to failure of transformers (Norris 1957, McNutt
1955).
The sum of axial forces (Fa) at the middle of the winding is given
by
( )
[ ] (N) (2.4)
Usually about 2/3 to 3/4 of the axial force is on the inner winding
and about 1/3 to 1/4 is on the outer winding.
The failure modes of windings are quite different for inward and
outward radial forces. The radial deformation occurs in two ways. One is the
forced buckling, that occurs when the inner winding is supported by spacers
located in the axial direction and this happens when the stress value exceeds
the material elastic limit as shown in Figure 2.2. The other strain is hoop
buckling where the conductor is deformed in one or more radial points of the
winding. The radial forces produced by the axial leakage field act outwards
on the outer winding tending to stretch the winding conductor, producing a
tensile stress (also called as hoop stress) as shown in Figure 2.3. The
occurrence of radial deformation in the inner winding (buckling) is more
common than in the outer winding (hooping).
24
Axial force is mainly directed away from the winding ends and
towards the middle of the winding. So the highest compression occurs in the
middle part of each winding. Figure 2.4 shows the bending of windings
between supporting columns which can result in broken conductor insulation.
When these axial forces are more than a certain limit, a failure can
occur due to tilting of conductors in a zigzag way as shown in Figure 2.5. In
this mode of failure, turning of conductor cross section occurs around the
perpendicular axis of symmetry.
( ⃗⃗⃗⃗) ⃗⃗ (2.5)
( ⃗⃗⃗⃗) ⃗ (2.6)
( )
(2.7)
The radial (Br) and axial (Bz) components of the magnetic flux
densities are computed using Equations (2.5), (2.6) and (2.7).
⃗ (2.8)
27
From the radial and axial components of flux densities, the axial
(Fz) and radial (Fr) components of electromagnetic forces can be computed
using Equation (2.9) as
Using the field approach, both the flux and force distribution can be
estimated for the entire transformer which is essential for the prediction of the
winding deformation profile. The mechanical deformation of the different
parts of the transformer is computed using Coupled Magneto-Structural
analysis.
( )
where F is the force, E is Young’s modulus and A is the area of cross section.
Figure 2.7 Surface plot of magnetic flux density under short circuit
Figure 2.9 shows the radial force distribution along the LV and HV
windings. Due to axial flux, a radial repulsive force between the inner and
outer is produced. The radial force is minimum at the ends in both the
windings and the maximum near the center for LV winding and near tappings
for HV winding. The LV winding experiences a buckling force acting inwards
tending to crush or collapse the conductor and the HV winding experiences
an outward force tending to stretch the conductor to produce hoop stress.
31
Table 2.1 gives the maximum values of forces in both the windings.
47% and 53 % of total radial forces act on LV and HV windings respectively.
In case of axial force, 75% and 25% of total axial forces occur in LV and HV
windings respectively agreeing well with Waters (1966).
Force (kN)
Type of Force
Simulated Analytical
(Waters 1966)
Axial force on HV 59 62
Figure 2.12 (a) and (b) show the magnetic flux and flux density
plots. It is observed that the radial flux is maximum near the ends of the coil
and the axial flux is maximum at the center of the coil which results in both
radial ( outward) and axial ( compressive) forces.
35
Figure 2.13(a) shows the deformed coil and Figure 2.13 (b) gives
the displacements in both the axial (Uy) and radial directions (Ux). The coil
undergoes a maximum deformation at the center with the radial outward
displacement of 1.71x10-9 m, agreeing with the results of the literature with
the percentage error of 3.7% .
36
2.6 CONCLUSION
The magnetic flux and both the radial and axial force
distributions due to short circuit in a two winding transformer
is computed and analyzed using a 5 MVA, 22 kV/11 kV
transformer and the following are observed here.
37
In the next chapter, both the force distribution and the deformation
of a typical power transformer with two concentric windings are computed
and the change in winding reactance after short circuit is estimated.